Camp Lejeune Barracks Daylighting Analysis 19 October 2009 Center for Integrated Building Design Research School of Architecture - UNC Charlotte University of North Carolina at Charloe Charloe, NC Architects: LS3P 227 W. Trade Street Suite 700 Charloe, NC 28202
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Camp Lejeune Barracks
Daylighting Analysis19 October 2009
Center for Integrated Building Design Research School of Architecture - UNC Charlotte
University of North Carolina at CharlotteCharlotte, NC
Architects:LS3P227 W. Trade StreetSuite 700Charlotte, NC 28202
Camp Lejeune BarracksRadiance Simulation
54% visual light transmittance
9 a.m.
21% visual light transmittance
Simulations shown assume the following parameters:
South-facing aperture
VCT Floors: Warm Gray 7 M
Door Frames/Wall Base: Pantone 7531 M
Wall Paint: 7534 M
Ceilings: White
Window Frames: White
Camp Lejeune BarracksRadiance Simulation
54% visual light transmittance
10 a.m.
21% visual light transmittance
Camp Lejeune BarracksRadiance Simulation
11 a.m.
54% visual light transmittance
21% visual light transmittance
Camp Lejeune BarracksRadiance Simulation
12 noon
54% visual light transmittance
21% visual light transmittance
Camp Lejeune BarracksRadiance Simulation
1 p.m.
54% visual light transmittance
21% visual light transmittance
Camp Lejeune BarracksRadiance Simulation
2 p.m.
54% visual light transmittance
21% visual light transmittance
Camp Lejeune BarracksRadiance Simulation
3 p.m.
54% visual light transmittance
21% visual light transmittance
Camp Lejeune BarracksRadiance Simulation
4 p.m.
54% visual light transmittance
21% visual light transmittance
9 10 11 12 13 14 15 16
21 VLT Glazing 10 20 25 28 26.5 24 20 10
54 VLT Glazing 96 145 166 170 168 162 123 70
Average Sq. Ft with DF of 2 12% 79%
020406080
100120140160180
Sq. F
t of B
arra
cks
wit
h D
F of
2 LEED Daylighting Credit Graph
Camp Lejeune BarracksLEED Analysis
Exceeds LEED requirement for daylighting performance credit