*Created by ganjar budiarto*PERATURAN MENTERI TENAGA KERJA RI
NO. PER-02/MEN/1983 TENTANG INSTALASI ALARM KEBAKARAN OTOMATIKRuang
lingkup- Perencanaan- Pemasangan,- Pemeriksaan- Pengujian-
Pemeliharaan
Created by ganjar budiarto
-
*Created by ganjar budiarto*INSTALASI ALARM KEBAKARAN
OTOMATIK
TUJUAN AGAR KEBAKARAN DAPAT TERDETEKSI SEDINI MUNGKIN, SEHINGGA
TINDAKAN YANG DIPERLUKAN DAPAT SEGERA DILAKUKAN.
Created by ganjar budiarto
-
INSTALASI ALARM KEBAKARAN OTOMATIKRef : Permenaker
02/83BateraiIndikatorManual / DetektorResistor=
-
*Created by ganjar budiarto*PIK(MCFA) SHFGMBZone 1Zone 2Zone
3
Created by ganjar budiarto
-
*Created by ganjar budiarto*
Created by ganjar budiarto
-
*Created by ganjar budiarto*JENIS DAN TIPE DETEKTORULTRA
VIOLETINFRA REDFIXED TEMPERATURERATE OF RISEIONIZATIONOPTICPush
bottom Full downbreak glass Manual
Created by ganjar budiarto
-
*Created by ganjar budiarto*Merk :Model :Instalatir :Pengesahan
No :Tgl:MCFA2. Mimic Panel3. Anounciator Panel
Created by ganjar budiarto
-
*Created by ganjar budiarto*ZONA DETECTIONPanas 40 titikAsap 20
titikNyala 20 titikZONE 1ZONE 2ZONE 3EOLEOLEOLLuas tiap zone
deteksi - ruang tanpa sekat mak. 2000 m2 - terdapat sekat mak. 1000
m2
Created by ganjar budiarto
-
INSPEKSI HARIAN(SETIAP PENGGANTIAN SHIFT)
1.FIRE ALARM1.1Periksa control panel Indikator Suplai daya
listrik, Harus stand by ONApakah ada indikasi lain (Fault / Fire /
Silence)
1.2Periksa Buku harian , Apakah ada catatan dalam buku
harian.
1.3Catat kondisi status sistem deteksi dan alarm dalam buku
harian.
-
Catatan Piket HarianMinggu, 18 AgT 2002Jam 22,15Fire AlarmZone
16 (Lt 4)Siaga kebakaran(Alarm palsu)
Telah di Risettetap sensing
Bell silence
Gangguan belum ditemukanTtdKetua piket A
Serah terimaSenin, 19-08-2002TtdKetua piket B
-
INSPEKSI MINGGUAN (58)
2.FIRE ALARM2.1Periksa control panel Indikator Suplai daya
listrik, Harus stand by ONApakah ada indikasi lain (Fault / Fire /
Silence)
2.2Lakukan test semua fasilitas indikator. (Simulasi) Apabila
terdapat kelainan harus segera dilaporkan dan segera dilakukan
langkah-langkah sebagaimana mestinya
2.3Periksa Buku harian , Apakah ada catatan dalam buku
harian.
2.4Catat kondisi status sistem deteksi dan alarm dalam buku
harian.
-
INSPEKSI BULANAN (59)
3.FIRE ALARM3.1Periksa control panel Indikator Suplai daya
listrik, Harus stand by ONApakah ada indikasi lain (Fault / Fire /
Silence)
3.2Lakukan test semua fasilitas indikator. (Simulasi) Apabila
terdapat kelainan harus segera dilaporkan dan segera dilakukan
langkah-langkah sebagaimana mestinya
3.3.Test status (Kondisi)-Test detektor/Tombol manual-Test open
circuit3,4Kebersihan panel3,5,Periksa Buku harian , Apakah ada
catatan dalam buku harian.
3.6Catat kondisi status sistem deteksi dan alarm dalam buku
harian.
-
INSPEKSI TAHUNAN (60) Disaksikan pengawas
4.FIRE ALARM4.1Periksa control panel Indikator Suplai daya
listrik, Harus stand by ONApakah ada indikasi lain (Fault / Fire /
Silence)
4.2Lakukan test semua fasilitas indikator. (Simulasi) Apabila
terdapat kelainan harus segera dilaporkan dan segera dilakukan
langkah-langkah sebagaimana mestinya
4.3Test detektor/Tombol manual (20 % / kel)4.4Test open circuit,
tiap zone4,5Kebersihan panel4,6,Periksa Buku harian , Apakah ada
catatan dalam buku harian.
4.7Catat kondisi status sistem deteksi dan alarm dalam buku
harian.
-
PEMELIHARAAN, PEMERIKSAAN, PENGUJIAN FIRE ALARMPanel indikator
(stanby On)Periksa status indikatorMembunyikan alarm Test fungsi
sistem pada panel Periksa battery Test fungsi sistem
interconeksiTest fungsi detektor (20%HRVV-----BL----V
--THVVVVVVVMG--VV---Kebersihan panel--VV-V V-Test tombol manual-V
V-Test kondisi gangguan
-
*Created by ganjar budiarto*Bentuk 66 K (A)Spesifikasi Teknik
Instalasi Alarm Kebakaran Otomatik
NoPeralatanMerk/ModelJumlahStatusKeterangan1Panel
control2Announciator3Detektor panas4Detektor asap5Detektor
nyala6Detektor gas7Tombol manual8Alarm bell9Sinyal lampu
alarmCatatan :
Created by ganjar budiarto
-
*Created by ganjar budiarto*Bentuk 66 K (A)Data
pemasanganInstalasi Alarm Kebakaran Otomatik
NoLokasiZoneDetektorAlarmStatusGasNyalaPanasAsapTPMBellLamp
Created by ganjar budiarto
-
*Created by ganjar budiarto*HASIL PEMERIKSAAN DAN
PENGUJIANINSTALASI ALARM
NoPemeriksaan/PengujianHasilSyarat-syarat1Fungsi kerja
panel2Test Alarm3Test Foult4Interkoneksi
NoTanggalPelaksanaTanda tangan1234
Created by ganjar budiarto
-
*Created by ganjar budiarto*INTERCONECTION FIRE ALARM
SYSTEMDETEKTOR KEBAKARANLIFTOff
POMPAHYDRANTsupply dayaACOff
PRESS FANOnSPRINKLER(FS)Pasal 23Bangunan yang memiliki instalasi
alarm kebakaran otomatik maka harus dihubungkan dengan instalasi
listrik lift.
Created by ganjar budiarto
-
*Created by ganjar budiarto*CONTROL FIRE
INDIKATORDISCHARTCONTROL PANELBUZERALARMHEATSMOKEVALVEINSTALASI
PEMADAM KEBAKARANAUTOMATIC TOTAL FLOODING SYSTEMMedia pemadam Halon
(F, Cl, Br)
!!!!!!!!!!!!Mengandung potensi bahayakeracunan
HARUS MEMILIKI IJIN K3
Created by ganjar budiarto
-
*Created by ganjar budiarto*
Created by ganjar budiarto
-
SISTEM DETEKSI ALARM & PEMADAM OTOMATIK*Created by ganjar
budiarto*
DATA TEKNIS PEMASANGANLokasi RuanganKeteranganAplikasi System
*)Local ProtectionTotal FloodingJenis MediaJumlah. Tabung x kgTotal
: kgVolume ruang. M3HASIL PEMERIKSAAN
Created by ganjar budiarto
-
*Created by ganjar budiarto*
FC-3-1-10PerfluorobutaneC4F10HBFC-22B-1BromodifluoromethaneCHF2BrHCFC
Blend ADichlorotrifluoroethane HCFC-123 (4. 75 %)
CHCl2CF2Chlorodifluoromethane HCFC-22 (82%)
CHClF2Chlorotetrafluoroethane HCFC-124 ( 9. 5%)
CHClFCF3Isopropenyl-1-methylcyclohexene 3. 75
%)HCFC-124ChlorotetrafluoroethaneCHClFCF3HFC-125PentafluoroethaneCHF2CF3HFC-227
eaHeptafluoropropaneCF3CHFCF3HFC-23TriflouromethaneCHF3IG-541Nitrogen
(52%) N2Argon (40%) ArCarbondioxide (8%) CO2MEDIA PEMADAM CLEAN
AGENT(Dikutip dari NFPA 2001)
Created by ganjar budiarto
-
*Created by ganjar budiarto*CO2Lapisan Ozone
Created by ganjar budiarto
-
*Created by ganjar budiarto*Clean agentLC 50NOAELLOAEL
FC-3-1-10> 80.0 %40.0 %> 40.0 %HBFC-22B-110.8 %2.0 %3.9
%HCFC Blend A64.0 %10.0 %> 10.0 %HCFC-12423-29 %1.0 %2.5
%HFC-125>70.0 %7.5 %10.0 %HFC-227 ea>80.0 %9.0 %10.5
%HFC-23> 65.0 %50 0 %> 50 0 %IG-541N/A43.0 %7.5 %Halon
1301>80.0 %5.0 %5.0 %
TABEL 4Toxicity Information(Dikutip dari NFPA 2001)LC 50 :
Concentration lethal 50 % tikus percobaan mati dalam 4 jamNOAEL:No
Observable Adverse Effect Level LOAEL:Lowest Observable Adverse
Effect Level
Created by ganjar budiarto
-
*Created by ganjar budiarto*INVESTIGATORMedia
NRL3MNMERIfervalGLCCAnsul
FC-3-1-10 5.2 5.95.0 5.5 - -HFC 124- -- 6.4 - -HFC 227ea 6.6
-6.3 5.85.9 -HBFC 22B14.1 -4.4 3.93.9 -HFC 2312 -12.6 1212.7
-HFC-1259 -9.4 8.1- -IG 541- - - - - 29.1Halon 1301 3.1 3.92.9 33.5
-
Keterangan NRL:Naval Research laboratory NMERI:New mexico
engineering research instituteGLCC: great lakes chemical
coMpanyTabel 5DATA HASIL UJI COBA TERHADAP HEPTANE FLAMETOTAL
FLOODING QUANTITY (W/V: lb/cu ft) (Dikutip dari NFPA 2001)
Created by ganjar budiarto
-
*Created by ganjar budiarto*MediaVOLUME % INERTINGi-
BUTANEMETHANEPROPANE
FC-3-1-10 6.710.3HFC 124---HFC 227ea 11.3--HBFC 22B1 --11.3HFC
23-20.220.2HFC-125-14.715.7IG 541-43.049.0Halon 1301 6.7-7.7
Tabel 6DATA HASIL UJI COBAINERTING CONCENTRATION (V/V: %)(Dikutp
dari NFPA 2001)
Created by ganjar budiarto
-
POTENSI PEMANASAN GLOBAL DAN WAKTU TINGGAL DI ATMOSFIR*Created
by ganjar budiarto*
NamaDagangNama SebutanRumus KimiaPotensi Pemanasan GlobalWaktu
Tinggal di
AtmosfirFE-13FE-125FM-200FE-36CEA-308CEA-410PerfluorohexaneNN-100ArgotecArgoniteInergenKabut
airAerosol partikulat padatHFC 23HFC 125HFC 227eaHFC
236faFC-2-1-8FC-3-1-10FC-5-1-14IG-100IG-01IG-55IG-541CHF3CF3CHF2CF3CHFCF3CF3CH2CF3C3F8C4F10CF130.840.611.9-18.2-0000.826433375209260026003200gas
permanengas permanengas permanengas permanen
Created by ganjar budiarto
-
*Created by ganjar budiarto*Tekanan mak. 50 barTemp pecah 97o
C
Created by ganjar budiarto
*Created by ganjar budiarto*Created by ganjar budiarto*Created
by ganjar budiarto*Created by ganjar budiarto*Created by ganjar
budiarto*Created by ganjar budiarto*Created by ganjar
budiarto*Created by ganjar budiarto*Created by ganjar
budiarto*Created by ganjar budiarto*Created by ganjar
budiarto*Created by ganjar budiarto*Created by ganjar
budiarto*Created by ganjar budiarto