Electrical Power System

Fault Analysis

Prepared by: Jonryl P. Novicio 1

Page 2: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 2

Fault Analysis

INTRODUCTION Fault Studies play an important role of the power system analysis. The problem consists of determining bus voltages and line currents during various types of faults.An electrical fault is any failure which interferes the normal flow of current. Faults on power systems are divided into three-phase balanced faults and unbalanced faults. Different types of unbalanced faults are single line to ground fault, line to line fault, and double line to ground fault.

Page 3: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 3

Fault Analysis

The information gained from fault studies are used for: Proper relay setting and coordination.

Three – phase balanced fault is used to select and set phase relays Line to Ground Fault is used for ground relays

To obtained the rating of the protective switchgears (Three – phase Faults).

Page 4: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 4

Now, consider the typical system below.

Fault Analysis

Page 5: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 5

The magnitude of the fault current depends on the internal impedance of the generators plus the impedance of the intervening circuit.

Fault Analysis

Page 6: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 6

What are the Causes of Faults? There are several causes of failures and outages which are classified according to the reasons for its occurrence: a) Deterioration of insulation which are inherent in the system. As a result

breakdown may occur at normal voltage. b) Damage due to external causes such as birds, trees and kites. Failure may also

occur at normal voltage. Example of damage on open, outdoor equipment are due to birds with widely stretching wings by spanning an insulation or phase fault by bridging the bare conductors.

c) Breakdown due to deterioration of insulation accelerated by self generated surges following switching or other disturbances.

d) Collapse of insulation resulting from either direct lightning stroke or consequent disturbances. The fault would not be at normal voltage.

Fault Analysis

Page 7: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 7

Fault Analysis

Types of Faults on

3-Phase System

Faults in 3-phase system are classified as follows :( see-Fig.1) a. Balanced or symmetrical

three-phase fault b. Single-line to ground fault c. Double line-to-ground

fault d. Line-to-line fault

Page 8: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 8

Fault Analysis

A fault occurs when two or more conductors that normally operate with a potential difference come in contact with each other. The contact may be physical metallic one or it may occur through an arc.

What are the Effect of Faults? The directly resulting damage from system faults can be classified as follows: a) Thermal b) Mechanical c) Dielectric

Page 9: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 9

Fault Analysis

Thermal Effects. The amount of current will be much greater than

the designed thermal ability of the conductor in the power lines or machines feeding the fault. As a result, temperature rise may cause damage by annealing

of conductors and insulation charring. Please note that the thermal stress varies as a function of both

RMS current squared and the duration of current flow (I2t).

Page 10: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 10

Fault Analysis

Mechanical Effects of high instantaneous current involves magnetic forces (repulsion/attraction) of hundreds of pounds per foot run of conductor or bus as normally spaced and feed by modern generators.

The mechanical stress varies as a function of the peak current

squared and the ratio of the length of the peak conductor to the spacing between conductor centers (KI2

peak L/S).

Page 11: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 11

Fault Analysis

Dielectric Effects have several causes. One obvious cause of impairment or weakening of insulation strength or dielectric strength is the high temperature of the conductor carrying the fault currents, which may result to the burning or blistering of varnish insulation or cracking of ceramic ones.

Such defects may be present but not visible for months and may never be discovered due to the later breakdown destroying the evidence of its cause.

Similar danger of unsuspected latent weakness arise from surge voltage, either generated by fault switching or rapid displacement of the neutral following a ground fault or one phase.

Page 12: 194511440 Power System Analysis

Electrical Power System

(a) utility systems

(b) generators

(c) synchronous motors

(d) induction motors

Prepared by: Jonryl P. Novicio 12

Fault Analysis

Sources of Short-Circuit Current

Page 13: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 13

Fault Analysis

The utility system usually supplies power through step-down transformers at

the costumer’s desired voltage level. Although transformers are sometimes considered a source of short-circuit current, strictly speaking this is not correct. Transformers change voltage and current magnitude, but do not generate them.

Generators in the customer’s system can be a source of short-circuit current.

They are driven by prime movers such as steam or gas turbines, diesel engines and water wheels. When a short-circuit occurs, the generator continues to be driven by its prime mover and to produce voltage, since field excitation is maintained by the generator rotating at normal speed.

Page 14: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 14

Fault Analysis

Synchronous motors behave similarly to synchronous generators. When a fault occurs and the voltage of the system is reduced to a very low value, the synchronous motor stops taking power from the system to rotate its load, and starts slowing down.

But the inertia of the load tends to prevent the motor from slowing down quickly. The inertia acts as a prime mover and, with excitation maintained, the motor acts as a generator supplying short-circuit current for several cycles after the short circuit occurs.

Page 15: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 15

Fault Analysis

Induction motors contribute short-circuit current because of generator action

produced by the inertia of the load and rotor driving the motor after the fault occurs.

But there is a major difference between the short-circuit current contribution

of induction motors and synchronous motors. The field flux of the induction motor is produced by induction from the stator and not from a dc field winding.

Since this flux decays rapidly after a fault, the induction motor contribution

drops off quickly and dies out completely after a few cycles. There is no steady-state fault-current contribution. Consequently, induction motors are assigned only a sub-transient value of reactance, X’’d.

Page 16: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 16

Fault Analysis

The total symmetrical short-circuit current is a combination of all the sources of short-circuit current we have described.

Utility supply, generators, synchronous and induction motors all

contribute short-circuit current into a fault. The flux in the machines decays with time after the inception of

the fault, hence their fault-current contribution also decays with time.

Page 17: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 17

Fault Analysis

Consequently, the resulting total short-circuit current decays with time as shown at E in Fig. 3.

The current magnitude is highest during the first half-cycle and

decreases in value after a few cycles.

After one or two cycles, the induction-motor contribution disappears.

Page 18: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 18

Fault Analysis

Page 19: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 19

Fault Analysis

Fault Calculation should be made to ensure that the short-circuit ratings of the equipment are adequate to handle the currents available at the location of the fault. In general, the procedure is as follows: a.) Develop a graphical representation of the system with symbolic voltage

sources and circuit impedances. b.) Determine the total equivalent impedance from the source to specified

points. c.) At each point, divide the voltage by the total impedance to that point to

determine short-circuit current.

Page 20: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 20

Fault Analysis

To simplify the calculations, certain simplifying assumptions are usually made. The following assumptions are usually made: a.) The fault is bolted that is, it has zero impedance. This assumption

simplifies calculation since the resulting calculated values are maximum, and equipment selected on the basis will always have an adequate rating.

b.) A 3-phase fault is assumed because their type of fault generally

results in the maximum short-circuit current available in a system. In most systems, a 3-phase fault is frequently the only one calculated.

Page 21: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 21

Fault Analysis

Most faults actually involve arcing resistance or other undefined

impedances or both not considered in the fault calculation because of the assumed bolted fault condition as mentioned earlier.

Fault which are not 3-phase will usually be less than the 3-phase fault value. These are the following: a.) Bolted line-to-line current -, 87% of the 3-phase value b.) Bolted single-line-to-ground current - About 25-125% of the 3-phase fault

depending on system parameters. This is the most common among the faults, about 75% of the faults.

Page 22: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 22

Fault Analysis

Single-line-to-ground currents of more than 100% of the 3-phase value rarely occurs in industrial, institutional and commercial power systems.

In low- voltage systems, single-line-to-ground arcing fault currents are sometimes less than normal load currents and yet can be extremely destructive.

Page 23: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 23

Fault Analysis

Other assumption which effected simplification of the fault calculations are also being done as follows: a.) Load currents are not considered. b.) The voltages of power company and generator sources are

assumed to be equal to their nominal values at no-load. The actual values could be ± 5% of the nominal values.

c.) Motors are running with their rated voltage at the terminal when a fault occurs.

Page 24: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 24

Fault Analysis

Other assumption which effected simplification of the fault calculations are also being done as follows: d.) The transformer percent impedance values used will be actual

values or are often nominal values possibly subject to their ± 7.5% tolerance to anticipate worst case.

e.) The source X/R ratio will be assumed at relatively high value ( above X/R ratio of 15). This normally results in calculated values of short- circuit that are slightly high.

Page 25: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 25

Fault Analysis

Other assumption which effected simplification of the fault calculations are also being done as follows: f.) Switchboard and panel board bus impedances can be neglected. As the Impedances of the bus are usually of small values, excluding them from the calculation, the increase of fault current values is only very slight.

Page 26: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 26

Fault Analysis

Symmetrical Faults or

Balanced Faults

Page 27: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 27

Fault Analysis

The balanced three phase fault and three phase to ground fault occurs very

rarely, accounting for only about 5% of the total. For the purpose of fault studies, the generator behavior can be divided into

three stages. 1) The subtransient period

2) The transient period

3) Steady state period

Page 28: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 28

Fault Analysis

Subtransient exists for a period of few cycles from the instant of short circuit

followed by transient period appears for another few cycles. With less magnitude compared with subtransient and finally settling at a still higher synchronous (steady state) value called the steady state period.

In a modern large interconnected power system, heavy currents will flow through the fault which must be interrupted much before the steady state conditions are established.

The maximum current that a breaker has to carry momentarily is the peak

value of short circuited current which must also be determined.

Page 29: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 29

Fault Analysis

Transient due to Short Circuit When there is a sudden change in the current, because of the inductive property of

the power system component which give rise to transients. Transient condition in power system rises due to faults on the system which is

accompanied by sudden change in current.

Page 30: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 30

Fault Analysis

Page 31: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 31

Fault Analysis

Page 32: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 32

Fault Analysis

Page 33: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 33

Fault Analysis

Page 34: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 34

Fault Analysis

Page 35: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 35

Fault Analysis

Page 36: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 36

Fault Analysis

Page 37: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 37

Fault Analysis

Page 38: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 38

Fault Analysis

Page 39: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 39

Fault Analysis

Transients due to Short Circuit in a 3-Phase Alternator at No-load

Consider a three phase alternator running on no-load. Under steady state

short circuit conditions, the armature reaction of a synchronous machine produces a demagnetizing flux. The effect of armature reaction is modeled as a reactance Xa in series with induced e.m.f.

The combination of Xa with the leakage reactance X l of the synchronous

machine is called Xd synchronous reactance (direct axis synchronous reactance in case of salient pole machines).

Armature resistance being small can be neglected. The steady state short circuit model of a synchronous machine is shown in Fig. 4.3 (a).

Page 40: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 40

Fault Analysis

Page 41: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 41

Fault Analysis

Page 42: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 42

Fault Analysis

Page 43: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 43

Fault Analysis

Page 44: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 44

Fault Analysis

Page 45: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 45

Fault Analysis

Page 46: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 46

Fault Analysis

Page 47: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 47

Fault Analysis

Page 48: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 48

Fault Analysis

Page 49: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 49

Fault Analysis

THREE-PHASE FAULTS

Page 50: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 50

Fault Analysis

Page 51: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 51

Fault Analysis

Page 52: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 52

Fault Analysis

Page 53: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 53

Fault Analysis

Page 54: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 54

Fault Analysis

Page 55: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 55

Fault Analysis

Page 56: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 56

Fault Analysis

Page 57: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 57

Fault Analysis

Page 58: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 58

Fault Analysis

Page 59: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 59

Fault Analysis

Page 60: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 60

Fault Analysis

Page 61: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 61

Fault Analysis

Page 62: 194511440 Power System Analysis

Electrical Power System

Prepared by: Jonryl P. Novicio 62

Fault Analysis

Page 63: 194511440 Power System Analysis

Electrical Power System

• From the previous equations, the volume of copper is inversely proportional to the square of the transmission voltage and the power factor.

• Thus greater is the transmission voltage level, lesser is the volume of copper required.

• The weight of copper used for the conductors

• The required material is LESS for higher transmission voltage.

Prepared by: Jonryl P. Novicio 63

Fault Analysis