NO 1 2 3 4 5 6 7 8 ITEM CODE 602V003 602V002 600V008 600V034 600V035 600V036 600V038 600V039 QTY 1 1 1 2 3 1 1 1 DESCRIPTION 3,200L Septic Tank 3,200L S.C.A. Tank 950L Pump Well TJ Surround, 125 thick, Ø600 Void TJ Ø700mm Lid, 65mm Thick Pump Well Surround, Ø600 Void 400mm Turbojet Saddle 200mm Turbojet Saddle SCALE DATE DRAWN 1:25 R. Hourani CHECKED 601V002VIC A3 D. Egan Turbojet 2000 (Sheet 1 of 3) 0 NO 17/02/2010 DATE Product Redrawn REVISIONS UNCONTROLLED ONCE PRINTED ISO 9001:2008 SIZE REV DWG NO LIFTING TOTAL MASS NOTES TITLE W: www.mcpipes.com.au T: 1300 557 143 Excavation Level Ground Level 200 mm 1660 mm 400 mm 200 mm 50 mm In-Line Configuration Sewer Inlet Pump 1 1400 mm 510*mm 1910 mm 2290 mm 1 2 8 7 710 mm Air Water Jets Pump 2 2075 mm 50 mm 710 mm 1400 mm - Top of Primary Sewage & S.C.A. tanks to be installed level - "In-Line" configuration shown here. - Min of 50mm fall of pipe between tanks. - Top of cover & surround to be 75mm above ground level. - Deeper installations require one or more risers to bring to ground level, additional saddles & risers are available in 200/400mm increments. - Manifold to be located as high as possible in the saddle or the top riser. - Concrete tanks to be manufactured to AS 1546.1 - Patent No. 45342/89 applies. Infringement will result in legal action. Ø100 PVC Inspection Pipe & Cap by Others (TYP) 1610 mm 5 75 mm Alarm Float (Refer to Sheet 3 of 3) 300 mm 550 mm 1100 mm Min 150 - 300 mm Ø100mm U.P.V.C. Droppers 125 mm Contact Tank Capacity: 740L Primary Sewage Tank Capacity: 3,200L Submerged Contact Aeration Tank Capacity: 1,880L Humus Tank Capacity: 1,320L Vortex Sludge Return Line Retention Time Minimum of 1 Hour, Average Capacity 400L D.S.P. Tablet Dispensing Chlorinator (Not Standard, by Request Only) 6 Effluent to Approved Means of Disposal by Statutory Authority Ø19mm Recirculation Pipe (To be installed by others) *Deeper installations require one or more saddles and/or risers to bring to ground level. Please advise the sewer inlet depth determined on site. All saddles and risers to be sealed. For deeper installations raise the manifold to top riser and hang Pump 1 from a stainless steel bracket and chain. Also for deeper installations where a riser is used on the contact tank, position the valve & union in the riser so they can be accessed for servicing. 75 mm 15 mm Irrigation Kit (Sold Separately) 125 mm Top of Access Covers Min 75 mm Above GL 4 Attach Submersible Pump to Tank with Bracket OR Slude return line. Ø19mm recirculation pipe to be sleeved in crush proof conduit (by others). Ø100mm UPVC Dropper Contact Media Blocks Pump 1 Ø920 mm Ø800 mm Ø710 mm - Internal Base Alarm Float Control Panel Electrical supply (by others), seperate circuit from switchboard to control panel NOT covered by RCD unit. NOT Refer to Sheet (3 of 3) 20 AMP, 240V Pump 2 Through wall or saddle. All pipework & electrical conduits to be sealed inside & outside. Contact Media Blocks 870 mm 3 550 mm Barrel Unions Non-Return Valves (Locate as high as possible in tank) Turbojet 2000 Max Hydraulic Load 2000L/day Max BOD 625g/day 17/03/2010 01/19
3
Embed
2290 mm Turbojet 2000 Max Hydraulic Load Max BOD 625g/day · 400mm Turbojet Saddle 200mm Turbojet Saddle SCALE DATE DRAWN 1:25 R. Hourani CHECKED 601V002VIC D. Egan A3 Turbojet 2000
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
TJ Ø700mm Lid, 65mm ThickPump Well Surround, Ø600 Void
400mm Turbojet Saddle200mm Turbojet Saddle
SCALEDATE
DRAWN
1:25
R. Hourani CHECKED601V002VIC
A3D. Egan
Turbojet 2000 (Sheet 1 of 3)
0NO
17/02/2010DATE
Product RedrawnREVISIONS
UNCONTROLLED ONCE PRINTED
ISO 9001:2008
SIZE
REVDWG NO
LIFTING
TOTAL MASS
NOTES
TITLEW: www.mcpipes.com.au T: 1300 557 143
Excavation Level
Ground Level200 mm
1660 mm
400 mm 2
00 m
m 50
mm
In-Line Configuration
SewerInlet
Pum
p 1
1400 mm
510*mm
1910 mm
2290 mm
12
8
7
710 mm
Air Water Jets
Pum
p 2
2075 mm
50
mm
710 mm
1400 mm
- Top of Primary Sewage& S.C.A. tanks to beinstalled level- "In-Line" configurationshown here.- Min of 50mm fall of pipebetween tanks.- Top of cover & surroundto be 75mm aboveground level.- Deeper installationsrequire one or morerisers to bring to groundlevel, additional saddles& risers are available in200/400mm increments.- Manifold to be locatedas high as possible in thesaddle or the top riser.- Concrete tanks to bemanufactured toAS 1546.1- Patent No. 45342/89applies. Infringementwill result in legal action.
Ø100 PVCInspection
Pipe & Cap byOthers (TYP)
1610 mm
5
75 mm
Alarm Float(Refer to Sheet 3 of 3)
300 mm
550 mm
1100 mmMin
150 - 300 mm
Ø100mm U.P.V.C.Droppers
125 mm
Contact TankCapacity: 740L
Primary Sewage TankCapacity: 3,200L
Submerged ContactAeration TankCapacity: 1,880L
Humus TankCapacity: 1,320L
Vortex SludgeReturn Line
Retention Time Minimum of1 Hour, Average Capacity 400L
D.S.P. TabletDispensing Chlorinator
(Not Standard, by Request Only) 6 Effluent to ApprovedMeans of Disposal byStatutory Authority
Ø19mm Recirculation Pipe(To be installed by others)
*Deeper installations require one or more saddlesand/or risers to bring to ground level. Please advisethe sewer inlet depth determined on site. All saddlesand risers to be sealed. For deeper installations raisethe manifold to top riser and hang Pump 1 from a stainlesssteel bracket and chain. Also for deeper installationswhere a riser is used on the contact tank, position thevalve & union in the riser so they can be accessed for servicing.
75 mm
15
mm
Irrigation Kit(Sold Separately)
125 mm
Top of AccessCovers Min
75 mm Above GL4
Attach SubmersiblePump to Tank with Bracket
OR
Slude return line. Ø19mm recirculationpipe to be sleeved in crushproof conduit (by others).
TJ Ø700mm Lid, 65mm ThickPump Well Surround, Ø600 Void
400mm Turbojet Saddle200mm Turbojet Saddle
SCALEDATE
DRAWN
1:25
R. Hourani CHECKED601V002VIC
A3D. Egan
Turbojet 2000 (Sheet 2 of 3)
0NO
15/03/2010DATE
Product RedrawnREVISIONS
UNCONTROLLED ONCE PRINTED
ISO 9001:2008
SIZE
REVDWG NO
LIFTING
TOTAL MASS
NOTES
TITLEW: www.mcpipes.com.au T: 1300 557 143
Horse Shoe Configuration
- Top of Primary Sewage& S.C.A. tanks to beinstalled level- "In-Line" configurationshown here.- Min of 50mm fall of pipebetween tanks.- Top of cover & surroundto be 75mm aboveground level.- Deeper installationsrequire one or morerisers to bring to groundlevel, additional saddles& risers are available in200/400mm increments.- Manifold to be locatedas high as possible in thesaddle or the top riser.- Concrete tanks to bemanufactured toAS 1546.1- Patent No. 45342/89applies. Infringementwill result in legal action.
1660 mm
Contact TankCapacity: 740L
Primary Sewage TankCapacity: 3,200L
ORAlarm Float
Control
Panel
Electrical supply(by others), seperate
circuit fromswitchboard to
control panel NOTcovered By RCD
unit.
Refer to Sheet (3 of 3)20 AMP, 240V
NOT
Submerged ContactAeration TankCapacity: 1,880L
Humus TankCapacity: 1,320L
2290 mm
Slude return line. Ø19mm recirculationpipe to be sleeved in crush
proof conduit (by others).
House
Inlet
3600 mm900 mm
4200
mm
2900 mm
Pump 2
Excavation Parameter
1610
mm
1200 mm
4200 mm
290 mm
300 mm
290 mm
2110
mm
1910
mm
200
mm
2100 mm 2100 mm
Excavation Level
75 mm75 mm
520 mm
160 mm
OutletInlet
1400
mm
510*mm
125 mm4 5
78
1
2
Ground Level
PLAN VIEW SIDE VIEW A-A
3
Through wall or saddle.All pipework & electrical
conduits to be sealedinside & outside.
Primary Sewage TankCapacity: 3,200L
Submerged ContactAeration TankCapacity: 1,880L
*Deeper installations require one or more saddlesand/or risers to bring to ground level. Please advisethe sewer inlet depth determined on site. All saddlesand risers to be sealed. For deeper installations raisethe manifold to top riser and hang Pump 1 from a stainlesssteel bracket and chain. Also for deeper installationswhere a riser is used on the contact tank, position thevalve & union in the riser so they can be accessed for servicing.
Ø100mm UPVC Dropper
Pump 1
Contact MediaBlocks
Turbojet 2000Max Hydraulic Load
2000L/dayMax BOD 625g/day
17/03/2010 01/19
NO123
ITEM CODE QTY DESCRIPTIONSCALEDATE
DRAWN
1:2524/03/2010R. Hourani CHECKED
601V002VIC 0A3D. Egan
Turbojet 2000 (Sheet 3 of 3)
0NO
24/03/2010DATE
Product RedrawnREVISIONS
UNCONTROLLED ONCE PRINTED
ISO 9001:2008
SIZE
REVDWG NO
LIFTING
TOTAL MASS
CONCRETE GRADE
NOTES
TITLEW: www.mcpipes.com.au T: 1300 557 143
Please read these instructions carefully. It is critical that the system is wired to Icon-Septech specificationsso that the plant may be commissioned appropriately, and so that warranties are NOT made void.
1. Mount the controller approximately 1.5m to 1.7m from the finished ground level on the external structure that allows good accessfor future servicing.2. All conduits and unused penetrations must be sealed inside and outside against moisture and vermin.3. All work must be carried out by a licenced electrical contractor in accordance with the local authorities and regulations.4. Hard wire the controller from an independent 20 Amp circuit from the switchboard NOT RCD protected.5. Cables extended from the controller to each piece of equipment in the treatment plant must be, independent, continuous,heavy duty submersible flex (Versolex or approved equivalent).6. Cables extended from the controller must ONLY be joined to each piece of equipment in an accessible location within the treatment plant.At least 1.0m spare controller cable must be left, so that the piece of equipment may be brought to the surface and maintained.
Pum
p 1
Pum
p 2
Alarm Float(Refer to Sheet 2 of 2)
300 mm
550 mm
7. Join cables to each piece of equipment using in line crimp lugs in a staggered formation, individually insulated with resin cored heatshrink. Then insulate overall with resin cored heat shrink ensuring an overlap at each end of at least 50mm.
Control Panel Mk 5 Installation & Specs
AE N
A A
RemoteAlarm
A AN NE EPump 1 Pump 2
(Circulation) (Irrigation)6 Amp 6 Amp
Alarm Float(N/Closed Contacts Used)
20mm HDConduit to
SubmergedContactAeration
Tank
25mm HD Conduitto Contact
(Irrigation) Tank
240V Supply, seperate20 Amp circuit fromswitch board. (Notconnected to RCD
unit.)
50 mm, sand paper scratched& cleaned with primer fluid.
12mm resin core heat shrink
9mm resin core heat shrink
1.5mm copper crimp lugs
ControlPanel
1.0m of spare cable, coiled,cable-tied and positionedas high as possiblein the tank or saddle/riser.
25mm HD Conduit
Contact TankSubmerged ContactAeration Tank Humus Tank
20mm HDConduit
3 Core Versolex Cable
2 Core Versolex Cable
8. The float switch circuit is 3 Volts. Use normally closed contacts for high water (alarm float).