'1 \ i \ ' " SERVICE MANUAL 6202A " Operation, Installation and Maintenance FCE-500 Microprocessor-Based Field Code Emulator System September, 1986 A-09/88-250-2777-1 100038F, 0043F Replaces Type L - Form 502A Type L - Form 5048 Type L - Form 504C Field Relay Code Systems UNION SWITCH & SIGNAL DIVISION AMERICAN STANDARD INC./ SWISSVALE, PA 15218
152
Embed
6202A SERVICE MANUAL FCE-500 - Global Product Support
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
'1 \ i \ '
"
SERVICE MANUAL 6202A
" Operation, Installation and Maintenance
FCE-500 Microprocessor-Based Field Code Emulator System
September, 1986 A-09/88-250-2777-1 100038F, 0043F
Replaces
Type L - Form 502A
Type L - Form 5048
Type L - Form 504C
Field Relay Code Systems
UNION SWITCH & SIGNAL DIVISION AMERICAN STANDARD INC./ SWISSVALE, PA 15218
SERVICE MANUAL 6202A
" Operation, Installation and Maintenance
FCE-500 Mic-roprocessor-Based Field Code Emulator System
September. 1986 A-09/86-260-2777-1 l00038f, 0043F
Replaces
Type L - Form 502A
Type L - Form 5048
Type L - Form 504C
Field Relay Code Systems
UNION SWITCH & SIGNAL DIVISION AMERICAN STANDARD INC./ SWISSVALE, PA 15218
m UNION SWITCH & SIGNAL
REVISION INDEX
Revised pages of this manual are listed by page number and date of revision:
FCE Equipment Mounting Card File FCE Storage Unit Preparing and Installing Cardfile System Power Requirements System Grounding Installation of Connectors and Cabling Auxiliary Equipment Final Stick Relay Code Line Arresters Cycle Recorder Control Outputs Indication Inputs SPECIAL APPLICATION DATA Type L - Form 502A LCS and Storage Units Introduction Control/Indication Capabilities Unit Mounting Plug Connectors Programming Guidelines Switch and Jumper Settings - Controller PCB Switch Settings - Serial FRC Interface PCB Control Outputs Indication Inputs Cycle Recorder Type L - Form 504B or 504C, LCS and Storage Units Introduction Control/Indication Capabilities Unit Mounting Plug Connectors
Programming Guidelines Switch/Jumper Settings Control Outputs Indication Inputs R Relay and Series Line Resistor RP and RPP Relay Code Line Filter Cycle Recorder
FUNCTIONAL DESCRIPTION 3.1 OFFICE/FIELD SYSTEM LOGIC 3.2 GENERAL CONFIGURATION OF CODE UNIT 3.3 FIELD STATION BASIC OPERATION 3.3.1 General 3.3.2 Control Code From Office (502A, 5048 and 504C) 3.3.3 Field-Initiated Indication Code (502A only) 3.3.4 Field-Initiated Indication Code (5048 and 504C only) 3.3.5 Auto Recall Mode (502A, 5048 and 504C) 3.3.6 Field Station Disconnect (5048 and 504C only) 3.4 PCB OPERATIONS AND FUNCTIONS 3.4.1 Controller PCB 3.4.1.1 3.4.1.2 3.4.1.3 3.4.1.4 3.4.1.5 3.4.1.6 3.4.1.7 3.4.2 3.4.3 3.4.4 3.4.5
General Station Address Jumpers Program Switches Toggle Switches LED Indications FRC Interface PCB Signals Card File Bus Signals Control Delivery PCB Transmitter-Opto PCB FRC Parallel Interface PCB (5048 or 504C) FRC Serial Interface PCB (502A)
FIELD MAINTENANCE 4.1 INSPECTION 4.2 CLEANING 4.3 SYSTEM TROUBLE ANALYSIS
IV SHOP MAINTENANCE 5.1 GENERAL 5.2 SYSTEMATIC PCB TROUBLESHOOTING 5.2.1 Controller PCB 5.2.1.1 Test Procedure Comments 5.2.1.2 Required Test Equipment 5.2.1.3 Test Set-Up 5.2.1.4 Procedure
Sequential Delivery PCB Test Procedure Comments Required Test Equipment Test Set-Up Procedures Transmitter-Opto PCB Test Procedure Comments Required Test Equipment Test Set-Up Procedure Power Supply Converter PCB Test Procedure Comments Required Test Equipment Test Set-Up Procedure FRC Parallel Interface PCB Test Procedure Comments Required Test Equipment Test Set-Up Test Procedure FRC Serial Interface PCB Test Procedure Comments Required Test Equipment Test Set-Up Procedure
VI SUPPLEMENTAL DATA 6.1 FCE-500 TO DDL-601BX UPGRADE PROCEDURE 6.1.1 6.1.2 6.2 6.3
APPENDIX A A.l A.2 A. 3 A.4 A. 5 A.6 A.7 A.8
General Procedure RECOMMENDED REFERENCE LITERATURE SCHEMATIC DIAGRAMS
PARTS LIST CARD FILE ASSEMBLY CONTROLLER PCB N451441-4303 SEQUENTIAL DELIVERY PCB N451441-5001 TRANSMITTER-OPTO PCB N085722-1001 FRC PARALLEL INTERFACE PCB N451441-6801 FCR SERIAL INTERFACE PCB N451441-70011 POWER SUPPLY CONVERTER PCB N451441-3303 FCE STORAGE UNIT AND CABLE ASSEMBLY
AUXILIARY EQUIPMENT PARTS LIST AND APPLICATION GUIDE
L-10 RELAY, SHELF AND RACK MOUNTING DN-11 RELAY, SHELF AND RACK MOUNTING DN-22 RELAY, SHELF AND RACK MOUNTING PN-150/250 RELAY, SHELF MOUNTING PN-150/250 RELAY, RACK MOUNTING CAPACITOR/RESISTOR UNIT, SHELF AND RACK MOUNTING CODE LINE LIGHTNING ARRESTER CODE LINE FILTER, SHELF AND RACK MOUNTING P-4 TYPE RELAY, SHELF MOUNTING
ILLUSTRATIONS
FCE-500/Relay Code System Block Diagram FCE-500 Card File PCB Arrangement USSP-11 Surge Suppressor Installation on System Power Input Lines Typical FCE-500 Application to 502A Field Relay Code System Standard FCE-500 PCB External Wiring, 502A Mode Controller PCB Manually Selected Options for 502A Cycle Recorder Layout and Connections for 502A System Systems Typical FCE-500 Application to a 504B Field Relay Typical FCE-500 Application to a 504C Field Relay Standard FCE-500 PCB External Wiring, 504B Mode Standard FCE-500 PCB External Wiring, 504C Mode Controller PCB Manually Selected Options for 504B and 504C Code Line Filter Application for 504B: Without DC Blocking or Carrier Blocking Code Line Filter Application for 504B: With DC Blocking and Without Carrier Blocking Code Line Filter Application for 504B: With DC Blocking and With Carrier Blocking Code Line Filter Application for 504C: Without DC Blocking or Carrier Blocking Code Line Filter Application for 504C: With DC Blocking and Without Carrier Blocking Code Line Filter Application for 504C: With DC Blocking and With Carrier Blocking Cycle Recorder Layout and Connections for 504B or 504C Systems
The Field Code Emulator FCE-500 is used to upgrade existing CTC relay-logic field stations to digital logic on a station-by-station basis. The unit can also be used to add new field stations in an existing relay code system. All line coding, addressing, control, and indication operations of the relay code field units are duplicated by the FCE-500. No changes ~re required in the office relay logic. The FCE-500 is designed to be fully compatible with the connector and mounting hardware of the existing field relay code equipment.
The FCE-500 is a standard digital data link code unit containing an FRC Interface (serial or parallel) printed circuit board (PCB), microprocessor (Controller) PCB, power supply converter PCB and a set of relay-output and optical-input PCB's. When a control instruction is processed, the Controller PCB drives the relay-output PCB's. These PCB's are used to operate wayside control relays. When an indication instruction is processed, the Controller PCB scans the optical-input PCB's. These PCB's are designed to receive wayside indication contact inputs on a continuous basis. The Field Relay Code (FRC) Interface PCB connects the de code line data for the FCE-500 Controller PCB. The FRC PCB allows the Controller PCB to communicate with the office relay logic.
Once all relay code field stations have been upgraded with FCE-500 units, the system as a whole can be converted to all-digital operation. This is accomplished, in part, by upgrading the office relay code logic with a DDL-601 Office code unit, and replacing the de code line with a digital carrier modem system. As part of the upgrade process, the FRC Interface PCB in the FCE-500 card file is removed: the FCE-500 is then designated DDL-601BX. A DDL-601BX field code unit is a DDL-6018 unit with an "extended" range of control delivery output times to accomodate the relay timing of the existing code system. Refer to SM-6200 for information on DDL-601BX operation in an all-digital logic system.
This manual describes the FCE-500 that is compatible with 502A, 5048 and 504C relay code systems.
1.2 COMPONENTS
1.2.1 Package (N451583-09XX)
The FCE-500 is housed in a shelf or rack-mountable printed circuit board card file. The card file carries a terminal plug-in board, a code line interface PCB (FRC Interface), one microprocessor logic PCB (Controller), a power supply converter PCB and a set of relay-output and optical-input PCB's arranged according to the application. The general arrangement and functions of the cardfile PCB's are shown in Figure 1-2. Internal circuit connections between boards are made on PCB card edge connectors along the inside of the cardfile rear panel. These connectors share a printed circuit "motherboard", which carries board communications. The PCB's are also connected to a terminal
(Text continued on page 1-4)
6202A, P• 1-1
°' N 0 N :,:,, ... 'd . r-"" I
N '>l .....
IQ s::: ~ (I)
r-"" I
r-"" . ',;! (') tx:J I
U1 0 0 ........ l;d ro r-"" Ill ~
(') 0 0., ro en ~ en (T ro = 0:, r-"" 0 () ~
0 ..... Ill
IQ ~ Ill
=
RELAY CODE OFFICE
•
• OFFICE LINE CODING UNIT
l 1 STORAGE UNIT
l CONTROL CENTER
r
EXISTING RELAY CODE FIELD STATION
I
FCE-500 STATION
DC : CODE LINE
LINE &
START
r-+
4 __ I
• FIELD
LINE CODING STORAGE UNIT
R,RP,RPP RELAYS CYCLE
REC. ETC.
•
() z O Q z ()
d1 • ~ ~ 0 -,... ~ !!! IJJ -I -(/) cil
()
OJO _z .......... Cl)~ ,...
"S" UNIT #1
"S" UNIT #2
• () - 0 -is !!!~ is
210 cil~ o cri~ ,... ~
6 6 z z IJJ
~
• ' . WAYSIDE
FINAL STICK RELAYS
WAYSIDE INDICATION CONTACTS
CONTROL BITS*
INDICATION BITS*
FCE-500
POWER SUPPLY CONV.
PCB
j
A
• RELAY·
OUTPUT PCB
CONTROL WORD
j
m ~ m lJ -< ~ c ~ .!!!
() 0 z ~ 0 ,... IJJ =l Cl)
• CONTROLLER
PCB (INCLUDES
ADDRESSES FOR "S" UNITS)
+
EXISTING DC SUPPLY (16 V. NOM.) ....._._
v
• I I WAYSIDE
L__,,.J_ .J FINAL STICK I -r-r1 RELAYS I ...-
I
OPTOINPUT PCB (IND.
WORD)
"'
m-~~ m o lJ )> -< -I
~~ c IJJ ~ =l .!!! Cl)
WAYSIDE INDICATION CONTACTS
•
• FRC
INTER FACE PCB
'
A.RP, APP RELAYS CYCLE
REC. ETC.
•
--
CODE LINE 1/0 *
INTERNAL SIGNALS*
EB c z 0 z I ~ ::z: Q!I en Gl z )> ....
"ll .... IQ ~ .., (I)
I-' I
N . "ll (") tXl I
V1 0 0
(") DJ .., 0..
"ll .... I-' (I)
'ti (") tp
> .., .., DJ :::, IQ (I) l:I (I) :::, rt"
°' N 0 N > ..
'O . I-' I w
POWER
0 ~ ON OFF
0 +5 VOLTS
0 0 +12 VOLTS
0 -12 VOLTS
POWER SUPPLY
PCB I I J1
r----...J I APPLICABLE
I POWER SUPPLY CONVERTER PCB:
: -;.4s1«1·3303 -
WORD WORD WORD WORD WORD 1 2 3 4 5 O LED1
O LED2
O LED3
O LED4
h ... N w ... O LED5 ~ z ::u .....
en c:, c:, :z: n en en
~ en O LED& 0 ..... a a ii 0
::u ::u s? ! > > 0 C) C) C) O LED7 t; m m m m c c c c
~ SW8 z z z z :::j :::j :::j :::j n n n n i 0 0 0
~ SW7 !i ..... z z ~ ~ ::u ::u
0 0 0 0
~ SW& .... .... J;; t; en en
-0 SW4
= ~ SW 5
DLVR DLVR DLVR DLVR DLVR (i)) SW 1
0 0 0 0 0 G>) SW2
ADRS ADRS ADRS ADRS ADRS
0 0 0 0 0 @ SW3
:J2 J3 J4 JS JI
I ' .I "'-""'" I APPLICABLE RELAY-OUTPUT PCB: I N451441·3601
I I
J7
;I ... i! !e !~ ~
n 0
!i ::u 0 e ::u .,, n 1111 c
! ... t ... J,,. f!i en
PCB N461441-8801 ONLY
WORD WORD WORD WORD WORD 1 2 3 4 5
h ... N w ~ en z ::u en ..... c:, c:, :z: iii en en en en S! a ..... ..... a 0 0 n ::u ::u ::u ::u ~ > > > > C) C) C) C)
0 m m m m z c c c c en z z z z
:::j :::j :::j :::j
iii z z iii c:, c:, S! 0
" " " n g > ~ > g ::::! 0 0 z z z z en en en en
LOW LOW LOW LOW LOW BYTE BYTE BYTE BYTE BYTE
0 0 0 0 0
HIGH HIGH HIGH HIGH HIGH BYTE BYTE BYTE BYTE BYTE
0 0 0 0 0
i , J8 Jg ~ J11 J1~ I I APPLICABLE OPTICAL-INPUT PCB'S: I I N451«1.3201 I I N085722· 1001 I I I
. .,, :a n z -I m :a .,,
0 ::,:,,. n m
M
l 0 CON, NECT
.. 0 z z z ~ 0 0 ..... XMT ..... c c c en en 0 en m m m 0 0 0
REC
0
0
J13 J14 I J1s: J16
r--.J L.--, I STANDARD I
PCB I ', N451441·6801(5048/C) I
OR I N451441-7001(502A) :
c z 0 z I ~ :c • (I)
ci z )> r
EE
UNION SWITCH & SIGNAL
plug-in board on top of the card file. These terminals are directly compatible with the existing connectors that interface external equipment such as power supplies, wayside relays etc. Slots Jl3, Jl4 and Jl6 are not used in FCE-500 applications, however PCB connectors are provided in these slots to allow installation of extra optical-input PCB's when the code unit is converted to a DDL-601BX.
1.2.2 FCE Storage Unit and Cable Assembly (N451458-540X and 550X)
The FCE Storage Unit simulates the storage unit of the existing relay code system. It contains a set of plug connectors identical to the top plug connectors of the existing storage unit. However, this unit contains no internal relays or electronics: it is only a wiring connection unit. The functions of the relay code storage units are now handled by relay-output and optical-input PCB's in the FCE-500 card file. Factory-assembled cables are connected to the underside of the FCE Storage Unit terminal board. Plugs at the other end of the cables are inserted in the upper card edge connectors of relay-output and optical-input PCB's in the card file. (The -540X series of assemblies substitute for 502A storage units, while the -550X series substitutes for the 504B and 504C storage units.)
1.2.3 Card File Printed Circuit Boards
1.2.3.1 Controller PCB (N451441-4305)
The Controller PCB performs all logical decisions and calculations for the FCE-500. Its main functions include managing of instructions and data to and from the office (through the FRC Interface PCB) and execution of watchdog and testing routines. It processes wayside controls and indications through the output and input boards in the cardfile. Key components include:
Microprocessor
The principal component of the Controller PCB is a 6809 microprocessor chip. It is an NMOS device operating from a single 5 Vdc power supply.
PROM
There is one 2732 Programmable Read Only Memory (PROM) IC on the PCB. It has a capacity of 32,768 bits or 4K, 8 Bit bytes of memory and is used to store system software.
PIA's
The Controller PCB contains two 6821 Peripheral Interface Adapter (PIA) IC's. The PIA's interface all data and system status information to and from the microprocessor.
PTM's
The Controller PCB contains two 6840 Programmable Timer Modules (PTM's). The PTM's measure the time width of pulses to and from the Office and provide various time-out functions.
6202A, p. 1-4
UNION SWITCH & SIGNAL m RAM
One Random Access Memory (RAM) IC is used on the board for short term or "scratch-pad" memory. It has a capacity of 2048 8-bit words.
LED's
Seven LED's are provided on the Controller PCB for miscellaneous monitoring and board troubleshooting purposes. The LED's are mounted on the foward edge of the board to allow observation in the cardfile.
Toggle Switches
The Controller PCB is equipped with three SPDT toggle switches. These are used to simulate code line data bits during system tests and inhibit processor circuit operation during such tests.
Jumper, Rotary and DIP Switches
The Controller PCB contains two 8-position rotary switches and three Dual In-Line Package (DIP) rocker switches (8 rockers each) on the front edge of the PCB. The board also has seven jumper sockets. These devices are used to configure the FCE-500 unit for the associated code system (i.e., establishing system size and storage unit addresses).
1.2.3.2 Control Delivery PCB (N451441-3601)
US&S provides one standard relay-output PCB for the Control Word locations of the FCE-500 card file (502/504 version): Control Delivery PCB N451441-3601. The card file may contain from one to five of these PCB's, as determined by application.
This PCB is equipped with 16 mercury-wetted (Form C) relays that output control bits to external circuits. One quad exclusive-OR gate is provided for address decoding. One triple NAND gate processes address acknowledgement and data bit load/deliver signals. Four quad latching IC's hold bit prior to delivery. Hex buffer/inverters are used to drive the relays and two LED's.
1.2.3.3 Transmitter-Opto PCB (N085722-1001)
US&S provides one standard optical-input PCB for the Indication Words of the FCE-500 card file: Transmitter-Opto PCB (N085722-1001). From one to five of this PCB will be installed in slots JS through Jl2 of the card'file, as determined by the application. The name "Transmitter Opto" is carried over from a previous application of the N085722-1001 PCB and does not apply to FCE-500 operation.
There are 16 photo-Darlington optical coupler's mounted on this PCB, one for each input line. The couplers allow input of relay contact data, while electrically isolating the relay circuit currents from the board logic. The couplers also provide transient voltage protection and are designed to accept 5 to 32 volts ac or de. Tri-state hex inverter/buffer !C's are used to accept
6202A, p. 1-5
UNION SWITCH & SIGNAL
contact data and to allow parallel transmission of the 16 indication bits over the 8 bit motherboard bus to the Controller PCB. A quad exclusive OR gate IC (CMOS) is provided for address decoding, while two NAND gates are used for byte selection among the bits on the tri-state buffers. Two LED's are included for routine monitoring.
1.2.3.4 Power Supply Converter PCB
US&S provides one standard power supply converter PCB f9r the FCE-500: N451441-3303. This is a de/de converter that regulates operating power for the other card file PCB's and power for external equipment, when required by the application. The nominal power input range for the board is 12 vdc from an unregulated source. The full range is 9 to 18 Vdc. Three different output voltages are developed by three converters, including +5 Vdc at 3 amps, +12 Vdc at 1 amp and -12 Vdc at 1 amp. A surge suppressor is installed across the input lines for transient voltage protection, while an input filter is used to eliminate line noise into the converters. An LED is installed across each of the output lines to monitor performance. This PCB also contains the FCE-500 power on/off switch (SPDT toggle).
1.2.3.5 FRC Interface PCB (Serial or Parallel)
The Field Relay Code Interface PCB is used in the FCE-500 system to interface microprocessor-based circuits to the de code line. There are two versions of this PCB.
FRC PCB N451441-6801 is used for the parallel de code line in 5048 and 504C applications. Major components include four mercury-wetted, double pole relays and one optical isolator re. The relays include "XMT" (code line shunt during indication transmissions), "M" (set proper polarity for external "R" relay), "MP" (code line filter control) and •connect• (disconnect circuits in some applications). The optical coupler is used to electrically isolate the Controller PCB from code line signals, while passing on code line data.
FRC PCB N451441-7001 is used exclusively for the serial de code line in the 502A application. It is equipped with the same components as the -6801 board, however there are only three relays ("Connect• relay not used).
1.3 SPECIFICATIONS
1.3.1 Physical/Mechanical
Overall dimensions, system card file:
Overall dimensions, FCE Storage
Card file PCB access:
Card file mounting:
Storage unit mounting:
6202A, p. 1-6
W = 19", H = 15-5/8", D = 10-5/8"
W = 12-13/16", H = 3", D = 6-31/32"
Hinged/removable front cover
Rack (19" standard) or shelf
Shelf
System card file connections:
Storage unit connections:
1.3.2 Electrical
System power supply PCB fuse:
System power supply input:
System power supply outputs:
UNION SWITCH & SIGNAL
Plug connector (502A): 75 terminals using three 5" X 5• plug connector boards
Plug Connector (5048 and C): 80 terminals using two 5" X 5", and one 5" X 6" plug connector board
Plug connector: 50 terminals using two 5" x 5" plug conqector boards
NMOS, 6809 microprocessor, 2732 PROM, Support IC's: CMOS
Half duplex
TS-200 Series Test Sets: DDL-601BX: FCE-500 (506, 506A, 506C, 514):
SM-6171 SM-6200 SM6202
UNION SWITCH & SIGNAL ~ SECTION II
APPLICATION, INSTALLATION AND ADJUSTMENT
2.1 GENERAL APPLICATION DATA
2.1.1 Equipment Mounting
2.1.1.1 Card File
The FCE-500 system cardfile (equivalent of LCS unit) ca~ be mounted on a shelf or in a 20" equipment rack. The cardfile requires a mounting space 19" wide, 10-5/8" deep and 15-5/8• high. Make sure to allow space for handling connectors on the topside terminal board (if these are used in the application). Also, leave a space approximately 17" wide by 12-1;2• deep in front of the cardfile to allow the door to open fully. This door provides access to the internal printed circuit boards. Refer to the special applications section (2.2) for dimensional differences between the card file and the LCS unit it is intended to replace.
If the cardfile is to be shelf mounted, check whether the shelf has front lip which rises above the top surface of the shelf. A lip would restrict the cardfile door and prevent removal of the plug-in PCB's. The lip should be removed if possible, or the shelf should be raised above the lip. The cardfile can be screwed or bolted to the shelf using 9/32• mounting holes. These holes are located in mounting feet on the sides of the unit. Centers of the mounting feet holes are space at 18-3/8•. Use 1/4• screws or bolts for shelf mounting.
If mounting the FCE-500 system cardfile in a rack, use all four four mounting points on the front vertical brackets. These are spaced at 4" x 3• x 4• intervals. This mounting requirement can be met with racks which use universal E.I.A. Standard RS-310 vertical spacing (i.e.: 112• x 5/8" x 5/8" x 112• x 5/8" x 5/8" x etc.). US&S recommends the following equipment:
Item Description US&S Part No.
Equipment Rack 6' 9-5/8" H X 20" W X 12" D US&S R396261
Speed Nut For #12-24 screw and rack frame thick- US&S J480203, ness of .051" to .109• Tinerman No.
C509-1224 or equivalent
Screw #12-24 x 1/2",steel pan head US&S J507261
The cardfile shelf mounting feet, located on each side, must be removed before the cardfile is inserted in the rack. The mounting feet are attached with #10 screws, washers and nuts which can be removed with a screwdriver and wrench.
6202A, P• 2-1
UNION SWITCH & SIGNAL
2.1.1.2 FCE Storage Unit
The FCE Storage unit must be shelf mounted. The unit can be screwed or bolted to the shelf using 9/32n mounting holes. These holes are located in mounting feet on the sides of the unit. Centers of the mounting feet holes are spaced at 12-5/16n. Use l/4n screws or bolts for shelf mounting.
The distance from the FCE-500 system cardfile to the FCE Storage unit is limited by the length of the standard connector/cable assemblies provided with each code system application (refer to section 2.2). T~ese assemblies connect the Storage unit plug terminals to the connector edges in the cardfile. The following tabulation shows the maximum physical distance allowed between the cardfile and storage unit:
Storage Unit Max. Physical Sep.
u 5 ft. #2 7 ft. #3 9 ft. #4 11 ft.
2.1.2 Preparing and Installing Cardfile PCB's
The FCE-500 is shipped with the PCB's in separate packages. Install the PCB's according to the instruction label on the inside face of the front cover (see also Figure 1-2). The Controller PCB must be manually programmed (switches and jumpers) to configure the unit for the customer's particular application In addition, the FRC Serial Interface PCB (N451441-7001, 502A applications) must be configured for proper operation on the customer's particular code line. Refer to section 2.2 for all required programming procedures. To install or remove a PCB, loosen the 1/4-turn screws on the cardfile front door and lower the door so that the PCB can be pulled straight out.
CAUTION
DO NOT REMOVE OR INSTALL ANY FCE-500 SYSTEM PRINTED CIRCUIT BOARD WITH POWER ON, OTHERWISE EQUIPMENT DAMAGE AND/OR UNRELIABLE EQUIPMENT OPERATION MAY RESULT.
NOTE
To prevent undesired operation of the Connect and Transmit relays on the FRC Interface PCB, set SW2 on the Controller PCB to OPERATE and SW3 to MARK.
Make certain to close and lock the cardfile front door after the Contoller PCB has been reinstalled. The power supply converter, relay-output and opticalinput boards do not require any initial adjustments. If switch and jumper selections on the Controller PCB are to be changed afterwards, one of the following must occur for the board logic to accept the change:
6202A, p. 2-2
UNION SWITCH & SIGNAL
1. Toggle switch SWl on the power supply converter PCB (slot Jl) must be turned off and back on.
2. Reset toggle switch SWl on the Controller PCB (slot J7) must be moved to the RESET position, then back to NORMAL.
3. The Controller PCB watchdog timer circuit must trigger. This will be shown by lighting of the Watchdog LED.
2.1.3 System Power Requirements
FCE-500 system power input specifications are 9 to 18 Vdc input (12 Vdc nominal) at 2 amps maximum, and with a maximum ripple of 5%. The FCE-500 can use the existing power source of relay code system. However, a US&S USSP-11 surge suppressor must be added to the power lines of the existing system, if not already available. This suppressor contains lightning arresters. Its wiring is shown in Figure 2-1.
The FCE-500 system indication input power limits are the same as the operating limits of the system. The maximum current draw of each indication input on the optical-input PCB's is 3 milliamps.
2.1.4 System Grounding
The FCE-500 system requires a solid ground for proper operation. This ground is made by connecting two #6 AWG wires to the ground stud on the back of the FCE-500 system cardfile and running them to the house or case prime ground. Keep these ground wires (a) away from all other wiring as much as possible, (b) as short as possible and (c) with no sharp bends.
2.1.5 Installation of Connectors and Cabling
The FCE-500 accepts the plug connectors of the existing relay code system. These connectors can be used without modifications. When inserting the connectors on the FCE-500, do not apply excessive pressure to the back of the cardfile. The cardfile back panel does not have external support. Excessive pressure on the connectors may cause the equipment to warp.
When the plug connectors are removed for servicing, they are stored on •s• hooks. The •s• hooks will suspend the plug connector above its unit. Mounting of the "S" hooks can be accomplished in either a rack or shelf mount configuration. US&S recommends •s• hook J056179 (Campbell Chain Co. #62 or equivalent).
There are no additional hardware required to shelf mount the "S" hooks. The "S" hooks are mounted in holes drilled into the bottom of the lip of the next higher shelf.
6202A, p. 2-3
m UNION SWITCH & SIGNAL
16V INSTALLATION (OPERATING) (Maximum Rating for Suppressor: 32 voe@ 15A)
Run grounds separate from all other wiring and metal to the prime ground bus, as directly as possible and with a minimum number of bends.
Figure 2-1. USSP-11 Surge Suppressor Installation on System Power Input Lines
The following part is required to rack mount the •s• hooks:
Item Description US&S Part No.
Mounting bar For 20" rack M371705
Mounting bar For 31" rack M341877
A clearance of at least 12" should be allowed between the top of the FCE-500 equipment and the •s• hook. for either shelf or rack mounted equipment.
6202A, p. 2-4
UNION SWITCH & SIGNAL ffi 2.1.6 Auxiliary Equipment
2.1.6.1 Final Stick Relay
The FCE-500 system uses the final stick relays to store controls in the same way as the field relay code system. Refer to section 2.2 for typical wiring of these relays in specific code systems. When the FCE-500 replaces an existing field relay code system, the final stick relays can be used without modification. If a new location is to use an FCE-500, the final stick relays are selected as follows:
US&S recommends the use of the following relay hardware:
Relay PN-150B Biased Type, 0.8K Ohm Coil, 6FB Contacts With Front Testing: N322500-702 Without Front Testing: N322500-802
Relay PN-150B Biased Type, I.OK Ohm Coil, 6FB Contacts With Front Testing: N322500-703 Without Front Testing: N322500-803
Relay PN-250B Biased Type, I.OK Ohm Coil, 6FB-6F-3B Contacts With Front Testing: N322554-701
Without Front Testing: N322554-801
Relay PN-250B Biased Type, I.OK Ohm Coil, 8FB-4F-2B Contacts With Front Testing: N322554-702
Without Front Testing: N322554-802
Base PN-150B Type N451376-0302
Base PN-250B Type N438689-003
The final stick relay can be shelf or rack mounted. Appendix B lists all required mounting hardware.
6202A, P. 2-5
UNION SWITCH & SIGNAL
2.1.6.2 Code Line Arresters
The code line arresters are used to protect the FCE-500 from high voltage surges on the code line. Refer to section 2.2 for typical wiring of the code line arresters in the specific relay code systems. When the FCE-500 replaces a field relay code system, the existing arresters can be used without modifications. If a new location is to use a FCE-500 system, the arresters are selected as follows:
US&S recommends the use of the following arresters:
Item Description US&S Part No.
Arrester USG-A high voltage type, 500 to 1300 Vdc N451552-0201 firing voltage
The code line arresters can be shelf or wall mounted. Appendix B lists all required mounting hardware. The USG-A arrester may be mounted on a wall or on the top of a shelf, but should not be mounted upside down on the under side of a shelf. It may be mounted horizontally or vertically. If mounted vertically, the open end of the cover should be placed down to prevent accumulation of debris inside the cover. Allow a one inch minimum clearance between the open end of the arrester and a flat mounting surface to permit escape of gases.
2.1.6.3 Cycle Recorder
The cycle recorder may be used with FCE-500 when replacing an existing field relay code system, or when installing an FCE-500 at a new location. This device provides a convenient means for measuring and recording time intervals such as code impulses. The two-punch recorder gives a complete record of a entire code on one tape. Odd numbered impulses are recorded by one magnetic punch on one line; even numbered impulses by the another magnet punch on a second line. When the cycle recorder shifts from one line to the other, there will not be an overlap of more than one punch. An overlap of more than one perforation, or loss of perforations, indicates that the cycle recorder needs adjustment. A correct recording is shown as follows:
1 2 3 4 1/2 1/2 1/2 J./2 1/2 OVERLAP < < < < < <
< < < < < l 2 3 4 5
1 2 3 4 1/2 1/2 J./2 1/2 1/2 < < < < <
< < < < < l 2 3 4 5
6202A, p. 2-6
UNION SWITCH & SIGNAL
To read a cycle recorder tape, count each perforation as 1/2 cycle and disregard the OVERLAP punch in the count. When using the cycle recorder for measuring code line timing, the right hand punches are for odd numbered pulses and the left hand punches are for even numbered pulses. When using the cycle recorder to measure coding time with the FCE-500 system, observe the limits defined in section 2.2 for the specific code system application. Cycle recorded part numbers are as follows:
The cycle recorder tape tape will fit on existing equipment by removing the paper guide.
2.1.7 Control Outputs
The FCE-500 system uses relay contacts to connect the wayside control final stick relays to microprocessor logic levels of the Controller PCB. The control final stick relays are applied to the FCE-500 system in the same way as the relay code system. Refer to section 2.2 for control output set-ups in the specific code systems.
The FCE-500 system control output power limits are the same as the operating limits of FCE-500 system. The current output of each control output is a function of the resistance of the final stick relay. For example, in the case of an 800 ohm PN-150B relay operating at 16 Vdc, the output current will be 0.02 amps. The maximum current available per output on a relay-output board is 2 amps or 100 VA (resistive load).
2.1.8 Indication Inputs
The FCE-500 system uses optical-isolators to convert wayside indication voltage levels to the microprocessor logic levels of the Controller PCB. These voltages are applied to different cardfile and storage unit plugboard terminals in the same way as the existing field relay code system.
6202A, P• 2-7/8
UNION SWITCH & SIGNAL
502A
2.2 SPECIAL APPLICATION DATA
2.2.1 Type L - Form 502A LCS and Storage Units
2.2.1.1 Introduction
The following part numbers describe the FCE-500 systems applied to 502A based code systems:
Description US&S Part No.
FCE-500, 502A Emulator, with no storage unit N451583-0921 FCE-500, 502A Emulator, with 1 storage unit N451583-0922 FCE-500, 502A Emulator, with 2 storage units N451583-0923 FCE-500, 502A Emulator, with 3 storage units N451583-0924 FCE-500, 502A Emulator, with 4 storage units N451583-0925
Figure 2-2 shows a t~cal application of the FCE-500 in a 502A code system. Wires marked with a I are not required in new FCE-500 installations. Figure 2-3 shows the standard 502A wiring between FCE-500 cardfile PCB's, various external terminals and FCE Storage units. The standard cable distances for connecting the cardfile to storage units are as follows:
Cable/Connector Assembly Description US&S Part No.
502A, cardfile to 1st storage unit, length = 5 ft. N451458-5401 502A, cardfile to 2nd storage unit, length = 7 ft. N451458-5402 502A, cardfile to 3rd storage unit, length = 9 ft. N451458-5403 502A, card file to 4th storage unit, length = 11 ft. N451458-5404 502A, cardfile to Xth storage unit, length = 17 ft. N451458-5405*
*This assembly may be added or replaced where adjacent space is not available.
2.2.1.2 Control/Indication Capabilities
The FCE-500 is capable of handling the maximum control and indication limits of the 502A system. Each FCE-500 relay-output PCB outputs five control steps. The first (slot J2) relay-output PCB serves the same function as the LCS part of the 502A. Each additional five control outputs require another relay-output PCB for the FCE equivalent of a 502A storage unit. The limit (five relay-output PCB's, slots J2 - J6) of control outputs available with the 502A-mode FCE-500 is 25 controls.
6202A, P• 2-9
UNION SWITCH & SIGNAL
502A
Each optical-input PCB accepts seven indications inputs. The first optical input PCB (slot J8) serves the same function as the LCS part of the 502A code system. Each additional seven indication inputs require another optical input PCB for the FCE equivalent of a 502A storage unit. The limit (five optical-input PCB's, slots J8 - Jl2) of indication inputs available with the 502A-mode FCE-500's is 35 indications.
2.2.1.3 Unit Mounting (Refer also to Sections 2.1.1.1 and 2.1.1.2)
As indicated below, the FCE-500 cardfile is slightly higher and deeper than the 502A LCS unit:
502A Line Coding Storage Unit FCE-500 Card File
23• W x 14-1/2" H x 7-3/8• D 19• W x 15-5/8• H x 10-5/8• D
The FCE Storage unit requires more horizontal space, but has a lower profile:
502A Storage Unit FCE-500 Storage Unit
11-1/2• W X 14-1/2• H x 7-1/4• D 12-13/16" W x 3• H X 6-31/32 8 D
•ff• is the height of unit with external plug connector attached, but without required clearance needed to remove external plug connector. •n• is the depth without clearance for external wires, if required. These spaces differences should be taken into account when preparing to mount the FCE-500 cardfile and any storage units.
2.2.1.4 Plug Connectors (Refer also to section 2.1.5)
If a new location is to use an FCE-500 system, US&S recommends selection of the plug connectors according to the following tabulation:
Type of Unit Position (L to R) US&S Part No.
Card File 1 Nl73240
Card File 2 Nl73242
Card File 3 Nl73219
Storage Unit 1 Nl73240
Storage Unit 2 Nl73246
6202A, p. 2-10
.0. SMD
:IRCUITS qcE
{
<->ZL
(+IYL
TYPICAL APPLICATION OF FCE-500 IN 502A MODE
TO OTHER F !ELOS
(- IZL } LINE ClRCUJT
~---"<•~l~YL~I .
UNlT
FCE-500 - 502A W[TH NO STORAGE UNIT FCE-500 - SOZA W[TH I STORAGE UNIT FCE-500 - 502A WITH 2 STORAGE UNITS FCE-500 - 502A WITH 3 STORAGE UNITS FCE-500 - 502A WITH 4 STORAGE UNITS
PART NO. ----UN451583-092l UN451583-0922 UN45 I 583-0923 UN451583-0924 UN451583-0925
STANDARD CIRCUIT
0"451272-1605
F'CE-500 CAROFILE
GROUND STUD , .. HOOSE PIHi,£
GROUNO
,--------- .. ---------------. -,·----ov
POWER SUPPLY PCB
UN4514"41-3303 CAROFH.E LOCATION JI
SERVICE MANUAL 6202A
~-·---1 CODE
~ I 12J~1lA~iN
------=-----~i ,/ -->-------@--- --+, I r--®=-'L
I I ' -+..+-------®--- ---+- • : ~~~E~~
-.f,o,l-------@-- - --+ ... ... :~~\~ S UNJ1
-.f,o,l-------®------.. + ... PLUG E
--...... ------@--- _ _,. ... ...
--------®------+ ... -~------®--- -----+
COOE i --@)- - - - ! 12Sf~~~~H I
I I --@------1--, .&. :
1..,..1'* \ I
STANOARO WIRING DIAGRAM -@- - - - -+, I 1 - --€ci\-- NI
I I y 0451273-1602
NIC -®-----.. .. : L---
-@-----.. ... :
--®-----.. ... : NOTES, I
NIC - NO {NTERNAL CONNECTION -®------+ ... I
£ - EXTERNAL CONNECTION NOT REQUIRED UNLESS UNIT TO SE USED I
::x~~!~~:A~~~A~i\~":! :i~!/!~\:~~~ FIELD RELAY CODE UNIT £ -®-------+ : £ - TERVINAL 67 SHOWN IN TWO PLACES {-®- ~
---------------------,------------J ~ ¥ ~ ~ ~ i i ¥ f ¥ ~ f------------, "" t;;;;;3 l---------------- '--L--------J NIC
Figt
I o ::, <Il
ZL
YLI
22 •
'i 6 i 7 4 -~-·r-·- J7 CONTROLLER
BO ARO
JI 5 ,FACE SO. 441-7001
J_
M ~)>=2"-1---,
1-;-' ---,-/ -,-
1 ~y--<~ ( TX. DATA
-o.--------"---~)) IS : l 1
11
1
BN ~ ( COM. MOOE
ISOLATOR
~)22 11 BK ~(c.M. FEED
>----~>'9 11 I lo ((REC. DATA
~ 21 u,
j;o 9 q q
~ z
.~'(is >I:Y~:-:-E--------------~BK"-----~ 18 ~ 6 7 • RECORDER R
I. THE FOLLOWING REPRESENT THE PC. NOS, N45i 583-0921 • FCE 500-502A WI TH NO STORAGE UNIT. N451583-0922 • FCE 500-502A WITH I STORAGE UNIT. N45i 583-0923 • FCE 500-502A WITH 2 STORAGE UNITS, N451583-0924 • FCE 500-502A WI TH 3 STORAGE UNI TS, N451583-0925 • FCE 500-502A WI TH 4 STORAGE UNI TS,
The following items must be considered when planning the programming of the FCE-500 for a 502A system:
1. Is Auto Recall desired? When Auto Recall is active, the FCE-500 system will respond with a indication code when a valid control code is
502A
received. This will increase system coding time. lherefore, the decision to use Auto Recall must be based on number of trains and the system response time required.
2. What resistance should the "R" relay be set at? When replacing an existing unit, use the following tabulation to determine the "R" relay resistance:
When developing a new location on an existing line, determine the "R" relay resistance at an existing location on that line, then use the same resistance at the new location. On a new line. consult the code line calculation for the value of the "R• relay.
2.2.1.6 Switch and Jumper Settings - Controller PCB (Location J7)
A. LCS Address
The 502A LCS address is set with jumpers on the plug connectors on the FCE-500 cardfile. The address is set as follows:
LCS Address Step Post Address Step Connect Post
2 52 First 51 3 53 Second 59 4 54 Third 49 5 55 6 56 7 57 8 58
6202A, P• 2-15
UNION SWITCH & SIGNAL
502A
Examples:
Address 234 - Connect post 51 to 52, post 59 to 53 and post 49 to Address 456 Address 678
- Connect post 51 to 54, post 59 to 55 and post 49 to - Connect post 51 to 56, post 59 to 57 and post 49 to
NOTE
In the 502A address selection process, only three unique long steps are acceptable. The ERROR LED on the Controller PCB (LED 4) will light if more than
54 56 58
or less than three steps are selected as longs, .2!:. if the address selected is the same as an address selected for a storage unit within the same cardfile.
B. First Storage Unit Address
The 502A 1st storage unit address is set with DIP switch SW8 on the Controller PCB (location J7). Figure 2-4 shows the general arrangement and operation of the Controller PCB switches and jumpers for 502A system emulation. The long steps of the address are set by placing the rockers to the open ("l") position. The short steps of the address are set by placing the rockers to the closed ("O") position. ("X" = rocker position not pertinent to any particular function).
2 :llo x 0 0 0 0 0 0 1 3 x 0 0 0 0 0 1 0 4 x 0 0 0 0 1 0 0 5 x 0 0 0 1 0 0 0 6 x 0 0 1 0 0 0 0 7 x 0 1 0 0 0 0 0 8 x 1 0 0 0 0 0 0
For example, address 234 would be set as follows:
SWITCH SW8 Rockers
8 7 6 5 4 3 2 1
x 0 0 0 0 1 1 1
6202A, p. 2-16
CONTROLLER PCB N451441-4305
COMPONENT SIDE (NOT TO SCALE)
4TH STORAGE UNIT ADDRESS
ALWAYS USE 7 JUMPERS.
UNION SWITCH & SIGNAL
502A
sw5: SET TO "O" FOR 502A
r-- :-e:-: /~ _· ==========-SW4: SYSTEM SIZE
D SMS
D O = LCS ONLY 3 =3 S. UNITS 1 = 1 S. UNIT 4 =4 S. UNITS 2 = 2 S. UNITS 5-8 = NOT USED
D9MS~M.._S--i-----~,~-S~~~~~~ 234 5678
~-[i]~li]~~~[i]
PCB MAY BE EQUIPPED WITH LOW OR HIGH PROFILE (ROCKER) DIP SWITCHES.
-----OPEN-----
\ } t 3RD STORAGEYUNIT ADDRESS NOT
USED
-----OPEN-----
\..._ _____ y } i 2ND STORAGE UNIT ADDRESS AUTO
RECALL
1 234 5678
tl [i1~ ~ ~ li1 El t1 -----OPEN-----
\ ) l 1 ST STORAG~T ADDRESS
NOT USED SWITCHES SHOWN IN .. OPEN .. POSITION
Figure 2-4. Controller PCB Manually Selected Options for 502A
6202A, p. 2-17
UNION SWITCH & SIGNAL
502A
c. Second Storage Unit Address
The 502A 2nd storage unit address is set with DIP switch SW7 on the Controller PCB (location J7). The long steps of the address are set by placing the rockers to the open c•1•) position. The short steps of the address are set by placing the rockers to the closed c•o•) position. Rocker 48 is used for selection of Auto Recall; refer to section G on page 2-19.
The 502A 3rd storage unit address is set with DIP switch SW6 on the Controller PCB (location J7). The long steps of the address are set by placing the rockers to the open c•1•) position. The short steps of the address are set by placing the rockers to the closed c•o•) position. c•x• = rocker position not pertinent to any particular function):
2 .. x 0 0 0 0 0 0 1 3 x 0 0 0 0 0 1 0 4 x 0 0 0 0 1 0 0 5 x 0 0 0 1 0 0 0 6 x 0 0 1 0 0 0 0 7 x 0 1 0 0 0 0 0 8 x 1 0 0 0 0 0 0
E. Fourth Storage Unit Address
The 502A 4th storage unit address is set with the Station Address jumpers on the Controller PCB (location J7). When the jumper is set to the no• side, the address step is short. When the jumper is set to the •1• side, the address step is long. The numbering of the 4th storage unit addresses at the Controller PCB jumpers is as follows:
6202A, p. 2-18
,t
Jumper Pos.
1 2 4 8
16 32 64
F. 502A Mode Selection
4th Storage u. Address Step
2 3 4 5 6 7 8
UNION SWITCH & SIGNAL
502A
The 502A mode is selected using rotary switch SW5 on the Controller PCB (location J7). Set this switch to the "O" position for the a 502A system.
G. Auto Recall Selection
The Auto Recall mode for 502A is controlled with rocker #8 of DIP switch SW7 on the Controller PCB (location J7). To activate the Auto Recall mode, set this rocker to the open position. To keep this mode inactive, set rocker #8 to the closed position. Make certain not to readjust any of the other SW7 rockers used to set for other functions.
H. System Size
The size of the 502A system is defined using rotary switch SW4 on the Controller PCB (location J7). The switch settings are as follows:
SW4 Position System Size
0 LCS Unit Only 1 1 Storage Unit 2 2 Storage Units 3 3 Storage Units 4 4 Storage Units 5 Not Used 6 Not Used 7 Not Used
If SW4 is set at position "l", the address for the first storage unit must be properly set, otherwise the system will lock up. This will be indicated with the lighting of LED 4 on the Controller PCB (location J7). The same is true for the remaining storage unit settings. If switch SW4 is set to positions 5, 6, or 7, the system will again lock up (LED 4 on).
6202A, P• 2-19
UNION SWITCH & SIGNAL
502A
2.2.1.7 Switch Settings - FRC Serial Interface PCB (N451441-7001)
The code line "R• coil resistance for the 502A system is set on FRC Interface PCB N451441-7001 (location Jl5), using toggle switch SWl (3-position type). The switch options are as follows:
SWl Position "R" Coil Resistance
18 18 Ohms 29 29 Ohms 70 70 Ohms
2.2.1.a Control Outputs
The following tabulation lists relay-output PCB slot and plug connector terminal numbers that pertain to control outputs for 502A mode:
Control Control Cardfile Output Outputs
Slot Function Emulated Terminals Served
J2 LCS Unit 1 to 8 ( 1 to J3 1st Storage Unit 1 to 8 ( 6 to J4 2nd Storage Unit 1 to 8 (11 to J5 3rd Storage Unit 1 to 8 (16 to J6 4th Storage Unit 1 to 8 ( 21 to
2.2.1.9 Indication Inputs
5) 10) 15) 20) 25)
The following tabulation lists optical-input PCB slot and plug connector terminal numbers that pertain to indication inputs for the 502A mode:
Indication Indication Cardfile Input Inputs
Slot Function Emulated Terminals Served
JS LCS Unit 9 to 15 ( 1 to 7) J9 1st Storage Unit 9 to 15 ( 8 to 14) JlO 2nd Storage Unit 9 to 15 (15 to 21) Jll 3rd Storage Unit 9 to 15 (22 to 28) Jl2 4th Storage Unit 9 to 15 (29 to 35)
6202A, p. 2-20
2.2.1.10 Cycle Recorder (Refer also to section 2.1.6.3)
UNION SWITCH & SIGNAL
502A
Figure 2-5 shows the various connections from the cycle recorder to the FCE-500 for a 502A system. The tabulated numbers represent plug connector terminals on top of the cardfile.
When using the cycle recorder to measure coding time with the FCE-500 system, make certain to observe the following limits:
Received Pulses Minimum Maximum
-Pulse 1 (Indication) 115 ms (7 Cycles) 270 ms (16 Cycles)
Pulse 1 (Control) 280 ms (16.5 Cycles) 535 ms (32 Cycles)
All shorts 50 ms (3 Cycles) 190 ms (11.5 Cycles)
All longs 250 ms ( 15 Cycles) 550 ms (33 Cycles)
Shortest recognized pulse 35 ms (2 Cycles) --Minimum line quiet time re- -- 650 ms (39 Cycles) quired for receive reset
Transmitted Pulses Nominal Value Tolerance
Pulse 1 133 ms (8 Cycles) +0.5, - 0.5 Cycles
Odd Shorts 84 ms (5 Cycles) +0.5, - 0.5 Cycles
Even shorts 108 ms (6.5 Cycles) +0.5, - 0.5 Cycles
Odd longs 350 ms ( 21 Cycles) +o. 5, - 0.5 Cycles
Even longs 417 ms (25 Cycles) +0.5, - 0.5 Cycles
Minimum line quiet time 1033 ms (62 Cycles) +0.5, - 0.5 Cycles required before indic-ation transmission
Minimum line quiet time re- 1369 ms (82 Cycles) +0.5, - 0.5 Cycles quired before indication
" transmission after an indi-cation transmission from this location (SS delay)
6202A, p. 2-21
m UNION SWITCH & SIGNAL
Notes
The received pulses (first table) represent absolute limits. Deviations beyond these limits will cause improper operation of the FCE-500. Proper operation is only possible if the office and field relay equipment meets service specifications. These specifications are listed in the respective service literature for that equipment.
FCE-500 transmit timing is not adjustable. If.the timing of transmitted pulses is consistently outside the tolerance listed in the second table, either the Controller or FRC Interface PCB is defective. Transmit timing must be measured with all units quiet, except the one under test.
r- - -- - - -- -1 +1 -1 I 105
-2 I I
105
I I I I 1P
1R I I --' -I
115 VOLT [ I AC
I 502A I
LCS UNIT I 67
ON
9 OFF
L __ --- -c--_r-1 PAPER ) _
......._; ..
Figure 2-5. Cycle Recorder Layout and Connections for 502A System
6202A, p. 2-22
..
..
UNION SWITCH & SIGNAL
(2.2 SPECIFIC APPLICATION DATA, Continued) 504B and 504C
2.2.2 Type L - Form 504B or 504C, LCS and Storage Units
2.2.2.1 Introduction
The following part numbers describe the FCE-500 systems applied to 504B or 504C based code systems:
Description US&S Part No •
FCE-500, 504B Emulator, with no storage unit N451583-0926 FCE-500, 504B Emulator, with 1 storage unit N451583-0927 FCE-500, 504B Emulator, with 2 storage units N451583-0928 FCE-500, 504B Emulator, with 3 storage units N451583-0929 FCE-500, 504B Emulator, with 4 storage units N451583-0930 FCE-500, 504C Emulator, with no storage unit N451583-0931 FCE-500, 504C Emulator, with 1 storage unit N451583-0932 FCE-500, 504C Emulator, with 2 storage units N451583-0933 FCE-500, 504C Emulator, with 3 storage units N451583-0934 FCE-500, 504C Emulator, with 4 storage units N451583-0935
Figures 2-6 and 2-7 show typical LCS and storage unit applications of the FCE-500 in a 504B and 504C code systems, respectively. Wires marked with a ~ are not required in new FCE-500 installations. Figures 2-8 and 2-9 show the standard 504B and 504C wiring, respectively, between FCE-500 cardfile PCB's, various external terminals and FCE Storage units. The standard cable distances for connecting the cardfile to extension units are as follows:
Cable/Connector Assembly Description US&S Part No.
504B, cardfile to 1st storage unit, length = 5 ft. N451458-5501 506C, cardfile to 2nd storage unit, length = 7 ft. N451458-5502 506C, cardfile to 3rd storage unit, length = 9 ft. N451458-5503 506C, cardfile to 4th storage unit, length = 11 ft. N451458-5504 506C, cardfile to Xth storage unit, length = 17 ft. N451458-5505* 514, cardfile to 1st storage unit, length = 5 ft. N451458-5501 514, cardfile to 2nd storage unit, length = 7 ft. N45l458-5502 514, cardfile to 3rd storage unit, length = 9 ft. N451458-5503 514, cardfile to 4th storage unit, length = 11 ft. N451458-5504 514, cardfile to Xth storage unit, length = 17 ft. N451458-5505*
*Indicates this assembly may be added or replaced where adjacent space is not available
6202A, p. 2-23
UNION SWITCH & SIGNAL
504B and 504C
2.2.2.2 Control/Indication Capabilities
The FCE-500 is capable of handling the maximum control and indication limits of the 504B and 504C systems. Each FCE-500 relay-output PCB outputs seven control steps. The first (slot J2) relay-output PCB serves the same function as the LCS part of the 504B or 504C system. Each additional seven control outputs require another relay-output PCB for the FCE equivalent of a 504B or 504C storage unit. The limit (five relay-output PCB's, .slots J2 - J6) of control outputs available with the 504B and 504C-mode FCE-500's is 35 controls.
Each optical-input PCB accepts seven indications inputs. The first optical input PCB (slot JS) serves the same function as the LCS part of the 504B or 504C code system. Each additional seven indication inputs require another optical input PCB for the FCE equivalent of a 504B or 504C storage unit. The limit (five optical-input PCB's, slots J8 - Jl2) of indication inputs available with the 504B and 504C mode FCE-500's is 35 indications.
2.2.2.3 Unit Mounting (Refer also to Sections 2.1.1.1 and 2.1.1.2)
As indicated below, the FCE-500 cardfile is slightly higher and deeper than the 504B and 504C LCS unit:
504B or 504C Line Coding Storage Unit FCE-500 Card File
23• W X 14-1/2• H X 7-3/8 8 D 19• w x 15-5/a• H x 10-5/a• o
The FCE Storage unit requires more horizontal space, but has a lower profile:
506C or 514 Storage Unit FCE-500 Storage/Extension Unit
11-1/2• W X 14-1/2• H X 7-1/4• D 12-13/16 8 W x 3• H x 6-31/32 8 D
•ff• is the height of unit with external plug connector attached, but without required clearance needed to remove external plug connector. •o• is the depth without clearance for external wires, if required. These differences should be taken into account when preparing to mount the FCE-500 cardfile and any storage units.
2.2.2.~ Plug Connectors (Refer also to section 2.1.5)
If a new location is to use an FCE-500 system, US&S recommends' selection of the plug connectors according to the following tabulation:
Unit Type Pos. ( L to R) Part No. Unit Type Pos. (L to R) Part No.
Card File 1 Nl84690 Storage u. 1 Nl84690 Card File 2 Nl84689 Storage u. 2 Nl84691 Card File 3 Nl01931
6202A, p. 2-24
..
..
..
t I
4- I
UNION SWITCH & SIGNAL m 504B
LI } LIN£ L2 crncun
TYPICAL APPLICATION OF FCE-500 IN 504B MODE
FCE-500 CAROFILE
ARRESTERS
/ GROUND STUD
~ HOUSE PRJl,E GROUND
6 ~ A FUSETROHS / STORAGE UNIT r----I i-~~~~~~~~~~~~~~~~~~ ~
R?P
~ TELEPHONE
I I I
I I I I I
FILTER
L-----
l .FOR CIRCUITS ANO EOUIPIENT BETIIJEEN THE FCE-500 UNIT ANO THE CODE LINE. SEE LINE CIRCUIT Pl.AN FOR EACH INSTALLATION. CONNECTIONS TO CARRIER EOUIPI.ENT, ANO 'SPECIAL CONNECTIONS FOR f!ELO STATION DISCOUNT SCHEME, M-!EN USED, ARE ALSO SHOWN ON LINE CJRCUIT Pl.AN,
816 R
CYCLE TIMER CONNECTIONS
m!l2U
-0- TERMINAL
-a:i-- VARISTOR
__m_ REACTOR
-oL 111.lLTIPLE TERMINAl. CONNECTIONS TO All STORAG£ UNITS
-oL lr,IJLTIPLE TERMINAL CONNECTIONS TO LEADING STORAGE UNIT OF EACH GROUP
:8: POLAR STICK DOUBLE COIL RELAY - 0100£
-4-- OPTO ISOLATOR - RESISTOR
CONOENSER
-0-- ORDINARY RELAY
B DOUBLE COIL RELAY
:0 NEUTRAL VlTAL SLOW RELEASE RELAY
--; T I TRANSFER I CONT ACTS
J. POLAR STICK RELAY CONTACTS
:0 NEUTRAL VITAL RELAY
:so)NIC B CONNECT
~
FRC INTERFACE PCB
UN451441-6801
'CAROFILE
LOCATION JIS
RPP r- ------------, -,---- ~----------------, TYPICAL WAYSIDE CONNECT! ONS
~
16 TOPINZT
N (LP~lLri 2
RP
I • ov _I!
: POaER SUPPLY PCB B
~pp I UN4514<11-3303 I CAROfILE LOCATION JI N
l : NIC~}
; FIELD STATION I : £~N :1s OISCONN£CT SC>ltME l I ---..__ IC~ NIC
I 1. ---.. .....
L--------------------------------~ I I €9----l ' l I RP I
,~l , : £<._ ', I
NIC~NIC
INPUT PCB IND I f I I CONTROLLER PCB
I I UNOB5772-IOOJ
UN451441-43()5' CARDFILE IND 2 CAROFILE LOCATION LOCATION J7 J8 FOR LCS UNIT INC 3
J9 FOR S UNIT I
JlO FOR S UNIT 2 IND•
Jll FORS UNIT 3
~ W AR 86 NIC =! ~ z r-----> ,----!-
PO 816 NIC IT w ,-----
___ ._16 LOP ... ASPR
!!
I R-IN ~ R INPUT
Jl2 FORS UNIT <I IND 5
IN06 =~~~~======~~~~============~==============~~~~~========~~========~~====~~~~~~~~~~~ I
INC 7
WIRED
~ I I
I
~_;___ : - ..-~ I COO£ I !,..-.
.IL-.@-- L"~~'U~i., I NIC ""'
ADO 2 e"/ ---, ; / l TER "/ ®------+ I r--@::--ft- NIC ~ A003 e I I , ' ,,, ®----~ • ' ' ·--·. " ADO 4 e ,£;\_ I I LCS UNIT'S
/. ~ - - - _. .... .... I PLUG BOARO-
AOO , e" 1 ~·~.~:~· .. LOCATION I ~ @r----. + + I PLUG BOARD
FCE-500 - 5048 WITH NO STORAGE UNIT FCE-500 - 5048 WITH I STORAGE UNIT FCE-500 - 5046 WITH 2 STORAGE UNITS FCE-500 - 5048 WITH 3 STORAGE UNITS FCE-500 - 5048 WITH 4 STORAGE UNITS
--@-----4- I : ~---------------..1 r-------------r-----------~-~--~~, NdTES1
NIC - NO INTERNAL COHHECTION
.£_ - EXTERNAL CONNECTION NOT REQUIRED UNl.ESS UNIT TO SE USED AS 1NTERCHANGEABt.E PART WITH TYPE 5048 FJELD RELAY CODE UNIT <EXCEPTION PIN 27 TO RP RELAY +I TERIO
I I I •
@)------.. ~ I I
@-----.. + ...
sw. @
SIG. ;
@ I AR J e •1•-0-
SW. SIG.
@@ @ @
Nl6
Lo-1-8-J ON-22A
®-----.. + +
'------------¥ ¥ f ¥ f ¥ f ¥~'~ff¥¥ f ff f #-------, . "" l :=.=~~i~ @ @
FIG 9. SMD NIC L-------------------L--------~ L. sJ1Rr1t.fJRNDs\'=ttlAlONsT~S _L ____ ~l~~a:ORr~nr.J'~Pr ___.
Figurle 2-6. Typical FCE-500 Application to 504B Field Relay Code System
6202A, p. 2-25/26
''<'
"'
UNION SWITCH & SIGNAL
LI } LINE
L CIRCUIT
TYPICAL APPLICATION OF FCE-500 IN 504C MODE
FCE-500 CAROFILE
ARRESTERS
/
RPP
~ TELEPHONE
t FOR CIRCUITS ANO EOUJPt.E:NT BETWEEN THE FCE-500 UNIT ANO THE CODE LINE, SEE LINE CIRCUIT PLAN FOR EACH INSTALLATION, CONNECTIONS TO CARRIER EOUIPIENT, ANO SPECIAL CONNECTIONS FOR FIELD STATION DISCOUNT SCHEt.E, MiEN USED, ARE ALSO SHOWN ON LINE CIRCUIT PLAN,
FRC INTERFACE PCS
UN451441-6801
'CAROflLE
LOCATION JIS
~ RPP
···~ RPP ~Q_l~.!!L2.! ~Q_~~-.7.!
RP RPP
; FIELD STATION O I SCONNECT SCHEWE.
GROUND STUD ~
ov
POW\£R SUPPL 't PCB
UN45l441-3303 CAROFILE LOCATION JI
HOUSE PRil,E GROUND
B CONNECT ~~~=====1_~_ (/
INPUT PCB IND 1
CONTRot.LER PCB ,
I I UN085712-1001
UN45!44t-4305 CARDflLE '""' CAROFILE LOCATION LOCATION J7 JS FOR LCS UNIT IND 3
J9 FOR S UNIT l
JIO Frut S UNIT 2 !NO • JI I FOA: S UNIT 3
6 ~ A FUSETRONS ,! STORAGE UNIT
..
TYPICAL WAYSIDE CONNECTIONS
NlC 16~.--t---------._ , __ __.!!!.! .:... ~ f PO ... t
FCE-500 - 504C WITH NO STORAGE UNIT FCE-500 - 504C WITH I STORAGE UNIT FCE-500 - 504C WITH 2 STORAGE UNITS FCE-500 - 504C WITH 3 STORAGE UNITS
PART NO. ---- STANDARD CIRCUIT
0451272-1607
S£RVICE MANUAL 6202A
STANDARD WIRING DIAGRAM
0451273-1603
USR
~--------~··•»-------------<
~----------'•23)-------------
NIC -@-----L., : & ; :
""
fil.§.
~
OR
FCE-500 - 504C WI TH -4 STORAGE UN I TS
UN451583-093 I UN45 I 5B3-0932 UN451583-0933 UN-451583-0934 UN45l 583-0935 {
--@---0---1 r---@-- NIC . ;
1.-1..-1• I I
--@-------+I: ~---------------~ r-------------r-------------------. -, NOTES a
NlC - NO INTERNAL CONNECTION
_£, - EXTERNAL CONNECTION NOT REQUIRED UNLESS UNIT TO BE USED AS INTERCHANGEABLE PART WITH TYPE S0-4C F IELO RELAY COOE UNIT !EXCEPTION PIN 27 TO RP RELAY +I TERM)
I I I @------+ + I I
I @-------+ ....
sw. SIG. I @ I
.. J e ···-o-SW. SIG~
8@ ••• I ~ I AR2 I LLJ-+-O-J ON-22A
e •••-...!-.t.I""-~··· ®------+ ......
•----------------~ f ff ff f ¥~'~ff f f f f ff f--------1 . . .. l ::.=~~i~ I I I SETTJNG
00 ,_ ; : ; : : : 6 J 1 I II I ~ r:n E1 lcfl :j :j :j g r,n~
...... v. V- v. v, ~, ~, ~, ~. ~. ~. ~, ·,,,,. ~, 1,,(1. r, 1J: 1. J. r. r. I, r, uJ: ... w,aa,c • /J,=1/:J,J/::::'~:f J~~I;R~~ltllltl;R!l,f lf~l~ STORAGE • 1111111 t~ . I t t t . t t . 1111 UNIT #I ,
r---------------------------------------- ADO ON F<JFl N451583-0928----------------------------------
I I I I I I I I I I I I I I I I
JI O INPUT 80 N085722-I 001
INDICATION COMMON ~ ~ i i i ; i J [----1-~I I lr I ~ r:n" rrcn'"f~ :j E 0 r,nVi, v v v v ~ v v v v v v v v v l f_l f !.f 1 I I I I I !_f_!_)_1
_r ff l°-----+-f F ~ :i§f'I-f :§i:ro1:1:Q1:====P3=:c::
8
::J::v: :~=,~f)f~'~'~Ip~1R~1·!15J1
6
!I7
=~'~i)[)[)[x=~ EXTERNAL 50 :--12 i"°" :;- 6 6 7 49 ;;-- 19 ;--; W ~ ;-T ;-;-- 14 ;-;- ;;- U ;;-, /17 STORAGE • • @ • • • • • • ) • • • (!: • • o • o • • • UNIT #I ,
I ' r-------------. --------------------------- ADO ON FOJ1 N451583-0929 ---------------------------------
1 1 . --------------------~"'"'!. ~~!.'~"-"'------------------------ ----! "' '~"' '" """'"'-'"" l I I I I I i ,s 't''"'""""'.., E"'~ ~ ~ J \\ J
INDICATION COMMON - N ~ v "' "' ~ r-=11 :1 1Jl "' ~ "' "' ~ rn· "' ~ ...... v. v. v. v, U, U. t U, , , . , . [Jk "r, 1,J, U. U. r, U,.t1:. ·.
NOTE, I. THE FOLLOWING REPRESENT THE PC. NOS.
N451583-0926 = FCE 500-5048 WITH NO STORAGE UNIT. N451583-0927 = FCE 500-5048 WITH I STORAGE UNIT. N451583-0928 = FCE 500-5048 WITH 2 STORAGE UNITS, N451 583-0929 = FCE 500-5048 WITH 3 STORAGE UN I TS, N451583-0930 = FCE 500-5048 WITH 4 STORAGE UNITS,
STORAGE • 11 4 1111 t~ ' t • • t • • t • t 11 t UNIT #I
" r---------------------------------------- ADO ON roil N451583-0930 ---------------------------------
'""""'00,:~:"' '"-~"';'~' i i i i JI [""1~ I I I I ~ r-=nJ6 E1Pur=n441~0~ E E ~ rn~1 ~ - - .. ,, v v v v v v v v v v v '"' I l fj r 1 r l I I I I I ! _r-1_11
' r r f r1~01:>1:§i:Q1:1:01:====i#E3=:c::8:~J::v:P.:;:'~i'~iM=,~1~1p~1Ri1j15116~17=~'}}'J[)})}'~ EXTERNAL STORAGE UN[T #l
~ INDICATION J Ll r 111 4 :ou ET.. on 4 4 4 4 4 an~~ • COMMON -: ~ ~ ~ ll? ~ ": I ~\: (11 N = ";..\ :...\ ~\ ~\ ';..\ ~ ~ ~
! ! ! ! ! ! !--~ V V ! ! ! ! ! ! ! 3 -1,c 6 J V {l ,,· 13 M 2. 14 P R !. { { £7 J9 16 18 T W 'x ''N.e '(R,s '(r.u Yv
R
BK
" "'
l2131'4_,l;s:y6r7>1,a 1·8 c.o E,f H zi I2 Iz~i Il F CT ~~ "'1 u °'i i >I "'l "'1 I O >l ~1 :1 :1 Ol O >-! 0. C)L > 0 (0 0 >- 0 CO > 0 0:: Sfi ~ ~ BN ~ ~ ~ ~ ~ ~ BN ~ ~ ~ ~
62 63 IM 65 ,J.?6 67 68 I 2 3 4 5 6 7 ••@•£.!)•• ••••••• '~
9 I 9 l O 20 I I I 2 l 3 l 4 15 23 22 21 ffi • • • • • • • • • • • •
R B-BAT.
BK N-BAT. j
r-------- - ---------- - -- - ---- - ------------ ADD ON FOR 1451583-0932------- - - ------------------------·
v :.,: ... :·~-: v j j I 1 1 1 i J Ll. l I 1rt1ru Iftf ?? i' Pf ru\\ _r r r r----+--0 r r J:ffi1· =1':>1:01y:551:1>:01:====1r=r=r=~J=~V=,~1Jt)}M=,W:'~ip='i({R=~1~~15}16~i7=P:l~~1l!l)[}{X=~
E UERNAL iso I 2 3 4 5 6 7 49 ' 9 I 9 I O 20 ll I 2 I 3 I 4 IS 23 22 ;;--, /77 STORAGE @ • • • • • • • • • • • • • • • • • • • • UNIT #I
r----- - ----------------- ----------------- ADD ON FOR N•s1 sa3-0933- ---------------------------------
J10 INPUT BO N085722-1001 J4 OUTPUT 80 N451441-3601
v :NDl~ATl~N C:MMO~ v i ~ ! ! ~ i. ~ J LI 1 I I I i''rn ~ rn iii' i' i'? ru~ r rt r r r J~ffiiI·Il-1:>J:ol:====!$,==·=~££=~·~i .. :~1M=P:,~{p='<{R=~i~~{
~---------------------------------------------j ______________________________________ _ I ADD ON FOR "{451563-0934
I . ,------------------+1-----------------------------------------------. ------~--------------,·~"·,~~~~~~---------------------------! v : .. ~:-·:·'·:~~: ~ "i"'i'i i ! 1 i l l I I I f lrfl· f[ri'J~ Pr f ru\\
( r ~c r r r ~t"1'(' 1,,2131'(4151· ,6 >17 1#2,3 yC, ,a IJ v 'Q'. "~11311'1,,M (f:( o1R~1• ~15 5516 ,::17 Q'6~11a:1r ;1w:1x
NOTE• l, THE FOLLOWING REPRESENT THE PC, NOS,
N45 I 583-0931 F CE 500-504C WI TH NO STORA GE UN IT, N45 I 583-0932 FCE 500-504C WITH I STORAGE UNIT. N451583-0933 = FCE 500-504C WITH 2 STORAGE UNITS. N451563-0934 = FCE 500-504C WITH 3 STORAGE UNITS, N451583-0935 = FCE 500-504C WITH 4 STORAGE UNITS,
Figre 2-9. Standard FCE-500 PCB External Wiring, 504C Mode
6202A, P• 2-31/32
UNION SWITCH & SIGNAL
5048 and 504C
2.2.2.5 Programming Guidelines
The following items must be considered when planning the programming of the FCE-500 for 5048 or 504C systems:
1. Is Auto Recall desired? When Auto Recall is active, the FCE-500 system will respond with a indication code when a valid control code is received. This will increase system coding time. Therefore, the decision to use Auto Recall must be based on number of trains and the system response time required.
2. Use a station code preference plan based on geographical layout and list the plan on a code and function sheet, or on the wayside plans. The proper address preference based on geographical layout is as follows, with the location closest to the office listed first:
The 504B or 504C LCS address is set with jumpers on the plug connectors on the FCE-500 cardfile. The address is set as follows:
LCS Address Step Post Address Step Connect Post
2 62 First 69 3 63 Second 70 4 64 Third 29 5 65 6 66 7 67 8 68
6202A, p. 2-33
UNION SWITCH & SIGNAL
504B and 504C
Examples:
Address 234 - Connect post 69 to 62, post 70 to 63 and post 29 to 64 Address 456 - Connect post 69 to 64, post 70 to 65 and post 29 to 66 Address 678 - Connect post 69 to 66, post 70 to 67 and post 29 to 68
Note
In 504B/504C address selection, only three unique long steps are acceptable. The ERROR LED on the Controller PCB (LED 4) will light if more than or less than three steps are selected as longs.
B. First Storage Unit Address
The 504B or 504C 1st storage unit address is set with DIP switch SW8 on the Controller PCB (location J7). Figure 2-10 shows the general arrangement and operation of the Controller PCB switches and jumpers for 504B or 504C system emulation. The long steps of the address are set by placing the rockers to the open c•1•) position. The short steps of the address are set by placing the rockers to the closed c•o•) position. ("X" = rocker position not pertinent to any particular function).
The 504B or 504C 2nd storage unit address is set with DIP switch SW7 on the Controller PCB (location J7). The long steps of the address are set by placing the rockers to the open ("l") position. The short steps of the address are set by placing the rockers to the closed ("O") position. Rocker i8 is used for Auto Recall selection; refer to section G on page 2-37.
6202A, p. 2-34
CONTROLLER PCB N451441-4305
COMPONENT SIDE (NOT TO SCALE)
4TH STORAGE UNIT ADDRESS
ALWAYS USE 7 JUMPERS.
z w ~
LOWP.
D SW5
D swsSW4
UNION SWITCH & SIGNAL
5048 and 504C
SWS: SYSTEM MODE
SET TO "1" FOR 5048 OR 504C
SW4: SYSTEM SIZE
'~f • c::::::::i •
5• • 3
0 • LCS ONLY 1 • 1 S. UNIT 2 • 2 S. UNITS
3 •3 S. UNITS 4 =4 S. UNITS
5-8 • NOT USED
D SW6
1 234 5678
,.._,.____--... ~ ~ ~ [i] ~ ~ ~ ~ SW7
HIGH P.
PCB MAY BE EQUIPPED WITH LOW OR HIGH PROFILE (ROCKER) DIP SWITCHES.
-----OPEN
\ J t 3RD STORAGE~NIT ADDRESS NOT
USED
-----OPEN
\ J l y
2ND STORAGE UNIT ADDRESS AUTO
RECALL
1234 5678
E]~eJ~El~El~ -----OPEN-----_____ )
--.......-1 ST STORAGE UNIT ADDRESS i \
NOT USED
SWITCHES SHOWN IN "OPEN " POSITION
Figure 2-10. Controller PCB Manually Selected Options for 5048 and 504C
The 5048 or 504C 3rd storage unit address is set with DIP switch SW6 on the Controller PCB (location J7). The long steps of the address are set by placing the rockers to the open c•1•) position. The short steps of the address are set by placing the rockers to the closed c•o•) position. c•x• = rocker position not pertinent to any particular function):
2 ... x 0 0 0 0 0 0 1 3 x 0 0 0 0 0 1 0 4 x 0 0 0 0 1 0 0 5 x 0 0 0 1 0 0 0 6 x 0 0 1 0 0 0 0 7 x 0 1 0 0 0 0 0 8 x 1 0 0 0 0 0 0
E. Fourth Storage Unit Address
The 504B or 504C 4th storage unit address is set with the Station Address jumpers on the Controller PCB (location J7). When the jumper is set to the •o• side, the address step is short. When the jumper is set to the •1• side, the address step is long. The numbering of the 4th storage un~t addresses at the Controller PCB jumpers is as follows:
6202A, p. 2-36
Jumper Pos.
1 2 4 8
16 32 64
F. 5048 or 504C Mode Selection
4th Storage u. Address Step
2 3 4 5 6 1 8
UNION SWITCH & SIGNAL
5048 and 504C
The 5048 or 504C mode is selected using rotary switch SW5 on the Controller PCB (location J7). Set this switch to the "l" position for either the 5048 or 504C system.
G. Auto Recall Selection
The Auto Recall mode for 5048 or 504C is controlled with rocker #8 of DIP switch SW7 on the Controller PCB (location J7). To activate the Auto Recall mode, set this rocker to the open position. To keep this mode inactive, set rocker #8 to the closed position. Make certain not to readjust any of the other SW7 rockers set for other functions.
H. System Size
The size of the 504B or 504C system is defined using rotary switch SW4 on the Controller PCB. The switch settings are as follows:
SW4 Position System Size SW4 Position System Size
0 LCS Unit Only 4 4 Storage Units 1 1 Storage Unit 5 Not Used 2 2 Storage Units 6 Not Used 3 3 Storage Units 7 Not Used
If SW4 is set at position "l", the address for the first storage unit must be properly set, otherwise the system will lock up. This will be indicated with the lighting of LED 4 on the Controller PCB (location J7). The same is true for the remaining storage unit settings. If switch SW4 is set to positions 5, 6, or 7, the system will again lock up (LED 4 on).
6202A, p. 2-37
UNION SWITCH & SIGNAL
504B and 504C
2.2.2.7 Control Outputs
The following tabulation lists relay-output PCB slot and plug connector terminal numbers that pertain to control outputs for the 504B or 504C:
Control Control Cardfile Output Outputs
Slot Function Emulated Terminals Served
J2 LCS Unit 9 to 15 & 19 to 23 ( 1 to 7) J3 1st Storage Unit 9 to 15 & 19 to 23 ( 8 to 14) J4 2nd Storage Unit 9 to 15 & 19 to 23 (15 to 21) J5 3rd Storage Unit 9 to 15 & 19 to 23 (22 to 28) J6 4th Storage Unit 9 to 15 & 19 to 23 ( 29 to 35)
2.2.2.8 Indication Inputs
The following tabulation lists optical-input PCB slot and plug connector terminal numbers that pertain to indication inputs for 504B or 504C:
Indication Indication Cardfile Input Inputs
Slot Function Emulated Terminals Served
J8 LCS Unit 1 to 7 ( 1 to 7) J9 1st Storage Unit 1 to 7 ( 8 to 14) JlO 2nd Storage Unit 1 to 7 (15 to 21) Jll 3rd Storage Unit 1 to 7 (22 to 28) Jl2 4th Storage Unit 1 to 7 (29 to 35)
2.2.2.9 R Relay and Series Line Resistor
The R relay is the Receive Data interface to the code line for the FCE-500. Refer to Figures 2-6 and 2-7 for typical wiring of the R relay'and associated equipment in 504B and 504C systems. When the FCE-500 is used to replace an existing field relay code system, the R relay and associated equipment can be used without modification. If a new location is to use an FCE-500 system, the R relay and associated equipment are selected as follows:
6202A, p. 2-38
UNION SWITCH & SIGNAL
- 5048 and 504C
US&S recommends the use of the following relays and series line resistor:
Item Description US&S Part No.
Relay P4 Type, 1900 ohm coil N216112
Plug Connector P4 Type Nl09134
Resistor 2-Watt (minimum), wire wound --
Select a resistance value for the series line resistor that limits current flow through the P4 relay coil to 2 to 3 milliamps.
The R relay is shelf mounted. Appendix 8 lists all required mounting hardware.
2.2.2.10 RP and RPP Relay
If a field station disconnect function is required by the application, the FCE-500 system uses the RP and RPP relays in the same manner as the relay code system. When the FCE-500 is used to replace an existing relay code system with field station disconnect, the existing RP and RPP relays, and associated equipment, can be used without modification. If a new location is to use an FCE-500 with field station disconnect, the RP and RPP relays and associated equipment are selected as follows. (Refer to Figures 2-6 and 2-7 for recommended applications of this equipm~nt).
For the 5048 or 504C systems, US&S recommends the use of the following relays in conjunction with a standard capacitor/resistor unit:
Item
Relay (for RP)
Relay (for RP)
Relay (for RPP)
Relay (for RPP)
Capacitor/Resistor Unit
Description
Type L-10, dual 150/400 Ohm Coil
Type L-10, dual 150/400 Ohm Coil, equipped for plug connection
DN-11, Slow Release, 1500 Ohm Coil
DN-22, Slow Release, 1500 Ohm Coil
3000 mFd Capacitor and 30 Ohm Resistor
US&S Part No.
N234555
N234555-001
N262767
N234820
N266187
6202A, p. 2-39
UNION SWITCH & SIGNAL
5048 and 504C
This equipment will give a field station disconnect time of approximately 10 seconds at 70 deg. F., and should be satisfactory for most installations. If a greater disconnect time is required, additional capacitor/resistor units may be added in parallel to reach the desired value.
The RP and RPP relays, and the capacitor/resistor unit can be shelf or rack mounted. Appendix 8 lists all required mounting hardware.
2.2.2.11 Code Line Filter
The code line filter is a de pass/voice and carrier blocking unit that allows voice and carrier signals to be overlayed on the de line used by the code system. When the FCE-500 is used to replace a field relay code system, the code line filter can be used without modification. If the FCE-500 is to be installed at a new location, a code line filter is required. If there is no carrier or voice overlay on the code line, the filter is not required. The code line filter is selected as follows:
Item Description US&S Part No.
Code Line Filter Without de-blocking capacitors or N237446 carrier-blocking reactors
Code Line Filter With de-blocking capacitors, without N235113 carrier-blocking reactors
Code Line Filter With de-blocking capacitors, and with N235112 carrier-blocking reactors
If there is voice overlay on the code line and the voice communication devices have built-in de blocking, use code line filter N237446.
If there is voice overlay only on the code line, and the voice communication devices do not have built-in de blocking, use code line filter N235113.
If there is voice and carrier overlay on the code line, and the voice communication devices do not have built-in de blocking, use code line filter N235112.
Figures 2-11, 2-12 and 2-13 show the various connections from the code line filter to the FCE-500 for a 5048 system. Figures 2-13, 2-14 and 2-15 show the equivalent connections for a 504C system. The tabulated numbers represent plug connector terminals on top of the cardfile.
6202A, p. 2-40
UNION SWITCH & SIGNAL
504B
(J) z 0 j:: 0 r-, w z z I 0 I ~i 0 r----...I -, < a: I z w I a: ~ w
I ~ u: I w w z I I I ::i w I
I 0 I ... 0
L U> 0 --- - 1 alS
I IO
I ......
I I I I
l I a: L __
~ '\. '\. ') ~
') I I I
m ~ I I 1 ~ ;z ~ ...I ..... 1 L ..... ..... alS
w--- r0- -I~ r-- ~ z I I I I g 0 ::i .... ~
) '~ I 0 I ~
o ___
r ~ ~'1 t\l '? I alS
I :5 ~ U>
_J I ......
L------I I
L-------- _ _j
Figure 2-11. Code Line Filter Application for 504B: Without DC Blocking or Carrier Blocking
6202A, p. 2-41
UNION SWITCH & SIGNAL
5048
(J) z 0
@ z z 0 (.)
...I < z a:
~ I I I
L
L __
a: w ~ u:: w z ::::i w 0
8
r· I I u.1 I ~
I I
I
I J. I ~
I l a:
~r------/ ....
iL ~
', ') ( l I I
.... I I I c, <1 ~I L I ~ ~
~.Ac.Ac~.r-r<>-1 -~ )
- ., I I I I
.., I I I
L
L __
,---
r I 1
I I I I L ____ . _____ .J
w z 0
C\I :I: (.) a. - -- -- ------·--o--f 1----6--
- -- - -- - -- --o-f r-0--.... w (.) z
0 :I: a.
Figure 2-12. Code Line Filter Application for 5048: With DC Blocking and Without Carrier Blocking
6202A, p. 2-42
Cl) z 0
~ w z z 0 0 ...I <( z a: w ~ w
w- - - ,. z
o:::i I ~8 I o--..-r
I I I I I I I I I I L
L __
a: w ~ u::: w z :::i w 0
8
r· I I 11.i I ~
I I
I
I I I
~r----
l a:
', ') ') I
~I I I CD ;z .... L_ .... .... I~ ) \~
( ~ ; ') I I
l ______ -
L _______ _
UNION SWITCH & SIGNAL
-1 I I I I
1 I I I
L
I L_
r, I I r I I
_J I I
__ J
5048
Figure 2-13. Code Line Filter Application for 504B: With DC Blocking and With Carrier Blocking
6202A, p. 2-43
83
UNION SWITCH & SIGNAL
504C
CD z Q. ~ 0 w z z 0 0 ...J < z a: w ~ w
I I I
w---z 0 ::i ~w
0 0 o __ _
Ill ...J
,--. I
I il ~r----I I I
T ~- - -- -/ ....
~ LL u. :::!: ~ t\l
l, a: --,§ a: - - - -, r ', l L _____ I __ _J
I I I -:- I I ~I L r<>- -I
)
... (0
all It) .....
0 CX)
Figure 2-14. Code Line Filter Application for 504C: Without DC Blocking or Carrier Blocking
6202A, p. 2-44
en z 0 j::: () w z z 0 ()
..J <( z a: w ... x w
~---r 0::::;
I 1-W 0
8-r--+-I
L
a: w ... ..J u:: w z ::::; w 0 0 ()
ID ..J
j
r· I I I I I I
I I I l '
~i ~r----,,.... - - -- -
/ .... .... LL LL ::!: ::!: v C\I
a: --,~ a: ---, ' ) L _____ I_ ') I
";" I I ~I L ro-- -
I )
~ C\I
:5
I
;
w z 0
~ ~ --- -- --------o--t l----0-
- -- - - - - -- --o--f J---0-.... ()
w z 0 J: a.
UNION SWITCH & SIGNAL
504C
co ell ll) ,....
0 CX)
r ;::!: _ _J
~ ell --- ~
CX) --- ,.... ell
le
Figure 2-15. Code Line Filter Application for 504C: With DC Blocking and Without Carrier Blocking
6202A, P• 2-45
UNION SWITCH & SIGNAL
504C
Cl) z 0 i= (..) w z z 0 (..)
..J <( z a: w !i< w
I I I
w---.,. z
o:::i I 1-8 I 0- ..--r
I I I I I I I I I I L
L __
r-, I
I ~1 u. -~r---- U)
I "° It)
I ,...
I
-- - 0 Cl)
l, a: --,~ a:: -- - 1 r ', ') L _____ I __ _J
I I I -;- I I ~ L_
I )
Figure 2-16. Code Line Filter Application for 504C: With DC Blocking and With Carrier Blocking
6202A, p. 2-46
UNION SWITCH & SIGNAL
504B and 504C
2.2.2.12 Cycle Recorder (Refer also to section 2.1.6.3)
Figure 2-17 shows the various connections from the cycle recorder to the FCE-500 for a 504B or 504C system. The tabulated numbers represent plug connector terminals on top of the cardfile.
When using the cycle recorder to measure coding time with the FCE-500 system, make certain to observe the following limits:
Received Pulses Minimum Maximum
Pulse 1 (Indication) 115 ms (7 Cycles) 270 ms (16 Cycles)
Pulse 1 (Control) 280 ms (16.5 Cycles) 535 ms (32 Cycles)
All shorts 50 ms (3 Cycles) 190 ms (11.5 Cycles)
All longs 250 ms (15 Cycles) 550 ms (33 Cycles)
Shortest recognized pulse 35 ms (2 Cycles) --Minimum line quiet time re- -- 650 ms (39 Cycles) quired for receive reset
Transmitted Pulses Nominal Value Tolerance
Pulse 1 133 ms (8 Cycles) +0.5, - 0.5 Cycles
Odd Shorts 84 ms (5 Cycles) +0.5, - 0.5 Cycles
Even shorts 108 ms (6.5 Cycles) +0.5, - 0.5 Cycles
Odd longs 350 ms ( 21 Cycles) +0.5, - 0.5 Cycles
Even longs 417 ms (25 Cycles) +0.5, - 0.5 Cycles
Minimum line quiet time 1033 ms (62 Cycles) +0.5, - 0.5 Cycles required before indic-ation transmission
Minimum line quiet time re- 1369 ms (82 Cycles) +o.5, - 0.5 Cycles quired before indication transmission after an indi-cation transmission from this location (SS delay)
6202A, p. 2-47
E:l3 UNION SWITCH & SIGNAL
Notes
The received pulses (first table) represent absolute limits. Deviations beyond these limits will cause improper operation of the FCE-500. Proper operation is only possible if the office and field relay equipment meets service specifications. These specifications are listed in the respective service literature for that equipment.
FCE-500 transmit timing is not adjustable. If.the timing of transmitted pulses is consistently outside the tolerance listed in the second table, either the Controller or FRC Interface PCB is defective. Transmit timing must be measured with all units quiet, except the one under test.
115 VOLT [ I AC ----+---i
504B,504C LCS UNIT
I I I
72 ---------1
n--------ON
9 OFF
L------r--rJ PAPER ) L-.---J
Figure 2-17. Cycle Recorder Layout and Connections for 5048 or 504C systems
6202A, p. 2-48
SECTION III FUNCTIONAL DESCRIPTION
3.1 OFFICE/FIELD SYSTEM LOGIC
UNION SWITCH & SIGNAL ffi
Refer to service manuals SM-502A, SM-504B, SM-504C for functional descriptions of the relay code systems emulated by the FCE-500.
3.2 GENERAL CONFIGURATION OF CODE UNIT
The minimum FCE-500 code unit operating set-up in a typical relay code application requires a Controller PCB, a power supply converter PCB, at least one relay-output PCB, one optical-input PCB, and an FRC Interface PCB (serial or parallel). When the FCE-500 replaces a field relay code station with storage units, one additional relay-output and one additional optical-input PCB will be required for each storage.
From one to five relay-output PCB's are inserted in cardfile slots J2 to J6 (see Figure 1-2). A relay-output PCB installed in slot J2 obtains the Line Coding Storage (LCS) unit Control Word address by four internal Program Bit inputs on the corresponding "B" connector. Additional relay-output PCB's are installed in slots J3 through J6. These assume control functions of storage units: each PCB replaces one such unit.
From one to five optical-input PCB's are inserted in cardfile slots J8 through Jl2. An optical-input PCB installed in slot J8 obtains the LCS Indication Word address at that slot by four internal Program Bit inputs. A voltage source provides the indication inputs to these PCB's. Additional opticalinput PCB's are installed in slots J9 through Jl2. These assume indication functions of storage units: each PCB replaces one such unit. When the battery source to an indication input is switched on, the bit is read as a logic •1•. When the source is switched off, the bit is read as a logic •o•.
An FRC Interface PCB is installed in slot Jl5 of the FCE-500 cardfile in all applications. The FRC Parallel Interface board N451441-6801 is only used in the 504B and 504C-eumlating systems. The FRC Serial Interface board N451441-7001 is only used in the 502A-emulating system. When the FCE-500 is converted to a DDL-601BX, this PCB is removed. The slot may then be used for additional indication inputs.
3.3 FIELD STATION BASIC OPERATION
3.3.1 General
Figure 3-1 is a block diagram of a typical FCE-500 system used for 502A emulation. Figure 3-2 is the equivalent diagram for a 504B or 504C system emulation. To meet minimum operating requirements, the basic FCE-500 field location contains the following:
6202A, p. 3-1
UNION SWITCH & SIGNAL
a. Code Line d. Battery Source b. Code Line Lightning Protection e. Battery surge suppressor
The FCE-500 unit c. 8 R8 Relay and Associated Hardware f.
In 5048 and 504C systems, the field station disconnect circuit and code line filter are optional, according to the application.
3.3.2 Control Code From Office (502A, 5048 and 504C)
Under normal conditions, with no data being processed, the code line is inactive and Ll is positive with respect to L2. The Line (•R•) relay is energized and the Received Data signal to the Controller PCB is at a logic 1.
When the office begins transmitting control data, the code line potential goes to zero. The 8 R8 relay will de-energize and the Controller PCB will begin processing data. Received data is decoded and checked for station address and format. If the data has the correct address and format for that station, the Controller PCB reformats the data and delivers it to the appropriate relayoutput PCB(s). The relay output PCB(s) deliver their control bits to the corresponding external relays.
3.3.3 Field-Initiated Indication Code (502A only)
NOTE
Some signal names from the Controller PCB, such as •common Mode• are carried over from a different application of this PCB and are not related to FCE-500 operations. Refer only to signal names on the circuits between the Controller and the FRC Interface.
When the status of an indication input changes at the FCE-500 location, the system will attempt to transmit this new indication back to the office. The FCE-500 is subject to the same restrictions or preference conditions as the prior relay code field station. These include:
a. On simultaneous starts of field stations, the station closest to the office in the code line takes preference.
b. Office transmissions will take priority and lock-out all field transmissions.
c. During a transmission by another field location, a current increase in the code line, or open line, will still cause a lock-out to the FCE-500 station.
In all of the above cases, the Controller PCB memory will retain any indication code that has yet to be transmitted to the office. When the code line goes back to normal or reset, the FCE-500 will again try to initiate a transmission.
6202A, p. 3-2
'-..1 I .... IQ c: I"! Cl)
w I
...... •
'-..1 () tr.I I
Ul 0 0
'-..1 ..... (1) ...... 0,
en rr $lJ rr ..... 0 :::,
tJ:j ...... 0 () ;:,;"
t:, .... $lJ IQ I"! $lJ s I
Ul 0 N > en
°' lo<: N en 0 rr N Cl)
> = ... 'O . w I
w
L2 -TO
OFFICE ..
--L1
SECTIONALIZING RESISTOR --+
rF~ - --- -,:~..,-----' ! PROTECTION
I I I
I I I
I I I I
"R" RELAY
I "R" I B>--, i
I IL __ _
"M" "XMT"
~
FILTER
L__ -11 I B I BATTERY I I _[___ SURGE BATTERY -
SOURCE --N SUPRESSOR
L2
L1
--+ TO OTHER
FIELD STATIONS
---- ------, CONTACT
PROTECTION
OPTO ISOLATOR
"XMT" RELAY
MASTER "M"
RELAY
FRCINTERFACE PCB FOR
502A STYLE
5VOLT BUFFER
I I I I
XMT DATA
COM· MON
MODE
REC I DATA
I -- _ _j
TO PCB's
....-~~~~-............... ~~~~~--( SV +12V ·12V )
POWER SUPPLY
FCE-500 SYSTEM
502A
c 0 N T R 0 L L E R
p c B
TO EXTERNAL CONTROL RELA VS
~
RELAY OUTPUT
PCB
CONTROLS
INDICATIONS
D
J I
l"""'J I~
OPTICAL INPUT PCB
I INPUTS FRO
I ,,,_, '°":"
c z 0 z I ~ :c QI u,
c5 z )> r
EE
Cl'\ N 0 N !l>' '.:! .. .....
'° 'O s= . ,., (I)
w I w
.i:,.. I N . '.:! () l:1j I u, 0 0
'.:! ..... (I) ...... 0.,
tll rt" Ill rt" ..... 0 :,
o:i ...... 0 () ~
0 ..... Ill
'° ,., Ill El
I
u, 0 .i:,..
o:i
0 ,., u, 0 .i:,.. (')
tll "<: Cll rt" (I)
El
L1 CODE {
L: I LINE -~
r
I I
FIELD STATION DISCONNECT SCHEME
LINE AND
CONTACT PROTECTION
"XMT"
I -'- I I I I I I I L2 "M"
I CODE I II I LINE I
FILTER I L __ J I "XMT"
IR--"R" ---, +2
I R+ ._ __ _,+1
I
I : B >---,"R", I ! RIN ... , FILTER
OPTO ISOLATOR t---.i
"CONNECT" RELAY
"XMT" RELAY
MASTER "M"
RELAY
FRCINTERFACE PCB FOR
5048/C
SVOLT BUFFER
B
---, I I REOTO
SEND
I
XMT DATA
I COMMON I MOOE
I I I I I I I REC
DATA
I I
BATIERY
SOURCE
B
N
L ____ ------ -- -------- __ _J
BATIERY SURGE
SUPPRESSOR
11 TO PCB's
,------~-------( SV H2V -12V )
POWER SUPPLY
FCE-500 SYSTEM 5048/C
c 0 N T R 0 L L E R
p c B
TO EXTERNAL CONTROL RELAYS
( ...... ;.; ...... )
RELAY OUTPUT
PCB
CONTROLS
INDICATIONS
OPTICAL INPUT PCB
D
JI
,JIBdJ INPUTS FROM
EXTERNAL SOURCE
EE c z 0 z I ~ :c Ir> en (5 z )> ....
UNION SWITCH & SIGNAL
When the code line is normal and an indication change is acknowledged, the Controller PCB will energize two relays on the FRC Interface PCB, the Master (•M•) and the Transmit c•xMT") relays. An "XMT• relay contact opens and closes the code line, and the "Mn relay opens and closes the code line to all other field stations further along the line. Indication data is then transmitted to the office by applying and removing energy on the code line. The condition of the line is monitored by the "R" relay for completion and verification of the transmitted message.
3.3.4 Field-Initiated Indication Code (5048 and 504C only)
NOTE
Some signal names from the Controller PCB, such as "Common Mode• are carried over from a different application of this PCB and are not related to FCE-500 operations. Refer only to signal names on the circuits between the Controller and the FRC Interface.
When the status of an indication input changes at the FCE-500 location, the system will attempt to transmit this new indication back to the office. The FCE-500 is subject to the same restrictions or preference conditions as the prior relay code field station. These include:
a. On simultaneous starts at one station, station code preference will be in effect.
b. Office transmissions will take priority and lock-out all field transmissions.
c. During a transmission by another field location, the code line pole change will still cause a lock-out to the FCE-500 station.
In all of the above cases, the Controller PCB memory will retain any indication code that has yet to be transmitted to the office. When the code line goes back to normal or reset, the FCE-500 will again try to initiate a transmission.
When the code line is normal and an indication change is acknowledged, the Controller PCB will energize two relays on the FRC Interface PCB, the Master ("M") and the Transmit c•xMT") relays. An "XMT• relay contact shunts the code line and the •M" relay contacts condition the "R" relay for proper polarity after the office pole-changes the code line. Indication data is then transmitted to the office by applying and removing a shunt from the code line. The condition of the line is monitored by the "R" relay for completion and verification of the transmitted message. An additional "M" contact is used for shunting of a resistor in the code line filter, during a transmission. As the code line is being shunted by one "XMT" contact, another contact of this relay will open, removing the source voltage for deenergization of the •R• relay. This keeps the timing constant.
6202A, p. 3-5
UNION SWITCH & SIGNAL
3.3.5 Auto Recall Mode (502A, 504B and 504C)
The FCE-500 incorporates an Auto Recall capability. Auto Recall allows the system to return an indication code independent of an indication bit change, after it has received a valid control code message. The receipt of a control code will recall an indication code. Refer to Section 2.2 for the switch setting of the Auto Recall Mode for the various system applications.
3.3.6 Field Station Disconnect (504B and 504C only)
Certain faults at a field station can cause that station to interfere with other stations that are operating in a normal manner. Equipment can be furnished, when desired, to enable the operator to eliminate the faulty station. The operator presses the STATION DISCONNECT button for a prescribed time, which prevents all field stations from transmitting indication codes. The operator then recalls the stations, one at a time, to determine the faulty one. All other field stations may be reactivated by means of the recall (faulty station kept in the inactive condition).
When an FCE-500 system receives a valid control or recall code, the Contoller PCB initiates a signal that momentarily picks the •coNNEcT• relay on the FRC Interface board. The CONNECT relay contact picks the field disconnect circuitry to its normal condition.
3.4 PCB OPERATIONS AND FUNCTIONS
3.4.1 Controller PCB N451441-4305 (See Figures 3-3 and 6-1)
3.4.1.1 General
The Controller PCB consists basically of the microprocessor, peripherals (PROM, RAM, PTM's, PIA's) and additional support !C's. The 6809 microprocessor is the exclusive controlling chip on the board. Its clock signal is generated by 4.0 Mhz crystal XTAL l; the chip divides this frequency by four. The resulting 1 MHz signal is used to sequence various operations.
The microprocessor and its peripherals communicate over a 16 line address bus (AO to Al5), an eight line data bus (DO to D7) and a five line control bus (IRQ, FIRQ, E, RESET, R/W). Address lines Al2 to Al4 are used to select the RAM, PTM's PIA's or latches for addressing. These lines control a decoder IC which selects one of eight lines (SEL 1 to SEL 8) on the address decoder bus. Line Al5 is used exclusively for PROM addressing. The IRQ (interrupt request) line is used by the PIA's and PTMl to flag the microprocessor when they require serv1c1ng. The FIRQ line {fast interrupt request) is only used for microprocessor servicing of PTM-2. The E {enable) control line is the basic clocked output from the microprocessor and is used to sequence peripheral operations. The RESET line is used to place the microprocessor, PTM's and PIA's in a reset condition. A reset is generated at power-up or when the SYSTEM toggle switch (SWl) is momentarily moved to the RESET position. (If SWl is held in the RESET position, the processor program is inhibited from executing). The microprocessor uses the R/W (read/write) line to inform the peripherals when it is requesting a read (data received from peripherals) or
6202A, p. 3-6
UNION SWITCH & SIGNAL
write (data sent to peripherals) operation. All other unused microprocessor control lines are disabled by pull-up resistors.
PIA 2 interfaces all signals pertaining to the FCE-500 relay-output and optical-input PCB's. Lines PBO through PB7 from the PIA output control bits and input indication bits. A tri-state transceiver (IC12) buffers these lines. The station address bits are also output from PBO to PB6, through the IC16 buffers. When these bits match the bits developed with the station address jumpers, AND gate IC21 sends an interrupt to the PIA.
PIA 1 is used for FRC Interface PCB data. It also accepts five switch inputs (DIP switch SW6) for several program options, and drives LED's that monitor the system status. Code line inputs are made through the 5 volt buffer IC15. Separate drivers are used for the Transmit Data and Request To Send outputs to the FRC interface PCB. The Controller PCB watchdog circuitry consists of a retriggerable one-shot timer (IC22) which is normally retriggered by the microprocessor in repeated, discrete time intervals. If the microprocessor fails to retrigger IC22, the watchdog circuitry will generate a signal that attempts to reset the microprocessor for normal operation. A watchdog LED (LED 7) monitors the output of the watchdog circuit. This LED will flash whenever the watchdog reset occurs.
!C's 9, 10, and 11 are transparent latch !C's that input program options from the rotary (SW4, SW5) and DIP (SW6, SW7, SW8) switches directly to the microprocessor. When selected by the address decode line, these latches output the switch positions in a "O" = switch closed, "l" = switch open format. SW4 and SW5 are octal coded switches that use three switch contacts to generate eight binary bits patterns.
3.4.1.2 Station Address Jumpers
The seven Station Address jumper locations on the Controller PCB are only used in certain applications of the FCE-500 system. Refer to Section 2.2 for this information. The Controller PCB circuits require jumpers at all jumper locations, even if they are not used for a particular programming function.
3.4.1.3 Program Switches
All FCE-500 program switch functions are determined by the PROM software. When the code unit is upgraded to a DDL-601BX, new software is incorporated which may change the functions of some of these switches (i.e. modem communications control). Refer to Section 2.2 for the specific settings of these switches with each application.
3.4.1.4 Toggle Switches
The tabulation at the top of page 3-9 describes the functions of the three toggle switches on the Controller PCB. These switches will be used for modem testing when the FCE-500 is uprgraded to DDL601BX. During routine operation, SW2 is left in the OPERATE position and SW3 is left in the MARK position.
6202A, p. 3-7
°' N 0 N > ..
'"O . w I
(X)
"ii I-'· IQ ~ l"'I <D
w I
w . () 0 :::, rt l"'I 0 ..... ..... <D l"'I
"Cl () 0:,
0:, ..... 0 () ~
t;; I-'• SlJ IQ l"'I SlJ !:3
--
+
I+
XMIT LED (1)
I I f
TTL XMIT
I ...
EIA
DRIVE .. (2)
COMMON MODE RELAY
WATCHDOG
RESET
"'
TOGGLE SWITCHES
• MESSAGE REC.AND FORMAT LED'S (4) lJ m
~ 0 > i!
... I P1A
DATA
CONTROL ...... 2K X 8
..... DATA ADD
ADDRESS i-- RAM
SELECT
.. ' "' j. I+-
I+-- DECODE
XTAL CLOCK
STATION ADDRESS DRIVE
, PIA2
STATION DATA
ADDRESS'-... CONTROL JUMPERS
. .
- ADDRESS
- SELECT
.4KX8 PTM 1
ADD DATA DATA
PROM CONTROL
4 .. ..... ADDRESS
j~ SELECT
MICRO· PTM2 PROCESSOR DATA
CONTROL CONTROL
i,- ADDRESS
DATA ,..... t ADDRESS
. ,..,.. SELECT .
ADDRESS BUS
CONTROL BUS
DATA BUS
CHIP-SELECT BUS
- . --I+
i..t
-
I~
o-
2-WAY rBUFFERS
CONTROL/ INDICATION
I BITS
. DELIVER LED
I
BUFFERS PCB ADDRESS ~
OUTPUT CONTROL.
BOARD PRESENT
(OPTO PCB'S ONLY)
TRAN SP. SWITCHES
LATCH +-- SW4, SW5 SW6
TRAN SP. I+-- SW7 LATCH
TRAN SP. +-- swa LATCH
'
EB c z i5 z I ~ :r: et en c5 z > ...
Switch No .
SWl
SWl
SWl
SW2
SW2
SW3
SW3
UNION SWITCH & SIGNAL m Position Function
RESET (momentary) Microprocessor, PTM's and PIA's simultaneously reset.
RESET (hold) Logic inhibited, SW2 and SW3 active.
NORMAL Logic in routine system operation.
ON Connect relay "Up" (SWl in RESET).
OPERATE Connect Relay "down" (SWl in RESET).
SPACE
MARK
Transmit relay "up"; code line shunted (SWl RESET)
Transmit relay "down"; code line not shunted (SWl in RESET)
3.4.1.5 LED Indications
The functions of the seven LED's on the Controller PCB are listed in the following tabulation:
LED No. Name
1 LINE DETECT
2 RECEIVE DATA
Function
Code line voltage
Reports incoming data
3 ~ESSAGE ACCEPT Station addressed
4 ERROR
5 DELIVER
6 TRANSMIT
7 WATCHDOG
Misc. errors such as configuration set-up error and Controller PCB hardware faults.
Delivery of controls from code unit
Indicates reconnect pulse delivery.
Timing out of watchdog timer.
Behavior·
On steady when code line is not energized.
On steadily when valid data is being received or transmitted.
Flashes on after accepting a complete and correct control message.
Normally off. Flashes when interna' error occurs. Stays on if address has been programmed incorrectly.
On steady during delivery time.
On steadily when reconnect pulse i~ being delivered.
Stays off under normal conditions.
6202A, p. 3-9
UNION SWITCH & SIGNAL
3.4.1.6 FRC Interface Signals
There is one input from the FRC Interface PCB (serial or parallel) to the Controller PCB, and three outputs to the FRC PCB. The external lines between these devices are given names related to FCE-500 operation. The pin-outs on the Controller PCB keep names related to modem/digital code system operations (future FCE-500 upgrade to DDL-601BX). The following tabulation describes this interface:
Controller PCB Line Pin-Out Desiqnation
Request to Send Connect Control (5048 and c only)
Transmit Data Transmit Data
Common Mode Relay M-Relay Control (Front Contact)
Common Mode Relay M-Relay Control (Heel) Feed
Receive Data Rec. Data
3.4.1.7 Card File Bus Signals
Tvoe of Siqnal
EIA output level, short 1.0 second pulse latch.
EIA output level.
0-volt return through contact.
0-volt feed from FRC PCB.
TTL input, logic
Function
Pulse CONNECT relay for field disconnect latch.
Energize/deenergize XMT relay to shunt code line in proper format.
Energize FRC PCB M relay during transmit sequence.
Source Feed
R relay data: Logic 1 = relay pick Logic O = relay drot
The cardfile bus signals are divided into eight control/indication bit lines and eight PCB control lines. These lines are common to all relay-output and optical-input PCB's in the cardfile. The control/indication bit lines will not carry data unless the PCB control lines have been enabled (refer to paragraph 3 of section 3.4.1.1). All lines carry CMOS level signals.
Four PCB addressing lines (Address Bit 2X) are included in the control lines. Their function is to present various 4-bit word addresses to relay-output or optical-input PCB's in the cardfile; these addresses are selected by the office to execute tasks with specific Control and Indication Words. Each PCB has a characteristic cardfile slot address; when the word address matches the slot address, the PCB is enabled.
The Address Bit 20 line is not used for PCB address selection. This line is referred to as the •Byte Pointer•. Each relay-output or optical-input PCB is capable of executing 16 bits for external functions. Since there are only eight control/indication lines on the bus, the bits are presented in consecutive eight-bit bytes. The Byte Pointer is used to select the bits 0-7
6202A, p. 3-10
UNION SWITCH & SIGNAL
byte or the bits 8-15 byte. Data Strobe is an enable function. In conjunction with the Address Bit 20, it is used to steer the proper byte or Control Word into latch circuits on the relay-output PCB. The Deliver line is used to enable the 16 control bit outputs of the relay-output PCB(s) "Deliver Set-Up", and •Req.-Service Int.• are not used in FCE-500 system operation.
3.4.2 Control Delivery PCB N451441-3601 (See Figure 6-2)
The PCB cardfile slot is provided a pre-assigned, programmed word on the bus connector (Program Bit 2x). The IC11/IC12 address decode logic compares this address with the 4-bit binary word address generated by the Controller PCB (Address Bit 2x). If the two addresses agree, LED 1 (ADDRESS) is lit. The Controller PCB then sets up the first eight control bits (0-7) with the byte pointer (Address Bit 20) at a logic •o•. When the Controller toggles the Data Strobe signal, the data (low byte) is loaded into two quad latches, IC2 and IC3. Then, the second byte is set up with the byte pointer line at a logic •1•. A second Data Strobe signal is sent, loading the data (high byte) into the other quad latches, IC7 and IC8. The Controller PCB then strobes a series of deliver pulses, and LED 2 (DELIVER) lights at this time. When this deliver pulse occurs, the information stored in the 16 quad latches is transferred to the 16 mercury-wetted relays. Their contacts now represent the control bit information received from the Controller PCB, and are delivered to the external circuits.
NOTE
The 502A version of the FCE-500 utilizes eight of the 16 relays for its five control bits. The 5048 and 504C versions utilizes 12 of these 16 relays for its control bits.
The time given for total operation of each board is approximately four seconds. Figure 3-4 shows the timing of Controller PCB signals on the bus, to the Control Delivery PCB •
.-------------4 SEC.---------------.i
WORD ADDRESS LOW-BYTE v HIGH-BYTE
DATA STROBE
CONTROL DATA
.. 32 PULSES-----1•~1
DELIVER _____ nnnnn.f f.
NOT TO SCALE
Figure 3-4. Timing Of Relay-Output PCB Operations
6202A, P• 3-11
UNION SWITCH & SIGNAL
3.4.3 Transmitter Opto PCB N085722-1001 (See Figure 6-3)
The PCB cardfile slot is provided a pre-assigned, programmed word on the bus connector (Program Bit 2x). The IC5-IC7 address decode logic compares this address with the 4-bit binary word address generated by the Controller PCB (Address Bit 2X). When the two agree, gates ICl and IC2 are enabled for the first eight inputs (0 - 7) with the byte pointer (Address Bit 20) at a logic •o•. The Board Present line is also enabled, verifying for the Controller PCB that an optical-input PCB is in the addressed slot. LED 1 (WORD •o•) is lit when the first eight bits are selected. This is a rapid event which may not be observable on the LED. When the byte pointer is switched to a logic •1•, the gates for inputs 8 - 15 are enabled and LED 2 is lit (WORD 1). The Address Disable and Output Inhibit circuits are not actively used by the Controller PCB in the FCE-500 system. On the bit O input, diode Dl is used for half-wave rectification of ac type inputs. Diode 034 assures a current limit of 2.2 milliamps over the PCB's input voltage range (5 to 32 volts ac or de).
NOTE
In the FCE-500 system, only the first seven bits are used for indication information on each optical-input PCB. The second byte or word on this PCB is used for the station address of the LCS unit and is only active in cardfile slot JS. All other storage unit addresses are programmed with the switches and jumpers on the Controller PCB.
Figure 3-5 shows the general timing of Controller PCB signals on the bus to the Transmitter-Opto PCB.
WORD ADDRESS LOW-BYTE :v HIGH-BYTE
I I I
BYTE POINTER I I I
I I I
INDICATIONS i 1ST 8 BITS u 2ND 8 BITS
BOARD PRESENT -+t I+< 4µS
Figure 3-5. Timing of Optical-Input PCB Operations
6202A, p. 3-12
UNION SWITCH & SIGNAL
3.4.4 FRC Parallel Interface PCB N451441-6801 (See Figure 6-4)
The FRC Parallel Interface PCB is designed to isolate the Controller PCB logic from noise on the code line during communications. Optical isolator ICl and relays RLY-1 through RLY-4 are used for this purpose. Ll and L2 are the two code line inputs to this board. The acceptable input range on these lines is 12 to 240 volts de. Overvoltage protection is provided by MOV devices Vl and V2. A RC network Cl, C2 and Rl2 are also across the code line to protect the contacts of the relays.
The state of the external "R" relay contact (line or receive data) is read at contacts Al4 and Al5 on the PCB. (Battery positive is applied to this contact). ICl converts the "R" relay status to standard TTL 5 volt logic. Buffer IC2 lights LED 4 (REC) and delivers the received data to the Controller PCB via PCB contact Al9.
The FRC Parallel Interface PCB accepts three functions from the Controller PCB, including Transmit Data (XMT), Common Mode and Request-to-Send (REQ.). XMT Data is an EIA level input signal repeated by relay RLY 1 through transistor driver Q2. One of the RLY-1 relay contacts is used to apply and remove a short between Ll and L2 (code line shunt for transmission of indication message back to the office). The Common Mode input is the return of the common mode feed (de common) through a relay contact on the Controller PCB. When the Controller PCB's Common Mode relay is energized, RLY-2 (Mor Master relay) will also energize. Req.-to-Send is an EIA level signal from the Controller PCB that indicates a valid field station address. This signal is a 1 second pulse and is repeated by RLY 4 ("Connect") through transistor driver Ql. Each function on the -6801 FRC interface PCB has an LED indicator for monitoring.
3.4.5 FRC Serial Interface PCB N451441-7001 (See Figure 6-5)
The FRC Serial Interface PCB is designed to isolate the Controller PCB logic from noise on the code line during communications. Optical isolator IC2 and relays RLY-1 through RLY-3 are used for this purpose. Pins 6 and 7 are the two code line inputs to this board, and pin 4 is the series output. The acceptable input range on these lines is 12 to 240 volts de. Overvoltage protection is provided by MOV devices Vl and V2. A RC network RlO, C5 and R9, C4 are also located across the code line to protect the contacts of the relays.
The state of the •R• relay (line or receive data) is normally energized on the PCB. (Battery positive is applied to the "R" contact). IC2 converts the •R• relay status to standard TTL 5 volt logic. Buffer ICl lights LED 3 (REC) and delivers the received data to the Controller PCB via PCB contact Al9.
The FRC Serial Interface PCB accepts two functions from the Controller PCB, Transmit Data (XMT) and Common Mode. XMT Data is an EIA level input signal repeated by relay RLY 3 through transistor driver Ql. The XMT relay contact is used to open and close the code line for proper field transmission to the office. The Common Mode Input is the return of the Common Mode feed (de
6202A, P• 3-13
UNION SWITCH & SIGNAL
common) through a relay contact on the Controller PCB. When this relay is energized, RLY-2 c•M• or Master relay) also energizes. The •M• relay contacts are used to (a) open the series code line to field stations further out on the line, and (b) increase the code line current from the office for field transmission acknowledgement. Each function on the FRC Serial Interface PCB has an LED indicator for monitoring.
6202A, p. 3-14
..
4 .1 INSPECTION
SECTION IV FIELD MAINTENANCE
UNION SWITCH & SIGNAL ffi
FCE-500 equipment should be periodically inspected in conjunction with inspections of related equipment, in accordance with the customer's preventive maintenance schedule. The inspection should include the following:
1. Check the mounting of the cardfile and storage units. Tighten any loose mounting fasteners.
2. Make certain the cardfile front cover is secure. If loose, lower the cover and check that all PCB's are fully inserted in their slots. Also check that rear card edge connectors are tight.
3. Examine PCB's for loose or missing components, broken component leads, evidence of burning, cracked circuit board material, and broken copper tracks. (Power should be turned off before removing or installing any PCB.)
4. Make certain all plug-connector couplers or plugs are firmly connected to the terminal board and that all nuts are tight.
5. Check for frayed or broken wires on the plug-connector plug or under the plug-connector terminal board.
4. 2 CLEANING
Do not use any kind of solvents, detergents or abrasive cleaners on the cardfile or internal components. Dust accumulated on the outside of the cardfile should be removed with a vacuum cleaner, if possible. Do not use vacuum cleaner inside the cardfile.
4.3 SYSTEM TROUBLE ANALYSIS
Before making any checks on the FCE-500 itself, make certain all associated equipment is working properly and that all local cabling is in good condition. Verify that all voltages necessary for system operation are present such as code line, battery voltage, "R" relay input and associated logic power supply output voltages. Power supply output voltages may be read from test points on the foward edge of the board. Readings should be 1 0.5 Vdc of nominal. Recheck all switches and jumpers on the Controller PCB and plug connector jumpers for proper selection per the application.
With the system powered up, make the following observations on the FRC Interface PCB (serial and parallel):
1. When the code line is not carrying data, the REC led should be lit steadily.
2. The REC LED should flash when the code line is active or communicating.
6202A, P• 4-1
UNION SWITCH & SIGNAL
3. When the field station is powered up, it should transmit the indication inputs to the office when the code line is clear. checked by observing flashing of the XMT, Mand REC LED'~·
current This can be
Spare printed circuit boards and miscellaneous components should be kept on hand. Replacement of all plug-in components or boards should be conducted before considering removal of the FCE-500 unit.
6202A, p. 4-2
5.1 GENERAL
SECTION IV SHOP MAINTENANCE
UNION SWITCH & SIGNAL ffi
The maintenance procedures provided in this section should only be attempted by qualified and properly equipped personnel. A faulty FCE-500 unit or PCB{s) may be returned to US&S for repair. To obtain the proper Returned Material Report (RMR) Form, contact the US&S district sales representative, or:
Union Switch & Signal Division American Standard Inc. 1789 South Braddock Avenue Swissvale, PA 15218 Attn: Customer Service Department
US&S designed test sets are used for troubleshooting of some of the FCE-500 printed circuit boards. These are as follows:
NAME
TS-205
TS-203
TS-204
APPLICABLE PCB's
Control Delivery N451441-3601
Power Supply Converter N451441-3303 Transmitter-Opto N085722-1001
Controller N451441-4305
The FRC Interface PCB (serial or parallel) requires general-purpose test equipment.
The TS-200 series test sets are only used to localize a PCB problem in a functional sense; the maintainer must continue with standard component-performance and circuit continuity tests to pinpoint the source of the problem. The design and general operating characteristics of the test sets are discussed in SM-6171. No attempt should be made to troubleshoot any FCE-500 PCB without these test sets. Except for the PROM !C's on the Controller PCB, all PCB components may be replaced from sources other than US&S, provided component values, tolerances, etc. are noted carefully (see Appendix A).
5.2 SYSTEMATIC PCB TROUBLESHOOTING
5.2.1 Controller PCB (N451441-4305)
5.2.1.1 Test Procedure Comments
The TS-204 is used to store a 16K (2K x 8) bit test PROM IC which is substituted for the service PROM on the Controller PCB. The test PROM contains diagnostic software which runs the boa~d through a limited hardware examination. Three toggle switches on the set are used to select specific areas of the board for diagnostics. The TS-204 also contains a digital LED
6202A, P• 5-1
UNION SWITCH & SIGNAL
display which provides various codes representing the results of individual diagnostics routines. Nominal test codes are given with each procedure step. When the actual code does not agree with the nominal code, an error code interpretation table (Table 4-1) may be consulted to determine the general nature and location of the problem. The table gives the numbers of Controller PCB IC's pertaining to each tested area, however these IC's are only listed as a guide to follow-up troubleshooting.
The Controller PCB test procedure is divided into four parts. In the first part (steps 1 and 2) the board power circuits are given _continuity and voltage checks. The second part (step 3) consists of EIA and TTL communications interface voltage checks. The third part (step 4) is a general performance check of the microprocessor and peripherals, conducted by the Test PROM software. This is the first part of the test procedure to use the TS-204 digital display. The fourth part (steps 5 through 19) consists of tests of the program switches and jumpers.
The first three parts of the Controller PCB test procedure should be run in the indicated order to verify the basic operating condition of the board. The part-four tests do not have to be run in order and may also be repeated on a selectively as required. There is a remote possibility the service PROM is the source of the fault, in which case the TS-204 would show nominal test results. A spare service PROM may be used to verify the condition of the original.
5.2.1.2. Required Test Equipment
TS-204 Test Set
Digital or Analog Electronic Voltmeter (Qty.= 1)
5.2.1.3 Test Set-Up
Description
N451400-3202, includes test PROM N451575-0701
a. Remove the Controller PCB from the cardfile (power supply converter PCB power OFF).
b. Remove the service PROM (IC26) from the board; avoid placing the PROM under bright lights.
c. Take the test PROM from the TS-204 holder and install in the IC26 socket.
d. Record the programmed positions of the various switches and jumpers so that they can be reset to the original positions after testing. Figure 5-1 provides a chart for recording these positions.
6202A, p. 5-2
UNION SWITCH & SIGNAL ffi e. Set the switches on the Controller PCB as follows:
SWl SW2 SW3 SW4
RESET ON SPACE Position "O"
SW5 SW6 SW7 SW8
Position "O" All closed (•0 11 side) All closed (•0 11 side) All Closed ("O" side)
STATION ADDRESS JUMPERS All to ·o· side
f. Plug the TS-204 into standard 120 Vac source, with the POWER switch OFF.
g. Insert the Controller PCB into the test set edge connectors with the component side facing the test set control panel.
CAUTION
DO NOT INSTALL OR REMOVE THE CONTROLLER PCB FROM THE TS-204 WITH TEST SET POWER ON, OTHERWISE COMPONENT DAMAGE MAY RESULT.
5.2.1.4 Procedure
Operation Verification
1. Measure the resistance between 1. v.o.M. should show the the following pairs of test points:
Common Lead +v Lead
TP2 TPl greater than 15 ohms TP3 TPl greater than lK ohms TPl TP4 greater than lK ohms TP3 TP4 greater than SK ohms
2. Turn on TS-204 power and measure 2. Meter should show the voltages on the following test voltages: points, as referenced to TP2 (OV)
CHECK BOX 00 TO RECORD POSITION OF JUMPER · OR SWITCH
0 0 0 0 0 0 0
0000000-0 0 0 0 0 0 0
0000000~ 0 0 0 0 0 0 0
JUMPERS
SW6 SW7
co00 co OD "-00 .... oo
'°OD '°DO inOO ffi inOO z w
Q.
•OD o Q.
•DO o
Moo Moo NOD NOD -DD -DO
CHECK BOX 00 TO RECORD POSITION OF JUMPER OR SWITCH
0 0 0 0 0 0 0
0000000-0 0 0 0 0 0 0
0000000~ 0 0 0 0 0 0 0
SW6
r.o00 .... oo
1'°00 linOO ffi! 1•00 g;I
!Moo 1\
INog II
JUMPERS
SW7
co OD .... oo '°OD inOO ffi
a. •OD 01
l·Moo NOD
1-oo '
0 :1 0
~
1
D•=•D SW5 5 3
0 • 0 0
0 ~ 0
~
1
0 • = • 0 SW4 5 3
0 • 0 0
swa
co OD .... OD '°DO inOO ffi
Q.
•OD o Moo NOD -DO
0 ~ 0
~
1
D•=•D SW5 5 3
0 • 0 0
0 ~ 0
~
1
D• = •D SW4 5 3
0 • 0 0
swa
\r.ooo .... DO <DOD I
linDO ~. 1·00 0
1MOO I jNDD 1-00
CHECK BOX 00 TO RECORD POSITION OF JUMPER OR SWITCH
0 0 0 0 0 0 0
0000000-0 0 0 0 0 0 0
'.JOO ODDO 9 0 0 0 0 0 0 0
SW6
co OD .... DO '°OD inOO ffi
Q. ..,DO o
Moo NOD -oo
JUMPERS
SW7
r.oOO .... oo '°OD inOO ffi
a. ..,DO o
..,oo NOD -oo
CHECK BOX 00 TO RECORD POSITION OF JUMPER OR SWITCH
0 0 0 0 0 0 0
0000000-0 0 0 0 0 0 0
000000[]9 0 0 0 0 0 0 0
JUMPERS
SW6 SW7
r.o00 '11 .... oo <DOD ,I
I
inoo ~I •DO 0 ! t~o: II
Ir.coo 1 .... 00 i '°DO I in OD ffi I Cl. i"'DO ol I I
;MOO I !Noo I
1-00 I
O SJ O
~
1
D• = •D SW5 5 3
0 • 0 0
0 ~ 0
~
1
D• =~D SW4 5 3
0 • 0 0
swa
r.oCO .... LO <000 1()00 z
~ •DO O
Moo NOD -oo
O SJ O
~
1
D•=•D SW5 5 3
0 • 0 0 0
0 • 0
~
1
D• = •D SW4 5 3
0 • 0 0
SW8
r.o00 .... DO '°OD in00 ffi
a. •DO o
Moo I
/NOD !
Figure 5-1. Controller PCB Switch/Jumper Programming Record
6202A, p. 5-4
Operation
3. Position toggle switches SWl, SW2 and SW3 as follows and read voltages on PCB edge "A" pins 6, 7, 8 and 9:
SWl
RESET RESET RESET
SW2
ON ON OPERATE
SW3
SPACE MARK MARK
3.
4. Move toggle switch SWl on the 4. Controller PCB to the NORMAL position and observe the TS-204 digital display and board LED's.
5. Move Controller PCB toggle switch 5. SWl to the RESET position.
6. Set TS-204 switches S2 and Sl to 6. •o• and so to •o•, then move PCB toggle SWl to NORMAL.
UNION SWITCH & SIGNAL m Verification
Meter should show the following voltages(+/- 0.5 Vdc) on the pins:
Pin No.: 6 7 8 9
+5 +5
0
+5 0 0
+6* +6* -6* -6* -6* -6*
*5 to 7 Vdc, + 1 Vdc
All seven PCB LED's should flash in a regular, sequential pattern and the TS-204 should run through and repeat the following sequence:
1. 999 (initial display) shows shows for approx. one sec.
2. Various numbers flash quickly 3. 601 (successful test) shows
shows for approx. one sec. 4. 127 (reset) shows for approx.
one second.
If the digital display stops on an error code number, or does not display any numbers, refer to Table 5-1 (p. 5-8) for error code definitions.
6202A, p. 5-5
ffi UNION SWITCH & SIGNAL
Operation
7. Position SW6 rockers to the following positions and observe the test set digital display (1 = open, 0 = closed):
1
0 1 1 1 1 1 1 1
2
0 0 1 1 1 1 1 1
3
0 0 0 1 1 1 1 1
SW6 Rockers
4
0 0 0 0 1 1 1 1
5
0 0 0 0 0 1 1 1
6
0 0 0 0 0 0 1 1
7
0 0 0 0 0 0 0 1
8
0 0 0 0 0 0 0 0
8. Move PCB toggle SWl to RESET.
9. Set TS-204 switch so to •1•, switches Sl and S2 to •o•, then PCB toggle SWl to NORMAL.
7.
8.
9.
Verification
TS-204 should display the following codes; if an error code is displayed, refer to Table 5-1 for error code definitions. (Each readout is a binary sum, with rocker 1 the LSB.)
Nominal Readout:
000 001 003 007 015 031 063 127
10. Set SW7 rockers to same positions as step 7, then with all rockers to the •1• position. Observe the test set digital display.
10. TS-204 should display the same codes as shown in step 7, plus "255" for the all-"l's" setting. If an error code is displayed, refer to Table 5-1 for error code definitions.
11. Move PCB toggle SWl to RESET. 11.
12. Set TS-204 switches SO and S2 to 12. "O" and Sl to •1•, then move PCB PCB toggle SWl to NORMAL.
13. Set SW8 rockers to the same posi- 13. tions as step 7, then with all rockers to the "l" position. Observe the test set digital display.
14. Move PCB toggle SWl to RESET. 14.
15. Set TS-204 switches so and Sl to 15. "l" and S2 to "O", then move PCB toggle SWl to NORMAL.
6202A, p. 5-6
TS-204 should display the same codes as shown in step 7, plus "255" for the all-"l's" setting. If an error code is displayed, refer to Table 5-1 for error code definitions
UNION SWITCH & SIGNAL m Operation Verification
16. Set Controller PCB switches 16. TS-204 should display the follow-SW4 and SW5 as follows: ing codes. If error code is dis-
played, refer to Table 5-1 for error code definition. (Each readout contains the respective
17. Move PCB toggle SW! to RESET. 17. --18. Set TS-204 switches so and Sl to 18. --
"O" and S2 to 11 1•, then move PCB toggle SW! to NORMAL.
19. Position the Station Address 19. TS-204 should display the follow-jumpers as follows and observe ing codes. If error code is dis-TS-204 display (0 = jumper played, refer to Table 5-1 for jumper to 11 0 11 side, 1 = jumper error code definition. (943 is an to 11 1 11 side). is an error code. The other read-
outs correspond to the generated Jumpers station addresses.)
PTM-1, timer il accuracy error PTM-1, timer i2 accuracy error PTM-1, timer i3 accuracy error PTM-2, timer il accuracy error PTM-2, timer i2 accuracy error PTM-2, timer i3 accuracy error RAM error Watchdog circuit does not reset microprocessor EIA carrier detect line stuck low EIA CTS line stuck low EIA AVI data line stuck low EIA receive data line stuck low EIA carrier detect line stuck high EIA CTS line stuck high EIA AVI data line stuck high EIA receive data line stuck high EIA RTS line stuck low EIA RTS to send line stuck high EIA transmit data line stuck low EIA transmit data line stuck high Common mode relay drive error Control/indication bit linesl Deliver, deliver set-up error 2
Interrupt error Carrier detect interrupt error AVI data interrupt error Receive data interrupt error Request service interrupt error PTM-1, timer il interrupt error PTM-1, timer i2 interrupt error PTM-1, timer i3 interrupt error PTM-2, timer il interrupt error PTM-2, timer i2 interrupt error PTM-2, timer i3 interrupt error Microprocessor internal fault TTL carrier detect line stuck high TTL carrier detect line stuck low TTL AVI or RTS line stuck low TTL AVI or RTS line stuck high TTL receive data line stuck high TTL receive data line stuck low TTL CTS or transmit data line stuck high TTL CTS or transmit data line stuck low
2 If the DELIVER LED is not cycling, the error is in the Deliver function. Otherwise, the error is in the Deliver Set-Up function.
6202A, p. 5-8
UNION SWITCH & SIGNAL
Table 5-1. TS-204 Test Set Error Codes (Cont'd)
CODE DEFINITION FAULTY IC'S?
909. Board present data bit stuck high3 IC2, 17 910. Board present data bit stuck low3 IC2, 17 942 Sta. addr. decode reads more than one address IC16, 21 943 Sta. addr. decode reads no address IC16, 21 . Data Strobe Error3 IC13 X66 Word Addressl
Buffer or PIA fault (PCB LED's cycle twice)4 Microprocessor, RAM or test PROM fault4 I Cl, 6, 26
1 Any digit may appear in "X" 4 No display 3 Decimal point flashes
5.2.2 Control Delivery PCB (N451441-3601)
5.2.2.1 Test Procedure Comments
The test procedure for the Control Delivery PCB requires the TS-205 Test Set. This set is designed to simulate all Controller PCB inputs, including card file addressing and loading/strobing of data bits. The set also monitors and display the relay contact outputs, using LED's.
The objective of the test procedure is to run the PCB through a wide range of addressing, data bit and byte-control configurations and verify that relay outputs correspond correctly to data inputs. The test procedure is presented in the form of an illustrated truth table (Figure 5-2). The table lists test set switch positions and LED responses from both the test set and the PCB. Test set LED's are depicted in their panel arrangement. When test set outputs do not correspond to inputs, as shown in figure, the associated input and output lines/components are isolated for follow-up testing.
5.2.2.2 Required Test Equipment
This test procedure requires the TS-205 test set (N451441-3101).
5.2.2.3 Test Set-Up
1. Remove PCB from cardfile (power supply converter PCB power OFF).
2. Plug test set into standard 120 Vac source, POWER switch OFF.
3. Insert PCB in the slot that includes part number suffix "3601". The PCB is inserted with the component side facing the test set controls.
6202A, P• 5-9
ffi UNION SWITCH & SIGNAL
CAUTION
DO NOT INSTALL OR REMOVE THE CONTROL DELIVERY PCB FROM THE TS-205 WITH TEST SET POWER ON, OTHERWISE COMPONENT DAMAGE MAY RESULT.
4. Turn test set power on.
5. Operate LAMP TEST button to verify test set LED's.
6. Move the BOARD SELECT switch to the position corresponding to the part number suffix for the board.
5.2.2.4 Procedure (See Figure 5-2)
a. Board Addressing
Position the ADDRESS BIT and PROGRAM BIT switches for board addressing tests, according to the ADDRESS BIT AND PROGRAM BIT columns in Figure 5-2. The ADDRESS BIT switches simulate word address inputs from the Controller while the PROGRAM BIT switches simulate the program address obtained from the cardfile slot. In those steps where the switches are properly matched, the ADDRESS LED on the board should light. These switches are only reset after each even numbered step because two steps (1 & 2, 3 & 4, etc.) are required to load data bits. When an addressing test is successful, the ADDRESS LED should remain on for the rest of the step until the ADDRESS BIT and PROGRAM BIT switches are reset.
b. Input Bits Set-Up
Position the eight INPUT BITS switches on the test set according to the INPUT BITS column. Input bit loading is accomplished in two steps. In the odd numbered steps, load the first eight bits of data by setting the ADDRESS BIT 2° switch (equivalent to the Controller PCB byte pointer) to "O" and momentarily pressing the DATA STROBE pushbutton (indicated with arrow on the chart). In the even numbered steps, load the second byte of data by setting ADDRESS BIT 2° to "l" and pressing DATA STROBE again.
c. Relay Actuation
Move the DELIVER switch (DEL in Figure 5-2) to the "l" position to output all 16 bits in parallel. This happens in every even-numbered step since only eight bits of data are loaded in the odd numbered steps. The DELIVER LED on the PCB should stay on until the DELIVER switch on the test set is returned to "O".
6202A, p. 5-10
NOTE
Due to PCB inhibit circuitry and switch bounce from the test set, this step may have to be repeated several times to initiate relay sequencing.
UNION SWITCH & SIGNAL m RELAYS LEO'S
ADDRESS PROGRAM AOOR. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 IS 16 BIT BIT AODR. INPUT BITS BIT DATA HO DEL
STEP 2' 2' 2' 2' 2' 2' 2' 2' LED 0 1 2 3 4 5 8 7 2• STRB. DEL. NC LEO DEL
-----CONTINUE BINARY COMBINATIONS OF ADDRESS BIT ANO PRO· GRAM BIT SWITCHES UNTIL COMPLETING ADDRESS 15 (STEPS 39/40). ADDRESS 1 STARTED ON STEP 11/12. REPEAT INPUT BITS FOR STEPS 17/18 ANO 19/20.
Figure 5-2. Control Delivery PCB Troubleshooting Program (Cont'd).
6202A, p. 5-12
UNION SWITCH & SIGNAL m d. Relay Output Indications
When the board is initially addressed, all 16 N.C. RELAYS LED'S should light. PCB relays are automatically energized in the normally-closed position. When the DELIVER switch is operated, the RELAYS LED's should change to a pattern which matches the INPUT BITS switches. RELAYS LED's 1 - 7 should match the positions of the INPUT BITS switches sent on the first DATA STROBE, while LED's 8 - 16 should match the bits sent on the second DATA STROBE. An INPUT BITS switch set at •1• should light the corresponding N.O. RELAYS LED. An INPUT BITS switch set at •o• should light the corresponding N.c. RELAYS LED. Only one LED of each pair should light at any time.
e. Close Out
After each even-numbered step (one complete relay loading and delivery), move the DELIVER switch back to •o•. All N.O. RELAYS LED'S should go dark.
5.2.3 Transmitter-Opto PCB (N085722-1001)
5.2.3.1 Test Procedure Comments
The Transmitter-Opto (N085722-1001) PCB is tested in the TS-203 test set. The TS-203 is designed to simulate all Controller PCB inputs to the PCB, including cardfile addressing and loading/reading of data bits. The set also simulates the low current indication contact inputs from wayside circuits, and operates the Address Disable and Output Inhibit circuits. Although Address Disable and Output Inhibit are not used by the Controller PCB, they do not pertain to the internal operation and testing of the board. The CONNECTOR SELECT knob, METER TEST pushbutton and digital display are not used in these tests.
The test procedure is to runs the PCB through a variety of addressing, byte-control and indication bit configurations, and verifies that bits received by the board correspond with those output to the Controller PCB. The procedure is presented in an illustrated truth table (Figure 5-3). The table lists test set switch positions and LED responses from both the test set and the PCB. When test set outputs do not correspond to inputs, as shown in the diagram, the associated input and output lines/components may be faulty.
5.2.3.2 Required Test Equipment
This test procedure requires the TS-203 test set N451400-2201 •.
5.2.3.3 Test Set-Up
a. Remove PCB from cardfile (power supply converter PCB power OFF).
b. Plug TS-203 into standard 120 Vac source with POWER switch OFF.
c. Set all LOW BYTE and HIGH BYTE switches in the •o• position and the OUTPUT INHIBIT and ADDRESS ENABLE switches in the •o• position.
6202A, p. 5-13
UNION SWITCH & SIGNAL
d. Insert PCB into test set edge connector marked "3201" with component side facing control panel.
CAUTION
DO NOT INSTALL OR REMOVE THE INDICATION-OPTO OR TRANSMITTER-OPTO PCB FROM THE TS-203 WITH TEST SET POWER ON, OTHERWISE COMPONENT DAMAGE MAY RESULT.
e. Turn TS-203 power ON.
f. Operate LAMP TEST button to verify the OUTPUTS LED's.
g. Throw each of the LOW BYTE and HIGH BYTE switches to verify adjacent LED's. Do the same for the OUTPUT INHIBIT and ADDRESS ENABLE LED's.
5.2.3.4 Procedure (See Figure 5-3)
a. Input Bits Set Up
Position the eight LOW BYTE and eight HIGH BYTE switches as indicated in the first two columns of Figure 5-3. These correspond to the 16 indication inputs provided by external circuit contacts. When a BYTE switch is set to the "l" position, the adjacent LED should come on, otherwise the LED should be off.
b. Board Addressing
Position the ADDRESS BIT and PROGRAM BIT switches for board addressing tests, according to the ADDRESS BIT AND PROGRAM BIT columns. The ADDRESS BIT switches simulate word address inputs from the Controller, while the PROGRAM BIT switches simulate the program address obtained from the cardfile slot. Also, move the ADDRESS ENABLE switch (ADD ENA in the figure) to the "l" position. When the BOARD PRESENT LED lights (BRO PRS on chart), the address test is successful.
c. Input Bits Loading
Move the ADDRESS BIT 20 switch (byte pointer) to LOW. This places indication bits O - 7 on the output data lines. The WORD O LED should light at this time. Next, move the ADDRESS BIT 20 switch (byte pointer) to HIGH. This places indication bits 8 - 15 on the output data lines. On the Transmitter-Opto PCB, the WORD 1 LED should light at this time. OUTPUT INHIBIT is kept off at this point to allow delivery'of both bytes.
d. Output Bits Indications
When ADDRESS BIT 20 is set to LOW, the seven OUTPUTS LED's on the test set should match the positions of the LOW BYTE switches. When ADDRESS BIT 20 is set to high, the OUTPUTS LED's should match the positions of the HIGH BYTE switches. In both cases, a BYTE switch set to "l" should cause the corresponding OUTPUTS LED to light. A BYTE switch set to "O" should leave the corresponding OUTPUTS LED off.
6202A, p. 5-14
STEP LOW BYTE HIGH BYTE
0 1 2 3 c 5 & 7 I I 10 11 12 13 14 15
1 •••••••• --------0 0 0 0 0 0 0 0 ..., ....
I.Q 2 SAME AS STEP 1 --------
s:: .., (I) 3 SAME AS STEP 1 ------ - -U1 I w • 4 SAME AS STEP 1 ------ - -. 8 .., QI
RUN ALL OTHER BINARY COMBINATIONS OF ADDRESS ANO PRO· GRAM SWITCHES (15 TOTAL). ANY INPUT BIT CONFIGURATION ACCEPTABLE.
OUT INH
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
• 0
OUTPUTS
0 1 2 3 C 5 6 1
•••••••• SAME AS STEP 1
SAME AS STEP 1
.SAME AS STEP 1
oeoeoeo•
eoeoeoeo
SAME AS STEP 5
SAME AS STEP 6
•••••••• SAME AS STEP 9
-
v c z 0 z I ~ ::c 11!1 UI c5 z ), r
m
UNION SWITCH & SIGNAL
5.2.4 Power Supply Converter PCB N451441-3303 (TS-203 Test)
5.2.4.1 Test Procedure Comments
The TS-203 checks all +5, +/- 12 Vdc outputs points on the Power Supply Converter PCB. This includes 16 contacts on the •B• connector edge (logic level voltage to other cardfile PCB's): 9, 10, 16, 17, 19, 20, 21 and 22. On the •A• connector edge, eight contacts are checked: 1, 6, T, 18, v, 20, x, 22 and z. A four digit (7 segment type) display indicates voltages at these points. When the CONNECTOR SELECT knob is moved between the three left-hand voltage positions, outputs are displayed from the •A• connector edge contacts. The right-hand positions provide outputs from the •B• contacts. The TS-203 is equipped with resistors which simulate the load from other FCE-500 PCB's. The ADDRESS DISABLE, OUTPUT INHIBIT, ADDRESS, PROGRAM etc. switches do not participate in these test procedures and may be left in any position.
' 5. Move CONNECTOR SELECT knob to • -12• position.
6. Move CONNECTOR SELECT knob to •B• side, •+12•, •+5• and •-12• positions.
7. Adjust oscilloscope controls as follows:
1.
2.
Verification
LED's 1, 2 and 3 should light with equal brightness. If none light, check fuse and replace (SW! OFF) if necessary. If only one or two LED's light, continue with Steps 3 through 6 to check individual converter modules.
3. Meter should show •-12•, + 0.38.
4. Meter should show •+5•, + 0.17.
5. Meter should show •-12• + 0.38.
6. Same results should be obtained as steps 3, 4 and 5.
7. --
- Vertical attenuation: 20 millivolts/Div. - Coupling: ac or ac - Horizontal time base: 10 millisec./Div. - Trigger level: Auto - Trigger: CH! - Scope: + - Probe: !OX (use short ground clip on
scope probe).
6202A, p. 5-17
m UNION SWITCH & SIGNAL
Operation
8. Connect oscilloscope Common to TP2.
9. Connect oscilloscope probe to TPl.
10. Move probe to TP3, then TP4.
11. Turn PCB SWl switch off.
8.
9.
Verification
Ripple in oscilloscope waveform should not exceed 600 millivolts.
10. Same ripple maximum should be obtained as in Step 9.
11. --
12. Adjust de power supply to 16 Vdc. 12.
13. Turn PCB SWl back on.
14. Repeat steps 3 through 6.
13. --
14. Same results as shown in steps 3 through 6 should be obtained.
5.2.5 FRC Parallel Interface PCB N451441-6801
5.2.5.1 Test Procedure Comments
The FRC Parallel Interface PCB test procedure (section 5.2.5.4) is divided into two parts. In steps 1 through 25, continuity is checked on relay circuits, using a variety of operating states. Toggle switches are used to simulate some Controller PCB inputs during these tests. In steps 26 through 28, the "R• relay output (to the Controller) is checked, using an oscilloscope. A function generator is used to simulate the •R• relay input.
5.2.5.2 Required Test Equipment
Item
Oscillosope (Suggested Model: Textronix 465)
DC Power sut~l~ (Qty= 2, Suggested Model: HP o B):
6202A, p. 5-18
Specifications
- Frequency range: de to 30 MHz - Time base: .02 msec./div. to
12 sec./div. - Time base accuracy: 1% - Dual channel inputs with chopped or
alternate operation - ac or de coupling - External sweep mode - Accuracy: +3% - Veritcal amp. sensitivity: .05 V/div.
- 0 to 20 Vdc@ 0 to 1.5 amps.
UNION SWITCH & SIGNAL
Item Specifications
Function Generator (Suggested Model: - Frequency range: 10 Hz to 10 KHz Wavetek 112): - Output amplitude: 10 volts peak to
peak - Frequency accuracy: 2% - Output impedance: 50 ohms
v.o.M. (Suggested Model: Simpson 260) - Ohmmeter accuracy: ±. 5% reading at center scale
b. Stand PCB vertically (mercury relay contact arrow up).
c. Connect test equipment according to Figure 5-4, but leave card edge connector disconnected from PCB.
d. Turn on both power supplies. Adjust #1 power supply to 5 Vdc + 1% and power supply #2 to 12 Vdc + 1%. Turn both supplies off.
e. Turn on function generator and adjust to produce a square wave output, 24 volts peak to peak.
f. Turn off function generator and attach card edge connector to the FRC Interface PCB. Do not turn on any test equipment until instructed in the test procedure.
5.2.5.4 Test Procedure
Operation Verification
1. Set switches Sl, S2 and S3 to the 1. All LED's on the board should be off position. dark.
2. Use V.O.M to measure the res is- 2. v.o.M. should show a short circuit tance between the following pairs between each pair of pins. of PCB pins:
2A and 3A 4A and 6A 5A and 7A 9A and lOA 12A and 13A
6202A, p. 5-19
UNION SWITCH & SIGNAL
FUNCTION H i---------------------------<,14A GENERATOR
60Hz 24V P/P
SR.WAVE L~----------------------<~15A
i----:.i. PROBE OSCILLOSOPE
OFF S1 ON~SA c ¢,A
OFF S2 ON~1A ,-0 OFF
~3- ~-ON...,,.~OA ~
POWER (+)t----i~-------------__. SUPPLY
#1 5VDC (-)-
POWER (+)t---1.,._--------------------<,198 SUPPLY
#2 12VDC (-)t---4~------------------<i~72B
~
Figure 5-4. FRC Interface PCB Test Set-Up
Operation Verification
UN451441 ·6801
3. Measure resistance between the following pairs of pins:
3. v.o.M. should show open circuit between each pair of pins.
lA and 3A 4A and SA 6A and 7A 8A and 9A llA and 12A
4. Turn switch Sl to the on position. 4.
5. Measure resistance between the following pairs of pins:
6202A, p. 5-20
2A and 3A 4A and 7A SA and 6A 8A and 9A 12A and 13A
5.
LED 1 on the PCB should light.
v.o.M. should show short circuit between each pair of pins.
Operation
6. Measure resistance between the following pairs of pins:
lA and 3A 4A and SA 6A and 7A 9A and lOA llA and 12A
7. Turn switch S3 to on position.
6.
7.
UNION SWITCH & SIGNAL m Verification
V.O.M. should show open circuit between each pair of pins.
LED's 1 and 2 on the PCB should light.
8. Turn switch SWl to off position. 8. LED 1 on the PCB should go dark (LED 2 on only).
9. Measure resistance between the following pairs of pins:
2A and 3A 4A and 6A 5A and 7A 9A and lOA llA and 12A
10. Measure resistance between the following pairs of pins:
lA and 3A 4A and SA 4A and 7A 5A and 6A 8A and 9A 12A and 13A
11. Turn switch S2 to on position.
12. Turn switch S3 to off position.
13. Measure resistance between following pairs of pins:
lA and 3A 4A and 5A 4A and 6A SA and 6A 5A and 7A 9A and lOA 12A and 13A
the
9. V.O.M. should show short circuit between each pair of pins.
10. v.o.M. should show open circuit between each pair of pins.
11. LED's 2 and 3 on the PCB should light.
12. LED 2 on the PCB should go dark (LED 3 on only).
13. v.o.M. should show' short circuit between each pair of pins.
6202A, p. 5-21
ffi UNION SWITCH & SIGNAL
Operation
14. Measure resistance between the following pairs of pins:
2A and 3A 8A and 9A llA and 12A
15. Turn switch Sl to on position.
16. Measure resistance between the following pairs of pins:
lA and 3A 4A and 5A 8A and 9A
17. Turn switch S2 to off position.
18. Measure resistance between the following pairs of pins:
2A and 3A 4A and 7A 5A and 6A SA and 9A
19. Measure resistance between the following pairs of pins:
lA and 3A 4A and 5A 9A and lOA
20. Turn switch Sl to off position.
21. Measure resistance between the following pairs of pins:
6202A, p. 5-22
2A and 3A 4A and 6A 5A and 7A 9A and lOA 12A and 13A
Verification
14. V.O.M. should show open circuit between each pair of pins.
15. LED 1 on the PCB should light.
16. v.o.M. should show short circuit between each pair of pins.
17. LED 3 on the PCB should go dark (LED 1 on only).
18. v.o.M. should show short circuit between each pair of pins.
19. v.o.M. should show open circuit between each pair of pins.
20. All LED's on the PCB should be dark.
21. v.o.M. should show short circuit between each pair of pins.
Operation
22. Measure resistance between the following pairs of pins:
lA and 3A 4A and SA BA and 9A llA and 12A
23. Turn all three test switches to the on position.
24. Measure resistance between the following pairs of pins:
lA and 3A 4A and SA 6A and 7A 4A and 6A BA and 9A llA and 12A
25. Measure resistance between the following pairs of pins:
2A and 3A 9A and lOA 12A and 13A
UNION SWITCH & SIGNAL m Verification
22. v.o.M. should show open circuit between each pair of pins.
23. LED's 1, 2 and 3 should light.
24. v.o.M. should show short circuit between each pair of pins.
25. v.o.M. should show open circuit between each pair of pins.
26. Turn on scope and attach probe 26. Scope should show zero volts. to pin 19A or TP3.
27. Turn on function generator. 27. LED's 1, 2 and 3 should be on. LED 4 should flash very rapidly (appears to be on steady). Scope should show a 60Hz pulse wave with a positive level at 5 Vdc and negative level at O Vdc. The positive pulse width should not be less than 3.5 milliseconds.
28. Turn off and disconnect all test 28. --equipment.
6202A, p. 5-23
UNION SWITCH & SIGNAL
5.2.6 FRC Serial Interface PCB N451441-7001
5.2.6.1 Test Procedure Comments
The FRC Serial Interface PCB test procedure (section 5.2.6.4) is divided into three parts. Steps 1 through 4 check the impedance of the "Rn relay and input circuit. Steps 5 through 9 check the contacts of the Master and Transmit relays. Steps 10 through 22 the interface to the Controller PCB, in conjunction with the circuits which convert relay level signals to logic level signals. A five volt power supply is used to simulate ~ine voltage, while a separate 12 volt supply provides system voltage.
5.2.6.2 Required Test Equipment
Item
DC Power Supply (Qty= 2, Suggested Model: HP 62008):
Specifications
- 0 to 20 Vdc@ 0 to 1.5 amps.
v.o.M. (Suggested Model: Simpson 260) - Ohmmeter accuracy: ± 5% reading at center scale
b. Stand PCB vertically (mercury relay contact arrow up).
c. Connect test equipment according to Figure 5-5, but leave card edge connector disconnected from PCB.
d. Turn on both power supplies. Adjust #1 power supply to 5 Vdc + 1% and power supply #2 to 12 Vdc + 1%. Turn both supplies off.
e. Set switches Sl and S2 to the off position and attach card edge connector to the PCB. Do not turn on any test equipment until instructed in the test procedure.
I NOTE: BOARD MUST BE SET VERTICALLY FOR OPERATION.
Figure 5-4. FRC Serial Interface PCB Test Set-Up
5.2.6.4 Test Procedure
Operation
1. Turn on both power supplies (Sl and S2 should be off).
2. Set SWl on the PCB to position 18 and read the ammeter.
3. Move SWl to position 29 and read the ammeter.
4. Move SWl to position 70 and read the ammeter.
5. Connect voltmeter leads on PCB pins 7A (+) and 4A (-).
1.
2.
3.
4.
5.
Verification
LED's 1 and 2 should be off, LED 3 should be on.
Ammeter should show 278 milliamps, + 20 % •
Ammeter should show 172 milliamps + 20%.
Ammeter should show 71 milliamps + 20%.
Voltmeter should show O volts.
6202A, p. 5-25
m UNION SWITCH & SIGNAL
Operation
6. Move switch Sl to on position. 6.
7. Move switch S2 to on position. 7.
8. Move switch Sl to off position. 8.
9. Move switch S2 to off position. 9.
10. Connect voltmeter neg. lead to 10. pin 16A and pos. lead to pin 13A.
11. Move switch Sl to on position. 11.
12. Move voltmeter pos. lead to 12. pin 19A.
13. Move switch Sl to off position. 13.
14. Move voltmeter pos. lead to 14. pin 15A.
15. Move switch S2 to on position. 15.
16. Move switch Sl to on position. 16.
17. Move switches Sl and S2 to off 17. position.
6202A, p. 5-26
Verification
Voltmeter should show 5 Vdc, + 5%. Ammeter should show O -amps. LED's 1 and 3 should be off, and LED 2 should be on.
Voltmeter should show 0 Vdc. Ammeter should show O amps. LED's 1 and 2 should be on, and LED 3 should be off.
Voltmeter should show O Vdc. Ammeter should show 71 milliamps, + 20% • LED's 1 and 3 should be -on, and LED 2 should be off.
LED's 1 and 2 should be off, and LED 3 should be on.
Voltmeter should show 12 Vdc, + 2%.
Voltmeter should show O Vdc. LED's 1 and 3 should be off, and LED 2 should be on.
Voltmeter should show O Vdc.
Voltmeter should show 5 Vdc, + 10% • LED's 1 and 2 should be off, and LED 3 should be on.
Voltmeter should show O Vdc.
Voltmeter should show O Vdc. LED's 1 and 3 should be on, and LED 2 should be off.
Voltmeter should show 12 Vdc, + 2%. LED's 1 ano 2 should be -on, and LED 3 should be off.
Voltmeter should show O Vdc. LED's 1 and 2 should be off, and LED 3 should be on.
UNION SWITCH & SIGNAL ffi Operation Verification
18. Set SWl on PCB to position us. 18. Same results as step 17.
19. Set SWl on PCB to position #29. 19. Same results as step 17.
20. Move switch Sl to on position. 20. Voltmeter should show 12 Vdc, + 2% . LED's 1 and 3 should be -off, and LED 2 should be on.
21. Set SWl on PCB to position us. 21. Same results as step 20. ..
22. Turn off power supplies before 22. --disconnecting test leads.
6202A, p. 5-27
SECTION VI SUPPLEMENTAL DATA
UNION SWITCH & SIGNAL m 6.1 FCE-500 TO DDL-601BX UPGRADE PROCEDURE
6.1.1 General
This section provides a DDL-601BX station. been replaced with a unit is installed in
the procedure for converting an FCE-500 field station to In this procedure, it is assumed that the code line has
digital carrier system modem and that the field modem the equipment rack.
US&S provides FCE to DDL conversion kit X451584-1102. This contains a new PROM IC {containing the digital code system functions software), a new card file name plate and a new label for the inside of the card file front cover, identifying DDL-601BX card slots and the Controller PCB manually selected functions.
6.1.2 Procedure
CAUTION
MAKE CERTAIN THAT ALL POWER SOURCES ARE KEPT OFF UNTIL ALL UPGRADE PROCEDURES ARE COMPLETE, OTHERWISE EQUIPMENT DAMAGE MAY RESULT.
1. Remove the cable connectors from the Controller PCB and the FRC Interface PCB's.
2. Remove the Controller and FRC Interface PCB's from the card file.
3. Remove the PROM from IC26 and install the DDL-601BX PROM {N451575-0604) from the conversion kit.
-4. Reprogram all DIP and rotary switches on the Controller PCB for the new digital code system functions, according to the instructions in section 5.3 of service manual 6199.
5. Reinstall the Controller PCB in the card file.
6. Attach the modem interface cable to the modem and the Controller PCB. Refer to SM-6199 sections 4.3 through 4.5 for connector/cable assembly ordering/construction information.
7. Attach a new cable indentification tag to the connector on the Controller PCB. Refer to SM-6199 section 4.14 for tag instructions.
8. Reset the carrier control switches on the Controller PCB as follows: SWl to NORMAL, SW2 to OPERATE and SW3 to either position. This sets up the Controller PCB for normal modem communications. Refer to SM-6200, section 2.4.1.5 for test mode instructions using these switches.
6202A, p. 6-1
UNION SWITCH & SIGNAL
9. Apply the new card file plan label (kit, M451559-8301) to the inside of the front cover.
10. Attach the new code unit name plate in place of the existing FCE-500 plate.
11. Turn on code unit power and perform routine system start-up checks.
6.2 RECOMMENDED REFERENCE LITERATURE
The following publications provide additional data on the Controller PCB components:
M6809 Programming Reference Manual, Motorola Semiconductor Products, Inc.
Microprocessor Applications Manual, Motorola Semiconductor Products, Inc.
Motorola CMOS Data, Motorola Semiconductor Products, Inc.
Signetics Bfpolar & MOS Memory Data Manual, Signetics Corporation.
The TTL Data Book, Texas Instruments, Inc.
6.3 SCHEMATIC DIAGRAMS
This section provides the complete schematic diagrams for all FCE-500 plug-in printed circuit boards. Refer to Section III for operating descriptions and Appendix A for component specifications and part numbers.
6202A, p. 6-2
+5 +5 rczq
+5 CONNECTOR A
+5 011 TP16 ~ -12v I~
,/ I 12V
+5
TP15
L.
TP5 I
R31l 10K
•5
I I
R3 IK
R2q 10K
av
LEDi LINE
DETECT
5-3.3K RESISTORS
I z 6821
PA0
4 PAI PA2
6 PA3 PA4 PAS
q PA6 PA7 !CJ
4° CAI PIA!
Jq CA2
RESET~ ENABLE ZS
RIN 21
!ROB 37
SW6~5 • ::---+--+/ 1-1 =IB::, I
9 /REQUEST TO SEND <CAI
S I TRANSMITTED OAT A <BAI
+50-----..-'--1
RI I -"IV
IM
+5~ IN4003
PR83510
RLY-1 2
04
IN4003
RIB OV ---'>N
DY
3.3K RESNET 5
SYSTEM •5 ~ET I
OO.. l ~ ·u, q SW I OV -----• r s I IC20""" 10 NORMAL RI 9 4011
av -'VV'-ON IOOK
CAf:l~R ;~ =:.---OPERATE OV ~ I 12
MARK ~ IIC20hll ~eT~ ~~ =:.--• 13 4011
SPACE
D451626-1601, Rev. 6
Jq 1CB2
TPH
• RESET
R32 101<
~· -i:::::_ 1· I I I +'5V HIIBI
I R36 ~ ) 01 6J.qK 2N3q06 !/SW 2K ±Ir.
R35 8 OUT HYS
IC28 I TP4 6.8M 8212
l THR V+r+l2V R37 voo 21il.0K GNO I/SW ±1%
t 0V
+5V OV TP! C/ CONNECTOR B
+5VOC
C24 01 !0MFO !N4003
ov ~ 02
+I C23 'u~ t .~,,.., +r l~M<U l lN4003 !eMFD IN4003 b +12VDC ~
' FRONT OF CONN, BLOCK ~ TYPICAL "-._CONTACTS "A" 8 "I"
FOR "JA" OR "JS" AT THIS END
CONNECTOR "JA"
WIRING DIAGRAM <504BIC>
!~: 5 . 6 7
CONNECTOR "JB"
FRONT OF BLOCK
A B c D E F
50 WIRING DIAGRAM <502A>
He.-! "'D"''I
"TS" 1ils·,1·o wHT I
18
49 WIBK/GN
tt~~~=::: 11 -e12
Ltjj~iG~E::::; : ~ 19
1-1.~~~-- ~ 0
W..iµ@'7<;;~--. 20 W..!!.!~~~-23 L-IHl-':*;.-':,;;---.,,. I 5 1-4+.:*:;'*-- 22 1-1.~,W.:;fu-:~ 21
W4!~-',;l-;,-} SPARES
SHIELD
~·Je ..
!~ c D E F H
2
"TS 11
7,8,'3.~~ OR I O 0------1
lA
E"TB~
0 II 12 13 14 15 25
24
SHIELD
3
/8
TO TERMINAL STRIP "TS" ON FCE-500 UNIT <FOR REF ONLY>
SEE WIRING DIAGRAM ~
~ ...I al
.... ::c ~
0
I ~
l s
15
STORAGE UNIT UNDERSIDE VIEW
' "TB"
10
l/' •
0
t'HT
0
21
UNION SWITCH & SIGNAL m 15
STORAGE. UN I T UNDERSIDE VIEW
2 "TB"
22
30 •
0
WHT
,2 SPARE WIRE I ~
UN
END WIRE
.3
I 12
~ND OF BRACKET
9---t 3--~ ? 6-1 0
1
1LJ 1-
.I 8
10 •+
n--f
5048 504C
UN
502A
F451458-54, Rev. 1, F4f1458-55, Rev. 1 and D451584-26, Rev. O
·------··--'--- 23, 24, 25, 26, 27
18, 19, 20, 21
~ -.ti- -. ~ -~------------· -~---------------· ---------------r-, I I I I I I
M -~ T: I
I I I I I I I I I I I ,-··
:V' 20, 21, 29 : I I
I I
ml- @. T: I·
: 22 ! : I \_ ' I I
,fff'\ I 1 I
-@- -;w \ ! -<ID: -@-. .
28
17
16,"--~, I I I I I I I I I I I I I I
1· I ~
f,r.--1 I I I I, .it,l,f--lt.' •• __ _; ___ _
FCE Storage Unit, Cable Assembly and Wiring Diagram
6202A, p. A-17/18
FCE-500
SERVICE MANUAL 6202A ADDENDUM 1
Field Code Emulator
This addendum updates service manual SM-6202A, which was printed in September, 1985. No replacement pages are included in the addendum. The following corrections may be marked in the manual:
2-9
2-11/12 and
2-13/14
2-23
2-25/26 to
2-31/32
October. 1987 ID0038F,0043F A-10/87-75-2777-AD1
PRINTED IN USA
sec./Fig.
Sec. 2.2.1.1
Figures 2-2 and 2-3
section 2.2.2.1
Figures 2-6 to 2-9
Revision
Scratch out the following system part numbers (no longer available):
N451583-0923 N451583-0924 N451583-0925
Same as above.
Scratch out the following system part numbers (no longer available):
N451583-0926 N451583-0927 N451583-0928
N451583-0929 N451583-0930
Same as above.
UNION SWITCH & SIGNAL AMERICAN STANDARD INC.IPITISBURGH, PA 15237
COPYRIGHT 1987, usas DIVISION OF AMERICAN STANDARD INC.
WIDE RANGE POWER SUPPLY CONVERTER PCB N451441-7601
for
DDL-601 A and DDL-601 B/X
Field Code Units
SAM-II
Stand Alone Monitor
FCE-500 Field Code Emulator
GENISYS
Non-Vital logic Emulator
EVENlTRAK
Digital Event Recorder - Monitor Unit
NOTE: Attach a copy of this appendix to each of the service manuals listed above.
February, 1988 100161F A-02/88-300·2853·1
PRINTED IN USA
UNION SWITCH & SIGNAL AMERICAN STANDARD INC./PITISBURGH, PA 15237
COPYRIGHT 1988. usas DIVISION OF AMERICAN STANDARD INC.
1.1 GENERAL
SECTION I DESCRIPTION
The Wide Range DC/DC Power Supply Converter PCB N451441-7601 is designed as a direct replacement for the N451441-3301, -3302 and -3303 Power supply converter PCBs used in the DDL-601A, DDL-6018, SAM-II, FCE-500, GENISYS and EVENTTRAK systems. It input accepts de voltage in the range of 9.5 to 35 Vdc, and outputs +5, +12 and -12 Vdc to power internal circuits on these systems.
The -7601 board is installed in the same cardfile slot as the N451441-3301, -3302 and -3303 boards. No changes in •a• connector keying plugs are necessary. The board is compatible with existing power input connector/cable assemblies.
1.2 DESIGN
Electronic components of the -7601 board include a single de/de power converter module, a choke, two capacitors, a diode, a transient voltage suppressor (see Figure 1) and four LEDs with current-limiting resistors. The converter module generates regulated +5 and .:!:,12 Vdc outputs from the unregulated 9.5 to 35 Vdc input. This module can be switched on and off externally, and is capable of adjusting its output according changes in the load on the 5 Vdc output (refer to section 1.3). Choke Ll and capacitors Cl/C2 form an LC filter for battery noise on the converter module input. Diode Dl provides reverse polarity protection, while voltage spikes are limited by MOV surge suppressor 02. LED4 indicates the presence of the 9.5 to 35 Vdc input to the converter module, while LEDs 1, 2 and 3 monitor the +5 Vdc, +12 Vdc and -12 Vdc outputs, respectively.
1.3 REMOTE ON/OFF AND REMOTE SENSE
Two functions are incorporated in the Wide Range Power Supply Converter PCB that were not available on the -3301, -3302 and -3303 boards·. These are remote on/off control and a remote sense capability.
The remote on/off control allows the board to be turned on and off from a remote location (power on/off switch by-passed). This is accomplished by switching or connecting the •control• line to the input voltage return line or pins(-). For remote switching, the on-board power on-off switch must be left in the ON position. When not used, the •control• line should be left open.
The •sense• lines enable the power converted module to compensate for voltage changes caused by line resistance or loads on the 5 Vdc output. This is accomplished with external connections between the •sense+• line and 5 Vdc and between the •sense-• line and the COM at the destination point. When a voltage drop occurs, the •sense• line level is monitored by the converter module and the 5 volt output is automatically adjusted to the correct output voltage level. For the DDL-601A/BX, SAM-II, FCE-500, GENISYS and EVENTTRAK systems, no external connections are required to utilize the remote sense capability. These connections are already exist on the cardfile motherboard.
p. 1
selected specifications of the -7601 board are as follows:
Fuse: 7.5 amp, 32 V Choke: 1 mH, 10 amps, 0.038 ohms Power Input: 9.5 to 35.0 Vdc@ 50 w, 5% ripple
Sink to 10 mA Remote On/Off control: Outputs: +5 Vdc@ 3 amps,+ 1%
+12 Vdc@ 1 amp,+ 2% -12 Vdc@ 1 amp,+ 2%
SECTION II MAINTENANCE
If the Wide Range Power supply Converter PCB is not supplying proper operating voltage for the system, first check the front edge LEDs. LED 4 indicates· if the board is receiving external input power. LEDs 1 through 3 indicate whether the power converter module is supplying output voltages. If all of these LEDs are dark, check the input level at TPS (+) and TP6 (-). In addition, check the input fuse. If these checks do not reveal a problem, the entire board should be replaced. Do not attempt to replace or repair the converter module.
To verify output voltage levels, attach a digital voltmeter common to TP2 and •+• probe in sucession to TPl (+SV), TP3 (+12V) and TP4 (-12V) See Figures 1 and 2 for test point locations. The voltmeter should show the output values listed in the Section I specifications. If any of these values are out of tolerance, the board should be replaced.
The Wide Range Power supply converter PCB may be tested in TS-203 test set. Use the same procedures as those for the earlier N451441-3301, -3302 and -3303 boards. Auxiliary test equipment, test point numbering and values are the same as those for the earlier boards.
CAUTION
DO NOT INSTALL OR REMOVE THE WIDE RANGE POWER SUPPLY CONVERTER PCB FROM THE TS-203 WITH TEST SET POWER ON, OTHERWISE COMPONENT DAMAGE MAY RESULT.
p. 2
~
~ ~
' ii!
ri[;~ t + !
(
f ~ +,~
§(:
~(: -(~ : !?
I i l I l I I I I I I
~ +
I!:
h~
-= ...
£
~ i
;;: I ..:
'( r J~i---,--------1
Eg:J, l :1 ·
~ ~
' ~ i!
~~ g ~ l g I;!~ : ~
+
~
:l §
• J
·r ::c .. - ; ! ~ !
i I g
-zt.::u- I §
.~ ~ ·-
10 a.- o·
t3 ··-. I 13
r I!:
• ii: I
[~~~' ~~~~~:JI Figure 1. Schematic Diagram
"' ti . t• et ~ 0 c .. z .,
ii : : .. " ... , . • I : 3 .. 0 ,. .. •• ... .... ... t • 1 ., • 1 v s . •• ~. ... ~. I l $$ •• ... ,r
~h t~N 2
SECTION III ORDERING AND PARTS LIST
(See Figure 2)
New systems such as the EVENTTRAK Monitor, FCE-500 Field Code Emulator and GENSISY Non-Vital Logic Emulator are shipped with Wide Range Power supply Converter PCB N451441-7601. When ordering replacements for the earlier N451441-3301, -3302 or -3303 power supply converter PCBs, specify the N451441-7601 PCB in all cases. None of the earlier boards will be supplied as replacements, howvever US&S will continue to provide repair service on these boards.
The component parts list for the -7601 board is as follows: