-
THOMAS & BETTS POWER SOLUTIONS5900 EASTPORT BOULEVARD,
RICHMOND, VIRGINIA 23231-4453
TEL: 800.238.5000 FAX: 804.236.4040 WWW.CYBEREX.COM
POWER DISTRIBUTION MODULEPDM II SERIES
Owners/Operators Manual
Document No.: 94-12-669281Rev No.: G
Release Date: 05.17.10
94-12-669281_Complete Cyb Manual Cover.qxp 6/3/2010 2:27 PM Page
1
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 2 of 120
TABLE OF CONTENTS
TABLE OF CONTENTS
......................................................................................................
2
SPECIFICATIONS/CHARTS...............................................................................................
3 1.0 System Packaging
....................................................................................................
4 2.0 System Unpacking and
Inspection............................................................................
4 3.0 Positioning the System
.............................................................................................
5 4.0 System
Specifications...............................................................................................
7 5.0 Installation
................................................................................................................
9 6.0 System Start-Up
.....................................................................................................
13
6.1 Initial
Start-up......................................................................................................
13 6.2 Final
Start-up.......................................................................................................
14
7.0 Operation and Configuration using the
GUI............................................................ 15
7.1 Operational Concepts and
Scenarios..................................................................
15 7.2 Security
...............................................................................................................
16 7.3 System
Setup......................................................................................................
17 7.4 System Access Configuration
.............................................................................
19
7.4.1 Ethernet and TCP/IP
Configuration..............................................................
20 7.4.2 SNMP Configuration
....................................................................................
21 7.4.3 Modbus
Configuration..................................................................................
21
7.5 Software Upgrade/Software
Downgrade.............................................................
21 7.6 Viewing System
Information................................................................................
23 7.7 User Interface Board
...........................................................................................
24
8.0
Monitoring...............................................................................................................
26 8.1 Overview
.............................................................................................................
26 8.2 Product
Description.............................................................................................
26
8.2.1 Mechanical
Overview...................................................................................
26 8.3
Features..............................................................................................................
29 8.4 Modbus
...............................................................................................................
30 8.5 PDU "View"
Windows..........................................................................................
31 8.6 BCM "View" Windows
(Optional).........................................................................
36 8.7 SFCM "View" Windows (Optional)
......................................................................
39 8.8 Event Log and Alarm/Warning
Annunciation.......................................................
41
9.0 Alarm/Warning Limits and Ratings Configuration
................................................... 48 9.1 PDU
"Config" Windows
.......................................................................................
48 9.2 BCM "Config" Windows (Optional)
......................................................................
51 9.3 SFCM "Config" Windows (Optional)
....................................................................
54
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 3 of 120
Appendix A: Display GUI Password Management
............................................................ 57
Appendix B: Modbus Register Map
...................................................................................
59 Appendix C: Access
..........................................................................................................
66 Appendix D: Spare Parts List
............................................................................................
76 Appendix E: Mission Critical Reconnection Instructions
.................................................... 78 Appendix F:
Kick Plate Installation Instructions
.................................................................
85 Appendix G: Multiple Bay Reconnection Instructions
....................................................... 90 Appendix
H: Floor Stand Installation Instructions
.............................................................. 97
Appendix I: Web
Server...................................................................................................
100 Appendix J: SNMP Trap Monitor
.....................................................................................
118 SPECIFICATIONS/CHARTS
Chart 3-1: Physical Specifications
.......................................................................................
6 Chart 4-1: Electrical Characteristics: 480V Input (4-Wire)
................................................... 7 Chart 4-2:
Color Code Chart: Three Phase
.........................................................................
7 Chart 4-3: Heat Output at Full Load
....................................................................................
8 Chart 4-4: Rated Power (KVA) vs. Operating Temperature
................................................ 8 Chart 5-1:
Torque Ratings
.................................................................................................
13
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 4 of 120
1.0 System Packaging
Every Cyberex product is fully tested and has passed our
thorough quality control inspection prior to delivery. Once the
product is tested and quality control inspected, the unit is then
carefully packaged for delivery.
Your Cyberex system is protected by a 60 mil thick stretch wrap
material to protect the systems heat treated, matte finished, and
powder coated paint against abrasion and vibration during transit.
In addition, Cyberex then protects each of the four corners with
double wall corrugated corner boards which protect the unit during
transit. If shipping by common carrier is necessary, Cyberex can
custom crate your Cyberex system by using 3/4 plywood crate, giving
you the ability to move the system easily from truck to dock.
The system is built on a base structure and is equipped with
four (4) 360o swivel casters. This allows the unit to roll freely
while eliminating the need for palletizing the unit. This feature
enables the installer to easily remove the unit from the delivery
vehicle and literally roll the system directly onto the computer
room raised floor without the need for forklifts, pallet-jacks, or
other costly and time-consuming rigging equipment.
2.0 System Unpacking and Inspection
You should unpack your Cyberex product with the same care
Cyberex used in packing the product for safe and efficient delivery
to your facility. Please follow these steps in unpacking the
system:
Inspect the system for any exterior damage that may have
occurred during transit from the factory. Any damage should be
reported to the trucking company and marked on the bill of lading
while the driver is still on the premises. Also report any damages
to Cyberex Field Service Support by calling 1-800-647-4782.
1. Carefully remove the stretch wrap by cutting the material at
one of the rear corners of the system. REMEMBER, this stretch wrap
is the final layer of packing material on the system so be careful
in both cutting and removing the stretch wrap.
2. If computer power cables are attached to the system,
carefully remove the packing material by repeating steps 1 and 2
above.
3. Open the systems front door and again inspect the system for
any damage that may have occurred during transit. Verify the
systems main circuit breaker, any secondary main circuit breaker,
and all branch circuit breakers are in the OFF position prior to
initial system start-up.
4. Make sure the rating nameplate is located properly inside the
right front door, upper left side of your unit. This nameplate
should match the configuration you ordered.
5. Review points 1-5 to verify proper care has been taken in
preparing the system for safe operation.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 5 of 120
3.0 Positioning the System
Your Cyberex product has been designed to perform at optimum
efficiency when the following positioning concerns are taken into
consideration:
1. The system is designed to allow the Cyberex staff to use
every available square foot of computer room space for operating
your computers versus your power conditioning equipment. Cyberex
products require thirty-six inches (36) of FRONT ACCESS as well as
one other side (LF, RT, RR) for service area. Please refer to
Appendix 1 for exact service and operational access requirements.
Cyberex also requires an eight inch (8) rear clearance for
ventilation. The thirty-six inches (36) of front access as well as
one other side allows the unit to be fully serviced while also
complying with the current National Electrical Code for access to
circuit breaker distribution equipment.
MAKE SURE ALL VENTILATION OPENINGS ARE CLEAR OF OBSTRUCTIONS
2. The system is designed to properly cool by using natural
convection. Positioning the unit onto the raised floor ensures
optimum placement practices.
3. The system is enclosed in one of the industrys most
substantial cabinets and contains electrical apparatus such as
molded case circuit breakers, high isolation transformers, and
distribution panelboards. Consequently, floor loading should be
addressed to verify the Cyberex system does not exceed your raised
floor load specifications. Refer to Chart 3 - 1 for weight and
dimensional specifications of your Cyberex product.
4. If additional raised floor supports are required, contact
your raised flooring supplier or Cyberex for either floor jacks or
full frame floor stand specifications.
5. It is always a good practice to roll the Cyberex system to
its location on the computer room raised floor by placing two (2) 4
x 8 x 3/4 sheets of plywood onto the computer room floor, then
rolling the system on the plywood versus on the raised floor
itself. If kick plates were provided with your unit, rolling the
system to location could be a little difficult, consider removing
the kick plates and then re-installing once unit is in place. NOTE:
The solid kick plate option is only available for applications
where the PDM is installed on a computer raised floor with chilled
air being fed through the floor into the PDM for cooling. For all
other applications, vented kick plates must be used to insure
adequate system cooling.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 6 of 120
Chart 3-1: Physical Specifications
CABINET kVA WIDTH DEPTH HEIGHT UNIT WEIGHT IN CM IN CM IN CM LB
KG
34 Main Cabinet 50 34 86 34 86 77.4 196.6 1,260 572 75 34 86 34
86 77.4 196.6 1,310 594 100 34 86 34 86 77.4 196.6 1,510 685 125 34
86 34 86 77.4 196.6 1,810 821 150 34 86 34 86 77.4 196.6 1,860 844
200 34 86 34 86 77.4 196.6 2,160 980 225 34 86 34 86 77.4 196.6
2,310 1,048 300 34 86 34 86 77.4 196.6 2,800 1,270
46 Main Cabinet 300 46 116 34 86 77.4 196.6 2,960 1,343
10 Side Cabinet 34 86 10 25 74 187 304 138
24 Side Cabinet Front Access 24 61 34 86 74 187 442 200
24 Side Cabinet Front/Rear Access 24 61 34 86 74 187 579 263
34 Side Cabinet Front Access 34 86 34 86 74 187 568 258
34 Side Cabinet Front/Rear Access 34 86 34 86 74 187 628 285
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 7 of 120
4.0 System Specifications
The charts within this section have been developed to assist you
in documenting and understanding the electrical and mechanical
characteristics of your Cyberex product.
Chart 4-1: Electrical Characteristics: 480V Input (4-Wire)
kVA FULL LOAD
AMPS
MAIN BREAKER RATING
15 30 50
75 100 125
150 200 225 288 300
18 36 60
90 120 150
181 240 271 346 361
25 AMP 45 AMP 80 AMP
125 AMP 150 AMP 200 AMP
225 AMP 300 AMP 350 AMP 450 AMP 450 AMP
Chart 4-2: Color Code Chart: Three Phase CONDUCTOR 480V 60 Hz
208V 60 Hz
Phase A Phase B Phase C Neutral Ground
Brown Orange Yellow White Green
Black Red Blue
White Green
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 8 of 120
Chart 4-3: Heat Output at Full Load kVA BTU/HOUR* AC LOAD
(TONS)
15 30 50
75
100 125
150 200 225 300
1,260 2,525 3,515
4,400 6,413 7,336
7,814 8,886 9,997
13,330
.10 .21 .29
.36 .53 .61
.65 .74 .83
1.11
*All BTU/hour calculations are based on systems having a 0.80
Power Factor.
Chart 4-4: Rated Power (KVA) vs. Operating Temperature
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 9 of 120
5.0 Installation
The following procedure is intended to serve as an outline only
in installing your Cyberex product. Naturally, only qualified
electricians following the guidelines of the current National
Electrical Code should install any electrical apparatus, including
this Cyberex product. Please remember that the intended application
of this unit is as an information technology distribution
system.
FOR ALL STAGES OF INSTALLATION, PLEASE USE CAUTION AND REFER TO
ALL WARNING LABELS THAT ARE PROVIDED ON YOUR PDM.
UNIT MUST NOT BE INSTALLED IN AN AREA WITH A POLLUTION RATING
ABOVE 2.
THIS PDM IS DESIGNED TO RECEIVE POWER FROM ONE (1) POWER SOURCE.
WHEN THE POWER SOURCE IS ENERGIZED, THIS UNIT CONTAINS HAZARDOUS
VOLTAGES. HAZARDOUS VOLTAGES EXIST WITHIN THE PDM PANEL. BEFORE
MAKING ANY CONNECTIONS TO THE UNIT OR PERFORMING ANY MAINTENANCE,
ENSURE THAT ALL POWER IS TURNED OFF AND LOCKED OUT.
AS LETHAL VOLTAGES EXIST WITHIN ALL OPERATING MODES OF THE PDM,
MAINTENANCE MUST BE PERFORMED BY QUALIFIED AND TRAINED SERVICE
PERSONNEL.
CYBEREX NEITHER RECOMMENDS NOR KNOWINGLY SELLS THIS PRODUCT FOR
USE WITH LIFE SUPPORT APPLICATIONS OR OTHER FDA-DESIGNATED CRITICAL
APPLICATIONS.
ALL WIRING SHOULD BE PERFORMED BY QUALIFIED ELECTRICIANS AND IN
ACCORDANCE WITH LOCAL AND NATIONAL ELECTRICAL SAFETY CODES. BEFORE
PLACING THE UNIT INTO SERVICE, A THOROUGH INSPECTION AND SUPERVISED
START UP SHOULD BE PERFORMED BY A QUALIFIED TECHNICIAN.
1. Located under each corner of the PDM base is a stabilizing
foot (see Figure 5-1). Each stabilizing foot should be lowered to
make contact with the floor. This procedure will help to keep your
system stable and in place. If a floor stand is used, then the
leveling feet should be removed entirely and a 1/2-13x3 bolt should
be installed through the floor stand and into leveling foot nut.
Both a flat washer and lock washer should be used under the head of
the bolt.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 10 of 120
Figure 5-1: Leveling Foot Location
2. For Main Input Power, at least (4) equally sized conductors
should be used; (1) each for phase A, B, C, and ground. The three
phase conductor should run directly through the top or bottom gland
plate, through the middle of the cabinet, and terminate at the
Input Terminal Block OR the Line Side of the Main Input Circuit
Breaker. The ground wire shall terminate at the main ground bus as
shown in Figure 5-2, and shall not pass through the ground CT. All
wires should use the same color codes as indicated in Chart 4-2.
Appropriate measures should be taken to ensure that all input power
conductors avoid touching any sharp edges or any bolts and screws.
To properly install your source inputs, please consult NEC code and
any local governing codes for proper wire information. Please refer
to Chart 5-1 for proper torque information as provided by the
manufacturer.
Leveling Foot
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 11 of 120
FIGURE 5-2: MAIN GROUND LOCATION
3. All output computer power cable loads should be balanced and
terminated onto the 42-pole circuit breaker panelboards, and/or
output sub-feed breakers. Ground bus locations for the sub-feed
breakers can be found in the outline drawing specific to the
cabinet configuration in question. To properly install your
distribution outputs, please consult NEC code and any local
governing codes for proper wire information. Please refer to Chart
5-1 for proper torque information as provided by the manufacturer.
Branch circuit cards have been provided to list each cable and
breaker designation. These cards are located above each panelboard.
Note:
MAKE SURE ALL GND CONNECTIONS ARE PROPERLY SECURED AND
GROUNDED
Main Ground Bus
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 12 of 120
4. All Remote Emergency Power Off (REPO) pushbutton stations,
building alarm interface points, and other points should be
attached to the interface board at this time. The interface board
is located behind the top left dead front, attached to the surface
of the left side wall. A cable pathway is provided up the left
inside wall through a series of cable retainers as shown in Figure
5-3. Please refer to Section 7.8 for details on the User Interface
connections.
Figure 5-3: Cable Pathway
SAFETY ... SAFETY ... SAFETY ... SAFETY ... SAFETY
5. Check all connections within the system to verify the
connections are tight and secure.
a. Terminal Block-Line and Load Side (if applicable) b. Ground
conductor lugs c. Line side of main circuit breaker lugs d. Load
side of main circuit breaker lugs e. Input lugs on main isolation
transformer f. Output lugs on main isolation transformer g. All
panelboards, ground bus kits, and neutral bus kit lugs
CABLE RETAINERS
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 13 of 120
h. All branch breaker wiring i. Load side of all subfeed
breakers j. Control wiring on interface board
If using top exit side car, make sure to use conduit bushings
after installing cables to ensure no openings are exposed to
falling objects.
Chart 5-1: Torque Ratings: User Interface Manufacturer
Recommendations
Location Manufacturer Torque Rating
Wire To Input Terminal Block Ferraz Shawmut 500 in. lbs. GND
& NEU Bus Bar 30 ft. lbs. Branch Breaker to Panelboard Square
D/GE 18-21 in. lbs. Wire to Branch Circuit Breaker Square D/GE See
Circuit Breaker
THE PDM IS NOT A PARALLELING DEVICE! UNDER NO CIRCUMSTANCES
SHALL A COMBINATION OF MAIN INPUT OR TIE CIRCUIT BREAKERS BE
INSTALLED IN THE SYSTEM THAT WILL PERMIT TWO (2) OR MORE
INDEPENDENT SOURCES TO BE CONNECTED TOGETHER UNLESS CUSTOM
CONFIGURED FOR THIS APPLICATION.
6.0 System Start-Up
6.1 Initial Start-up
Prior to energizing the system, the installing electrical
contractor should verify the following:
1. Proper phase rotation and safe grounding practices have been
exercised. 2. All conductor sizing meets or exceeds conductor sizes
as detailed in the
guidelines of the current National Electric Code. 3. All
building interface points are terminated onto the systems interface
board
(see Figure 7-1). 4. The Cyberex systems main input circuit
breaker and all subsequent circuit
breakers are all in the OFF position.
** DOUBLE CHECK ITEMS 1-4 AFTER THE STEPS ABOVE HAVE BEEN
PERFORMED **
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 14 of 120
6.2 Final Start-up
1. The installing electrical contractor should now verify that
the input voltage to the unit properly matches the input voltage
rating of the unit as reflected on the systems identification label
(affixed to the inside of the front door of the unit) and as
indicated on the transformer label located on the top of the high
isolation transformer positioned in the rear of the unit.
2. Turn the buildings circuit breaker feeding the Cyberex
product to the ON position. The systems red Emergency Power Off
pushbutton should now be illuminated as well as display LCD screen
indicating power is present at the line side of the Cyberex system
main circuit breaker.
3. Energize the Cyberex product by turning the systems main
input circuit breaker to the ON position.
4. Next, the output voltages from the system should be verified.
Identify the output voltage of the transformer by using a true RMS
digital volt-meter. If the output voltage of the transformer is not
the desired voltage, access the systems 2 1/2% compensation taps.
Compensation tap configurations are clearly marked on the label
affixed to the top of the high isolation transformer itself. The
contractor should re-verify the output voltage to determine that
the optimum compensation tap combination is used to achieve an
output voltage as close to your output voltage as possible.
5. The installing contractor should now verify that the
Emergency Power Off (EPO) circuit and the Remote Emergency Power
OFF (REPO) circuit (if applicable) are connected and working
properly.
6. Now that the emergency power off circuit has been verified
and input/output voltages are adjusted properly, energize the
systems secondary main circuit breakers (if purchased). Next,
sequentially energize the branch circuit breakers to distribute
power to your critical load.
PER NEC ARTICLE 645.10 AN EMERGENCY POWER OFF BUTTON (EPO) IS
REQUIRED. IF THIS OPTION IS NOT INSTALLED ON THE PDM, A REMOTE EPO
MUST BE INSTALLED. SEE PAGE 21 FOR LOCATION OF CONNECTION.
Your Cyberex system is now distributing power to your connected
load. Section 7.0 Section 8.0 is dedicated to assisting you in
operating your display/monitoring system. Prior to continuing to
Section 7.0, please take a moment to familiarize yourself with your
Cyberex product. If you have any questions, please feel free to
call your local representative or our Cyberex Field Service Support
staff at 1-800-647-4782.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 15 of 120
7.0 Operation and Configuration using the GUI
7.1 Operational Concepts and Scenarios
1. Each PDM unit has a GUI Display/Control Panel.
2. The GUI display/control panel is also used to monitor/control
optional built-in Branch Circuit Monitors (BCMs), Subfeed Circuit
Monitors (SFCMs), and/or Main Feed Circuit Monitors (MFCMs).
3. Each PDM unit has a User Interface Board (UIB), which is
provided for the user's connections.
4. External monitoring systems, e.g., Building Management
Systems, can be used to poll the PDM units using Modbus RTU (on an
RS-485 bus) or Modbus/TCP. Each unit connected in the Modbus
network shall be configured with a unique Modbus ID.
5. This product has a limited SNMP Trap feature.
The operation of the Display Module is based on GUI menus and
screens as follows.
Figure 7.1-1: Main Status Window with Menu Bar
The Main Menu Bar is shown above.
When the first item in the menu, Command, is selected, the
dropdown submenu will appear as shown below.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 16 of 120
Figure 7.1-2: The "Command" Submenu
7.2 Security
Login and Logout
To login in to a particular security level, select CommandLogin.
The following popup window will appear.
Figure 7.2-1: Security Login Window
In the pop up window (above) select the proper User Name and
Password and then click OK. This will login the user to the
appropriate security level. (The default User Names are shown in
Appendix A.)
To logout, select CommandLogout. Once the user logs out, any
open windows, which allow configuration changes, will be closed,
and the items in the menus for opening these windows will be
disabled for security purposes.
Set Password
The user can change the password by selecting the submenu Item
Set Password in the Command menu items. (CommandSet Password). The
following popup window will appear.
user
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 17 of 120
Figure 7.2-2: Set Password Window
Fill in the fields accordingly to change the password, and
select the OK button.
7.3 System Setup
Under Options on the menu bar, the user can open windows for
configuring the unit as shown below. The user must be logged in as
'admin' (or higher) to access the items under "Options".
Figure 7.3-1: The "Options" Submenu
System Config Window
The System Config window (shown below) is opened by selecting
OptionsSystem on the menu bar. The Audible Alarm and Manual Restart
options can be enabled/disabled on this window.
Note that in some firmware versions, the Security option can
also be enabled/disabled with the 'admin' login. Otherwise, a
higher-level login is required.
user
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 18 of 120
Figure 7.3-2: System Config Window
Time & Date Configuration Window
The Time and Date of the unit can be set on the Time & Date
Configuration window shown below. This window is opened by
selecting OptionsTime on the menu bar. To change date and time,
fill in the date and time and select the OK button in the window as
shown below.
Figure 7.3-3: Time & Date Configuration Window
LCD Contrast Window
The LCD display contrast level can be adjusted manually or
automatically on the "LCD Contrast" window shown below. This window
is opened by selecting OptionsDisplay on the menu bar.
Nov 20 2008
12 30 24
Eastern Time (GMT-5)
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 19 of 120
Figure 7.3-4: LCD Contrast Window
7.4 System Access Configuration
The following table lists the available interfaces and their
configuration parameters.
Table 7.4-1 System Access Configuration
Interface Description Configuration Parameters References
Email Not currently available. N/A N/A
Telnet Remote command-line interface for Thomas & Betts
Power Solutions use.
IP Address IP Gateway Subnet Mask
Figure 7.4.1-1
Web Provides means for viewing meter readings and changing
configuration settings using a Web browser.
IP Address IP Gateway Subnet Mask
Figure 7.4.1-1
IP Address IP Gateway Subnet Mask
Figure 7.4.1-1 SNMP The unit sends SNMP-Trap messages
(indicating Summary Alarms only), which can be monitored using the
Cyberex PDU/RPP SNMP-Trap Monitor PC application. (See Appendix
J.)
NMS #1 IP Address NMS #2 IP Address
Figure 7.4.2-1
IP Address IP Gateway Subnet Mask
Figure 7.4.1-1 Modbus TCP
Modbus protocol over the Ethernet interface.
Client #1 IP Address Client #2 IP Address Unit ID
Figure 7.4.3-1
Modbus RS-485
Modbus protocol over the RS-485 interface.
Baud Rate Stop-Bits Parity Unit ID
Figure 7.4.3-1
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 20 of 120
The Access Configuration window (shown below) is used to enable
or disable the various interfaces and protocols listed above in
Table 7.4-1. To open this window, select OptionsAccess on the menu
bar. As mentioned earlier, the user must be logged in as 'admin'
(or higher) to access the menu items under "Options". Note that to
disable or enable the Web or SNMP features in this window, the user
must be logged as 'service' (or higher). Also note that changing
the state of an interface will require a reboot of the display
before the actual interface changes states.
Figure 7.4-1: Access Configuration Window
7.4.1 Ethernet and TCP/IP Configuration
A number of features on this unit utilize the Ethernet
interface.
The TCP/IP settings are configured on in the TCP/IP
Configuration Window shown below. To open this window, select the
second "Config" button on the Access Configuration window (shown
above in Figure 7.4-1).
Figure 7.4.1-1: TCP/IP Configuration Window
172
Factory
016 001 056
172 016 000 001
255 255 255 000
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 21 of 120
7.4.2 SNMP Configuration
The SNMP related parameters are configured in the Modbus
Configuration window shown below. To open this window, select the
"SNMP Config" button on the Access Configuration window (shown
above in Figure 7.4-1).
See Table 7.4-1 (System Access Configuration) above for more
guidance.
Figure 7.4.2-1: SNMP Configuration Window
7.4.3 Modbus Configuration
The Modbus related parameters are configured in the Modbus
Configuration window shown below. To open this window, select the
lower "Config" button in the Access Configuration window (shown
above in Figure 7.4-1).
See Table 7.4-1 (System Access Configuration) above for more
guidance.
Figure 7.4.3-1: Modbus Configuration Window
7.5 Software Upgrade/Software Downgrade
Note that to access the windows and perform software upgrades as
shown in this section, the user must be logged in to a security
level higher than "admin", otherwise, the "Upgrade" menu item
(shown below) will be disabled (grayed-out).
172 016 001 037
000 000 000 000
19200 None 1
001
For Modbus/TCP only: Set "Addr #1" to the IP address of the main
BMS. Set "Addr #2" to the IP address of the alternate BMS (if
applicable). You can use a Unit ID of 001 on all units with
Modbus/TCP.
For Modbus/RTU (serial RS485) only: Baud, Parity, Stop bits.
With Modbus/RTU (serial RS485), each unit must have a unique
Unit ID number.
172 016 001 037
For the limited SNMP-Trap feature: Set "Addr #1" to the IP
address of the main NMS. Set "Addr #2" to the IP address of the
alternate NMS (if applicable).
000 000 000 000
public
private
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 22 of 120
Figure 7.5-1: Selecting "CommandUpgrade" on the Menu Bar
FTP Upgrades
To perform a software upgrade via FTP, enter the FTP Upgrade
Mode by selecting CommandUpgradeFTP on the menu bar. Once in FTP
Upgrade Mode, the operator should execute a FTP (File Transfer
Protocol) application from a remote host using the units IP
address. Enter the user name admin and then the administrator
password for the unit.
At the FTP prompt, enter put xxx.bin, where "xxx.bin" is the
software upgrade filename. (The file name must contain fxromz.) The
file transfer will begin, and the status will be displayed in the
Upgrade Progress popup window (shown below). The unit will
automatically reboot after completion.
Figure 7.5-2: Upgrade Progress Popup Window
TFTP Upgrades
To perform a software upgrade via TFTP, select
CommandUpgradeTFTP on the menu bar. A TFTP server must also be
running on the host device. Enter the file name (fxromz.bin is the
default) and the TFTP host address in the TFTP Configuration popup
window (shown below). When the OK button is clicked, the file
transfer will begin, and the status will be displayed in the
Upgrade Progress popup window (shown above). The unit will
automatically reboot after completion. .
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 23 of 120
Figure 7.5-3: TFTP Configuration Popup Window
7.6 Viewing System Information
The System Information window (shown below in Figure 7.6-2) can
be accessed by selecting ViewSystem on the "View" submenu (shown
below in Figure 7.6-1). Details about the other items in the View
submenu will be covered later in this manual.
Figure 7.6-1: The "View" Submenu
Figure 7.6-2: System Information Window
172 016 001 054
fxrom.bin
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 24 of 120
7.7 User Interface Board The User-Interface Board (UIB) provides
an interface for connecting the PDM to external monitoring and
control equipment. The main features of this board include the
following items. (Also see Figure 7.7-1 below.)
1) Alarm Relay Contacts (Form C)
Alarm Designation Terminals (J2) Contact Type
1 - 3 NO/CFA Summary Alarm 2 - 3 NC/OFA 4 - 6 NO/CFA
Unacknowledged Events 5 - 6 NC/OFA
NO = Normally Open (when relay coil is de-energized) NC =
Normally Closed (when relay coil is de-energized) CFA = Closed for
Alarm OFA = Open for Alarm
2) Remote Emergency Power Off (REPO) User Input
Closing the circuit between J8-11 and J8-12 forces a shunt-trip
on the input breaker. (For use with isolated dry contacts.)
3) Ethernet Connection
J7 (RJ-45 connecter) is for an Ethernet connection to the
PDM.
4) RS-485 (Modbus-RTU) Connection The 5-point terminal block,
J3, is for an RS-485 (Modbus-RTU) connection.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 25 of 120
Figure 7.7-1: User Interface Board
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 26 of 120
8.0 Monitoring
8.1 Overview
The metering module will be used to monitor various voltages
& currents in a power distribution panel. The meter will also
compute various other parameters such as power, energy, demand,
frequency, power factor etc.
8.2 Product Description
The Metering module board will acquire the voltage & current
signals from an analog signal conditioning board. It will calculate
energy and power quality parameters. These parameters are passed to
the display board/PC for display and data logging. It will also
receive control/command/system parameter data from display board or
a third party display module.
8.2.1 Mechanical Overview
Figure 8.2-1: Display Module Front View (Mounted on Door)
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 27 of 120
Figure 8.2-2: Display Module Front View (Not Mounted)
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 28 of 120
Figure 8.2-3: Display Module Back View
Figure 8.2-4: Display Module Bottom View
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 29 of 120
8.3 Features
The following are standard features of the PDM:
1. Thermal shutdown (shunts trip input breaker when goes past
acceptable thermal levels).
2. TVSS or Surge Arrestor fault indication. This indication
could mean that there is a fault with the TVSS or the Surge
Arrestor (if applicable).
3. Over temperature warning.
4. Manual Restart (requires a manual restart of the input
breaker when there is a power outage).
5. Local Emergency Power Off button (EPO).
6. Remote Emergency Power Off contacts (REPO).
The following parameters will be computed from the
measurements:
1. RMS Output Voltages (3-phase, L-L and L-N).
2. RMS Input Voltages (3-phase, L-L and L-N).
3. RMS Output Currents (3-phase).
4. RMS Neutral Current.
5. RMS Ground Current.
6. Active Power (kW).
7. Apparent Power (kVA).
8. Active Energy Consumption (kWh).
9. Frequency.
10. Power Demand (kW Max).
11. Percentage Load.
12. Voltage THD in %.
13. Current THD in %.
14. Crest Factor for Load.
15. Power Factor.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 30 of 120
8.4 Modbus
The PDM acts as a Modbus slave, and can be accessed by the
Modbus master using either Modbus RTU (via RS-485) or Modbus TCP
(via Ethernet). The PDM is identified by a unique slave ID by the
master. The default Modbus RTU settings are as follows.
Baud Rate: 19200
Parity: None
Stop bits: 1
The Modbus register map is shown in Appendix B.
The standard PDM unit consists of the Display Module and the
Basic Module Metering (BMM). The PDM may also have additional
optional modules, including Branch Circuit Monitors (BCMs) and
Subfeed Circuit Monitors (SFCMs). Each module connected inside of
the PDM needs to be configured with a unique Modbus ID.
The BMM has a default Modbus ID of '2', which is not visible to
the outside world. The BMM Modbus registers (listed in Appendix B
Table 3) and the other PDM registers listed in Appendix B (Table 1
and Table 2) are accessed from the outside world (e.g., the BMS)
using the Modbus ID set in the Modbus Configuration window (Figure
7.4.3-1) and shown in the System Information window (Figure
7.6-2).
The optional BCM modules have a default Modbus ID of '7', and
the optional SFCM modules have a default Modbus ID of '8'. The
Modbus registers for these modules are accessed from the outside
world using the Modbus ID setting of each individual module.
Therefore, special attention must be taken when connecting multiple
PDU units on an RS-485 bus, since each PDM, BCM, and SFCM on the
bus must have unique Modbus IDs. Also, inside each PDM unit, the
BCM and SFCM cannot have the same Modbus ID as the BMM. The Modbus
IDs of the BMM, BCM, and SFCM can be changed via the individual
module's service port.
The Modbus IDs of the internally connected modules can be seen
by opening the Device Status window by selecting 'CommandDevice
Status' on the menu bar. An example screenshot of the Device Status
window is shown below, which shows a unit with an optional BCM/SFCM
module with the Modbus IDs set to the default values.
Note that the device listed as Type 'PDU' below is actually the
BMM module, and as mentioned above, its Modbus ID (of '2') is not
visible to the outside world.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 31 of 120
Repeated from above: The BMM Modbus registers (and the other PDM
registers) are accessed from the outside world using the Modbus ID
set in the Modbus Configuration window (Figure 7.4.3-1) and shown
in the System Information window (Figure 7.6-2).
Figure 8.4-1: Device Status Window
Table 1: Function Codes Supported Function Code Function Type
Application
03h Read Holding Register Read metering data and Configuration
data.
05h Force Single Coil Reset kWh/kVAh/Demand
06h Preset Single Register Change configuration data/reset
warnings & alarms.
10h Preset Multiple Registers Change configuration data/reset
warnings & alarms.
Table 2: Exception Responses Error Code Error Meaning
1 Illegal Function Function code requested by Master is not
supported.
2 Illegal Data Address The Data Address requested by Master is
not valid.
3 Illegal Data Value The Data value is not acceptable.
8.5 PDU "View" Windows
The PDU related data can be viewed by selecting ViewPDU on the
menu bar as shown below.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 32 of 120
Figure 8.5-1: Selecting ViewPDU on the Menu Bar
PDM Status
The PDU Status window (shown below) is opened by selecting
ViewPDUStatus on the menu bar.
Figure 8.5-2: PDU Status Window
PDM Metering
The PDU Metering windows are opened by selecting ViewMetering on
the menu bar. The Metering parameters include the details of
Current, Voltage, Power and others. The details of each window are
shown below. The user can navigate to the different metering
windows by selecting the appropriate radio button.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 33 of 120
Figure 8.5-3: PDU Metering (Voltage) Window
Figure 8.5-4: PDU Metering (Current) Window
Figure 8.5-5: PDU Metering (Power) Window
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 34 of 120
Figure 8.5-6: PDU Metering (Harmonics) Window
PDU Metering (Others) Window
The PDU Metering (Others) window includes the metering details
of the ,Load, Crest Factor, Demand, Frequency and Phase Sequence,
as shown below.
Figure 8.5-7: PDU Metering (Others) Window
Viewing the PDU Limits/Rating Configuration Settings
The Limits/Rating configuration settings can be viewed by
selecting the submenu menu item under ViewConfig on the menu bar as
shown below.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 35 of 120
Figure 8.5-8: Selecting ViewConfig on the Menu Bar
PDU Config Limit View
The PDU Config Limit View window shows the Alarm/Warning Limit
settings, as shown in the example screenshot below.
Figure 8.5-9: PDU Config Limit (View) Window
PDU Config Rating View
The PDU Config Rating View window shows the configuration
details for the PDUs voltage, current, and frequency, ratings,
along with the Baud Rate setting for the communications to the
internal modules, the demand period, and the CT types, as shown
below.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 36 of 120
Figure 8.5-10: PDU Config Rating (View) Window
8.6 BCM "View" Windows (Optional)
The BCM related data can be viewed by selecting ViewBCM on the
menu bar as shown below.
Figure 8.6-1: Selecting ViewBCM on the Menu Bar
The BCM 'View' windows are shown below.
Figure 8.6-2: BCM System Config (View) Window
007
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 37 of 120
Figure 8.6-3: BCM Panel Status Window
Figure 8.6-4: BCM Panel Config (View) Window
Figure 8.6-5: BCM Panel Metering Window
007
007 01
007 01
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 38 of 120
In the 'BCM Branch Status' window below, the data for each of
the 42 branch circuits can be viewed by selecting the 'Next
6>>' and '
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 39 of 120
Figure 8.6-8: BCM Branch Config (View) Window
Figure 8.6-9: BCM Branch Metering Window
8.7 SFCM "View" Windows (Optional)
The SFCM related data can be viewed by selecting ViewSFCM/MFCM
on the menu bar as shown below.
Figure 8.7-1: Selecting ViewSFCM/MFCM on the Menu Bar
The SFCM 'View' windows are shown below.
007 01
01 01007
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 40 of 120
Figure 8.7-2: SFCM System (View) Window
Figure 8.7-3: SFCM Config (View) Window
Figure 8.7-4: SFCM Metering Window
The SFCM Metering Details window (below) is opened by selecting
the 'Details' button on 'SFCM Metering' window (above.
001
008
02008
00102008
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 41 of 120
Figure 8.7-5: SFCM Metering Details Window
8.8 Event Log and Alarm/Warning Annunciation
Overview
System events are logged in the Event Log. Each event contains
the following attributes:
Timestamp. Severity of Event (I = Informational, W = Warning, A
= Alarm). Active State Acknowledgement State Event Description
Some types of events remain active in the event log as long as
the cause of the event remains active and become inactive
afterwards. For example, an event triggered by a metered value that
exceeds a high limit will remain active until that data value falls
back below the high limit.
Some types of alarm/warning events also require acknowledgement
from the user after they become inactive. This will be discussed
below. Other types of alarm/warning events do not require
acknowledgement.
Viewing Events
The events can be viewed in the Event Log window by pressing the
Events button on the control panel or by selecting EventsView in
the menu (shown below.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 42 of 120
Figure 8.8-1: Events Menu
Note that the Email and Extra Info menu items (shown above) are
disabled and are not currently available. Also, the 'Delete
Selected' menu item can be used only at the 'manufacturer' security
level (or higher).
The 'Ack Selected' menu item can be used only at the 'admin'
login level (or higher). Note that some of these 'Events' menu
items will be disabled, depending on if the Event Log window is
opened or if any events have been selected.
An example screenshot of the Event Log window is shown
below.
Figure 8.8-2: Event Log Window
When pressing the Events button (or selecting EventsView) one of
the following Event screens may appear.
Line Scroll (Scrolls the event log line by line.) Page Scroll
(Scrolls the event log page by page.) Active Only (Shows the active
alarms/warnings only. Scrolls line by
line.)
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 43 of 120
These event screens are toggled by multiple presses of the
Events button and the screen that will appear depends on the screen
that was last viewed after closing (by pressing the Cancel button).
The Event screen that was last viewed can also affect the sounding
of the audible alarm, which will be discussed below.
Each event is represented by a text line on the Event screen
with the attributes listed above. The following symbols are used in
the event log display to convey the following attributes:
* An asterisk indicates the event is active. --> An arrow
indicates the event requires acknowledgement.
Examples:
The following event will appear in the event log if there is an
active over-temperature condition.
If the over-temperature condition (above) goes away, the
following event will appear in the event log. Also, the asterisk
(active event marker) in the previous event (above) will disappear,
but the arrow (requires-acknowledgement marker) will remain until
the event is acknowledged by the user.
17:37:48 I Transformer Restored of 190 degrees C
Event Description
Severity (Informational)
Timestamp (mm:ss)
-->37:48 W* Transformer over-temperature 190 degrees C
Event Description
Event is Active
Severity (Warning)
Timestamp (mm:ss)
Requires acknowledgement
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 44 of 120
Acknowledging Events
If logged in to a sufficient security level (admin or above) the
user can acknowledge events. The user has the choice to acknowledge
events individually, or to acknowledge all events at once.
Acknowledging Individual Events:
1) With the event log showing on the LCD, use the Next and
Previous buttons to highlight the event to be acknowledged. The
"highlighted" event will be surrounded by dotted lines as shown in
the example below.
2) Select the "highlighted" event by pressing the Enter button.
The selected event will appear as shown in the example below.
The event can be unselected by pressing the Enter key again. You
can select multiple events in this manner.
3) To acknowledge the selected events, press the menu button and
select EventsAck Selected on the menu.
Acknowledging All Events at Once:
1) With the event log showing on the LCD, press the menu button
and select EventsSelect All on the menu.
2) Press the menu button again and select EventsAck Selected on
the menu.
-->37:48 W* Transformer over-temperature 190 degrees C
-->37:48 W* Transformer over-temperature 190 degrees C
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 45 of 120
Event Filtering
The events displayed in the Event Log window can be temporarily
filtered by using the Event Filtering window (shown below). This
window is opened by selecting EventsFilter on the menu bar while
the Event Log window is opened. After choosing the filter criteria
in this window and selecting the OK button, the filtered events
will appear in the Event Log window and the filter criteria will
appear at the bottom of the Event Log window. The filter is cleared
by pressing the Events button on the control panel two or three
times to cycle through the various Event Log screens.
Figure 8.8-3: Event Filtering Window
Alarm/Warning Annunciation (Local)
The PDM Display Unit annunciates alarms/warning locally by the
following two different means.
Alarm/Warning LED Audible Alarm
The Alarm/Warning LED:
The Alarm/Warning LED, which is located under the LCD display,
can be in any of the following three states:
May 20103
May 20104
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 46 of 120
LED State Meaning
Green (Solid) Normal operating condition. No active alarms or
warnings are present.
Red (Solid) One or more active warnings are present. No active
alarms are present.
Red (Blinking) One or more active alarms are present.
The Alarm/Warning LED states (above) are non-latching. For
example, the LED will automatically change from red to green if a
warning condition disappears and there are no other active alarms
or warnings present.
The Audible Alarm:
When logged in as admin (or higher) the user can enable or
disable the Audible Alarm as mentioned in Section 7.3 System Setup.
When using this method, the new setting is permanently saved in
Flash memory.
Also, without being logged in, a user can temporarily disable
the Audible Alarm by selecting "CommandAlarm Ack (Audible)" on the
menu bar. (See Figure 7.1-2 (The "Command" Submenu.) When using
this method, the new setting is not saved in Flash memory and the
Audible Alarm checkbox control in the System Config window (shown
in Figure 7.3-2) is unaffected. The Audible Alarm will become
enabled again after the Display Module has rebooted.
The operation of the Audible Alarm is independent from the
Alarm/Warning LED. The Audible Alarm sounds only if there is one or
more alarm/warning events in the log that require acknowledgement,
in addition to the other caveats mentioned below. (Note that not
all alarm/warning events require acknowledgement.) Therefore, it is
possible for the Audible Alarm to be sounding while the
Alarm/Warning LED is green and for the Audible Alarm to be silent
while the Alarm/Warning LED is red.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 47 of 120
The operation of the Audible Alarm can also be affected by the
Event screen being viewed (or the last screen viewed before
closing). For example, if there are events in the log that require
acknowledgement but are not active, the Audible Alarm will sound
only if the Line Scroll or Page Scroll event screens were the last
viewed, but the Audible Alarm will be silent if the Active Only
event screen was the last viewed. When in this condition, the
Audible Alarm will toggle on and off as the user toggles through
the Line Scroll/Page Scroll and Active Only event screens (by
pressing the Events button).
Note that alarm and warning events from the BMM and optional
BCM/SFCMs do not require acknowledgement and will not cause the
Audible Alarm to sound.
Alarm/Warning Annunciation (Remote)
The PDM can annunciate alarms/warning remotely via two sets of
Form-C alarm relay contacts. (See Section 7.7 for the wiring
details.) These relay contacts are designated as follows:
Summary Alarm Contacts Unacknowledged Events Contacts
The Summary Alarm Contacts:
The Summary Alarm contacts will be in the alarm state if there
are one or more active warnings or alarms present. So basically,
the Summary Alarm contacts should follow the state of the
Alarm/Warning LED, i.e., they should be in the alarm state when the
Alarm/Warning LED is Red (Solid or Blinking) and should be in the
normal state when the Alarm/Warning LED is green.
The Unacknowledged Events Contacts:
The Unacknowledged Events contacts will be in the alarm state
only when there are one or more alarm/warning events in the log
that require acknowledgement and the state is also dependant on the
Event screen being viewed (or the last screen viewed before
closing) as mentioned above for the Audible Alarm. So usually, the
Unacknowledged Events contacts should be in the alarm state when
the Audible Alarm is sounding. See the caveats about the Audible
Alarm above in this section. Also note that disabling the Audible
Alarm does not disable the Unacknowledged Events contacts.
Note that both sets of alarm contacts will be in the normal
state if power is lost to the equipment.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 48 of 120
9.0 Alarm/Warning Limits and Ratings Configuration
This section shows the PDM's GUI configuration windows and shows
the range of adjustment that is possible using these windows. Note
that you must be logged in as admin or higher to access these
windows. The changes made are not saved until you select the OK
button near the bottom of each window.
If you are just viewing a window and are not making changes, to
close the window, press the Cancel button on the control panel (or
select the Cancel button on the window) instead of pressing the OK
button on the window.
WARNING: Use caution when making configuration changes using
these windows. In some cases, the GUI may not limit you from making
unwise changes that could cause the equipment to malfunction.
9.1 PDU "Config" Windows
The Limits/Rating configuration settings for the PDU can be
changed on the 'PDU Config' windows, which are opened by selecting
the submenu menu items under ConfigPDU on the menu bar as shown
below.
Figure 9.1-1: Selecting ConfigPDU on the Menu Bar
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 49 of 120
PDU Config Limit Window
The Over/Under Voltage and Over-Current Alarm /Warning limit
settings can set in the PDU Config Limit window (shown below). This
window is opened by selecting ConfigPDULimit on the menu bar.
Figure 9.1-2: PDU Config Limit Window
Table 9.1-1 below shows the defaults and the minimum and maximum
set point values that can be set using the "PDU Config Limit"
window above. The Modbus register numbers are also shown for
reference.
Table 9.1-1: PDU Alarm/Warning Limit Settings Description Min
Default Max Units Reg.Input OV Alarm Limit 100 115 130 % 219Input
OV Warning Limit 100 110 130 % 220Input UV Warning Limit 60 95 100
% 222Input UV Alarm Limit 60 85 100 % 221Output OV Alarm Limit 100
115 130 % 213Output OV Warning Limit 100 110 130 % 214Output UV
Warning Limit 60 95 100 % 216Output UV Alarm Limit 60 85 100 %
215Output OC Alarm Limit 50 125 200 % 217Output OC Warning Limit 50
115 200 % 218Neutral Current Limit 0 125 200 % 223Ground Current
Limit 0 20 200 A 224
115
085
115
085
110
095
110
095
125
115
125
020
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 50 of 120
PDU Config Rating Window
The PDUs voltage, current, and frequency ratings, along with the
Baud Rate setting for the communications to the internal modules,
the demand period, and the CT types, as shown below. This window is
opened by selecting ConfigPDURating on the menu bar.
Figure 9.1-3: PDU Config Rating Window
Table 9.1-2 below shows the defaults and range of values that
can be set using the "PDU Config Rating" window above. The Modbus
register numbers are also shown for reference.
Table 9.1-2: PDU Rating Settings Description Range Default Units
Reg. Baud Rate (Internal) 9600, 19200, 57600, 115200 115200 Baud
205 Max. Power Demand Period 1-60 15 Minutes 206 Input Voltage
Rating 0-600 * 480 V 207 Output Voltage Rating 0-600 * 208 V 208
Frequency Rating 50-60 60 Hz 210 Current Rating 200-1000 600 A 209
Line CT Type ** 800 A ** 211 Neutral CT Type ** 1600 A ** 212
* The unit may not perform correctly if the Voltage Ratings are
set to extremely low voltage settings. Setting the Voltage Ratings
to zero may corrupt the BMM's Flash Memory, and it will then
require a Factory Reset to correct.
** CT Types: 100, 200, 300, 400, 600, 800, 1000, 1200, 1500,
1600, 2000, 2500, 3000. (These numbers represent the primary
ratings of the CTs, while the secondary rating is 5A.)
115200
015
480
208
060
600
800
1600
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 51 of 120
9.2 BCM "Config" Windows (Optional)
The configuration settings for the BCM can be changed on the
'BCM Config' windows, which are opened by selecting the submenu
menu items under ConfigBCM on the menu bar as shown below. Note
that you must be logged in as admin or higher to access the menu
items under Config.
Figure 9.2-1: Selecting Config BCM on the Menu Bar
The 'BCM Config' windows are shown below.
Figure 9.2-2: BCM Global Config Window
Figure 9.2-3: BCM System Config Window
007 01
-
-
-
-
-
-
No On007
001 On 120 060
- - - -
001 Off 120 060
001 Off 120 060
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 52 of 120
Figure 9.2-4: BCM Panel Config Window
The ' BCM Panel Rating' window (below) is opened by selecting
the 'Other Ratings' button in the 'BCM Panel Config' window
(above).
Figure 9.2-5: BCM Panel Rating Window
Figure 9.2-6: BCM Branch Config Window
007 01
080
001
120
080
080
000
110
090
070
010
010
010
005
005
On
060
120
225
080
080
030
030
005
005
070
070
005
005
070
070
005
005
080
080
030
030
005
005
070
070
005
005
070
070
005
005
080
080
030
030
005
005
070
070
005
005
070
070
005
005
007 01
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 53 of 120
Table 9.2-1 below shows the defaults and the minimum and maximum
set point values that can be set using the BCM Configuration
windows above.
Table 9.2-1: BCM Configuration Settings Description Min Default
Max Units Reference
Panel Voltage Rating 0 * 120 600 Volts Figure 9.2-3 Figure
9.2-5
Panel Frequency Rating 0 * 60 60 Hz Figure 9.2-3 Figure 9.2-5
Panel Current Rating ** 0 * 225 600 Amps Figure 9.2-5 Panel OC
Alarm Limit 0 80 200 % Figure 9.2-4 Panel OC Warning Limit 0 70 200
% Figure 9.2-4 Panel UC Alarm Limit 0 1 100 % Figure 9.2-4 Panel OV
Alarm Limit 0 120 200 % Figure 9.2-4 Panel OV Warning Limit 0 110
200 % Figure 9.2-4 Panel UV Warning Limit 0 90 200 % Figure 9.2-4
Panel UV Alarm Limit 0 80 200 % Figure 9.2-4 Panel Over KW Alarm
Limit 0 80 200 % Figure 9.2-4 Panel Low PF Alarm Limit 0 0 100 %
Figure 9.2-4 Panel Current Alarm Delay 0 10 100 sec. Figure 9.2-5
Panel Current Warning Delay 0 5 100 sec. Figure 9.2-5 Panel Voltage
Alarm Delay 0 10 100 sec. Figure 9.2-5 Panel Voltage Warning Delay
0 5 100 sec. Figure 9.2-5 Panel PQ Alarm Delay 0 10 100 sec. Figure
9.2-5 Branch Current Rating 0 * 30 200 Amps Figure 9.2-6 Branch OC
Alarm Limit 0 80 200 % Figure 9.2-6 Branch OC Warning Limit 0 70
200 % Figure 9.2-6 Branch UC Alarm Limit 0 5 100 % Figure 9.2-6
Branch Current Alarm Delay 0 10 100 sec. Figure 9.2-6 Branch
Current Warning Delay 0 5 100 sec. Figure 9.2-6
* The unit may not perform correctly if these ratings settings
are set to extremely low values. ** The Panel Current Rating is
adjustable in steps of 5A.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 54 of 120
9.3 SFCM "Config" Windows (Optional)
The configuration settings for the SFCM can be changed on the
'SFCM Config' windows, which are opened by selecting the submenu
menu items under ConfigSFCM on the menu bar as shown below. Note
that you must be logged in as admin or higher to access the menu
items under Config.
Figure 9.3-1: Selecting Config SFCM/MFCM on the Menu Bar
The 'SFCM Config' windows are shown below.
Figure 9.3-2: SFCM Config Limit Window
Figure 9.3-3: SFCM Config System Window
080
005
080
120
080
100
010
110
090
005
008 02
070
001
-
001
-
-
-
On
-
-
-
120
-
-
-
060
-
-
Off
008
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 55 of 120
Figure 9.3-4: SFCM Config Others Window
Table 9.3-1 below shows the defaults and the minimum and maximum
set point values that can be set using the SFCM Configuration
windows above.
Table 9.3-1: SFCM Configuration Settings Description Min Default
Max Units Reference Voltage Rating 0 * 120 500 Volts Figure 9.3-3
Frequency Rating 0 * 60 60 Hz Figure 9.3-3 Current Rating 0 * 400
1000 Amps Figure 9.3-4 Line CT Scale 0 ** 16 200 N/A Figure 9.3-4
Neutral CT Scale 0 * 32 200 N/A Figure 9.3-4 OC Alarm Limit 0 80
200 % Figure 9.3-2 OC Warning Limit 0 70 200 % Figure 9.3-2 UC
Alarm Limit 0 5 100 % Figure 9.3-2 Neutral OC Alarm Limit 0 80 200
% Figure 9.3-2 OV Alarm Limit 0 120 200 % Figure 9.3-2 OV Warning
Limit 0 110 200 % Figure 9.3-2 UV Warning Limit 0 90 100 % Figure
9.3-2 UV Alarm Limit 0 80 100 % Figure 9.3-2 Over KW Alarm Limit 0
100 100 % Figure 9.3-2 Alarm Delay 0 10 100 sec. Figure 9.3-2
Warning Delay 0 5 100 sec. Figure 9.3-2
* The unit may not perform correctly if these ratings settings
are set to extremely low values. ** Setting the Line CT Scale to
zero will disable the Subfeed CB.
400
016
032
008 02 001
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 56 of 120
Appendix A: Display GUI Password Management
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 57 of 120
Appendix A: Display GUI Password Management
Display unit provides five layers of secured login access in the
GUI.
Login Name Password
Default
User switch
Admin
Service
Manufacture
Super
The Default login in the GUI would prompt upon turning on the
unit. There is no need of password for default mode. However, this
login mode has very limited capabilities (monitoring). The extended
login mode users can also configure the unit. The customer needs to
login as an administrator to modify password. Please contact
Technical Support for details. A login table has been inserted in
this section to keep record of any password modification.
Login Name New Password Date of Modification
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 58 of 120
Appendix B: Modbus Register Map
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 59 of 120
Appendix B: Modbus Register Map
Date and Time Registers The 'Date and Time' Modbus registers are
shown below in Table B-1. These registers are accessed using
Function Codes 03 (Read Holding Registers) and 16 (Preset Multiple
Registers).
Table B-1: Modbus Registers Date and Time Reg. No. Description
Format Type
1412 Month (1-12) int16 RW 1413 Day (1-31) int16 RW 1414 Year
(1970-2030) int16 RW 1415 Hours (0-23) int16 RW 1416 Minutes (0-59)
int16 RW 1417 Seconds (0-59) int16 RW 1418 Milliseconds (0-999)
int16 RW
System Status Registers The 'System Status' Modbus registers are
shown below in Table B-2. These registers are accessed using
Function Code 03 (Read Holding Registers)..
Table B-2: Modbus Registers System Status Reg. No. Description
Format Type
1002 System Status Bit 0: (Set = Summary Alarm) Bit 2: (Set =
Unacknowledged Events)
int16 R
1003 Outputs on UIB Port Bit 0: (Set = Summary Alarm) Bit 1:
(Set = Unacknowledged Events)
int16 R
1004
Inputs on UIB Port Bit 0: (Set = PDU Transformer Excess
Temperature)Bit 1: (Set = PDU Transformer Over Temperature) Bit 2:
(Set = TVSS Fault) Bit 3: (Set = EPO [Local or Remote]) Bit 4: (Set
= Circuit Breaker No. 1: Open) Bit 5: (Set = Circuit Breaker No. 2:
Open) * Bit 6: (Set = Circuit Breaker No. 3: Open) * Bit 7: (Set =
Circuit Breaker No. 4: Open) *
int16 R
1005 Display Board Temperature (C) int16 R
1006 PDU Transformer Excess Temperature (0 = Normal; 1 =
Warning) int16 R
1007 PDU Transformer Over Temperature (0 = Normal; 2 = Alarm)
int16 R
* Optional
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 60 of 120
PDM Monitoring and Configuration Registers The register map
shown below in Table B-3 includes metering, alarm, and warning
registers for the PDM system. These registers are accessed
internally inside the PDM from the BMM module.
On the floating-point registers noted below, the floating-point
numbers are expressed in the IEEE-754 (32-bit) format, which
require two Modbus (16-bit) registers. The low-order 16-bit word is
placed at the lower Modbus address (e.g., Reg. 121) and the
high-order 16-bit word is placed at the higher Modbus address
(e.g., Reg. 122).
The Type-R (Read-Only) registers listed in Table B-3 below are
accessed using Function Code 03 (Read Holding Registers). The
Type-RW (Read/Write) registers in Table B-3 can be accessed using
Function Code 03 (Read Holding Registers), 06 (Preset Single
Register), or 16 (Preset Multiple Registers).
Table B-3: Modbus Registers PDM Monitoring and Configuration
Reg. No. Description Format Scale Default Unit Type Notes
2 Output Voltage, A-B int16 1 N/A V R 3 Output Voltage, B-C
int16 1 N/A V R 4 Output Voltage, C-A int16 1 N/A V R 5 Output
Voltage, A-N int16 10 N/A V R 6 Output Voltage, B-N int16 10 N/A V
R 7 Output Voltage, C-N int16 10 N/A V R 9 Output Current, A int16
10 N/A A R
10 Output Current, B int16 10 N/A A R 11 Output Current, C int16
10 N/A A R 12 Ground Current int16 10 N/A A R 13 Neutral Current
int16 10 N/A A R 14 Input Voltage, A-B int16 10 N/A V R 15 Input
Voltage, B-C int16 10 N/A V R 16 Input Voltage, C-A int16 10 N/A V
R 17 Phase Sequence int16 1 N/A N/A R 0=ABC; 1=BAC 18 Frequency
int16 10 N/A Hz R 19 KVA, Total int16 10 N/A KVA R 20 KVA, A int16
10 N/A KVA R 21 KVA, B int16 10 N/A KVA R 22 KVA, C int16 10 N/A
KVA R 23 Load, A int16 10 N/A % R 24 Load, B int16 10 N/A % R 25
Load, C int16 10 N/A % R 26 KW, Total int16 10 N/A KW R 27 KW, A
int16 10 N/A KW R 28 KW, B int16 10 N/A KW R 29 KW, C int16 10 N/A
KW R 30 PF, A int16 100 N/A N/A R 31 PF, B int16 100 N/A N/A R 32
PF, C int16 100 N/A N/A R
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 61 of 120
Reg. No. Description Format Scale Default Unit Type Notes
33 kWh, Total int16 10 N/A kWh R * 34 kWh, A int16 10 N/A kWh R
* 35 kWh, B int16 10 N/A kWh R * 36 kWh, C int16 10 N/A kWh R * 37
kVAh,Total int16 10 N/A kVAh R * 38 kVAh, A int16 10 N/A kVAh R *
39 kVAh, B int16 10 N/A kVAh R * 40 kVAh, C int16 10 N/A kVAh R *
41 Peak Demand KW int16 10 N/A KW R 42 THD, Voltage, A-N int16 10
N/A % R 43 THD, Voltage, B-N int16 10 N/A % R 44 THD, Voltage, C-N
int16 10 N/A % R 45 Crest Factor, A int16 10 N/A N/A R 46 Crest
Factor, B int16 10 N/A N/A R 47 Crest Factor, C int16 10 N/A N/A R
48 THD, Current, A int16 10 N/A % R 49 THD, Current, B int16 10 N/A
% R 50 THD, Current, C int16 10 N/A % R 51 Alarm Register 1 int16
N/A N/A Flags R See Table B-4 below. 52 Alarm Register 2 int16 N/A
N/A Flags R See Table B-5 below. 53 Alarm Register 3 int16 N/A N/A
Flags R See Table B-6 below. 54 Alarm Register 4 int16 N/A N/A
Flags R See Table B-7 below. 61 Fund. Voltage, A-N int16 1 N/A V R
62 1st Harm., Voltage, A-N int16 100 N/A % R 63 3rd Harm., Voltage,
A-N int16 100 N/A % R 64 5th Harm., Voltage, A-N int16 100 N/A % R
65 7th Harm., Voltage, A-N int16 100 N/A % R 66 9th Harm., Voltage,
A-N int16 100 N/A % R 71 Fund. Voltage, B-N int16 1 N/A V R 72 1st
Harm., Voltage, B-N int16 100 N/A % R 73 3rd Harm., Voltage, B-N
int16 100 N/A % R 74 5th Harm., Voltage, B-N int16 100 N/A % R 75
7th Harm., Voltage, B-N int16 100 N/A % R 76 9th Harm., Voltage,
B-N int16 100 N/A % R 81 Fund. Voltage, C-N int16 1 N/A V R 82 1st
Harm., Voltage, C-N int16 100 N/A % R 83 3rd Harm., Voltage, C-N
int16 100 N/A % R 84 5th Harm., Voltage, C-N int16 100 N/A % R 85
7th Harm., Voltage, C-N int16 100 N/A % R 86 9th Harm., Voltage,
C-N int16 100 N/A % R 91 Fund. Current, A int16 1 N/A A R 92 1st
Harm., Current, A int16 100 N/A % R 93 3rd Harm., Current, A int16
100 N/A % R 94 5th Harm., Current, A int16 100 N/A % R 95 7th
Harm., Current, A int16 100 N/A % R 96 9th Harm., Current, A int16
100 N/A % R
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 62 of 120
Reg. No. Description Format Scale Default Unit Type Notes
101 Fund. Current, B int16 1 N/A A R 102 1st Harm., Current, B
int16 100 N/A % R 103 3rd Harm., Current, B int16 100 N/A % R 104
5th Harm., Current, B int16 100 N/A % R 105 7th Harm., Current, B
int16 100 N/A % R 106 9th Harm., Current, B int16 100 N/A % R 111
Fund. Current, C int16 1 N/A A R 112 1st Harm., Current, C int16
100 N/A % R 113 3rd Harm., Current, C int16 100 N/A % R 114 5th
Harm., Current, C int16 100 N/A % R 115 7th Harm., Current, C int16
100 N/A % R 116 9th Harm., Current, C int16 100 N/A % R
121-122 kWh, Total float 1 N/A kWh R * 123-124 kWh, A float 1
N/A kWh R * 125-126 kWh, B float 1 N/A kWh R * 127-128 kWh, C float
1 N/A kWh R * 129-130 kVAh, Total float 1 N/A kVAh R * 131-132
kVAh, A float 1 N/A kVAh R * 133-134 kVAh, B float 1 N/A kVAh R *
135-136 kVAh, C float 1 N/A kVAh R *
205 Baud Rate (Internal) int16 1 3 ** RW 206 Power Demand Period
int16 1 15 Min. RW 207 Input Voltage Rating int16 1 480 V RW 208
Output Voltage Rating int16 1 208 V RW 209 Current Rating int16 1
600 A RW 210 Frequency Rating int16 1 60 Hz RW 211 Line CT Type
int16 1 4 *** RW 212 Neutral CT Type int16 1 6 *** RW 213 Output OV
Alarm Limit int16 1 115 % RW 214 Output OV Warning Limit int16 1
110 % RW 215 Output UV Alarm Limit int16 1 85 % RW 216 Output UV
Warning Limit int16 1 95 % RW 217 Output OC Alarm Limit int16 1 125
% RW 218 Output OC Warning Limit int16 1 115 % RW 219 Input OV
Alarm Limit int16 1 115 % RW 220 Input OV Warning Limit int16 1 110
% RW 221 Input UV Alarm Limit int16 1 85 % RW 222 Input UV Warning
Limit int16 1 95 % RW 223 Neutral Current Limit int16 1 125 % RW
224 Ground Current Limit int16 1 20 A RW 225 Frequency Limit int16
10 0.5 Hz RW
* Note that there are two sets of kWh/kVAh registers shown above
in Table B-3. The preferred kWh/kVAh registers are the
floating-point register set ranging from 121 to 136, since the
other kWh/kVAh register set, ranging from 33 to 40, are Type int16,
which will roll over when the value of 6553.5 is exceeded.
** Internal Baud Rate Settings (Reg. 205): 0=9600; 1=19200;
2=57600; 3=115200
*** CT Types: 0=200:5A; 1=300:5A; 2=400:5A; 3=600:5A; 4=800:5A;
5=1200:5A; 6=1600:5A; 7=100:5A; 8=1000:5A; 9=2000:5A; 10=1500:5A;
11=3000:5A; 12=2500:5A
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 05/17/10
Rev. G
Page 63 of 120
Table B-4: Alarm Register 1 (Reg. 51) Bit Description
0 Output OV Alarm, A-B 1 Output UV Alarm, A-B 2 Output OV Alarm,
B-C 3 Output UV Alarm, B-C 4 Output OV Alarm, C-A 5 Output UV
Alarm, C-A 6 Output OV Alarm, A-N 7 Output UV Alarm, A-N 8 Output
OV Alarm, B-N 9 Output UV Alarm, B-N
10 Output OV Alarm, C-N 11 Output UV Alarm, C-N 12 Not Used 13
Output OC Alarm, A 14 Output OC Alarm, B 15 Output OC Alarm, C
Table B-5: Alarm Register 2 (Reg. 52) Bit Description
0 Input OV Alarm, A-B 1 Input UV Alarm, A-B 2 Input OV Alarm,
B-C 3 Input UV Alarm, B-C 4 Input OV Alarm, C-A 5 Input UV Alarm,
C-A 6 Neutral OC Alarm 7 Ground OC Alarm 8 Over Frequency Alarm 9
Under Frequency Alarm
10 Not Used 11 Phase Loss Alarm 12 Not Used 13 Not Used 14 Not
Used 15 Not Used
Table B-6: Alarm Register 3 (Reg. 53) Bit Description
0 Output OV Warning, A-B 1 Output UV Warning, A-B 2 Output OV
Warning, B-C 3 Output UV Warning, B-C 4 Output OV Warning, C-A 5
Output UV Warning, C-A 6 Output OV Warning, A-N 7 Output UV
Warning, A-N 8 Output OV Warning, B-N 9 Output UV Warning, B-N
10 Output OV Warning, C-N 11 Output UV Warning, C-N 12 Not Used
13 Output OC Warning, A 14 Output OC Warning, B 15 Output OC
Warning, C
Table B-7: Alarm Register 4 (Reg. 54) Bit Description
0 Input OV Warning, A-B 1 Input UV Warning, A-B 2 Input OV
Warning, B-C 3 Input UV Warning, B-C 4 Input OV Warning, C-A 5
Input UV Warning, C-A 6 Not Used 7 Not Used 8 Not Used 9 Not
Used
10 Not Used 11 Not Used 12 Not Used 13 Not Used 14 Not Used 15
Not Used
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 64 of 120
Reset kWh/kVAh/Demand
The Reset kWh/kVAh/Demand function can be performed using
Function Code 05 (Force Single Coil) to force Coil 3 off (by
sending "00 00").
Table B-8: Modbus Registers Reset (kWh/kVAh/Demand) Coil No.
Description Format Scale Default Unit Type Notes
3 Reset (kWh/kVAh/Demand) int16 N/A N/A N/A W Send "00 00" to
reset.
Table B-9: Sample Packets for Resetting kWh/kVAh/Demand Request
Response
Field Name Hex Field Name HexDevice Address 02 Device Address 02
Function 05 Function 05 Coil Address Hi 00 Coil Address Hi 00 Coil
Address Lo 02 Coil Address Lo 02 Output Value Hi 00 Output Value Hi
00 Output Value Lo 00 Output Value Lo 00 Packet CRC Hi 6C Packet
CRC Hi 6C Packet CRC Lo 39
Packet CRC Lo 39
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 65 of 120
Appendix C: Access
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 66 of 120
Appendix C: Access Figure 1.1 PDM STAND-ALONE
Figure 1.2 PDM/SIDE CAR LINE-UP PDM + 10 SIDE CAR
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 67 of 120
Figure 1.2 (cont.) PDM/SIDE CAR LINE-UP PDM + 10 SIDE CAR
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 68 of 120
Figure 1.3 PDM/SIDE CAR LINE-UP PDM + 24 SIDE CAR SIDE CAR
DISTRIBUTION ALL FRONT
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 69 of 120
Figure 1.3 (cont.) PDM/SIDE CAR LINE-UP PDM + 24 SIDE CAR SIDE
CAR DISTRIBUTION ALL FRONT
Figure 1.4 PDM/SIDE CAR LINE-UP PDM + 24 SIDE CAR SIDE CAR
DISTRIBUTION FRONT & REAR
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 70 of 120
Figure 1.5 PDM/SIDE CAR LINE-UP PDM +24 SIDECAR SIDECAR
DISTRIBUTION ALL FRONT NO DISTRIBUTION IN PDM
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 71 of 120
Figure 1.5 (cont.) PDM/SIDE CAR LINE-UP PDM +24 SIDECAR SIDECAR
DISTRIBUTION ALL FRONT NO DISTRIBUTION IN PDM
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 72 of 120
Figure 1.6 PDM/SIDE CAR LINE-UP PDM + 34 SIDE CAR SIDE CAR
DISTRIBUTION ALL FRONT NO DISTRIBUTION IN PDM
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 73 of 120
Figure 1.6 (cont.) PDM/SIDE CAR LINE-UP PDM + 34 SIDE CAR SIDE
CAR DISTRIBUTION ALL FRONT NO DISTRIBUTION IN PDM
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 74 of 120
Figure 1.6 (cont.) PDM/SIDE CAR LINE-UP PDM + 34 SIDE CAR SIDE
CAR DISTRIBUTION ALL FRONT NO DISTRIBUTION IN PDM
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 75 of 120
Appendix D: Spare Parts List
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 76 of 120
Appendix D: Spare Parts List Spares List-Level 1
Part Number Description Qty
08-13-010030 Fuse 1/4A 250V 3
420000002000 Fuse 1A 600V 3
Spares List-Level 2
Part Number Description Qty
560200003000 XFM 100VA 480-120 50/60HZ 480/208/120 1
41-98-669121 ASSY, BMM PDM MKII 1
43-50-667731 DISPLAY, ASSEMBLY, PDM MKII 1
41-98-669111 ASSY, UIB/PS PDM MKII 1
Spares List-Level 3
Part Number Description Qty
01455-49-R AC SURGE PROTECTOR, 208Y/120 1
01456-49-R AC SURGE PROTECTOR, 480/277V 1
08-13-040006 FUSE, 30A 125V ABC-30 3
420000002004 FUSE 600VAC 30AMP SLOBLO CLASS CC CART 3
440000061000 LIGHTNING ARRESTOR 1
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 77 of 120
Appendix E: Mission Critical 11 & 12 Reconnection
Instructions
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 78 of 120
Appendix E: Mission Critical Reconnection Instructions Section
1: Mechanical Reconnection Step 1: Identify the 8 mating holes on
the side of the PDM II cabinet (see Figure E.1).
Figure E.1: Cabinet Mating Hole Locations
1
2
3
4 5
6
7
8
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 79 of 120
Step 2: Push the two mating cabinets together until they are 0.5
to 1 apart. Step 3: Place one 15-10-667011 cabinet spacer between
the front of the cabinets so that the mating holes of spacer align
to the mating holes of the cabinet. Place a flat washer and lock
washer under the head of a 3/8-16x1.25 bolt, and insert the bolt as
shown in Figure 2. Place a flat washer, lock washer, and nut on the
end of the bolt leaving the bolt loose.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 80 of 120
Figure E.2: Cabinet Assembly Exploded View
Step 4: Repeat Step 3 for the back side of the cabinet. Step 5:
Push the two cabinets together. Step 6: Insert a 3/8-16x1.25 bolt,
with a flat washer and lock washer under the head of the bolt,
through each of the remaining 6 mating holes. Ensure that the bolts
are also passing through the 15-10-667011 cabinet spacers, and lock
all 6 bolts in place with a flat washer, lock washer, and nut on
the end of the bolt. Step 7: Tighten all 8 bolts.
15-10-
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 81 of 120
Section 2: Electrical Reconnection Overview When Mission
Critical units are shipped to the customer, the Static Transfer
Switch and the PDM is separated from each other. The open
(disconnected) wires are left inside of the PDM unit. It is up to
the customer and/or contracted electricians to properly AND SAFELY
reconnect the Mission Critical unit. Each wire hanging in the PDM
(wires that need to be connected to the Static Transfer Switch)
unit will be marked with a number. Each number is unique in the
unit. There should be no two numbers that are the same. The
corresponding numbers will be put in the Static Transfer Switch, at
the correct connection points. Procedure
1. Locate all wires inside the PDM unit that are hanging and
have numbers stuck on the end of each wire. Please see picture
below.
2. Drag each of these wires through the oval located at the
corner post of the PDM. 3. Correspond the numbers on the wires with
the connection point on the Static
Transfer Switch. Please refer to picture below for the number
locations. 4. Use the proper hardware that was given with the unit
and make sure to apply the
correct amount of torque necessary. Please see torque chart
below.
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 82 of 120
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 83 of 120
-
Document No: 94-12-669281 Product Type: PDM II Series
PDM II Series Owners/Operators Manual Release Date: 04/26/10
Rev. G
Page 84 of 120
Appendix F: Kick Plate Instal