PRODUCT DATA
® U.S. Registered TrademarkCopyright © 1996 Honeywell Inc. • All
Rights Reserved
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J;V8044A,B,E Motorized
Valves
V4043, V4044, V8043, V8044Replacement Powerhead
V4043, V8043
V8043 Inverted Flare V4044, V8044
APPLICATIONThese valves consist of an actuator motor and
valveassembly for controlling the flow of hot or cold water,
orsteam.
IMPORTANTThese valves are not for use in systems
containingdissolved oxygen.
FEATURES• The V4043 and V8043 provide 2-position, straight-
through control of water.
• The V4044 and V8044 provide 2-position divertingcontrol of
water.
• Compact construction for easy installation.
• Manual opener for valve operation on power failure.Valve
returns to automatic position when power isrestored.
• Choice of sweat or flare fitting brass end connectionsfor
standard copper tubing.
• Motor can be replaced by removing one screw,without disturbing
the valve body or draining thesystem.
• Complete powerhead may be removed or replacedwithout breaking
the line connections or draining thesystem.
• All models can be installed without disassemblingthe
valve.
• Fits under the cover of most baseboards.
• Available with integral auxiliary end switch (V4044B;V8043E,F;
V8044E) to permit sequencing of auxiliaryequipment.
• V4043E and V8043J provide straight-through controlof
steam.
Contents
Application...........................................................................
1Features
..............................................................................
1Specifications
......................................................................
2Ordering Information
...........................................................
2Installation
...........................................................................
10Operation and Checkout
..................................................... 20
60-2133-9
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 2
SPECIFICATIONS
TRADELINE® ModelsTRADELINE® models are selected and packaged to
provideease of stocking, ease of handling, and maximumreplacement
value. TRADELINE® model specifications arethe same as those of
standard models except as notedbelow.
TRADELINE® Models Available:V8043A,E, and V8043E,F (see Table
1).
Capacity Rating:3.5 Cv (3.0 kV) nominal. (See Electrical Ratings
table inStandard Models section and Table 1.)
Additional Feature:End switch enclosure included.
Standard ModelsModels:
V4043: line voltage, straight-through valves.V4044: line
voltage, 2-position diverting valves.V8043: low voltage,
straight-through valves.V8044: low voltage, 2-position diverting
valves.See Table 1.
Voltage Amperes Voltage Amperes
24 0.320a 220 0.042
100 0.087 240 0.040
120 0.080 277 0.037
208 0.044 — —aMaximum five V8043 Zone Valves per 40 VA
transformer.
Changeover Aquastat® Control:120V, 3.0A with 10.0A inrush.
End Switch:120V, 4.4A running with 26.4A inrush (60 Hz). Pilot
duty 50VA at 24V.
Timing:V4043 and V8043: Open or close in 15 seconds
maximum.V4044 and V8044: Divert flow in 30 seconds maximum.
Dimensions:See Fig. 1.
Manual Opener:Manual opener (on all except the straight-through,
normallyopen valves) allows opening the valve in case of
powerfailure. Valve returns to automatic position when power
isrestored.
ORDERING INFORMATIONFor ordering information when purchasing
replacement and modernization products from your TRADELINE®
wholesaler oryour distributor, refer to the TRADELINE® Catalog or
price sheets for complete ordering number, or specify:
1. Order number.2. Voltage and frequency.3. Size and type of end
connections.4. Cv (kV) rating.5. Lead length if different from
standard.6. Replacement parts, if needed.
If you have additional questions, need further information, or
want to comment on our products or services, please write
orphone:
1. Your local Honeywell Home and Building Control sales office
(check white pages of phone directory).2. Home and Building Control
Customer Relations
Honeywell, 1885 Douglas Drive NorthMinneapolis, Minnesota
55422-4386
In Canada—Honeywell Limited/Honeywell Limitee, 35 Dynamic Drive,
Scarborough, Ontario M1V 4Z9. International Salesand Service
Offices in all principal cities of the world. Manufacturing in
Australia, Canada, Finland, France, Germany, Japan,Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
Electrical Ratings(See Table 1 for Voltage of Specific
Models):
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—93
Fig. 1. Mounting dimensions in in. (mm) of V4043/44, V8043/44
Motorized Valves.
AUTO MAN OPEN
A B
AUTO MAN OPEN
A B
AUTO MAN OPEN
A B
AUTO MAN OPEN
A
AB
AB
B
HEIGHT NEEDED TO REMOVE COVER.
DIMENSIONS FOR 1/2 IN. COPPER TUBING.
DIMENSIONS FOR 3/4 IN COPPER TUBING.
DIMENSIONS FOR 1 IN. COPPER TUBING.
4-7/8 IN. (124) MAX ON V8034F WITH TERMINAL BOARD ENCLOSURE.
V4034B AND V8043B VALVES THAT ARE NORMALLY OPEN IN THE
DE-ENERGIZED POSITION HAVE NO MANUAL LEVER. THE VALVES ALSO HAVE A
REVERSED POWERHEAD WHERE THE LEADWIRES EXIT THE POWERHEAD ABOVE THE
B (OUTLET) PORT RATHER THAN ABOVE THE A (INLET) PORT.
REFER TO MOUNTING INSTRUCTIONS.
OPENING FOR 1/2 IN. CONDUIT ON MANUAL LEVER SIDE FOR V4043,
V8043; OPENING ON OPPOSITE SIDE FOR V4044, V8044.
1
1
6
7
8
1
6
5
2
3
4
8
1
4 3 2
7
2
3
4
7
8
7 7
1
2
3
4
5
6
7
8
M10175
V043, V8043 SWEAT COPPER CONNECTION MODELS V4044, V8044 SWEAT
COPPER CONNECTION MODELS
V4044, V8044 FLARE-FITTING MODELSV4043, V8043 FLARE-FITTING
MODELS
V8043 INVERTED FLARE MODELS
2-3/8(60)
7/8 DIA.(22)
7/8 DIA.(22)
1-1/2(38)
5-1/4(133)
5-1/4(133)
15/32(12)
IN OUT
INLET
OUT
3-1/2 (89)
1-3/4(44)
3/8(10)
3/8(10)
3/8(10)
1-3/4(44)
1-9/16(40)
1-3/4(44)
3-1/8(79)
3-1/2(89)
1-7/8(47)
3-11/16(94)
1-9/16(40)
3/8(10)
1-3/4(44)
3-1/8(79)
3-1/2(89)
1-7/8(47)
3-11/16(94)
2-3/8(60)
5-1/4(133)
1-3/4(44)
1-3/4(44)
1-7/8(48)
1-11/16(43)
1-1/2(38)
2-3/8(60)
1-3/4(44)
1-3/4(44)
3-1/8(79)
2-1/4(57)
7/8(22)
3-1/8(79)
3-1/2 (89)
1-3/4(44)
1-3/4(44)
2-11/32(59)
2-11/32(59)
2-11/32(59)
2-11/32(59)
1-13/16(46)
3-5/8 (92)
15/32(12)
2-3/8 (60)
1-1/2(38)
5-1/4(133)
OUTIN
IN
INLET
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 4
Table 1. Powerhead and Valve Body Specifications
Flow CapacityRating
PipeConnections
ModelControlCircuit Cv kV Wire Hookup Type
Size(in.)
ValveBody
De-energizedPosition
V4043A 120V, 60 Hz 1.0 .86 18 in. (457 mm) leadwires, Sweat 1/2
Straight- Normally 120V, 60 Hz 3.5 3.0 1/2 in. conduit opening.
Sweat or
Flare1/2 through Closed
120V, 60 Hz 8.0 7.0 Sweat 3/4
120V, 60 Hz 8.0 7.0 Sweat 1
120V, 60 Hz 3.5 3.0 NPT 1/2
120V, 60 Hz 3.5 3.0 NPT 3/4
120V, 60 Hz 10.0 8.6 NPT 1
208V, 60 Hz 3.5 3.0 Flare 1/2
220V, 50 Hz 3.5 3.0 Flare 1/2
240V, 50 or60 Hz
3.5 3.0 Sweat orFlare
1/2
V4043B 120V, 60 Hz 1.0 .86 18 in. (457 mm) leadwires, Sweat 1/2
Straight- Normally Open
120V, 60 Hz 3.5 3.0 1/2 in. conduit opening. Sweat orFlare
1/2 through
240V, 60 Hz 3.5 3.0 Sweat 1/2
V4043E(steam only)
120V, 60 Hza Cv notapplicable (15 psi [103 kPA] lowpressure
steam rating).
18 in. (457 mm) leadwires,1/2 in. conduit opening.
Sweatd 1/2 Straight-through
NormallyClosed
208V, 60 Hz Sweat 1/2
240V, 60 Hz Sweat 1/2
V4044A 120V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwires,1/2 in.
conduit opening.
Sweat orFlarec
1/2 2-positiondiverting
Port A NormallyClosed
120V, 60 Hz 7.0 6.0 Sweatc 3/4
120V, 60 Hz 4.0 3.4 Sweate 1/2
208V, 60 Hz 4.0 3.4 Sweat 1/2
220V, 50 Hz 4.0 3.4 Sweat orFlare
1/2
220V, 50 Hz 7.0 6.0 Sweat 3/4
240V, 50 Hz 4.0 3.4 Sweat orFlare
1/2
240V, 60 Hz 4.0 3.4 Sweat orFlare
1/2
277V, 60 Hz 4.0 3.4 24 in. (610 mm) leadwires,1/2 in. conduit
opening.
Sweat 1/2
V4044Bb,c(bottom inlet)
120V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwires,1/2 in. conduit
opening.
Sweat orFlare
1/2 2-positiondiverting
Port A NormallyClosed
120V, 60 Hz 7.0 6.0 Sweat 3/4
220V, 50 Hz 4.0 3.4 Flare 1/2
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—95
Flow CapacityRating
PipeConnections
ModelControlCircuit Cv kV Wire Hookup Type
Size(in.)
ValveBody
De-energizedPosition
V8043A 24V, 60 Hz 3.5 3.0 18 in. (457 mm) leadwires,1/2 in.
conduit opening.
Sweat orFlare
1/2 Straight-through
NormallyClosed
24V, 60 Hz 3.5 3.0 NPT 1/2
24V, 60 Hz 3.5 3.0 Sweat 3/4
24V, 60 Hz 8.0 7.0 36 in. (914 mm) leadwires,1/2 in. conduit
opening.
Sweat 3/4
24V, 60 Hz 3.5 3.0 18 in. (457 mm) leadwires,1/2 in. conduit
opening.
Sweat 1
V8043B 24V, 60 Hz 3.5 3.0 18 in. (457 mm) leadwires,1/2 in.
conduit opening.
Sweat 1/2 Straight-through
Normally Open
24V, 60 Hz 3.5 3.0 Sweat 3/4
24V, 60 Hz 3.5 3.0 NPT 3/4
V8043E 24V, 60 Hz 3.5 3.0 18 in. (457 mm) leadwiresand end
switch, 1/2 in.conduit opening.
Sweat 1/2 Straight-through
NormallyClosed
24V, 60 Hz 3.5 3.0 Sweat 3/4
24V, 60 Hz 3.5 3.0 Sweat 1
24V, 60 Hz 8.0 7.0 Sweat 3/4
24V, 60 Hz 8.0 7.0 Sweat 1
24V, 60 Hz 10.0 8.6 NPT 1
24V, 60 Hz 3.5 3.0 NPT 3/4
V8043F 24V, 60 Hz 3.5 3.0 Terminal Board and endswitch.
Sweat 1/2 Straight-through
NormallyClosed
24V, 60 Hz 3.5 3.0 Sweat 3/4
24V, 60 Hz 3.5 3.0 Sweat 1
24V, 60 Hz 8.0 7.0 Sweat 3/4
24V, 60 Hz 8.0 7.0 Sweat 1
V8043J 24V, 60 Hzd Cv notapplicable. (15psi [103 kPa]low
pressuresteam rating).
18 in. (457 mm) leadwires,1/2 in. conduit opening.
dSweat 1/2 Straight-through
Normally Open
24V, 60 Hz NPT 1/2
24V, 60 Hz NPT 3/4
V8044A 24V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwires,1/2 in.
conduit opening.
Sweat orFlaree
1/2 2-positiondiverting
Port A NormallyClosed
24V, 60 Hz 7.0 6.0 Sweat 3/4
24V, 60 Hz 4.0 3.4 50 in. (1270 mm)stranded leadwires,
1/2conduit opening.
Sweat 1/2
24V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwires,1/2 in. conduit
opening.
NPT 1/2
24V, 60 Hz 4.0 3.4 NPT 3/4
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 6
Approvals:Underwriters Laboratories Inc. Listed:
V4043A,B,E;V4044A,B; V8043A,B,E,J; V8044A,B,E: File MH11826, Vol.1,
dated 2-22-88.
Replacement Parts:Motor Part Numbers (use with V4043, V4044,
V8043,V8044):
802360JA 24 Vac, 60 Hz, Class A, plated.802360LA 120 Vac, 60 Hz,
Class F, plated.802360MA 208 Vac, 60 Hz, Class F, plated.802360NA
220V 50 Hz, 240V 60 Hz, Class F, plated.802360UA 24 Vac, 60 Hz,
Class F, plated.
Powerhead (see Table 2):Includes motor, housing and two mounting
screws.
Flow CapacityRating
MaximumCloseoff Pressure Max Fluid Min Fluid Max Ambient
Valve Family Cv kV psi kPa Temperature Temperature
Temperature
V4043A,B,E,J 1.0 .86 50 345 240°F (116°C) 40°F (5°C) 125°F
(50°C)
3.5 3.0 20 138 240°F (116°C) 40°F (5°C) 125°F (50°C)
10.0 8.6 6.5 45 240°F (116°C) 40°F (5°C) 125°F (50°C)
V8043A,B,E,F 3.5 3.0 20 138 200°F (93°C) 40°F (5°C) 125°F
(50°C)
8.0 7.0 8 55 200°F (93°C) 40°F (5°C) 125°F (50°C)
10.0 8.6 6.5 45 200°F (93°C) 40°F (5°C) 125°F (50°C)
V4044A,B 4.0 3.4 20 138 240°F (116°C) 40°F (5°C) 125°F
(50°C)
7.0 6.0 10 69 240°F (116°C) 40°F (5°C) 125°F (50°C)
V8044A,B,E 4.0 3.4 20 138 200°F (93°C) 40°F (5°C) 125°F
(50°C)
7.0 6.0 10 69 200°F (93°C) 40°F (5°C) 125°F (50°C)
V4043E, V8043J (steam) — — 15a 103 240°F (116°C) 40°F (5°C)
125°F (50°C)
Static Pressure Rating of 125 psi (862 kPa) applies to all
valves.a15 psi low pressure steam.
Conversion Kits:Conversion kits for converting old style (series
1-5) valvebodies to accept 40003916 Powerhead (use with
V4043,V4044, V8043, V8044). Includes metal plate with driveshaftand
rubber ball, O-Ring and four screws.
Two-way water valve body: 40003918-006.Three-way water valve
body: 40003918-007.Two-way steam valve body: 40003918-008.
O-Ring Part Numbers:272742A—Includes replacement ball plug,
large O-Ring
and four screws.272756A—Package of five large O-Rings.
Accessories:803867A Conduit Cover: Includes 803858 Cover
and803859 Case (for V8043F).
Flow and Temperature Ratings:
Flow CapacityRating
PipeConnections
ModelControlCircuit Cv kV Wire Hookup Type
Size(in.)
ValveBody
De-energizedPosition
V8044B 24V, 60 Hzb 4.0 3.4 18 in. (457 mm) leadwires,1/2 in.
conduit opening.
Sweat 1/2 2-positiondiverting
Port A NormallyClosed
V8044E 24V, 60 Hz 4.0 3.4 18 in. (457 mm) leadwiresand end
switch, 1/2 in.conduit opening.
Sweat 1/2 2-positiondiverting
Port A NormallyClosed
24V, 60 Hz 7.0 6.0 Sweat 3/4a 30 in. (762 mm) leads also
available.b Includes integral changeover Aquastat® Control.c 96 in.
(2438 mm) leads also available.d 30 in. (762 mm) leads also
available.e Valve available with reduced (2.5 Cv [2.1 kV] ) rating
on bypass port. Sweat fitting only.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—97
Table 2. Replacement Powerheads.
How to Find Maximum Valve OperatingTemperatureThe maximum
operating temperature for motorized valvesdepends on the maximum
ambient temperature at the valvelocation, and on the maximum fluid
temperature. Using thegraph in Fig. 2, find the maximum valve
operatingtemperature as follows:
� Measure the ambient temperature at the valve andlocate that
temperature on the ambient temperaturescale on the graph.
� Draw a line from the ambient temperature, parallel withthe
fluid temperature scale, to the maximum fluidtemperature line.
� Draw a line from that point down to the fluidtemperature scale
to find the maximum operatingtemperature. (Note the example shown
by the dashedline in Fig. 2.)
To find the maximum ambient temperature for a valve whenthe
fluid temperature is known, reverse the procedure.
ValveModel
Number Part Number
Electrical Connectionon Which Side of
Manual Lever
Voltage (Vac)and Frequency
(Hz)Current
Draw (A)Type of Electrical
Connection Motor
V4043A 40003916-022 Same 220/50, 240/60 0.04 18 in (457 mm)
leads(conduit opening)
Class F;plated
40003916-023 Same 240, 50 0.04
40003916-024 Same 120, 60 0.08
V4043B 40003916-030 Same 240, 60 0.04
40003916-031 Same 120, 60 0.08
40003916-042 Same 208, 60 0.04
V8043A 40003916-021 Same 24, 50/60 0.32 Class A
V8043B 40003916-027 Same 24, 50/60 0.32
V8043E 40003916-026 Same 24, 50/60 0.32
V8043F 40003916-048 Same 24, 50/60 0.32 Terminal Board
V4044A 40003916-034 Opposite 240, 50 0.04 18 in. (457 mm)
leads(conduit opening)
Class F;plated
40003916-035 Opposite 220/50, 240/60 0.04
40003916-036 Opposite 120, 60 0.08 96 in. (2438 mm)
leads(conduit opening)
40003916-047 Same 120, 60 0.08
V4044B 40003916-039 Opposite 220/50, 240/60 0.04 18 in. (457 mm)
leads(conduit opening)
40003916-040 Opposite 120, 60 0.08
40003916-045 Same 120, 60 0.08
V8044A 40003916-032 Opposite 24, 50/60 0.32 18 in. (457 mm)
leads(conduit opening)
Class A;plated
40003916-046 Same 24, 50/60 0.32
V8044B 40003916-037 Opposite 24, 50/60 0.32 18 in. (457 mm)
leads(conduit opening)
40003916-044 Same 24, 50/60 0.32
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 8
Fig. 2. Maximum temperature characteristics of valves with Class
F motors.
EXAMPLE: 150°F (66°C) IS THE AMBIENT TEMPERATURE AT THE
VALVE,235°F (113°C) IS MAXIMUM FLUID TEMPERATURE.
MAXIMUM AMBIENTTEMPERATURE LINE
MAXIMUM FLUIDTEMPERATURELINE
AM
BIE
NT
TE
MP
ER
AT
UR
E
FLUID TEMPERATURE M8164
210(99)
200(93)
190(88)
180(82)
170(77)
160(71)
150(66)
140(60)
130(54)
120(49)
110(43)
100(38)
90(32)
80(27)
DEGREES F
DEGREES C
70
(21)
80
(27)
90
(32)
100
(38)
110
(43)
120
(49)
130
(54)
140
(60)
150
(66)
160
(71)
170
(77)
180
(82)
190
(88)
200
(93)
210
(99)
220
(104)
230
(110)
240
(116)
250
(121)
How to Find Valve Pressure DropThe pressure drop in psi (kPa),
equivalent ft (m) of pipe, orfeet of water (kPa) can be calculated
from Fig. 3 through 8as follows:
� Calculate the flow rate to heat the zone.� Determine the Cv
(kV) rating of the motorized valve.� Select the graph corresponding
to the Cv (kV) rating
(Fig. 3 through 8).� Determine the pressure drop across the
valve using
the following procedures for calculating pressure drop.
Pressure Drop in psi (kPa)� Locate the flow rate at the bottom
of the graph.� Draw a line up from the flow rate to the
intersection of
the curve.� Draw a line from the intersection to the left edge
of the
graph to determine the pressure drop in psi (kPa).
Pressure Drop in Equivalent ft (m) of Pipe
NOTE: Both 1/2 and 3/4 in. pipe conversion scales areavailable
for this determination.
� Locate the flow rate at the bottom of the graph.� Draw a line
vertically to the top of the graph.
Determine the pressure drop for either the 1/2 or 3/4in.
pipe.
Pressure Drop in ft of Water (kPa)� Locate the flow rate at the
bottom of the graph.� Draw a line up from the flow rate to the
intersection of
the curve.� Draw a line from the intersection to the right edge
of
the graph to determine pressure drop in ft of water(kPa).
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—99
Fig. 3. Flow characteristics of 1 Cv (0.86 kV) flow.
PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF
PIPE)
500(152)
140(43)
120(37)
100(30)
90(27)
600(183)
700(213)
750(229 )
-50 (149)
-40 (119)
-30 (89.5)
-20 (60)
(3/4 IN. PIPE)(1/2 IN. PIPE)30 (207)
20 (138)
10 (69)
9 (62)8 (55)7 (48)6 (41)
5 (34)
4 (28)
3 (21)
2 (14)
1 (7)0 2
(0.13)4
(0.25)6
(0.38)8
(0.5)10
(0.63)12
(0.76)
-5 (15)
-10 (30)
M9183AGAL/MIN (l/s) FLOW RATEF
T O
F W
AT
ER
psi
(kP
a) P
RE
SS
UR
E D
RO
P
PR
ES
SU
RE
DR
OP
psi
(kP
a)
1CV(0.86 KV)
PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF
PIPE)
45(13.7)
60(18)
70(21.3)
8(2.4)
9(2.7)
10(3)
13(4)
11(3.4)
12(3.6)
12.5(3.8)
80(24.4)
65(20)
-50 (149)-40 (119)-30 (89.5)-20 (60)
(3/4 IN. PIPE)
(1/2 IN. PIPE)
50.0 (345)
10.0 (69)
5.0 (34)
1.0 (7)
.50 (3.4)
.10 (0.69)
.05 (0.34)
0 2(0.13)
4(0.25)
6(0.38)
8(0.5)
10(0.63)
12(0.76)
14(0.88)
-5 (15)
-1 (3)
-0.5 (1.5)
-0.1 (0.3)
-0.05 (0.15)
-10 (30)
M9184AGAL/MIN (l/s) FLOW RATE
FT
OF
WA
TE
R p
si (
kPa)
PR
ES
SU
RE
DR
OP
PR
ES
SU
RE
DR
OP
psi
(kP
a)
2.5CV(2.1 KV)
PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF
PIPE)
12(3.6)
11(3.4)
12.5(3.8)
8.0(2.4)
9.0(2.7)10
(3)
80(24.4)
45(13.7)
70(21.3)
65(20)
60(18)
-50 (149)-40 (119)-30 (89.5)-20 (60)
(3/4 IN. PIPE)
(1/2 IN. PIPE)
50.0 (345)
10.0 (69)
5.0 (34)
1.0 (7)
0.50 (3.4)
0.10 (0.69)
0.05 (0.34)
00 2
(0.13)4
(0.25)6
(0.38)8
(0.5)10
(0.63)12
(0.76)14
(0.88)
-0.05 (0.15)
-0.1 (0.3)
-0.5 (1.5)
-1 (3)
-5 (15)
-10 (30)
M5979BGAL/MIN (l/s) FLOW RATE
PR
ES
SU
RE
DR
OP
FT
OF
WA
TE
R p
si (
kPa)
PR
ES
SU
RE
DR
OP
psi
(kP
a)
3.5CV(3.0 KV)
13(4)
PRESSURE DROPEQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF
PIPE)
6.0(1.8)
50(1.5)
7.0(2.1)
8.0(2.4)
9.0(2.7)
10(3)
30(9.1)
40(12.2)
45(13.7)
50(15.2)
55(16.8)
60(18)
-50 (149)-40 (119)-30 (89.5)-20 (60)
(3/4 IN. PIPE)(1/2 IN. PIPE)
50.0 (345)
10.0 (69)
5.0 (34)
1.0 (7)
0.50 (3.4)
0.10 (0.69)
0.05 (0.34)
0 2(0.13)
4
(0.25)
6(0.38)
8
(0.5)
10(0.63)
12
(0.76)
14(0.88)
16
(1.0)
18(1.1)
20
(1.3)
22(1.4)
24
(1.5)
26(1.6)
28
(1.8)
30(1.9)
-0.05 (0.15)
-0.1 (0.3)
-0.5 (1.5)
-1 (3)
-5 (15)
-10 (30)
M5717BFLOW RATEGAL/MIN (l/s)
PR
ES
SU
RE
DR
OP
FT
OF
WA
TE
R p
si (
kPa)
PR
ES
SU
RE
DR
OP
psi
(kP
a)
4CV(3.4 KV)
Fig. 4. Flow characteristics of V4043A model with 2.5 Cv(2.1 kv)
rating and V4044A and V8044A bypass port (B)
with 2.5 Cv (2.1 kv) (reduced) rating.
Fig. 5. Flow characteristics of 3.5 Cv (3.0 kV) valve.
Fig. 6. Flow characteristics of 4 Cv (3.4 kV) valve.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 10
Fig. 7. Flow characteristics of 7 Cv (6.0 kV) valve.
PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF
PIPE)
2.0(0.6)
3.0(0.9)
3.5(1)
21(6.4)
24(7.3)
25(7.6)
22(6.7)
23(7)
20(6)
19(5.8)
17(5.2)
15(4.6)
13(4)
10(3)
-50 (149)-40 (119)-30 (89.5)-20 (60)
(3/4 IN. PIPE)
(1/2 IN. PIPE)
50.0 (345)
10.0 (69)
5.0 (34)
1.0 (7)
0.50 (3.4)
0.10 (0.69)
0.05 (0.34)
0 2(0.13)
4
(0.25)
6(0.38)
8
(0.5)
10(0.63)
12
(0.76)
14(0.88)
16
(1.0)
18(1.1)
20
(1.3)
22(1.4)
24
(1.5)
26(1.6)
28
(1.8)
30(1.9)
-0.05 (0.15)
-.1 (0.3)
-.5 (1.5)
-1 (3)
-5 (15)
-10 (30)
M9185AGAL/MIN (l/s) FLOW RATE
FT
OF
WA
TE
R p
si (
kPa)
PR
ES
SU
RE
DR
OP
psi
(kP
a)
7CV(6.0 KV)
PRESSURE DROP, EQUIVALENT FEET OF PIPE (EQUIVALENT METERS OF
PIPE)
2.0(0.6)
2.5(0.8)
1.5(0.5)
19(5.8)
17(5.2)
18(5.5)
15(4.6)
16(4.9)
14(4.3)
10(3)
12(3.7)
13(4)
8(2.4)
1(3.4)
9(2.7)
7(2.1)
-50 (149)-40 (119)-30 (89.5)-20 (60)
(3/4 IN. PIPE)
(1/2 IN. PIPE)
50.0 (345)
10.0 (69)
5.0 (34)
1.0 (7)
0.50 (3.4)
0.10 (0.69)
0.05 (0.34)
0.010 2
(0.13)4
(0.25)
6(0.38)
8
(0.5)
10(0.63)
12
(0.76)
14(0.88)
16
(1.0)
18(1.1)
20
(1.3)
22(1.4)
24
(1.5)
26(1.6)
28
(1.8)
30(1.9)
-0.05 (0.15)
-0.1 (0.3)
-0.5 (1.5)
-1 (3)
-5 (15)
-10 (30)
M9186AGAL/MIN (l/s) FLOW RATE
FT
OF
WA
TE
R p
si (
kPa)
PR
ES
SU
RE
DR
OP
PR
ES
SU
RE
DR
OP
psi
(kP
a)
8CV(6.9 KV)
Fig. 8. Flow characteristics of 8 Cv (6.9 kV) valve.
INSTALLATION
When Installing this Product…1. Read these instructions
carefully. Failure to follow them
could damage the product or cause a hazardouscondition.
2. Check the ratings given in the instructions and on theproduct
to make sure the product is suitable for yourapplication.
3. Installer must be a trained, experienced
servicetechnician.
4. After installation is complete, check out productoperation as
provided in these instructions.
CAUTION1. Disconnect power supply before connecting
wiring to prevent electrical shock or equipmentdamage.
2. Normally it is not necessary to remove thepowerhead from the
valve body duringinstallation. If the valve must be disassembled,be
certain that it is reassembled with the waterflow in the direction
of the arrow. Reversal of thepowerhead results in damage to the
gear train.
3. On 24V systems, never jumper the valve coilterminals even
temporarily. This can burn out theheat anticipator in the
thermostat.
IMPORTANTUse this valve in hydronic heating systems that donot
contain dissolved oxygen in the system water.The dissolved oxygen,
which is found in systemsthat have a frequent source of makeup
water,causes the rubber plug inside the valve todeteriorate and
eventually fail.
MountingThe valve can be mounted in any position on a vertical
line.See Fig. 9. If the valve is mounted horizontally; thepowerhead
must be even with or above the center line of thepiping. Make sure
to leave enough room above thepowerhead to remove the cover for
servicing.
M10162
VERTICALPIPING
HORIZONTIALPIPING
Fig. 9. Mounting positions.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—911
Mount the valve directly in the tube or pipe. Make sure thatthe
flow through the valve is in the direction indicated by thearrow
stamped on the valve body.
On diverting valves, the three fittings or ports are labeled
onthe bottom of the valve body casting. See Fig. 1. Port AB isthe
inlet port and is open at all times. Port A is closed whenthe valve
is de-energized; port B is open when the valve isde-energized.
Refer to the equipment manufacturerinstructions to determine which
port (A or B) should beconnected to the coil bypass.
Flare Fitting ModelsUse new, properly reamed pipe, free from
chips. The valvebody is threaded for standard 5/8 in. OD copper, 45
degreeSAE flare fitting nuts. These nuts are not furnished with
thevalve and must be obtained separately.
Sweat Copper Models� Use new, properly reamed pipe, free from
dents or
corrosion.� Place the valve on the pipe. Set the manual
opening
lever to MAN. OPEN position before applying heat.This protects
the plug inside the valve by removing itfrom the seat.
� Sweat the joints, keeping the outer surface free fromsolder.
DO NOT use silver solder because of the highmelting temperature
required.
To Install Replacement PowerheadSystem with Old Style Valve
Bodies (Series 1-5)To install a replacement powerhead in a system
with an oldstyle body (series 1-5), the valve body must be
converted toaccept the new powerhead using part no.
40003918Conversion Kit. The kit includes a metal plate with
adriveshaft and rubber plug, O-ring, and four screws.
IMPORTANTConverting the valve body for use with the newpowerhead
does not require removal of the valvebody from the pipeline.
However, it is necessary todrain the water from the system before
beginningthe conversion.
� Disconnect the power supply before connecting thewiring to
prevent electrical shock or equipmentdamage.
� Disconnect the leadwires to the powerhead at theterminal block
or conduit connection. Remove theconduit or cable connector if
fitted. Label each wire forrewiring later.
� Drain the water from the system.
� Remove the old powerhead from the valve body(Fig. 10):a. Place
the manual opening lever (normally closed
models only) on the old powerhead in the MAN.OPEN position (see
Fig. 10A).
b. Remove the cover (Fig. 10B).c. With the cover off, remove the
four screws
securing the powerhead to the valve body.d. Lift the powerhead
off the valve body (Fig. 10C).e. Remove the O-ring from the top of
the valve body.
� Install 40003918 Conversion Kit (Fig. 11):a. Insert the new
O-ring in the valve body.b. Place metal plate with the rubber plug
on top of
the valve body. Make sure the guide pins on theunderside of the
metal plate fit into the recesseson the valve body.
c. Secure the metal plate to the valve body with thefour screws
(two sets) provided. One set of screwshas heads with recessed
threads to insert screwsfor mounting the new powerhead; insert this
setinto the larger screw openings. The other set hasdomed heads;
insert this set into the smallerscrew openings. Each set of screws
must beinserted in opposite corners of the metal plate sothe screws
sit flat on the plate. Make sure theguide pins on the plate fit
into the recesses on thevalve body.
� Install new powerhead (see Fig. 12):a. Place the manual
opening lever (normally closed
models only) on the new powerhead in the MAN.OPEN position.
b. Fit the powerhead onto the valve body, ensuringthat the shaft
seats correctly. The powerheadshould be aligned with the manual
opening leveror slot for lever at the port A end of the valve
body.
c. Secure the powerhead to the valve body with thetwo screws
provided.
d. If fitted, reconnect the conduit or cable. Reconnectthe
leadwires at the powerhead.
e. Replace the powerhead cover.� Turn on the power.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 12
A
AUTO
MAN
OPEN
MANUAL OPENING LEVER
COVERRETAININGSCREW
M10174
A
B
V8043F 105
1
24V 50/60 C
Y
.32 AMP @ 6
0 CY
MADE IN CA
NADA
6
A
B
V8043F 105
1
24V 50/60 C
Y
.32 AMP @ 6
0 CY
MADE IN CA
NADA
6
A
B
C
Fig. 10. Remove old powerhead from systems using old style valve
bodies.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—913
Fig. 11. Install 40003918 Conversion Kit.
Fig. 12. Install new powerhead.
Systems with New Style Valve Bodies (Series 6)
IMPORTANTOn a new style valve body or a valve body that
wasconverted to accept the new powerhead, it is notnecessary to
drain the system if the valve bodyremains in the pipeline.
� Disconnect the power supply before connecting thewiring to
prevent electrical shock or equipmentdamage.
� Disconnect the leadwires to the powerhead at theterminal block
or conduit connection. Remove theconduit or cable connector, if
fitted. Label each wire forrewiring.
� Remove the old powerhead (see Fig. 13):a. Place the manual
opening lever (normally closed
models only) on the old powerhead in the MAN.OPEN position (Fig.
13A).
b. Remove the screw securing the cover to thepowerhead (Fig.
13B).
c. Lift off the cover from the powerhead.d. Remove the two
screws securing the powerhead
to the valve body (Fig. 12).e. Lift the powerhead off the valve
body.
� Install the new power head (see Fig. 12):a. Place the manual
opening lever (normally closed
models only) on the new powerhead in the MAN.OPEN position.
b. Fit the powerhead onto the valve body, ensuringthat the shaft
seats correctly. The powerheadshould be aligned with the manual
opening leveror slot for lever at the port A end of the valve
body.
c. Secure the powerhead to the valve body with thetwo screws
provided.
d. If fitted, reconnect the conduit or cable. Reconnectthe
leadwires to the powerhead.
e. Replace the powerhead cover.� Turn on the power.
WiringDisconnect the power supply before connecting wiring
toprevent electrical shock or equipment damage.
All wiring must comply with local codes and
ordinances.Connections to the individual valves are shown in Fig.
14and 15. See Fig. 16 through 22 for typical hookups.
If replacing a Taco, Dole, Flair or White Rodgers 3-wire
valvewith a 2-wire V8043E or F, see Fig. 23 through 35. Checkthat
the pressure rating of the new valve is appropriate forthe
application.
A
B
HEX-NUT SCREWWITH DOMED HEADS (2)
HEX-NUT SCREWSWITH RECESSEDTHREADS ANDSHOULDER SHANK (2)
ADAPTER PLATE
O RING
LOCATING RECESSES (3)
VALVE BODY M10160
A
B
V8043F 103
6
24V 50/60 C
Y
.32 AMP @ 6
0 CY
MADE IN CA
NADA
6
SECURING SCREW (2)
REMOVABLE HEAD
SHAFT
REMOVABLE HEADVALVE BODY ASSEMBLY
M10173
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 14
A
AUTO
MAN
OPEN
MANUAL OPENING LEVER
COVERRETAININGSCREW
M10161
A
B
B
V8043F 103
6
24V 50/60 C
Y
.32 AMP @ 6
0 CY
MADE IN CA
NADA
6
A
B
Fig. 13. Remove old powerhead from systems using newstyle valve
bodies.
AUXILIARYSWITCH
MOTOR
YELLOWLEADS
TO CIRCULATOR OR ANOTHER VALVE
RED LEADS
THERMOSTAT(TYPICALLY T87F)TO
LINE
M5953
Fig. 14. Typical wiring for V8043E, V8044E.
R
L1 (HOT)L2
1
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
END SWITCH
TO CIRCULATOROR ANOTHER VALVE
TH TR
24VTRANSFORMER
THERMOSTAT(TYPICALLY T87F)
TH TR
M5952
Fig. 15. Typical wiring for V8043F.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—915
Fig. 16. T822 Thermostat, V8043A valve hookup.
L1 (HOT)L2
1
1
2
2
2 2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
CONNECT V8043A BLACK LEADWIRE TO THERMOSTAT.
T822 T822 T822
V8043A V8043A V8043A
M10168
L1 (HOT)L2
1
1
2
2
3
2 2
3 3 3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT.
CONNECT V8043E RED LEADWIRES TO L1 (HOT) LINE ANDPRIMARY
CONTROL.
T822 T822 T822
V8043E V8043E V8043E
M10169
TO OIL PRIMARYCONTROL OR TOTRANSFORMERAND LOW VOLTAGEGAS
VALVE
L4006A HIGHLIMIT
CIRCULATOR
Fig. 17. T822, V8043E zone hookup for gas or oil. Nodomestic hot
water.
RED
BLUE
YELLOW
MOTOR
HEATINGCOOLINGTHERMOSTAT
TOPOWER
V4044, V8044VALVE OPERATOR
AQUASTAT® CHANGEOVER CONTROL SWITCHES TO HEATING (RED)AT FLUID
TEMPERATURE OF 85°F (29°C) MAX TO COOLING (BLUE) ATFLUID
TEMPERATURE OF 60°F (18°C) MIN.
1
1
M10171
Fig. 18. Wiring diagram for V4044 and V8044 withAquastat®
changeover control.
L1 (HOT)L2
1
1
2
2
3
2 2
3 3 3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
CONNECT V8043E YELLOW LEADWIRE TO THERMOSTAT.
CONNECT V8043E RED LEADWIRES TO AQUASTAT®.
T822 T822 T822
V8043E V8043E V8043E
M10170
CIRCULATOR
T T
1
2 C1
TO BURNERCONTROLCIRCUIT
B1
B2
C2
Fig. 19. T822, V8043E zone hookup for gas or oil with orwithout
domestic hot water. Without domestic hot water,
use L8148J for gas, and L8148A for oil. With domestichot water,
use L8124E for gas, and L8124A or C for oil.
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 16
Fig. 20. Typical 3-zone system. Use an AT87A Transformer to
power up to five more zone valves.
M5980
ZONE 1 ZONE 2 ZONE 3 ZONE 4
END SWITCH
V8043F
TH-TR TH TR
END SWITCH
V8043F
TH-TR TH TR
END SWITCH
V8043F
TH-TR TH TR
END SWITCH
V8043F
TH-TR TH TR
ZONE 1 ZONE 2 ZONE 3 ZONE 4
T87F
INTEGRALTRANSFORMER
TO CIRCULATORCONTROL CIRCUIT
W775A PANEL
B
R
B
W
BR
B
R
B
W
BR
B
R
B
W
BR
B
R
B
W
BR
T87F
L1 (HOT)
L2
POWERSUPPLY
B
R
B
W
BR
RE
D
RE
D
YE
LLO
W
ZONE V8043E
YE
LLO
W
W775A PANEL
RED
YELLOW
RED
YELLOW
T87F T87F
CONNECTIONS FOR V8043E(LEADWIRE MODEL)
Fig. 21. Typical 4-zone system. Use an additional W775A to power
up to four more zone valves.
L1 (HOT)
L2
ZONE 1
T87F
ZONE 2 ZONE 3
V8043F
END SWITCH
TH-TR TH TR
L8124G
120 VPOWER SUPPLY
ADD JUMPER TO EACHVALVE
END SWITCH END SWITCH
V8043F V8043F
TH-TR TH TR TH-TR TH TR
TOCIRCULATOR TO BURNER
CIRCUIT
T87F T87F
TV T Z
C1 C2 B1 B2
2 1
M5954
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—917
ZONE 1
T87F
ZONE 2 ZONE 3 ZONE 4 ZONE 5
V8043F
END SWITCH
TH-TR TH TR
V8043F
END SWITCH
TH-TR TH TR
V8043F
END SWITCH
TH-TR TH TR
V8043E V8043E
T87F T87F T87F T87F
M10164
YELLOW
RED
YELLOW
RED
YELLOW
RED
YELLOW
RED
L1 (HOT)
L2 11 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVERLOAD PROTECTION AS REQUIRED.
TO BURNERAND / ORCIRCULATORCIRCUIT
AT87ATRANSFORMER
NOTE: IF CODE PERMITS, V8043E AND V8043F CAN BE USED
INTERCHANGEABLY WHEN WIRED AS SHOWN.
Fig. 22. Typical 5-zone system. Use an AT87A Transformer to
power up to five more zone valves.
L1 (HOT)
L2
1
A B
C
D
E
1
2
3
THERMOSTATTACO VALVE
TO AUXILIARYCIRCUITS
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED. M5958
Fig. 23. Existing Taco system. (Wires are identified withletters
to correspond with wires in Fig. 24 and 25.)
L1 (HOT)
L2
1C
A B
D
THERMOSTAT
V8043E
TOAUXILIARYCIRCUITS
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
M10163
YELLOW
YELLOW
RED
REDE
Fig. 24. Wiring Honeywell V8043E to Taco System.(Wires are
identified with letters to correspond
with wires in Fig. 23.)
A B
C
D
THERMOSTAT
END SWITCH
V8043F
TH-TR TH TR
L1 (HOT)
L2
1E
M5960
A
B
C
D
THERMOSTAT
END SWITCH
V8043F
TH-TR TH TR
L1 (HOT)
L2
1E
TO AUXILIARYCIRCUITS
TO AUXILIARYCIRCUITS
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
Fig. 25. Wiring Honeywell V8043F to Taco System(two options).
(Wires are identified with letters
to correspond with wires in Fig. 23.)
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 18
L1 (HOT)
L2
1A
B
F
D
E
THERMOSTAT
DOLE VALVE
TO TERMINALST, T ONBURNER RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
M5977
1
23
4C
Fig. 26. Existing Dole System. (Wires are identified withletters
to correspond with wires in Fig. 27 and 28.)
L1 (HOT)
L2
1A
B C D
ETHERMOSTAT
V8043E
TO TERMINALST, T ONBURNER RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
M5965
YELLOW
YELLOW
RED
REDF
A
B
C
F
THERMOSTAT
END SWITCH
V8043F
TH-TR TH TR
L1 (HOT)
L2
1E
M5966
A
B
C
F
THERMOSTAT
END SWITCH
V8043F
TH-TR TH TR
L1 (HOT)
L2
1E
TO TERMINALST, T ON BURNER RELAY
TO TERMINALST, T ON BURNER RELAY
D
D
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
M5978
A
B
C D
THERMOSTAT
FLAIR VALVE
L1 (HOT)
L2
1F
TO TERMINALST, T ONBURNER RELAY
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
E3
2
1
4 5
Fig. 27. Wiring Honeywell V8043E to Dole System.(Wires are
identified with letters to correspond
with wires in Fig. 26.)
Fig. 28. Wiring Honeywell V8043F to Dole System(two options).
(Wires are identified with letters to
correspond with wires in Fig. 26.)
Fig. 29. Existing Flair System. (Wires are identified
withletters to correspond with wires in Fig. 30 and 31.)
L1 (HOT)
L2
1A
B C D
ETHERMOSTAT
V8043E
TO TERMINALST, T ONBURNER RELAY
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
M5965
YELLOW
YELLOW
RED
REDF
Fig. 30. Wiring Honeywell V8043F to Flair System.(Wires are
identified with letters to correspond
with wires in Fig. 29.)
A
B
C
F
THERMOSTAT
END SWITCH
V8043F
TH-TR TH TR
L1 (HOT)
L2
1E
M5966
A
B
C
F
THERMOSTAT
END SWITCH
V8043F
TH-TR TH TR
L1 (HOT)
L2
1E
TO TERMINALST, T ON BURNER RELAY
TO TERMINALST, T ON BURNER RELAY
D
D
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
Fig. 31. Wiring Honeywell V8043F to Flair System(two options).
(Wires are identified with letters
to correspond with wires in Fig. 29.)
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—919
Fig. 32. Existing White-Rodgers System.
WATER VALVETHERMOSTAT
WHITE-RODGERS1311 OR 1321VALVE
TO AUXILIARYCIRCUIT
L1(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOADPROTECTION AS
REQUIRED.
M5711
1
2
3
4
5
6
4
5 6
1
1
L1(HOT)
L2
THERMOSTAT
TO AUXILIARYCIRCUIT
YELLOW
RED
RED
TO 6 ON THERMOSTAT
TO AUXILIARYCIRCUIT
YELLOW
YELLOW
RED
RED
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT, WIRE
AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
TAPE UNUSED END AND TUCK INTO HOLE.
1
2
3
5
4
6
M5712
1
2
3
1
L1(HOT)L2
THERMOSTAT
END SWITCH
L1(HOT)L2
V8043F
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT, WIRE
AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
TAPE UNUSED END AND TUCK INTO HOLE.
1
2
3
1
2
34
5 6
L1(HOT)L2
1
TO AUXILIARYCIRCUIT
TO AUXILIARYCIRCUIT
2
END SWITCH
TH-TR TH TR
M5714
Fig. 33. Wiring Honeywell V8043E toWhite-Rodgers System.
Fig. 34. Wiring Honeywell V8043F to White-RodgersSystem (one
option).
Fig. 35. Wiring Honeywell V8043F to White-RodgersSystem
(alternate option).
TO AUXILIARYCIRCUITS
V8043F
END SWITCH
TH-TR TH TR
5
4
6
1
2
3
THERMOSTAT
L1(HOT)
L2
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
IF TRANSFORMER SUPPLIES POWER TO AUXILIARY CIRCUIT, WIRE
AUXILIARY CIRCUIT AS SHOWN IN LOWER DIAGRAM.
TAPE UNUSED END AND TUCK INTO HOLE.
1
2
3
TH TRTH-TR
END SWITCH
1
2
L1(HOT)L2
M5713
TO AUXILIARYCIRCUITS
-
V4043A,B,E,J; V4044A,B; V8043A,B,E,F,J; V8044A,B,E MOTORIZED
VALVES
60-2133—9 20
Honeywell Europe S.A.3 Avenue du BourgetB-1140 Brussels
Belgium
Honeywell Asia Pacific Inc.Room 3213-3225Sun Hung Kai CentreNo.
30 Harbour RoadWanchaiHong Kong
Home and Building ControlHoneywell Limited-Honeywell Limitée155
Gordon Baker RoadNorth York, OntarioM2H 2C9
Honeywell Latin American DivisionMiami Lakes Headquarters14505
Commerce Way Suite 500Miami Lakes FL 33016
Helping You Control Your World®
60-2133—9 J.S. Rev. 11-96 Printed in U.S.A.
Home and Building ControlHoneywell Inc.Honeywell PlazaP.O. Box
524Minneapolis MN 55408-0524
OPERATION AND CHECKOUT
CAUTIONOn 24V systems, never jumper the valve coilterminals even
temporarily. This can burn out theheat anticipator in the
thermostat.
OperationAutomatic OperationOn a call for heat by the zone
thermostat, the valve opensand its auxiliary switch contacts make,
closing the circuit tothe system circulator. In a multizone system
with all the valveauxiliary switches wired in parallel, any zone
calling for heatcan operate the circulator. When the call for heat
ends, thevalve closes by integral spring return. The auxiliary
switchcontacts break the circulator circuit.
Manual OperationThe motorized valve can be opened manually by
lifting themanual opening lever over the stop and pushing slowly
andfirmly to the MAN. OPEN position. The stop permits the valveto
be locked in the open position. The valve returns toautomatic
position when the valve is energized.
Normally Closed ModelsWith the manual opener set to AUTO and the
powerheadenergized, the valve is opened as shown in Fig. 36A.
Whenthe powerhead is de-energized, a spring-return mechanismdrives
the valve to the closed position as shown in Fig. 36B.The valve can
also be opened with no electrical power bymoving the manual opening
lever over the stop and pushingslowly and firmly to the MAN. OPEN
position. The stoppermits the valve to be locked in the open
position. The valvereturns to the automatic position when the valve
isenergized.
Auxiliary switch is not energized when the valve is
manuallyopened.
Normally Open ModelsWhen the powerhead is de-energized, a
spring-returnmechanism drives the valve to the open position (Fig.
36A).When energized, the valve is closed as shown in Fig. 36B.A
reverse-acting thermostat is required to control a normally
B
OUT
OPEN POSITIONA
A
IN
B
OUT
CLOSED POSITIONB
A
IN
M5951
Checkout� Raise the setpoint on the zone thermostat above
the
room temperature to initiate a call for heat.� Observe all
control devices—the valve should open
and the auxiliary switch should make the circuit to
thecirculator or other valve at the end of the openingstroke.
� Lower the setpoint on the zone thermostat below theroom
temperature.
� Observe the control devices. The valve should closeand the
auxiliary equipment should stop.
ServiceThis valve should be serviced by a trained,
experiencedservice technician.
1. If the valve is leaking, drain the system and check tosee if
the O-ring needs replacing.
2. If the gear train is damaged, replace the entirepowerhead
assembly. See the Installation section. Ifthe motor is burned out,
replace the motor. SeeReplacement Parts list in the TRADELINE®
Catalog.
NOTE: Honeywell zone valves are designed and tested forsilent
operation in properly designed and installedsystems; however, water
noises can occur as a resultof excessive water velocity or piping
noises canoccur in high temperature (higher than 212°F(100°C)
systems with insufficient water pressure.Valves are designed for
normal cycling operations.Product life will be shortened if
energizedcontinuously.
open valve.
NOTE: Inlet Port is stamped A and Outlet Port is stampedB on the
valve body.
Fig. 36. V8043 operation for normally closed valve.
Printed on recycled paper containing at least 10% post-consumer
paper fibers. www.honeywell.com/building/components