UN CAJON
CALCULO ESTRUCTURAL DE ALCANTARILLA TIPO CAJON
DATOS:
F'c Concreto (kg/cm^2)250Peso especifico del concreto
(kg/m^3)2400Fy acero de refuerzo (kg/cm^2)4200Peso especifico del
suelo (t/m^3)1800Capacidad portante del suelo (kg/cm^2)1.5Angulo de
friccion interna del suelo ()18Profundidad del nivel fretico
(m)2.51.00 m
Camin de diseoHS-20-44Peso rueda trasera (kg)72503 mDIMENSIONES
DE LA SECCION
Ancho de alcantarilla (Ancho de via) (m)6Altura "H" (m)1.4Ancho
"B" (m)1.6Espesor de losas "e" (m)0.15NFEspesor "r" (m)1Altura
total "A"1.7H=1.40 mAncho total "L"1.9A= 1.70 m
PESO DE LA ESTRUCTURA
Peso losa superior (kg)576Peso losa inferior (kg)576B=1.60 mPeso
muro izquierdo (kg)612Peso muro derecho (kg)612Peso total de la
estructura (kg)2376L= 1.90 mPeso de relleno sobre la estructura
(kg/m^2)1800
CALCULO DE LA CARGA VIVA POR TRAFICO
Area de contacto Rueda HS-20-44a (m)0.2b (m)0.51
Dimensiones de propagacion del area de contactoPropagacion a
(m)2.419Propagacion b (m)2.729Carga P (kg)7250Coeficiente de
impacto0.3808Carga P+I (kg)9425Carga vehicular (kg/m^2)1427.72
EMPUJE DE TIERRAS
2.50 mNF
Angulo de friccion interna (Radianes)0.3142 Coeficiente activo
"Ka"0.5279Esfuerzo zona superior de muro (kg/m^2)2611.41Esfuerzo en
el nivel fretico (kg/m^2)4606.73Esfuerzo en la zona inferior del
muro (kg/m^2)5489.43
ANALISIS EN SITUACION DE ESTRUCTURA LLENA
CARGAS ULTIMAS SOBRE LOS ELEMENTOSMOMENTOS DE EMPOTRAMIENTO
Carga sobre la losa superior (kg/m^2)4731.12Extremo de losa
superior (kg.m)1423.28Reaccin del terreno (kg/m^2)7628.38Extremo de
losa inferior (kg.m)2294.87Carga sobre la losa inferior
(kg/m^2)-7628.38Zona superior de pared lateral (kg.m)906.16Carga en
zona superior del muro lateral (kg/m^2)2611.41Zona inferior de
pared lateral (kg.m)1044.79Carga en zona inferior del muro lateral
(kg/m^2)5489.434731.12 kg/m^2
2611.41 kg/m^22611.41 kg/m^2
5489.43 kg/m^25489.43 kg/m^2
-7628.38 kg/m^2
DISTRIBUCION DE MOMENTOS POR EL METODO DE CROSS
Calculo de rigidecesK=4EI/LLas secciones son iguales en todo el
cajon y el material es el mismo, asi que "EI" es constante
KAB2.11KAD2.351087.75-1087.75SUMA=4.46-213.43213.43Factor de
distribucion122.10-122.10FAB0.47-244.19244.19FAD0.531423.280.47-1423.28-906.16906.16-272.92272.92329.88-329.88-238.54238.54-1087.751087.75
0.530.53
1795.89-1795.89227.80-227.80-136.46136.46659.77-659.771044.79-1044.79-2294.870.472294.87590.32-590.32MOMENTOS
FINALES-295.16295.16MA=MB1087.75203.82-203.82MC=MD1795.89-1795.891795.89
CORTANTES EN LA ESTRUCTURACORTANTE IGUAL A CERO PARA CALCULAR EL
MOMENTO MAXIMOREVISION POR CORTANTE EN MUROS
En losa superior (kg)4494.56Calculando el cortante igual a cero
para determinar el momento mximoCortante que absorve el concreto
(kg)7542.03En losa inferior (kg)7246.96
EN PAREDES LATERALESX (cortante igual a cero)0.781En losa
superiorCUMPLECORTANTE ISOSTATICAf(x)=RA- (P1(2L-X)+P2X/2L)X0.00En
losa inferiorCUMPLEZona superior de pared lateral
(kg)3116.68f(x)^20.00En muros lateralesCUMPLEZona inferior de pared
lateral (kg)3769.03NOTA: Encontramos la distancia "X" con ayuda de
la herramienta "SOLVER",cada vez que se cambien algun parametro del
diseo se tendra que realizar de nueva cuenta el clculo.CORTANTE
HIPERESTATICAV-416.5564282188
En parte superior (kg)2700.12CAPACIDAD DEL SUELOEn parte
inferior (kg)4185.59
MOMENTOS EN LOS CENTROS DE CLAROCARGA (kg/m^2)7628.38CAPACIDAD
DEL SUELO (kg/m^2)15000Losa superior (kg)711.64FACTOR DE SEGURIDAD
">1.5"1.97SI CUMPLELosa Inferior (kg)1147.44Paredes laterales
(kg)426.16
1087.74681906031087.74681906034494.56 kg
1795.89274703231795.89274703232700.12 kg2700.12
kg711.63898667534494.56 kg
426.1618466821426.1618466821
7246.96 kg1147.4356533424185.59
kg1795.89274703231795.89274703234185.59 kg
1795.89274703231795.89274703237246.96 kg
ANALISIS EN SITUACION DE ESTRUCTURA VACIA
CARGAS SOBRE LOS ELEMENTOSMOMENTOS DE EMPOTRAMIENTO
Carga sobre la losa superior (kg/m^2)4731.1179169549Extremo de
losa superior (kg.m)1423.28Reaccin del terreno
(kg/m^2)5977.8547590602Extremo de losa inferior (kg.m)1798.34Carga
sobre la losa inferior (kg/m^2)-5977.8547590602Zona superior de
pared lateral (kg.m)906.16Carga en zona superior del muro lateral
(kg/m^2)2611.41zona inferior de pared lateral (kg.m)1044.79Carga en
zona inferior del muro lateral (kg/m^2)5489.43
4731.12 kg/m^2
2611.41 kg/m^22611.41 kg/m^2
5489.43 kg/m^25489.43 kg/m^2
-5977.85 kg/m^2
DISTRIBUCION DE MOMENTOS POR EL METODO DE CROSS
Calculo de rigidecesK=4EI/LLas secciones son iguales en todo el
cajon y el material es el mismo, asi que "EI" es constante
1149.62-1149.62KAB2.11-151.56151.56KAD2.35122.10-122.10SUMA=4.46-244.19244.19Factor
de
distribucion1423.280.47-1423.28FAB0.47-906.16906.16FAD0.53-272.92272.92198.85-198.85-169.39169.39-1149.621149.62
0.530.53
1471.96-1471.96165.92-165.92-136.46136.46397.71-397.711044.79-1044.79-1798.340.471798.34355.84-355.84-177.92177.92148.46-148.46-1471.961471.96MOMENTOS
FINALESMA=MB1149.62MC=MD1471.96
CORTANTES EN LA ESTRUCTURAREVISION POR CORTANTE EN MUROS
En losa superior (kg)4494.56Cortante que absorve el concreto
(kg)7542.03En losa inferior (kg)5678.96
EN PAREDES LATERALESEn losa superiorCUMPLECORTANTE ISOSTATICAEn
losa inferiorCUMPLEZona superior de pared lateral (kg)3116.68En
muros lateralesCUMPLEZona inferior de pared lateral (kg)3769.03
CORTANTE HIPERESTATICACAPACIDAD DEL SUELOV-189.6096840891
Zona superior de pared lateral (kg)2927.07CARGA
(kg/m^2)5977.85Zona inferior de pared lateral (kg)3958.64CAPACIDAD
DEL SUELO (kg/m^2)15000FACTOR DE SEGURIDAD ">1.5"2.51SI
CUMPLEMOMENTOS EN LOS CENTROS DE CLARO
En losa superior (kg.m)711.64En losa inferior (kg.m)899.17Centro
de pared lateral (kg.m)426.16
4494.56 kg1149.62192194091149.6219219409
2927.07 kg1149.62192194091149.62192194093958.64
kg711.63898667534494.56 kg
426.1618466821426.1618466821
5678.96 kg
899.16898667531471.95838489241471.95838489243958.64 kg3958.64
kg
1471.95838489241471.95838489245678.96 kg
CALCULO DE ACERO
LECHO EXTERIORLECHO INTERIOR
Mmx (kg.cm)179589.27Mmx (kg.cm)114743.57f'c (kg/cm^2)250f'c
(kg/cm^2)250Base (cm)100Base (cm)100Peralte d10Peralte
d10K0.0798174554K0.0509971401Indice de refuerzo w0.0839783497Indice
de refuerzo w0.0526314832Porcentaje de acero0.0049987113Porcentaje
de acero0.0031328264Porcentaje minimo0.0033333333SI CUMPLE
Anabel: SI EL PORCENTAJE CALCULADO ES MENOR QUE EL MINIMO, SE USARA
EL PORCENTAJE MINIMO PARA EL CALCULO DE ACERO.Porcentaje
minimo0.0033333333NO CUMPLEPorcentaje maximo0.0191212845SI
CUMPLE
Anabel: SI EL PORCENTAJE CALCULADO ES MAYOR QUE EL MAXIMO, NO
CUMPLE Y SE TIENE QUE MODIFICAR LA SECCION.Porcentaje
maximo0.0191212845SI CUMPLE
Area de acero (cm^2)5.00Area de acero (cm^2)3.33Varilla a
utilizar3Varilla a utilizar3Separacion de barras (cm)14Separacion
de barras (cm)21
ACERO POR TEMPERATURA PARA TODOS LOS ELEMENTOS
Porcentaje por temperatura0.0018Base (cm)100Peralte d10Area de
acero (cm^2)1.8Varilla a utilizar3Separacion de barras (cm)39
ARMADO DE LA ALCANTARILLA
3 @ 14 cm3 @ 39 cmNOTAS:
3 @ 21 cm3 @ 14 cm3 @ 14 cm3 @ 21 cm3 @ 21 cm3 @ 39 cm3 @ 39 cm3
@ 39 cm3 @ 21 cm3 @ 14 cm3 @ 39 cm
RESUMEN DE REFUERZOS
ELEMENTOLECHOAREA DE ACERO (cm^2)# DE BARRA A UTILIZARSEPARACION
(cm)Losa superiorExterior5.00314Losa superiorExterior por
temperatura1.8339Losa superiorInterior3.33321Losa superiorInterior
por temperatura1.8339Losa inferiorInterior3.33321Losa
inferiorInterior por temperatura1.8339Losa
inferiorExterior5.00314Losa inferiorExterior por
temperatura1.8339Paredes lateralesExterior5.00314Paredes
lateralesExterior por temperatura1.8339Paredes
lateralesInterior3.33321Paredes lateralesInterior por
temperatura1.8339
VOLUMEN DE MATERIALES
Volumen de concreto
Losa superior (m^3)1.44Losa Inferior (m^3)1.44Paredes laterales
(m^3)3.06Total de concreto (m^3)5.94
Cantidad de acero
LOSAS SUPERIOR E INFERIOR LECHO EXTERIORLOSAS SUPERIOR E
INFERIOR LECHO INTERIOR
Acero principalAcero principalLargo de barras (m)1.96Largo de
barras (m)1.96Numero de barras42.86Numero de barras28.57total de
ml84total de ml56Varilla a utilizar #3Varilla a utilizar #3Total de
varilla (kg)46.788Total de varilla (kg)31.192
Acero por temperaturaAcero por temperaturaLargo de barras
(m)6.06Largo de barras (m)6.06Numero de barras4.872Numero de
barras4.872total de ml29.52total de ml29.52Varilla a utilizar
#3Varilla a utilizar #3Total de varilla (kg)16.44Total de varilla
(kg)16.44
PAREDES LATERALES LECHO EXTERIORPAREDES LATERALES LECHO
INTERIOR
Acero principalAcero principalLargo de barras (m)1.76Largo de
barras (m)1.76Numero de barras12.14Numero de barras8.10total de
ml21total de ml14Varilla a utilizar #3Varilla a utilizar #3Total de
varilla (kg)11.904Total de varilla (kg)7.936
Acero por temperaturaAcero por temperaturaLargo de barras
(m)6.06Largo de barras (m)6.06Numero de barras4.359Numero de
barras4.359total de ml26.42total de ml26.42Varilla a utilizar
#3Varilla a utilizar #3Total de varilla (kg)14.71Total de varilla
(kg)14.71
TOTAL DE ACERO REQUERIDO (kg)320.27
CAJON DOBLE
CALCULO DE ALCANTARILLA TIPO CAJON DOBLE
DATOS:
F'c Concreto (kg/cm^2)250Peso especifico del concreto
(kg/m^3)2400Fy acero de refuerzo (kg/cm^2)4200Peso especifico del
suelo (t/m^3)1800Capacidad portante del suelo (kg/cm^2)1.5Angulo de
friccion interna del suelo ()19Profundidad del nivel fretico (m)2r=
0.65 m
Camin de diseoHS-20-44Peso rueda trasera (kg)72502.00 m
DIMENSIONES DE LA SECCION
Ancho de alcantarilla (Ancho de via) (m)6Altura "H" (m)1.4Ancho
"B" (m)2N.F.Espesor de losas "e" (m)0.22Espesor "r" (m)0.65A= 1.84
mH=1.40 mH=1.40 mAltura toral "A" (m)1.84Ancho total "L"
(m)4.66
PESO DE LA ESTRUCTURAB= 2.00 mB= 2.00 m
Peso losa superior (kg)2228.16Peso losa inferior (kg)2228.16Peso
muro izquierdo (kg)971.52L= 4.66 mPeso muro derecho (kg)971.52Peso
muro central (kg)739.2Peso total de la estructura (kg)7138.56
Peso de relleno sobre la estructura (kg/m^2)1170
CALCULO DE CARGA VIVA
Area de contacto Rueda HS-20-44a (m)0.2b (m)0.51
Dimensiones de propagacion del area de contactoPropagacion a
(m)2.069Propagacion b (m)2.379Carga P (kg)7250Coeficiente de
impacto0.3799Carga P+I (kg)9425Carga vehicular (kg/m^2)1914.81
EMPUJE DE TIERRAS
2.00 mNF
Angulo de friccion interna (Radianes)0.3316Coeficiente activo
"Ka"0.5088Esfuerzo zona superior de muro (kg/m^2)2489.59Esfuerzo en
el nivel fretico (kg/m^2)4220.48Esfuerzo en la zona inferior del
muro (kg/m^2)5813.95
ANALISIS EN SITUACION DE ESTRUCTURA LLENA
CARGAS ULTIMAS SOBRE LOS ELEMENTOSMOMENTOS DE EMPOTRAMIENTO
Carga sobre la losa superior (kg/m^2)5632.38EN LOSA
SUPERIORReaccin del terreno (kg/m^2)8720.22Puntos "A y C"
(kg.m)2523.51Carga sobre la losa inferior (kg/m^2)-8720.22Punto "B"
(kg.m)3084.29Carga en zona superior del muro lateral
(kg/m^2)2489.59En centro de losa superior (kg.m)1982.76Carga en
zona inferior del muro lateral (kg/m^2)5813.95EN LOSA
INFERIORPuntos "D y F" (kg.m)3906.97Punto "E"4775.19En centro de
claro "E" (kg.m)3069.77EN PARED LATERALPared lateral superior
(kg.m)1077.56Pared lateral inferior (kg.m)1265.145632.38
kg/m^2Pared lateral centro (kg.m)501.09
2523.51219233633084.29267952222523.5121923363 2489.59
kg/m^22489.59
kg/m^21077.56142306181982.761982.75957969281077.5614230618501.0851476354501.08514763541265.14430579633069.76579153833069.76579153831265.14430579635813.95
kg/m^25813.95
kg/m^23906.9746437764775.19123128183906.974643776-8720.22
kg/m^2
DISTRIBUCION DE MOMENTOS
Rigideces =4EI/LTramos horizontales1.7167381974Tramos
verticales2.1739130435Suma3.8906512409
Factores de
distribucionAB=CB=DE=FE0.441BA=BC=ED=EF0.306AD=DA=CF=FC0.559
ADBACBFCE DADABBABEBCCBCFFCFEEFEBEDDEDAF.
DIST0.5590.4410.3060.3060.3060.4410.5590.5590.4410.3060.3060.3060.4410.559M.
EMP.1077.56-2523.513084.29-3084.292523.51-1077.561265.14-3906.974775.19-4775.193906.97-1265.141.-
M.
DIST.807.93638.02-638.02-807.931476.131165.70-1165.70-1476.13TRANS.-738.07319.01-319.01738.07-403.96582.85-582.85403.962.-
M.
DIST.412.40325.67-325.67-412.40225.72178.25-178.25-225.72TRANS.-112.86162.83-162.83112.86-206.2089.12-89.12206.203.-
M.
DIST.63.0649.80-49.80-63.06115.2190.98-90.98-115.21TRANS.-57.6124.90-24.9057.61-31.5345.49-45.4931.534.-
M.
DIST.32.1925.42-25.42-32.1917.6213.91-13.91-17.62TRANS.-8.8112.71-12.718.81-16.096.96-6.9616.095.-
M. DIST.4.923.89-3.89-4.928.997.10-7.10-8.99M.
FINAL1480.72-1480.723603.75-3603.751480.72-1480.722451.03-2451.035499.61-5499.612451.03-2451.03
MOMENTOS
FINALESMAB=MCB1480.72MBA=BBC3603.75MDE=MFE2451.03MEF=MED5499.61
CORTANTES EN LA ESTRUCTURAREVISION POR CORTANTE EN MUROS
LOSA SUPERIORCortante absorvido por el concreto (kg)12821.45En
puntos extremos A y C (kg)4921.29En punto central B (kg)8202.16Losa
superiorCUMPLELosa inferiorCUMPLELOSA INFERIORParedes
lateralesCUMPLEEn puntos extremos D y F (kg)7619.29En punto central
E (kg)12698.82
EN PAREDES LATERALESCORTANTES ISOSTATICOSPuntos superiores A y C
(kg)3411.84Puntos inferiores D y F (kg)4227.42
CORTANTE HIPERESTATICAV-527.3428902527
CORTANTES FINALESPuntos superiores A y C (kg)2884.50Puntos
inferiores D y F (kg)4754.76CALCULO DE MOMENTO POSITIVO EN MURO
LATERALCAPACIDAD DEL SUELO
MOMENTOS EN CENTROS DE CLAROCalculando el cortante igual a cero
para determinar el momento mximoCARGA (kg/m^2)8720.22CAPACIDAD DEL
SUELO (kg/m^2)15000FACTOR DE SEGURIDAD ">1.5"1.72Losa
superior1279.97X (cortante igual a cero)0.84Losa
inferior1942.33f(x)=RA- (P1(2L-X)+P2X/2L)X0.00En paredes
laterales684.80f(x)^20.00
NOTA: Encontramos la distancia "X" con ayuda de la herramienta
"SOLVER",cada vez que se cambien algun parametro del diseo se
tendra que realizar de nueva cuenta el clculo.
3603.74656905434921.29 kg8202.16
kg1480.71759034121480.71759034122884.50
kg1480.71759034121480.71759034122884.50
kg1279.97311749411279.9731174941
8202.16 kg4921.29 kg684.7990549744684.79905497447619.29
kg12698.82 kg
1942.32771248631942.32771248634754.76
kg2451.02850840612451.02850840614754.76 kg
2451.02850840612451.028508406112698.82 kg7619.29
kg5499.6135810049
ANALISIS EN SITUACION DE ESTRUCTURA VACIA
CARGAS ULTIMAS SOBRE LOS ELEMENTOSMOMENTOS DE EMPOTRAMIENTO
Carga sobre la losa superior (kg/m^2)5632.38LOSA SUPERIORReaccin
del terreno (kg/m^2)7037.81Puntos "A y C" (kg.m)2523.51Carga sobre
la losa inferior (kg/m^2)-7037.81Punto "B" (kg.m)3084.29Carga en
zona superior del muro lateral (kg/m^2)2489.59En centro de losa
superior (kg.m)1982.76Carga en zona inferior del muro lateral
(kg/m^2)5813.95LOSA INFERIORLosa inferior "D y F" (kg.m)3153.20Losa
inferior punto "E"3853.91En centro losa inferior (kg.m)2477.51PARED
LATERALPared lateral superior (kg.m)1077.56Pared lateral inferior
(kg.m)1265.145632.38 kg/m^2Pared lateral centro
(kg.m)501.092523.51219233633084.29267952222523.51219233632489.59
kg/m^22489.59
kg/m^21077.56142306181982.75957969281982.75957969281077.5614230618501.0851476354501.08514763541265.14430579632477.51171428512477.51171428511265.14430579635813.95
kg/m^25813.95
kg/m^23153.19672727192477.51171428513153.1967272719-7037.81
kg/m^2
DISTRIBUCION DE MOMENTOS
Rigideces =4EI/LTramos horizontales1.7167381974Tramos
verticales2.1739130435Suma3.8906512409
Factores de
distribucionAB=CB=DE=FE0.441BA=BC=ED=EF0.306AD=DA=CF=FC0.559
ADBACBFCE DADABBABEBCCBCFFCFEEFEBEDDEDAF.
DIST0.5590.4410.3060.3060.3060.4410.5590.5590.4410.3060.3060.3060.4410.559M.
EMP.1077.56-2523.513084.29-3084.292523.51-1077.561265.14-3153.202477.51-2477.513153.20-1265.141.-
M.
DIST.807.93638.02-638.02-807.931054.95833.10-833.10-1054.95TRANS.-527.48319.01-319.01527.48-403.96416.55-416.55403.962.-
M.
DIST.294.73232.75-232.75-294.73225.72178.25-178.25-225.72TRANS.-112.86116.37-116.37112.86-147.3689.12-89.12147.363.-
M.
DIST.63.0649.80-49.80-63.0682.3465.02-65.02-82.34TRANS.-41.1724.90-24.9041.17-31.5332.51-32.5131.534.-
M.
DIST.23.0018.17-18.17-23.0017.6213.91-13.91-17.62TRANS.-8.819.08-9.088.81-11.506.96-6.9611.505.-
M. DIST.4.923.89-3.89-4.926.435.08-5.08-6.43M.
FINAL1580.89-1580.893553.66-3553.661580.89-1580.892057.84-2057.843022.65-3022.652057.84-2057.84
MOMENTOS
FINALESMAB=MCB1580.89MBA=BBC3553.66MDE=MFE2057.84MEF=MED3022.65
CORTANTES EN LA ESTRUCTURAREVISION POR CORTANTE EN MUROS
LOSA SUPERIORCortante absorvido por el concreto (kg)12821.45En
puntos extremos A y C (kg)4921.29En punto central B (kg)8202.16Losa
superiorCUMPLELosa inferiorCUMPLELOSA INFERIORParedes
lateralesCUMPLEEn puntos extremos D y F (kg)6149.29En punto central
E (kg)10248.82
PAREDES LATERALESCORTANTES ISOSTATICOSCAPACIDAD DEL SUELOPuntos
superiores A y C (kg)3411.84Puntos inferiores D y F
(kg)4227.42CARGA (kg/m^2)7037.81CORTANTE HIPERESTATICOCAPACIDAD DEL
SUELO (kg/m^2)15000V-259.21FACTOR DE SEGURIDAD ">1.5"2.13SI
CUMPLEPuntos superiores A y C (kg)3152.63Puntos inferiores D y F
(kg)4486.63
MOMENTOS EN CENTROS DE CLARO
Losa superior1254.93Losa inferior2235.70En paredes
laterales291.613553.65963466724921.29 kg8202.16
kg1580.89145911551580.8914591155
1580.89145911551580.89145911553152.63 kg3152.63
kg1254.92965030051254.92965030058202.16 kg4921.29 kg
291.6096093311291.60960933116149.29 kg10248.82 kg
2235.70275878252235.70275878254486.63
kg2057.83906276282057.83906276284486.63 kg
2057.83906276282057.839062762810248.82 kg6149.29
kg3022.6529340558
CALCULO DE ACERO
LECHOS EXTERIORESLECHO INFERIOR
Mu (kg.cm)549961.36Mu (kg.cm)223570.28f'c (kg/cm^2)250f'c
(kg/cm^2)250Base (cm)100Base (cm)100Peralte d17Peralte
d17K0.0845769101K0.0343822031Indice de refuerzo w0.0892797228Indice
de refuerzo w0.0351094818Porcentaje de acero0.0053142692Porcentaje
de acero0.0020898501Porcentaje minimo0.0033333333SI CUMPLE
Anabel: SI EL PORCENTAJE CALCULADO ES MENOR QUE EL MINIMO, SE USARA
EL PORCENTAJE MINIMO PARA EL CALCULO DE ACERO.Porcentaje
minimo0.0033333333NO CUMPLEPorcentaje maximo0.0191212845SI
CUMPLE
Anabel: SI EL PORCENTAJE CALCULADO ES MAYOR QUE EL MAXIMO, NO
CUMPLE Y SE TIENE QUE MODIFICAR LA SECCION.Porcentaje
maximo0.0191212845SI CUMPLE
Area de acero (cm^2)9.03Area de acero (cm^2)5.67Varilla a
utilizar4Varilla a utilizar4Separacion de barras (cm)14Separacion
de barras (cm)22
ACERO EN PARED INTERIOR CON ACERO MINIMO
BASE (cm)100PERALTE d17Pmin0.003333
Area de acero (cm^2)5.67Varilla a utilizar4Separacion de las
barras (cm)22
ACERO POR TEMPERATURA PARA TODOS LOS ELEMENTOS
Porcentaje por temperatura0.0018Base (cm)100Peralte d17Area de
acero (cm^2)3.06Varilla a utilizar3Separacion de barras (cm)23
ARMADO DE LA ALCANTARILLA
NOTAS:4 @ 14 cm3 @ 23 cm4 @ 22 cm3 @ 23 cm4 @ 22 cm4 @ 22 cm4 @
14 cm4 @ 14 cm4 @ 22 cm4 @ 22 cm3 @ 23 cm3 @ 23 cm3 @ 23 cm4 @ 22
cm3 @ 23 cm
4 @ 14 cm3 @ 23 cm
RESUMEN DE REFUERZOS
ELEMENTOLECHOAREA DE ACERO (cm^2)No. DE BARRA
PROPUESTASEPARACION (cm)Losa superiorExterior9.03414Losa
superiorExterior por temperatura3.06323Losa
superiorInterior5.67422Losa superiorInterior por
temperatura3.06323Losa inferiorInterior5.67422Losa inferiorInterior
por temperatura3.06323Losa inferiorExterior9.03422Losa
inferiorExterior por temperatura3.06323Paredes
lateralesExterior9.03414Paredes lateralesExterior por
temperatura3.06323Paredes lateralesInterior5.67422Paredes
lateralesInterior por temperatura3.06323Pared
centralVerticales5.67422Pared centralHorizontales ( por
temperatura)3.06323
VOLUMEN DE MATERIALES
Volumen de concreto
Losa superior (m^3)5.5704Losa Inferior (m^3)5.5704Pared interior
(m^3)1.848Paredes laterales (m^3)4.8576Total de concreto
(m^3)17.8464
Volumen de acero
LOSAS HORIZONTALES LECHO EXTERIORLOSAS HORIZONTALES LECHO
INTERIOR
Acero principalAcero principalLargo de barras (m)4.72Largo de
barras (m)4.72Numero de barras42.86Numero de barras27.27total de
ml202total de ml129Varilla a utilizar #4Varilla a utilizar #4Total
de varilla (kg)201.48Total de varilla (kg)128.21
Acero por temperaturaAcero por temperaturaLargo de barras
(m)6.06Largo de barras (m)6.06Numero de barras20.261Numero de
barras20.261total de ml122.78total de ml122.78Varilla a utilizar
#3Varilla a utilizar #3Total de varilla (kg)68.39Total de varilla
(kg)68.39
PAREDES LATERALES LECHO EXTERIORPAREDES LATERALES LECHO
INTERIOR
Acero principalAcero principalLargo de barras (m)1.9Largo de
barras (m)1.9Numero de barras42.86Numero de barras27.27total de
ml81total de ml52Varilla a utilizar #4Varilla a utilizar #4Total de
varilla (kg)81.10Total de varilla (kg)51.61
Acero por temperaturaAcero por temperaturaLargo de barras
(m)6.06Largo de barras (m)6.06Numero de barras8.00Numero de
barras8.000total de ml48.48total de ml48.48Varilla a utilizar
#3Varilla a utilizar #3Total de varilla (kg)27.00Total de varilla
(kg)27.00
PAREDES CENTRAL AMBOS LECHOS
Acero principalLargo de barras (m)1.9Numero de barras8.36total
de ml16Varilla a utilizar #4Total de varilla (kg)15.83
Acero por temperaturaLargo de barras (m)6.06Numero de
barras8.00total de ml48.48Varilla a utilizar #3Total de varilla
(kg)27.00
TOTAL DE ACERO REQUERIDO (kg)1392.04
HOJA DE APOYO
F'C CONCRETO180200250300350
GranularesOtrosTabla de varillas ELEGIRDiametro Nominal
(mm)diametro cmsDiametro nomnal (pulg)Area (cm2)Peso(kg/m)26.40.64
1/4 0.320.2512.57.90.79 5/160.490.38439.50.95 3/8
0.710.557412.71.27 1/2 1.270.996515.91.59 5/8 1.991.56619.11.91 3/4
2.872.25722.22.22 7/8 3.873.034825.42.5415.073.975928.62.861 1/8
6.425.0331031.83.181 1/4 7.946.2251134.93.491
3/89.577.5031238.13.811 1/211.48.938
f'cB (beta)Porcentaje balanceadoPorcentaje maxporcentaj
minporcentaje
min1500.850.01529702760.01147277070.0034523810.0072901481800.850.01835643310.01376732480.0034523810.00798595712000.850.02039603670.01529702760.0034523810.00841793792500.850.02549504590.01912128450.0034523810.00941154072800.850.02855445140.02141583860.0034523810.00996023843000.840.03007986930.0225599020.0034523810.01030982623500.800.03359347230.02519510420.0034523810.0111358851
4000.760.03667858710.02750894030.0034523810.01190476194500.730.03933521370.02950141030.0034523810.01262690685000.690.04156335220.03117251410.0034523810.01330992845500.660.04336300250.03252225190.0034523810.01395957075600.650.0436715140.03275363550.0034523810.0140859042