1 Model Remarks Introduction and Features Fengshen Series
31
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Aer Conditionat

1

Model Remarks

Introduction and Features

Fengshen Series

Page 2: Aer Conditionat

2

COOLING HEATING

42000 /4314 /5764 /

/ /

Sound Power Level dB (A)(H/M/L)***Dimension (H/W/D) ( mm)Dimension of Package(H/W/D) (mm)Net Weight /Gross Weight(kg)

Swing Motor ModelOutput of Swing Motor (W)Fuse (A)Sound Pressure Level dB (A)(H/M/L)

EvaporatorPipe Diameter (mm)Row-Fin Gap(mm)Coil length (l) x height (H) xcoil width (L)

Fan Motor Capacitor (uF)Fan Motor RLA(A)Fan Type-PieceDiameter-Length (mm)

Model of Indoor UnitFan Motor Speed (r/min)(H/M/L)Output of Fan Motor (w)Input of Heater (w)

1790 x 540 x 380

1960 x 670 x 475

58/72

ModelFunctionRated VoltageRated FrequencyTotal Capacity (Btu/h)Power Input (W)Rated Input (W)

4PCB 3.15A Transformer 0.2A

53

/

Φ73-1.5

839.5 x 430x43

SM016

Indoorunit

KF-120L/A21-M

460/420/380

100/

4.5/

Centrifugal Fan-1Φ379x180.5

Aluminum fin-copper tube

5.0/

Dehumidifying Volume (l/h)EER / C.O.P (W/W)

KF-120LW/A21-M

380V 3N~

Rated Current (A)

Air Flow Volume (m3/h) (H/M/L)**

50Hz

1500

Specifications and Technical Parameters

In case of any change of parameter data ,refer to the actual data specified on the nameplate of the unit.

Page 3: Aer Conditionat

KF-120W/lA21-M JT160BCBY1L

scroll65.8

/3750

InternalCapillary

Capacitor

–7 ~ 43Alum inum fin-copper tube

Φ9.522-1.8

1218X658X224

840

68/

3.5

/

Axial fan –2Φ450

Auto defros tT1I

IP24

2.5

0.6

60

/

1250 x 950 x 412

1280 x 1110 x 450

112/123

R22 / 3.85

Φ12Φ19

510

Connection Pipe

OuterDiam eterMaxDis tance

Length (m )Liquid Pipe (m m )Gas Pipe (m m )Height (m )Length (m )

Dim ens ion (H/W/D) ( m m )Dim ens ion of Package(H/W/D) ( m m )Net Weight /Gross Weight(kg)Refrigerant Charge (kg)

Perm iss ible Excess iveOperating Pressure for thePerm iss ible Excess iveOperating Pressure for theSound Pressure Level dB (A)(H/M/L)Sound Power Level dB (A)(H/M/L)

Defros ting MethodClim ate TypeIsolationMois ture Protection

Fan Motor Capacitor (uF)Air Flow Volum e of OutdoorUnitFan Type-PieceFan Diam eter (m m )

Coil length (l) x height (H) xcoil width (L)Fan Motor Speed (rpm )(H/M/L)**Output of Fan Motor (W)Fan Motor RLA(A)

Working Tem p Range (℃)CondenserPipe Diam eter (m m )Rows-Fin Gap(m m )

Outdoorunit

Model of Outdoor UnitCom pressor ModelCom pressor TypeL.R.A. (A)Com pressor RLA(A)Com pressor Power Input(W)Overload ProtectorThrottling MethodStarting Method

In case of any change of parameter data ,refer to the actual data specified on the nameplate of the unit.

Fengshen Series

Page 4: Aer Conditionat

COOLING HEATING

42000 445004650 43006100 8500

/ /

Sound Power Level dB (A)(H/M/L)***Dimension (H/W/D) ( mm)Dimension of Package(H/W/D) ( mm)Net Weight /Gross Weight(kg)

Swing Motor ModelOutput of Swing Motor (W)Fuse (A)Sound Pressure Level dB (A)(H/M/L)

EvaporatorPipe Diameter (mm)Row-Fin Gap(mm)Coil length (l) x height (H) xcoil width (L)

Fan Motor Capacitor (uF)Fan Motor RLA(A)Fan Type-PieceDiameter-Length (mm)

Model of Indoor UnitFan Motor Speed (r/min)(H/M/L)Output of Fan Motor (w)Input of Heater (w)

1790 x 540 x 380

1960 x 670 x 475

58/72

ModelFunctionRated VoltageRated FrequencyTotal Capacity (Btu/h)Power Input (W)Rated Input (W)

4PCB 3.15A Transformer 0.2A

53

/

Φ73-1.5

839.5 x 430x43

SM016

Indoorunit

KFR-120L/A21-M

530/490/460

10035003.5

/Centrifugal Fan-1Φ379x180.5

Aluminum fin-copper tube

52.58/3.02

Dehumidifying Volume (l/h)EER / C.O.P (W/W)

KFR-120L/A21-M

380V 3N~

Rated Current (A)

Air Flow Volume (m3/h) (H/M/L)**

50Hz

1500

In case of any change of parameter data ,refer to the actual data specified on the nameplate of the unit.

Page 5: Aer Conditionat

KFR-120W/lA21-MJT160BCBY1L

scroll/

65.83750

InternalCapillary

Capacitor

–7 ~ 43Alum inum fin-copper tube

Φ9.522-1.8

1218X658X224

840

68/

3.5

/

Axial fan –2Φ450

Auto defros tT1I

IP24

2.5

0.6

60

/

1250 x 950 x 412

1280 x1110 x 450

112/123

R22 / 3.75

Φ12Φ19

510

Outdoorunit

Model of Outdoor UnitCom pressor ModelCom pressor TypeL.R.A. (A)Com pressor RLA(A)Com pressor Power Input(W)Overload ProtectorThrottling MethodStarting MethodWorking Tem p Range (℃)CondenserPipe Diam eter (m m )Rows-Fin Gap(m m )Coil length (l) x height (H) xcoil width (L)Fan Motor Speed (rpm )(H/M/L)**Output of Fan Motor (W)Fan Motor RLA(A)Fan Motor Capacitor (uF)Air Flow Volum e of OutdoorUnitFan Type-PieceFan Diam eter (m m )Defros ting MethodClim ate TypeIsolationMois ture ProtectionPerm iss ible Excess iveOperating Pressure for thePerm iss ible Excess iveOperating Pressure for theSound Pressure Level dB (A)(H/M/L)Sound Power Level dB (A)(H/M/L)Dim ens ion (H/W/D) ( m m )Dim ens ion of Package(H/W/D) ( m m )Net Weight /Gross Weight(kg)Refrigerant Charge (kg)

Connection Pipe

OuterDiam eterMaxDis tance

Length (m )Liquid Pipe (m m )Gas Pipe (m m )Height (m )Length (m )

In case of any change of parameter data ,refer to the actual data specified on the nameplate of the unit.

Page 6: Aer Conditionat

3 Component Name

Air out

Display screen

Front panel

Air-in panelRemote controller

Air outlet

Air in

Sealing tapeDisplay screen

Air in

Connecting pipe

Drainage pipe

Air out

Page 7: Aer Conditionat

4 Overall and Installing Dimension

Overall and Installing Dimension of Indoor Unit

>30cm

>5cm

Rear

>4cm

>25cm Front>200cm

>25cm

Pipe Side:30cm at least

Fengshen Series

Page 8: Aer Conditionat

Overall and Installing Dimension of Indoor Unit

Unit: mm

Over 600

Over 600Over 600

Over 600

Nut Bolt

Wrench

Page 9: Aer Conditionat

55555 Electrical Diagram

In case of any change in the Electrical Diagram shown above, please follow the drawing on cabinet.

Fengshen Series

Page 10: Aer Conditionat

Controller Function Manual and Operating Instructions

6.1 Controller Function Manua 1 6.1.1 Temperature Parameters Indoor preset temperature (Tpreset) Indoor ambient temperature (Tamb.)

6.1.2 Basic Functions Once started under any mode, the compressor will keep running within 6 minutes. Once stopped, it cannot be restarted until after 3-minute lag. 6.1.2.1 Cooling Mode 6.1.2.1.1 Cooling Conditions and Process When Tamb.≥Tpreset+1 , the unit will run under cooling mode, in which case the compressor and outdoor fan will be ℃

started, the indoor fan will run at preset speed. When T amb≤Tpreset -1 , the unit will be stopped under cooling mode,℃ in which case the compressor and outdoor fan will be stopped and the indoor fan will run at preset speed. When Tpreset -1 <T℃ amb.< Tpreset +1 , the unit will maintain its original operating status.℃

6.1.2.2 Dehumidifying Mode 6.1.2.2.1 Dehumidifying Conditions and Process When T amb. Tpreset +2 , the unit will run under cooling mode, in which case the compressor and outdoor fan will be ℃started, the indoor fan will run at low speed. When Tpreset -2 ≤T℃ amb.≤Tpreset +2 , the compressor, and outdoor unit will run 6 minutes and stop 4 minutes in repeated ℃cycle, while the indoor fan will run at low speed.

When T amb.< Tpreset -2 , the c℃ ompressor and outdoor fan will be stopped. Indoor fan will run at low speed.

Under this mode, the switchover vlave can not be energized, and the temperature can be set within a range from 16

to 30 .The initial value is 25 .

Under this mode, the switchover vlave can not be energized, and the temperature can be set within a range from 16 to

30 .The initial value is 25 .The fan speed is forced to low sepped and unadjustable.No response if FAN button ispressed (including front panel and remote controller's).

Tpreset +1℃

Tpreset -1℃

Start cooling

Original operating status

Stop cooling ≥6 min.≥6 min. ≥3 min.

Tamb

Compressor

Outdoor fan

Indoor fan Preset speed

Run Stop

Compressor

Outdoor fan

Indoor fan

Run

Stop

Cooling

Dehumidifying

low speed

6 min.

Stop

6 min. 6 min. 4 min. 4 min.

low speed

Tpreset +2℃

Tpreset -2℃

amb.

66666

Page 11: Aer Conditionat

If T amb.≥Tpreset +1 , the compressor and outdoor fan will be stopped, the switchove℃ r valve will remain energized and the indoor fan will stop after 10s when it runs at low speed.When Tpreset -1 <T℃ amb.< Tpreset +1 , the unit will maintain its original operating status.℃

Under heating mode, the temperature can be set within a range from 16 to 30 . The initial value is 25 .℃ ℃ If the unit is switched off under heating mode or switched from heating mode to another mode, the 4-way valve will be de-energized after 2-minute lag.For the first startup of compressor , the exhaust protection will be shielded for 1 min.

6.1.2.5 AUTO Mode Under this mode, the system will automatically select its run mode (cooling, dehumidifying, heating or fan) with the change of ambient temperature. Once a mode is started, the unit will run at least 30 seconds before it can the run status under auto mode according to the ambient temperature. 6.1.3 Other Control 6.1.3.1 Sleep Function If the controller is under cooling or dehumidifying mode, the preset temperature will be increased by 1 one hour ℃

after running under sleep mode and will be increased by another 1 after two hours. The temperature will increased ℃

by 2 within two hours. After that, the unit will run at this temperature. ℃

6.1.2.3 Heating Mode (no this mode for cooling only unit)

When T amb.≤Tpreset -1 , the unit will run under heating mode, in ℃ which case the switchover valve, compressor and outdoor fan will be started, while the indoor fan will run in 90s at most.

6.1.2.3.1 Cooling Conditions and Process

Tpreset +1℃

Tpreset -1℃

Compressor

Outdoor fanIndoor fan

Switchover valve

Tamb

6 min.3 n.

Run Stop

Start heating

Original operating status

Stop heating

low

6min. 6min.3min.

Low speed

6.1.2.3.2 Defrosting Conditions and Process When detecting any frost in condenser, the system will start defrost, in which case the compressor will continue to run,andoutdoor fan,4-way valve and indoor fan stop running.The auxiliary electric heater,if any, will be stopped firstly. After 1-min lag, the switchover valve, indoor fan and outdoor fan will be stopped. Upon detecting completion of defrosting,the outdoor fan and 4-way valve will stat to run simultaneously,the indoor fan will run in 90s at most(overcurrent protection can not bedetected),and the compressor will maintain its original operating status.

Defrosting Notice:If auxiliary electric heater is stopped ,the indicator will blink and place for displaying ambient and presettemp.Once defrosting is completed ,the display of ambient will come back.

Compressor

Outdoor fan Indoor fan

During defrosting

4-way valve

Run Stop

6.1.2.4Fan Mode Indoor fan will run at preset speed

Auto Low Medium High

The temperature can be set within a range from 16 to 30 . The initial value is 25 .�

Fengshen Series

Page 12: Aer Conditionat

Set the Temperature Tpreset

T Bpreset B

T Bpreset B+2℃

T Bpreset B+1℃

1 hour 2 hours Over 2 hours

T Bpreset B

T Bpreset B-1℃

T Bpreset B-2℃

1 hour 2 hours Over 2 hours

Set the Temperature Tpreset

If the controller is under heating mode, the preset temperature will be decreased by 1 one hour after running under ℃

sleep mode and will be decreased by another 1 after two hours. The temperature wi℃ ll decreased by 2 within two ℃

hours. After that, the unit will run at this temperature.

No sleep function under FAN or AUTO mode,and it can not be set.

1.The controller with setting temp display will display temp with the change of it after sleep function is set.

3.After the sleep function is set,if press buttons except sleep button on the panel ,the sleeping time won't been recalculated,

if press buttons of the remote control ,it will be recalculated.

2.Sleep setting will be cleared upon switchover between modes, press of temp button on front panel and stop of unit, what'smore, sleep function can not be memorized.

6.1.3.2 Timer ON/OFF function 6.1.3.2.1Timer ONWhen the timer is set to ON, the system will be under Timer OFF status. At the time for Timer ON, the controller will remain under its preset mode. The time interval for Timer ON or OFF is 0.5h, and can be set within 0.5 - 24 hours.

You can set Timer OFF function when the unit is under ON status. Upon the time of Timer OFF the system will be switched off. The time interval for Timer OFF is 0.5h, and can be set within 0.5 - 24 hours.

6.1.3.2.2Timer OFF

6.1.3.2.3 Others1.If the remote control can display timing ,the timing is unnecessary to decrease after it is set.2.If timing is set,if repress buttons except TIMER on front panel or remote control ,the timing should be recalculated.

3.When controller for cooling only receives signal of stopping the unit of remote-control heating and after the unit is stopped,

time reaches,the whole unit will run under the running status before stop of the unit.

if set Timer ON of the unit by remote controller, the controller will receive the signal and setting is available.Once setting

6.1.3.3 Control of Swing Motor

Control it on or off with the swing key.If the indoor fan stops running ,the swing motor mustn't be started.

If the controller is powered on or receives the signal sent by the valid keys , the buzzer will beep.

6.1.3.4 Buzzer

Under this mode ,the indoor fan will automatically select high,mid,or low speed with the change of ambient temp,once

6.1.3.5 Auto Fan Speed Control of Indoor Fan

started,each of the speed can be switched by conditions in at least 30S.

indicator will blink every 6 sec.Different times of blink indicates different kind of protection.

E1: High pressure protection of compressor: once;

E2 : Indoor anti-freezing protection: twice;

E3: Low pressure protection of compressor: 3 times;

E4: High temperature protection of exhaust hose: 4 times;

E5: Overcurrent protection :5 times ;

E6 : Static dedusting protection: 6 times,defrosting: 7 times;

6.1.3.6 Indicator Control

If the controller is energized, the indicator will be red under standby status.Any one of the following cases happens,green

The indicator is always blinking under forcible cooling or heating;

Page 13: Aer Conditionat

Memory content, Mode ,Swing, Set temp., Set fan speed,air change,Timer (if timing hasn't arrived and power is off, when the

power is on, the timing will be recalculated; If timing has arrived and the power is off, the unit will run at the mode upon the timing after powered on.

Upon powered on after powered off ,the unit can automatically start by the memory content.

6.1.3.6 Power-off Memory

Press the mode button and select the mode as follows :

Auto,Cool,Dehumidify,Fan ,Heat (Cooling and heating type) Auto,Cool,Dehumidify,Fan( Cooling only type)

6.1.4.1 Mode Button

Press the fan speed button and select as follows:Auto,low,mid,hi

Under dehumidify mode,the fan speed is unadjustable.

6.1.4.2 Fan Speed Button

1.Every press of the temp button or ,setting temp will increase or decrease by 1 ,and adjustable temp range is 16 to

30 .Under auto mode,these buttons are invalid.If simultaneously press them,the function of all buttons on the panel willbe shielded, if repress them again,the shield function will be released.

6.1.4.3 Setting Temp Button (Temp and )

If heat mode is diplayed on the handset used to control the unit and the air conditioner is cooling only type,the unit will not6.1.4 Buttons

accept any signal except for turning off the unit.

If press the invalid buttons (anion,humidity, energy saving ),the buzzer will not respond,but for reserved air exchange it beeps.

The relay works after pressing the buttons 2 s.

2. For the first energization of the unit, if any valid button does not be pressed:

1) If press , the unit will immediately enter into forced heating operation , all loads will be started, indoor and outdoor fan will

run at high speed and all characters will be displayed.If it is detected that ambient temp or evaporator tube temp is too high or

low, the buzzer will beep.The unit will stop under normal standby status in 5 min.

2) Under OFF status of the unit,pressTimer button to set Timer on, and under ON status of the unit , press this button to set

Timer off.Matching wiith and ,if press this button, Timer,ON/OFF, Time, Hr will blink and then press or ,the timing will be increased or decreased by 0.5hr.3) If press , the unit will immediately enter into forced cooling operation , all loads except 4-way valve will be started, indoor and outdoor fan will run at high speed and all characters will be displayed.If it is detected that ambient temp or evaporator

tube temp is too high orlow, the buzzer will beep.The unit will stop under normal standby status in 5 min.� The above functions are only for test.

There is not forced heating for cooling only unit.

If press Timer button ,Timer,ON/OFF,hr and time will blink,in which case,adjust the timing through the buttons and .The6.1.4.4 Timer Button

setting range is 0.5 to 24 hr.If press timer again to confirm timer, the mark of Timer on /off will be displayed but not blink.PressTimer again to cancel , but Timer on/off,the mark of Timer on /off won't display.If not pressing Timer to confirm,the unit will

If pressTimer button for the first time,Timer,ON/OFF,hr and time will be displayed by 0.0 hr (press Timer again to cancel ).Presswhen setting time is 24hr, or press when setting time is 0.5hr.If timer display is 0.0 hr, press Timer again to cancel.

iresume its original setting in 10s.

If press Swing button once and indoor fan has run, swing motor will run.Repress this button, swing motor will stop running.6.1.4.5 Swing Button

If press Light button once,LED will display it.If repress it ,all displays on the screen except running indicator will be closed and6.1.4.7 Light Button(on displayer)

The LED can be controlled by the light button on the handset:if the light is valid,the screen display is valid;By the contraty,the6.1.4.8 Light Button(on remote control) LED lights,which is cycled like this.Every time of startup of the unit ,the light will be defaulted on .

light is invalid,all displays on the screen except running indicator will be closed.

It controls On and Off of controller.Every press of it, the on and off state will switch.

6.1.4.6 ON/0FF Button

Fengshen Series

Page 14: Aer Conditionat

� For floor standing unit with back light, its on or off can be controlled by Light button and it is allowed to on only there is display.

For floor standing unit with light case, its on or off can be controlled by Light button.

If the power is on, only power incon at the right lower corner is displayed under off status of the unit.

6.1.5 Icons Display

After starting the unit by remote controller or buttons, present setting running moe(cool,heat,dehumidify,fan,auto) will be displayed,

6.1.5.1

6.1.5.2 Mode Icon Display

and seting temp will also be displayed in tx seconds.

The small sector indicators will light or black orderly (circularly display).6.1.5.4 Swing Display

different for different fan speed for knowledge of speed.The internal small sector indictors are all light .

Corresponding fan speed(low,mid,high, auto) and dynamic sector icons will be displayed.The area of external big sector is6.1.5.3 Fan Speed Display

Middle speed:five-layer icon lights or blacks orderly from inner to outer --circularly displayLow speed:three-layer icon lights or blacks orderly from inner to outer --circularly display

High speed:seven-layer icon lights or blacks orderly from inner to outer --circularly display

Under auto mode,the unit will select low,mid or high fan speed and display corresponding icon according to detected temperature.

If the unit hasn't received timing signal for continuous 9s during timer setting,the timer display will disappear.6.1.5.5 Timer Display

During stop of the unit:if timer on is set,clock, ON, hr and corresponding timing will be displayed. During start of the unit:if timer off is set,clock, OFF, hr and corresponding timing will be displayed.

6.1.5.5 Sleep The crescent icon will be displayed during setting the sleeping.

When the light function is off,it only power icon is displayed.�

6.1.5.6 Low-voltage Protection

When the conpressor is running,and it is detected that the current exceeds 25A,the unit will stop by the indoor ambient temperature reaching preset temp.After the conpressor hasn¡¯t runned for 3 min.,the unit will automatically resume its

original running status.If there are more than 6 times protection (If the compressor hasn¡¯t runned for more than 6 min.,the times of protection will be cleared),theindicator light flickerd,and the unit not resume its original running status,so

press the ON/OFF key to stop the unit and repress the key to resume operation.

5.Under heat mode,if compresoor is running while outdoor fan is stopped(Hi-temp. protection),the detection will be shield till the outdoor fan resumes running.

4.Under heat mode,if the outdoor ambient temp. is lower than 0 or equal to 0 ,this detection will be shielded.

low,the system will enter into antifreeze protection status, in which case,the indicator will blink ,E2 will be displayed at the place

6.1.6 Protection 6.1.6.1 Indoor Antifreeze Protection When the unit is cooling under cool or dry mode(T amb Tpreset +2 ) , if it is detected that the evaporator tube temp is too

Thebuttons will not be shielded under antifreeze protection.been stopped for 3 min, the indicator will black, display will be resumed and the controller will run under setting mnode.

6.1.6.2 Compressor High-pressure Protection If high-pressure protection (including under off state of the unit) is detected in 3 successive seconds, the unit will close all loads

that compressor high-pressure protection is released in seccessive 6 seconds, the indicator will still blink and E1 will be displayed, in which case you have to press ON/OFF button to switch off the unit before you can clear E1 display and turn off the indicator. Repress ON/OFF button to resume the operation. 6.1.6.3 Compressor Low-pressure Protection

and shield all buttons and remote-control signal,meanwhile,the indicator will blink and only E1 will be displayed.If it is detected

, the complete unit will be stopped and the Indicator will blink. In 3 minutes, the unit will resume running automatically. If

1.After the compressor is started for 3min, if it is detected for 3 minutes successively that the low-pressure switch is broken

and repress it again to resume operation.the unit won't resme running automatically so as to remind the user of air leakage. Press ON/OFF button to switch off the unit low-pressure switch protection occurs 2 times successively, the indicator will blink and only E3 be displayed ,in which case

minutes later.

2.Under defrost mode, low-pressure switch signal can not be detected,which should be done after defrosting is finished 10

detection by pressing ON/OFF key to switch off the unit and pressing it again to start the unit. low pressure switch signal for purpose of air collection. Detection will resume automatically after 6 minutes,or you can resume 3.From the controller, you can press down SWING button and FAN SPEED button simultaneously to shield the detection of

where ambinet temp(if no,setting temp) is displayed and the other displays will also be kept.The compressor,outdoor fan,indoor fan and swing motor will keep their original status. When the evaporator tube temp resumes normal and the compressor has

Page 15: Aer Conditionat

will be stopped,the indicator blink and only E3 be displayed, in which case the unit cannot be restarted automatically. You 6.If it is detected that the low-pressure switch is off in successive30s when the compressor is stopped, the complete unit

have topress ON/OFF button to switch off the unit and press this key again to restart. 6.1.5.4 Exhaust Pipe High-temp. Protection

After the compressor is started, if the exhaust temperature is too high or exhaust sensor is in short circuit (or open circuit), the indicator will flickerand the unit will be stopped when the indoor ambient temperature reaches the preset value.After the compressor is stopped for 3 minutes, the complete unit will be restarted when the exhaust

temperature is resumed to normal. If above phenomena occurs twice continuously, the complete unit cannot be restarted automatically, the indicator will

blink and E4 will be displayed. Press ON/OFF key to switch off the unit and press it again to switch on the unit. If the exhaust temperature is normal, the unit will run under preset mode.

6.1.5.6 Low-voltage Protection

When the conpressor is running,and it is detected that the current exceeds 25A,the unit will stop by the indoor ambient temperature reaching preset temp.After the conpressor hasn¡¯t runned for 3 min.,the unit will automatically resume its

original running status.If there are more than 6 times protection (If the compressor hasn¡¯t runned for more than 6 min.,the times of protection will be cleared),theindicator light flickerd,and the unit not resume its original running status,so

press the ON/OFF key to stop the unit and repress the key to resume operation.

6.1.5.5 Indoor ultra-high temp. protection Under heating mode, if it is detected the temp. of evaporator pipe is too hi.,the outdoor fan will stop(defrosting won't be detected),if temp. gets right, outdoor fan will start running(defrosting will be detected).

6.1.5.7 Fault Code

Fault Code Definition E1 Compressor High-pressure Protection E2 Indoor Antifreeze Protection E3 Compressor Low-pressure Protection E4 Exhaust Pipe High-temp. Protection E5 Low-voltage Protection

Fengshen Series

Page 16: Aer Conditionat

77777

Disassemble Air-in Panel

Use screwdriver to unscrew the holding screw at the air-in frame, and forcefully pull out the air-in grill.

Fig.7-1

Screw

Operating Procedures / Photos

Disassemble Electric Box Cover

Unscrew the screws on the elctric box cover to remove it.

Fig.7-2

Fig.7-1

Fig.7-2

Screw

Temp sensor

Disassemble Front Panel

Unscrew the two screws fixing the front panel, and make the air-in panel off the clasp, disconnect the wiring terminals to remove the front panel. Fig.7-3

Screw

Fig.7-3

Disassembly Process of Indoor Unit

Disassembly and Assembly Procedures

Page 17: Aer Conditionat

Disassemble Air Outlet Assy

Unscrew the 3 screws connecting the air outlet and

top cover and 2 screws connecting left and right side

plate.

Fig.7-4,7-5

Air Outlet Assy

Fig.7-4Screw

Air Guard

Fig.7-5

Disassemble Air Guard

Unscrew the 12 screws on the air guard to remove theair guard.

Fig.7-6

Screw

Screw

Fig.7-6

Disassemble Electric Box

Unscrew the three screws at the electric box and pull out each terminals as shown in the figure to remove the

electric box.

Fig.7-7

Screw

Fig.7-7

Operating Procedures / Photos

Fengshen Series

Page 18: Aer Conditionat

Disassemble Chassis and Top Cover

Unscrew the 4 screws fixing air-in joint plate to remove it.

Unscrew the 3 screws fixing the mounted plate of water

tray to remove it.Fig.7-8

Air-in joint plate

Mounted plate

Screws

Fig.7-9

Unscrew the 2 screws fixing protective top cover to remove

Unscrew the 5 screws fixing the chassis to remove it.

Fig.7-9,7-10

Fig.7-8

Screws

Fig.7-10

Screws

Disassemble Protective Top Cover

Unscrew the 7 screws fixing top cover to remove it.

it.Pull out tube temp sensor.

Fig.7-11

ScrewsProtective Top Cover

Fig.7-11

water tray

Operating Procedures / Photos

Page 19: Aer Conditionat

Disassemble Auxiliary Electric Heater Assy

Unscrew the screws fixing the auxiliary electric heater Unscrew the 2 screws fixing the guard grill to remove it.

Only for cooling and heating unit

assy.and loosen the tie lines to remove it.

Fig.7-12

Guard grill

Auxiliary electric heater

Fig.7-12

Disassemble Evaporator

Unscrew the screws fixing the evaporator, and then pullUnscrew the 2 screws fixing the guard grill to remove it.

out the right and left side plate to remove the evaporator. Evaporator

Capillary assy

Disassemble Water Tray Assy

Remove the mounted plate of water tray and put out the right and left side plate to remove the water trayupwards. Water tray

Fig.7-13

Fig.7-13

Fig.7-14

Fig.7-14

Operating Procedures / Photos

Fengshen Series

Page 20: Aer Conditionat

Disassemble Guide Ring and Centrifugal Fan

Unscrew the nut in the middle of the centrifugal fan toTurn the guide ring clockwise to a position to remove it.

remove it. Fig.7-15

Guide ring

Centrifugal fan

Nut

Fig.7-15

Disassemble Propeller Housing and Mtor

it.Unscrew the nut fixing the motor to remove it.

Unscrew the screws fixing the propeller housing to remove

Fig.7-16

Propeller housing

Screw

Nut

Motor

Fig.7-16

Operating Procedures / Photos

Page 21: Aer Conditionat

Disassembly Process of Outdoor Unit

Operating Procedures / Photos

Disassemble Rear Grill

Screw off the six tapping screws at the rear side plate, valve support chassis and condenser side plate to remove the rear grill. Fig 7-17

Disassemble Top Cover Plate

Screw off the tapping screws around the top cover, and then pull the top cover upward to remove it. Fig 7-18

Disassemble Front Side Plate

Screw off the three tapping screws at the front side plate, and then pull the front side plate upward to remove it.

Rear Grill

Screw

Screw Top Cover

Fig 7-18

Front Side Plate

Screw

Fig 7-19

Fig 7-17

Fig 7-19

Fengshen Series

Page 22: Aer Conditionat

Operating Procedures / Photos

Disassemble Cabinet

Unscrew the screws around the cabinet to remove the cabinet. Fig 7-20

Disassemble Electric Box

Unscrew the screws around the electric box sub-assy to remove it. Fig 7-21

Disassemble Right Side Plate

Unscrew the screws around the right side plate to remover the right side plate. Fig 7-22

Screw

Cabinet

Fig 7-20

Screw

Fig 7-21

Right Side Plate

Screw

Fig 7-22

Page 23: Aer Conditionat

Operating Procedures / Photos

Disassemble Axial Flow Fan

Use spanner to twist off the nut of the fan and remove the fan. Fig 7-23

Disassemble Outdoor Motor

Unscrew the screws around the electric box sub-assy to remove it. Fig 7-24

Disassemble 4-Way Valve

Screw off the holding nut of the 4-way valve coil and remove the coil. Use wet cotton cloth to wrap the 4-way valve, unsold the four soldering points connecting the 4-way valve, and remove the 4-way valve. Be quick during the unsoldering process, pay attention to keep the wrapping cloth wet and do not allow the soldering flame to burn the compressor lead-out cable. Fig 7-25

Nut

Nut

Fig 7-23

Motor

Screw Fixing the Motor

Motor Support

Fixing Screw

Fig 7-24

4-Way Valve

Fig 7-25

Fengshen Series

Page 24: Aer Conditionat

Operating Procedures / Photos

Disassemble Valve

Unscrew the two screws fixing the valve, unsolder the connecting pipe of the valve, and remove the valve. Fig 7-26

Disassemble Capillary

Unsolder the soldering points between the capillary and other pipes to remove the capillary. Fig 7-27

Disassemble Compressor

Unscrew the four foot screws of the compressor and unsolder the connecting pipe to remove the compressor. Fig 7-28

Screw Liquid Valve Gas Valve Screw

Fig 7-26

Capillary

Fig 7-27

Foot Screw

Fig 7-28

Page 25: Aer Conditionat

8

1

28 27

2

26 19~2425 18

17 16

10 11

11

3 4 5 6 7

15

13

9

14

8

A

A

Exploded View and Components and Parts List

Exploded View of Components and Parts of Indoor Unit

Fengshen Series

Page 26: Aer Conditionat

KF-120L/A21-M KFR-120L/A21-M1 Underpan 22224432 22224432 1 2 Left Side Plate Assy 01304278 01304278 1 3 Rear Plate Assy 01304277 0130427701 1 4 Top Cover Assy 22244437 22244437 1 5 Right Side Plate Assy 01304279 01304279 1 6 Evaporator Assy 010044461 010044461 1 7 Water Tray Assy 12414210 12414210 1 8 Assistant Heater Assy / 32004401 19 Air Guard Assy 01364436 01364436 1 10 Air Outlet Assy 200044344 200044345 1 11 Air Louver 10524431 10524431 6 12 swing motor 15214215 15214215 113 Air Guider 10514435 10514435 614 Display Board 305434511 305434501 1 15 Panel Assy 20004433 20004433 1 16 Air Intake Assy 200044371 200044371 1 17 Filter Assy 11124432 11124432 1 18 Main Board 30033051 30033050 1 19 Electric Box 01404211 01404211 1 20 Terminal Board (5位) 42010258 42010258 1 21 Transformer SC28D 43110237 43110237 1 22 Fan Capacitor 33010010 33010010 1 23 Senor Insert 42020063 42020063 1 24 4 Core Sensor 39000190 390001372 1 25 Diversion Circle 10374435 10374435 1 26 Snail Shell 12104444 12104473 1 27 Centrifugal Fan 10314401 10314401 1

Fan Motor LN100C 15014423 / 1 Fan Motor LN100B / 15014402 1

NO Name of Material QTY

28

Code of Material

Components and Parts List of Outdoor Unit

The above date are subject to change without prior notice

Page 27: Aer Conditionat

28 27 26

1

43

2

25 24 17

18~23

16

15

14

13

8765 9

10~12

Exploded View of Outdoor Unit

Fengshen Series

Page 28: Aer Conditionat

KF-120W/lA21-M KFR-120W/lA21-M1 Front Grill 22414102 22414102 22 Cabinet 01435436 01435436 13 Rear grill 01475432 01475432 14 Top Cover 01255262 01255262 15 Condenser Assy 011054362 0110516701 16 Motor Support Assy 01705433 01705433 17 Motor LW92A 15015421 15015421 28 Clapboard Assy 01235440 01235440 19 Gas-liquid Separator 07225433 07225011 110 4-way Valve Assy / 030234321 111 4-way Valve body / 43000405 112 4-way valve coil / 430004002 113 Suction Pipe Assy 03635452 03635446 114 Valve Assy 1/2" 071302362 071302362 115 Valve Assy 3/4" 07103401 07103401 1

Compressor JT160BCBY1L 00100113 00100113 1

Overload Protector built in built in17 Axial Flow Fan 10338731 10338731 218 Electrical Box 01414201 01414201 119 Wire Clamp 71010103 71010102 120 AC Contactor 44010226 44010226 1

21Over Current ProtectorUO-10-16A/16A 46020112 46020112 1

22 Terminal Board 42010258 42010258 123 Capacitor 3.5uF/450V 33010010 33010010 224 Handle 26235253 26235253 325 Valve support Assy 01715002 01715002 126 Rear Side Plate 01303712 01303712 127 Front Side Plate 01305034 01305034 128 Chassis Assy 01205438 01205438 1

NO Name of Material QTY

16

Code of Material

Components and Parts List of Outdoor Unit

The above date are subject to change without prior notice

Page 29: Aer Conditionat

1 0

Trouble-Shooting

Check insulation resistance for grounding; Confirm if air-conditioning unit has electrical leakage or is short-circuited

Air

–con

ditio

ning

uni

t ca

nnot

be

star

ted

Trip of circuitbreaker orburn-out of fuse

When set circuit breaker as“ON”, it trips immediately

When turning the air-conditioning unit to the“ON”status, trip of circuit breaker occursseveral minutes later

Both indoor unit and outdoor unit do not start

No power supply

Power plug is not firmly seated orconnection is poor

Line connection failure betweenindoor unit and outdoor unit

Emission failure of remotecontroller

Controller fuse burned out

Check if the connection linebetween Hi-volt PCB and Lo-voltPCB is secure

Check if transformer output line issecure and if there is voltage output

Check circuit breaker, measureresistance for short-circuit

Check power supply line

Power plug is not firmly seatedor connection is poor

Check remote controller

Replace controller fuse

Please secure connection line

Check the line connection according tothe electrical diagram and ensurecorrect connection

Secure connection line and check output voltage

Poor

coo

ling

effe

ct

Set temperature is notappropriate

Check if the cooling (heating)load is appropriate

Adjust the set temperature

Check the forecasted cooling (heating)

Failure of refrigerant flow

Insufficient air circulation

volume

4-way valve failure Replace 4-way valve

Insufficient refrigerant Charge refrigerant

Compressor failure Replace Compressor

Insufficient flow in valve Fully open the valve

Clean the filter grill Block in air filter

Fan speed was set too low Set fan speed as high or medium

Mounting position of outdoorunit is inappropriate

Outdoor side shall have good ventilation and installproper weather screen

1 0

Fengshen Series

Page 30: Aer Conditionat

—91—

Block in filter of indoor unit Periodically clean the filter

Leakage between internal high pressureand low pressure sections of compressor

Replace compressor

Poor

coo

ling

effe

ct

Replace capillary Partial block in capillary

Find out leakage position and chargerefrigerant Leakage of Refrigerant

Burn-out or wire break of indoor fanmotor

Repair or replace fan motor

When air supplymode is selected,the fan does notoperate

Correctly connect lines according toelectrical diagramWrong line connection

Replace it withfan capacitor of thesame model and spec. Open circuit or damage of fan capacitor

Wire break of relay coil Replace relay When in cooling mode, both outdoor unit and compressor do not operate.

Poor contact of relay Replace relay

Adjust the set temperature Improper temperature setting

Replace fan motor Outdoor fan motor is damaged

Wrong line connection

Outdoor fan capacitor is damaged

When in cooling mode, compressor operates but outdoor fan does not operate

Correctly connect lines according toelectrical diagram

Replace fan capacitor

Replace Compressor Compressor failure

When in coolingmode, outdoor fanoperates butcompressor doesnot operate

Operating capacitor of compressor isdamaged

Replace capacitor

It is suggested to equip voltage regulator Voltage is too low or too high

Wrong line connection Correctly connect lines according to drawing

Block or breakage of drainage pipe Replace drainage pipe

Water leakage The refrigerant pipe joint is notwrapped firmly Wrap and bind it again firmly

Page 31: Aer Conditionat

Fan of indoor unit touches otherpositions

Adjust fan position

Foreign articles inside the indoor unit Remove foreign articles

Vibration of compressor is violent Adjust support foot mat of compressor, tighten loose bolts

Abnormal soundand vibration

Pipes of outdoor unit bump together Separate bumping pipes

Metal plates bump together inside theunit

1. Tighten connection screws2. Attach vibration damping

gum between metal plates

Indoor fan bumps cabinet Adjust fan position

Abnormal sound from insidecompressor Replace Compressor

E1 Compressor High-pressure Protection

E2 Indoor Antifreeze Protection

E3 Compressor Low-pressure Protection

E4 Exhaust Pipe High-temp Protection

E5 Overcurrent Protection

Fault Code

Fengshen Series