MURELLE GREEN PLANET I-HE 35 MF & E-HE35 MF CONDENSING BOILER AUS User, Service and Installation Instructions
MURELLE
GREEN PLANET
I-HE 35 MF & E-HE35 MF
CONDENSING BOILER
AUS
User, Service and Installation Instructions
CONTENTS
1.0 USERS INSTRUCTIONS . . . . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
2.0 USERS PRE-SERVICE CHECK LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 6
3.0 BOILER REGISTRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7
4.0 COMMISSIONING BOILER CHECK LIST
5.0 SERVICE RECORDS
6.0 INSTALLERS INSTUCTIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
page 8
page 9
page 12
FONDERIE SIME S.p.A. of Via Garbo 27 - Legnago (VR) - Italy declares that its hot water boilers, which bear the CEmark under Gas Directive 90/396/CEE and are fitted with a safety thermostat calibrated to a maximum of 110° C,are not subject to application of PED Directive 97/23/CEE as they meet the requirements of article 1 paragraph3.6 of the Directive.
All descriptions and illustrations provided in this manual have been carefully prepared but we reserve the right to make change
and improvements in our products that may affect the accuracy of the information contained in this manual.
This Warranty is granted to you by Hunt Heating ABN 50 354
796 935, in respect of your acquisition of a Sime Central
Heating Boiler within the Commonwealth of Australia. This
Warranty does not in any way affect your rights under any
Trade Practices Act, and is in addition to your implied legal
rights.
Provided that the installation of the boiler is in accordance
with the specifications provided to you or your licensed instal-
ler, the boiler is warranted by Hunt Heating against defects
caused by the manufacturer’s faulty materials and/or work-
manship, in respect to parts and labour, for a period of twelve
months commencing from the date of commissioning of the
boiler. or a maximum of 18 months from the date of delivery from Hunt Heating which ever is the earlier
The Licensed Installer must complete the information at the
in section 3.0 of this manual. Failure to do so may cause the
Warranty to beco me null and void.
SIME CENTRAL HEATING BOILERS - WARRANTY
This document issued 091201 - HE-35 1st December 2009
Page 2 of 40
IMPORTANT
When carrying out the commissioning of the boilers, it is highly recommended that you perform the following checks:
– Make sure that there are no flammable liquids and or materials in the immediate vicinity of the boiler.
– Make sure that the electrical connections have been made correctly and that the earth wire is connected to a good
earthing system.
– Open the gas tap and check the soundness of the connections, including that of the burner.
– Make sure that the boiler is set for operation for the type of gas supplied.
– Check that the flue for the outlet of the products of the combustion is unobstructed.
– Make sure that any shutoff valves are open.
– Make sure that the system is charged with water and is thoroughly vented.
1.0 USER INSTRUCTIONS
WARNINGS– In case of fault and/or incorrect equipment operation, deactivate it, without making any repairs or taking any direct
action. Apply only to qualified technical personnel.
– Boiler installation and any other assistance and/or maintenance activity must be carried out by qualified personnel
registered as a licenced gas technician. Under no circumstances, the devices sealed by the manufacturer can be
tampered with.
– It is absolutely prohibited to block the intake grilles and the aeration opening of the room where the equipment is
installed.
– The manufacturer shall not be held liable for any damage caused by improper use of the appliance.
LIGHTING AND OPERATION
BOILER IGNITION (fig. 24)
The first ignition of the boiler must be car-
ried out by qualified technical personnel.Successively, if it is necessary to start up
the boiler again, adhere strictly to the fol-lowing instructions: open the gas tap toallow the flow of the fuel.
Move the main switch of the system to
“ON”. When fuel is fed to the boiler, asequence of checks will be carried out andthe display shows the normal condition of
the functioning, always indicating the pres-sure of the system. If the blue luminous bar
is on, this indicates the presence of voltage.N.B.: To the first pressure the keys of thecontrols (2) the display is illuminated, to
the successive pressure the operation
modality is active.
WinterPress the key of the controls (pos. 2)
to activate the winter mode functioning(heating and D.H.W.). The display will be asshown in the figure.
Summer
Press the key of the controls (pos. 2) toactivate the summer mode functioning(only the production D.H.W.). The display will
be as shown in the figure.
APRE
2
Fig. 24
OPEN
Page 3 of 40
REGULATION OF THE WATER
TEMPERATURE FOR HEATING (fig. 25)
To set the temperature of the water forheating, press the key of the controls
(2).The first time the key is pressed, the SET of
heating circuit 1 is selected. The secondtime it is pressed, the SET of heating circuit2 is selected. The display will be as shown
in the figure.
Change the values with the key and
. Standard visualisation will return to the
display by pressing the key again, orafter 10 seconds if no key is pressed.
Regulation of the external sensor
If an external sensor is installed, the valueof the output temperature is automaticallychosen by the system, which quickly adjusts
the environmental temperature on thebasis of the external temperature.
If you wish to change the value of the tem-perature, increasing or decreasing that cal-culated automatically by the electronic
card, proceed as indicated in the preceding
paragraph. The level of various correctionof a value of temperature proportional cal-culated. The display will be as shown in fig.
26/a.
REGULATION OF THE D.H.W. TEMPERATURE (fig. 26)
To set the desired temperature D.H.W.,press the key of the controls (pos. 2).The display will be as shown in the figure.
Change the values with the key and
.The display will return to the standardvisualisation by pressing the key again,or after 10 seconds if no key is pressed.
TO SWITCH OFF THE BOILER (fig. 24)
In the case of a short absence, press thekey of the controls (pos. 2). The display
will be as shown in the fig. 24. In this way,leaving the electricity and the fuel supplyconnected, the boiler is protected from
fros t and f r om the pump becoming
blocked.If the boiler is not used for a prolongedperiod, it is advisable to disconnect the
electricity supply, by switching off the mainswitch of the system, and to close the gas
tap and, if low temperatures are expected,to completely empty the hydraulic circuitsto avoid pipes being broken by the forma-
tion of ice in the pipes.
2
Fig. 25
2
Fig. 26
Fig. 25/a
Page 4 of 40
ANOMALIES AND SOLUTIONS
When there is a functioning anomaly, thedisplay shows an alarm and the blue lumi-
nous bar becomes red.Descriptions of the anomalies with the rela-
tive alarms and solutions are given below:
– ALARM 02 (fig. 27/a)
If the water pressure detected is lower
than 0.5 bar, the boiler will stop and thedisplay will show “ALL 02”.Bring the pressure back to normal by
means of the charge system (C) until thepressure indicated by the transducer is
between 1 and 1.5 bars.
ON COMPLETION OF THE OPERATION,MAKE SURE THE LOAD VALVES IS CLO-
SED.
If it is necessary to repeat the systemloading procedure, it is advisable tocontact qualified technical personnel
to check the seal of the heating system(to check whether there are any leaks).
– ALL 03Request assistance from qualifiedtechnical personnel.
– ALL 04
Request assistance from qualified
technical personnel.
– ALL 05
Request assistance from qualifiedtechnical personnel.
– ALL 06 (fig. 27/c)Press the key on the controls (2) to
re-start the boiler.
If the anomaly persists, request assi-
stance from qualified technical personnel.
– ALL 07 (fig. 27/d)
Press the key of the controls (2) to
re-start the boiler.If the anomaly persists, request assi-
stance from qualified technical personnel.
– ALL 08Request assistance from qualifiedtechnical personnel.
– ALL 09
Request assistance from qualified
technical personnel.
– ALL 10
Request assistance from qualifiedtechnical personnel.
– ALL 13 (fig. 27/e)
Press the key of the controls (2) to
re-start the boiler.
If the anomaly persists, request assi-
stance from qualified technical personnel.
– ALL 14
Request assistance from qualified
technical personnel.
– ALL 15
Request assistance from qualifiedtechnical personnel.
– From “ALL 20” to “ALL 29”Request assistance from qualified
technical personnel.
GAS CONVERSION
If it is necessary to change to a differenttype of gas, request assistance only from
authorised technical personnel.
MAINTENANCE
2
Fig. 27/c
2
Fig. 27/a Fig. 27/d
2
Fig. 27/e
175
125
60
Please refer to the maintenance schedule in Section 5 of this manual.The boiler is supplied is supplied with an electrical supply cable. If this is damaged in any way it should be replaced only by a new cable from Hunt Heating and installed by a qualifies technician.
Page 5 of 40
1 General.
Has the system worked before? if it did why did it stop?
Check that the power, gas, valves or thermostat are turned ON
Does it work? - If NO go to Q2
2 Power
With power to the boiler. Are there indicator lights on or any error messages? If the indicator lights are on which ones? Check with boiler manual to understand what lights or error message mean and correct if
Does it work? - If NO go to Q3
3 Gas
Is the gas isolation valve on? At the boiler, at the meter. Do other gas appliances work?
Check the gas isolation valve is on at the boiler and at the meter. If OFF do not turn on unless safe to do so. Check why it was turned OFF. Do the other gas appliances work?
Does it work? - If NO go to Q4
4 Room Thermostat.
Is the display very dim or not showing at all? Is the room thermostat calling for heat? Turn it off, turn on, does it click and show the correct symbol?
If nothing happens – the batteries may need replacing, the room thermostat may be faulty. Bridging out the switch can be used to test this. Check voltage before re-moving cover.
Does it work? - If NO go to Q5
5 Boiler.
Does the boiler start to work and then shut down? Fan, Pump, Ignition. Is there an usual noise coming from the boiler? Is there water running from the pressure relief valve?
Try turning knob on the pressure relief valve and releasing it. If it is still faulty turn OFF IMMEDIATELY and call Hunt Heating or your service technician.
Does it work? - If NO go to Q6
6 Radiators.
Are some radiators hot and others cold?
Check that the radiator valves are turned on, that the thermostatic heads are operating correctly and the lockshield valves are open. Is the system balanced properly?Is the top of the radiator cold but the bottom hot – Bleed air from the radiator.
2.0 USER’S PRE-SERVICE CHECK LIST
Before calling for Hunt Heating Boiler Service please check the following. I’m Cold ! – The Heaters not Working.
FOR WARRANTY AND SERVICE: Ring: 1300 001800Please have Product Details, Serial Number and Installer Information Ready before ringing refer to next page
Page 6 of 40
3.0 BOILER REGISTRATION
IMPORTANT INFORMATION
Please read before Inst allation fill in and retain for future use.
LOG BO OK - Installation, C ommissioning an d S ervice.
1. Installation Details
Owner - name
Installation A ddress - Street
City PC State
Installation Ph one N umber
Contact and Ph one Nu mber
Sime Product - Model
Serial Nu mber
Gas T ype Natural G as ?LPG? Internal ? External ?
Gas p ressure
Settings Max Pa Adjusted output setting kW
Central Heating
Water tre atment
System Volume Litres
No
?
Yes
Yes?
? ? Product Q ty Used Litres
Dilution rate Litres per 100 litres
System FLUSHED before installation of boiler
The System pipes MUST BE FLUSHED before the connecting this boiler
New ?Existing
Installer Company
Company Address
City PC State
Installer Name PIC Licence No.
Commissioning completed Date;- / /20 _ _
Date;- / /20 _ _
by
toHand Ov er completed ?
?
Internal - I-HE 35 or External - E-HE 35refer to data plate
Page 7 of 40
4.0 COMMISSIONING BO ILER CH ECK LIST
IF IN DOU BT AS K
A s uggested me thod of co mmissioning th e bo iler, ac tual me thod ca n v ary ac cording to th e bo iler
make type and the installation. The boiler must always be installed and commissioned by an approved ,
gas te chnician. The i nstaller ce rtifies th at this Boiler has b een in stalled to ma nufacturer’s
instructions, has been filled, commissioned and is ready for use.
No. Description üwhen done
1. Read carefully th e in struction ma nuals s upplied wi th t his bo iler.
BEFORE INSTALLING T HIS B OILER FLUSH OUT THE PIPES UNTIL CLEAN WATER IS ACHIEVED.2
–
.3.
Turn on wa ter to fi ll s ystem, ch eck fo r le aks r egularly an d b leed a ir fr om al l points.
B leed the air fr om all th e p umps i n the system, and r otate th e im peller sh aft4
Check th at al l r adiators v alves ar e op en,remove th e thermostatic valve heads, fully openall lockshields
5
Turn ON g as, bl eed a ir ou t at th e i solation va lve u nion. Re seal an d ch eck fo r gas leaks.
Tu rn g as OF F.6
Turn e lectricity on at th e po wer po int. At th e bo iler fr ont pa nel se t th e temperature setting
to th e lo west s etting, s witch b oiler to ON po sition.The “Power on ” In dicator sh ould lig ht. Tu rn th e bo iler of f at th e fr ont pa nel.
7
Turn th e r oom th ermostat to th e ma nual O N po sition s et th e t emperature to a high level so that it does
no t s witch of f du ring th e co mmissioning ph ase. Th e thermostat will unusually click and show an
a n in dicator in th e wi ndow,
8
Switch th e bo iler ON a t th e bo iler fr ont pa nel co ntrol.9
Boiler sh ould s tart fa n, pu mp an d ig nite g as. If it fa ils fi rst f ew t imes th is m ay be just residual air
In th e gas line. A noisy water pump indicates there is air in the water pipes.10.
Boiler lights a nd heats the water. 11.
Check g as flame is th e co rrect co lour an d fo r gas an d wa ter le aks
as the system heats up .
12.Check th at h eat i s go ing t o a ll r adiators th rough th e m anual or th ermostatic firstand r eturn via the lo ckshield v alve. If no t S TOP fi x NO W and any leaks.
13
Allow th e bo iler to hea t u p to th e se t te mperature an d sw itch of f. Re-adjust the boiler temperature
14
to a mi d t emperature po int. CA UTION, If t his is connected to a floor heating system. The boiler
sh ould re li ght a nd in crease th e water temperature to the new setting.
15
Check th at a ll r adiators a re hot al l th e wa y u p. If t he r adiator is co ld at th e to p,
then th ere is u sually a ir in th e r adiator Bleed the radiator. Balance the system so that all.
16.
Set th e r oom th ermostat to th e co rrect t imes a nd t emperatures ac cording to the ma nufacture’s
On completion of the commissioning phase, complete the information sheet at the front of this manual.
Hand over the installation to the owner and demonstrate how the system works plus basic fault
resolution and safety procedures. Make sure that this important document is kept in a safe accessible
place.
Turn off all services to this boiler - water, gas and power. Install the boiler as shown in the
instructions following and connect all services.
radiators are hot as according to the radiator installation manual. Adjust the boiler water temperature.
instructions
Page 8 of 40
Handover Ins tructionswhen d one
1. Fill in al l th e de tails on t his Bo iler manua.l
2. Instruct th e o wner /u sers on th e co rrect op eration of th e h eating s ystem, th is
includes ho w t o tu rn th e sy stems o n a nd of f, ad just th e t ime an d t emperature
settings .
3. How t o tu rn th e h eating s ystem of f i n s ummer an d on fo r w inter.
4. Where al l th e ma jor it ems ar e, th eir fu nctions an d how t o ch eck an d tu rn th em on or
off. Simple fault resolution i.e. power on.
5. How t o ch eck an d r emove ai r in th e r adiators. Gi ve t hem a bl eed ke y.
6.. The im portance of th is SERVICE RECORDS, ke eping s afe & accessible when r equired.
7. Recommend th at th e bo iler sh ould be s erviced at / before th e st art of wi nter ne xt
year th en ev ery t wo ye ars.
5.0 SERVICE REC ORDSService – 1 – Year 1 Date
Service te chnician Name PIC Li cence No .
Service Co mpany
Contact ph one nu mber
Work Co mpleted
Notes
ü
Page 8 of 20
Page 9 of 20
4 of 7
Service – 2 – year 3 Date
Service te chnician Name PIC Licence No .
Service Co mpany
Contact ph one nu mber
Work Co mpleted
Service
Service
–
–
3
4
–
–
year 5
year 7
Date :
Date :
Service te chnician
Service te chnician
Name: PIC Licence No .
Name: PIC Licence No .
Service Co mpany
Service Co mpany
Contact ph one nu mber
Contact ph one nu mber
Work Co mpleted
Work Co mpleted
Notes
Notes
Notes
Page 9 of 20
Page 10 of 40
Service – 5 – year 9 Date
Service te chnician Name PIC Licence No .
Service Co mpany
Contact ph one nu mber
Work Co mpleted
Service
Service
–
–
7
8
–
–
year 11
year 13
Date :
Date :
Service te chnician
Service te chnician
Name: PIC Licence No .
Name: PIC Licence No .
Service Co mpany
Service Co mpany
Contact ph one nu mber
Contact ph one nu mber
Work Co mpleted
Work Co mpleted
Notes
Notes
Notes
Please contact Hunt Heating for more service sheets
Page 10 of 20
Page 11 of 40
6.0 INSTALLER INSTRUCTIONS
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 9
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 16
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Page 12 of 40
1.1 INTRODUCTION
MURELLE GREEN PLANET are premixed
gas condensation thermal modules that
employ a microprocessor-based technologyto control and manage all the functions.
All modules are compliant with European
Directives 90/396/CE, 2004/108/CE,2006/95/CE and 92/42/CE.
For optimum installation and operation,always follow the instructions provided in
this manual.
This boiler has multi-function capacity beingable to supply hot water for heating only,
hot water for DHW using a calorifier orboth functions.
1 DESCRIPTION OF THE BOILER
385135 = =
==
85 70 70
70 70350
60125
42,5
450
170
92,5760
15
ø 6
0/1
001
25
175
125
60
700
65
190
Fig. 1
KEYR Central Heating Return 3/4” BSP MIM Central Heating Flow 3/4” BSP MIG Gas connection 3/4” BSP MIR3 D.H.W. tank return 3/4” BSP MI - CappedM2 D.H.W. tank flow 3/4” BSP MI - CappedS3 Condensation outlet 25 mm diaC Cold water inlet 1/2” BSP MI
1.2 DIMENSIONS
1.2.1 MURELLE GREEN PLANET I-HE 35 MF - INTERNAL BOILER
NOTEDiagram shows optional plumbing connec-tions. Standard connections brass maleiron fittings.
Page 13 of 40
1.2.2 MURELLE GREEN PLANET E-HE 35 MF - EXTERNAL BOILER
110
760
R M G
C
R3 M2
70 70
70 70
215
117,5
15
90
385= =
125 18
5
175
G
G RMR3CM2347 224
135
185
125
43,5
500
917
194
S3
Fig. 1/a
NOTEDiagram shows optional plumbing connec-tions. Standard connections brass maleiron fittings.
KEYR Central Heating Return 3/4” BSP MIM Central Heating Flow 3/4” BSP MIG Gas connection 3/4” BSP MIR3 D.H.W. tank return 3/4” BSP MI - CappedM2 D.H.W. tank flow 3/4” BSP MI - CappedS3 Condensation outlet 25 mm diaC Cold water inlet 1/2” BSP MI
Apply gasket seal to rear of cabinetpart no. A6229825 - 515 x 4 x 15 supplied
Page 14 of 40
6
Model I-HE 35 MF & E-HE 35 MF
Heat output - Gas pressures available
Nominal (80-60°C) kW 34.1
Nominal (50-30°C) kW 37.2
Reduced (80-60°C) kW 8.8
Reduced (50-30°C) kW 9.6
Heat input
Nominal MJ/h 125.6
Reduced Nat/LPG 1 MJ/h 32.5
Losses after shutdown to 50°C (EN 483) W/h 95
Supply voltage V-Hz 240 /50
Adsorbed power consumption W 145
C.H. setting range °C 20/80
Water content boiler l 6.1
Maximum water head bar 3
Maximum temperature °C 85
Capacity of the heating expansion vessel l 10
Pressure of the heating expansion vessel bar 1
Exhaust fumes temperature at max flow rate (80-60°C) °C 70
Exhaust fumes temperature at min. flow rate (80-60°C) °C 65
Exhaust fumes temperature at max flow rate (50-30°C) °C 40
Exhaust fumes temperature at min. flow rate (50-30°C) °C 35
Smokes flow min/max kg/h 14/60
CO2at max/min flow rate G20 Natural gas % 9.0/9.0
CO2 at max/min flow rate G31 LP gas % 10.0/10.0
Weight when empty kg 68
Main burner nozzle
Quantity nozzles n° 1
G20/G31 Nat Gas / LP gas injector diameter ø 8.5 / 5.2
1.3 TECHNICAL FEATURES
Page 15 of 40
27
28
29
23
30
12
3
1
21
262524
19
1817
4
16
11
1096
20
7 8
1.4 FUNCTIONAL DIAGRAM - Schematic only
KEY1 Fan 3 Primary exchanger4 Gas valve6 Aqua Guard Filter System 7 C.H. sensor (SM)8 Safety thermostat 100°C9 Diverter valve
10 Circulator with air release vent11 Water flow meter12 D.H.W. sensor (SS/SB)16 3 BAR safety valve17 Pressure transducer18 By-pass19 Boiler discharge20 Expansion vessel21 Condensate drain tap23 D.H.W. cock (optional)
24 Gas cock (optional)25 C.H. flow cock (optional)26 C.H. return cock (optional)27 D.H.W. tank discharge cock (optional)28 D.H.W. expansion vessel (optional)29 7 BAR D.H.W. tank safety valve (optional)30 D.H.W. tank (optional)
R Central Heating Return 3/4” BSP MIM Central Heating Flow 3/4” BSP MIG Gas connection 3/4” BSP MIE DHW tank return 3/4” BSP MI - CappedU DHW tank flow 3/4” BSP MI - CappedS3 Condensation outlet 25 mm diaC Cold water inlet 1/2” BSP MI
Fig. 2
All items shown in the grey area are not part of the standard boiler package but is included to illustrate the optional DHW heating capacity of this boiler.
Page 16 of 40
1
23
45
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Fig. 3
1.5 MAIN COMPONENTS
KEY1 Control panel2 Aqua Guard Filter System3 Condensate drain tap4 Air pressure tap5 Ignition transformer6 Safety thermostat7 C.H. sensor (SM)8 Ignition electrode9 Primary exchanger
10 Sensor fumes11 Suction/discharge fitting12 Expansion vessel13 Detection electrode14 Fan15 Water flow meter16 Diverter valve17 Automatic vent18 Circulator19 Coupling protection- optional
Page 17 of 40
The boiler must be installed in a fixed loca-
tion and only by specialised and qualifiedfirms in compliance with all instructionscontained in this manual.
Furthermore, the installation must be inaccordance with current standards and
regulations.
2.1 INSTALLATION
– These boilers can be installed in all normaldomestic environments as a room sealed
multi function boiler.– These boilers can also be installed in par-
tially covered areas, as per EN 297, with a
maximum ambient temperature of 60°Cand a minimum ambient temperature of -5°C. It is generally advisable to install the
boilers below weathered roofs, on the bal-cony or in a protected niche, to protectthem from exposure to weathering agents
(rain, hail and snow). All boilers provide astandard antifreeze function.
2.1.1 Anti-freeze function
The boilers are equipped with anti-freezefunction which activates the pumps and theburner when the temperature of the water
contained inside the appliance drops tobelow 6°C.
The anti-freeze function is ensured, howe-
ver, only if:- the boiler is correctly connected to the
gas and electricity supply circuits;
- the boiler is constantly fed;- the boiler ignition is not blocked;- the essential components of the boiler
are all in working order.In these conditions the boiler is protected
against frost down to an environmental
temperature of -5°C.
ATTENTION: In the case of installation in a
place where the temperature drops below0°C, the connection pipes must be pro-tected.
2.2 COMPLEMENTARY
ACCESSORIES
To simplify connections to the hydraulic and
gas supplies, it is also possible to use thefollowing accessories:– Mounting plate, code 8101218
– Kit with bends, code 8075423– Kit with faucets, code 8091820
– Solar kit INSOL only for heating boilers,
code 8092235– Mixed area kit ZonaMIX, code 8092234– Ant i f r eeze heaters k i t -15° C, code
8089805.– Hydraulic connection kit boiler/tank unit
code 8091112.
For detailed information on the assembly of
fittings, see the instructions contained in
the box.
2.3 CONNECTING UP SYSTEM
To protect the heat system from damagingcorrosion, incrustation or deposits, before
installation it is extremely important toclean the system using suitable products
such as, for example, FERNOX. Complete
instructions are provided with the productsbut, for further information please contactthe Hunt Heating technical department.
For long-term protection agains corrosionand deposits, the use of inhibitors such asFernox is recommended after cleaning the
system. It is important to check the con-centrat ion of the inhibitor af ter each
system modification and during maintenan-
ce following the manufacturer’s publishedinstructions. The safety valve drain must beconnected to a collection funnel to collect
any discharge during interventions. If theheating system is on a higher floor than theboiler, install the on/off taps supplied in kit
op t iona l on t he heat ing sys temdelivery/return pipes.
WARNING: Failure to clean the heat
system or add an adequate inhibitor inva-lidates the appliance’s warranty.Gas connections must be made in accor-
dance with current standards and regula-tions. When dimensioning gas pipes fromthe meter to the module, both capacity
volume (consumption) in m 3 /h and gasdensity must be taken into account.
The sections of the piping making up the
system must be such as to guarantee asupply of gas sufficient to cover the maxi-mum demand, limiting pressure loss
between the gas meter and any apparatusbeing used to not greater than:
– 1.0 mbar for family II gases (natural gas);
– 2.0 mbar for family III gases (butane orpropane).
An adhesive data plate is sticked inside the
front panel; it contains all the technical dataidentifying the boiler and the type of gas for
which the boiler is arranged.
2.3.1 Connection of condensation
water trap
The drip board and its water trap must be
connected to a civil drain through a pipewith a slope of at least 5 mm per metre to
ensure drainage of condensation water.
The plastic pipes normally used for civildrains are the only type of pipe which isappropriate for conveying condensation
to the building’s sewer pipes.
2.3.2 Filter on the gas pipe
The gas valve is supplied ex factory with an
inlet filter, which, however, is not adequateto entrap all the impurities in the gas or ingas main pipes.
To prevent malfunctioning of the valve, or incertain cases even to cut out the safetydevice with which the valve is equipped,
install an adequate filter on the gas pipe.
2.4 SYSTEM FILLING
Filling of the boiler and the system is done
by the charge system (10 fig. 4). The char-ge pressure, with the system cold, must be
4 5 6
7 8
10
Fig. 4
2 INSTALLATION
KEY4 3 BAR safety valve5 Boiler discharge6 By-pass (blue)7 Water pressure transducer8 Diverter valve
10 System loading
NOTE: They are evidenced inblue/white the members forwhich are previewed the verifica-tion and the control.
Page 18 of 40
between 1 and 1.5 bar . Let off air acting on
the knob 21 fig. 4/a.
2.4.1 Boiler draining
To drain the boiler turn off the boiler and
use the discharge valve (5 fig. 4).
2.5 INSTALLATION OF
COAXIAL DUCT(ø 60/100 - ø 80/125)
The axial suction and discharge pipes are sup-plied in a special kit (that can be purchasedseparately) along with assembly instructions.
The diagrams of f ig. 6 il lustrate someexamples of dif ferent types of dischargemodal i t ies al lowed and the maximum
lengths that can be reached.
2.6 INSTALLATION OF SEPARATE DUCTS (ø 80 - ø 60)
The kit with dedicated pipes enables toseparate the exhaust fumes pipes from theair suction pipes (Fig. 7):
- The kit with dedicated ø 80 pipes, code.8089912, includes a SUCTION DIAPH-
RAGM THAT IS NOT used for t hese
models. To be able to use the air tap, cutits base with a tool (A) and assemble it
(B).
- The kits with dedicated ø 60 pipes, code8089913, include a suction collar thatreplaces the boiler collar (C).
It is now possible to insert an expansion or
bend in polypropylene without gaskets or
sealant.
The maximum overall length, resulting
from the sum of all the suction anddischarge pipes, is determined by theload losses of the single connected acces-
sories and should not exceed 33.5 PaATTENTION: The total length of each pipe
should not exceed 50M, even if the total
loss is below the maximum exceptableloss.
See Table 1for information on the load los-ses of single accessories.
2.6.1 Separate duct kits
The diagrams of Figure 9 show a few examplesof the permitted exhausts configurations.
C33
6
5
3
2
C43
3
4 2
x
y
x + y = L (m)
H (
m)
C13
12
1
L (m)
2
Fig. 6
LIST OF ø 60/100 ACCESSORIES
1 Coaxial duct kit code 80962502a Extension L. 1000 code 80961502b Extension L. 500 code 80961513 Vertical extension L. 140 with coupling code 80869504a Additional 90° curve code 80958504b Additional 45° curve code 80959505 Tile for joint code 80913006 Terminal for roof exit L. 1285 code 8091205
Model Length of pipe Length of pipe
ø 60/100 ø 80/125
L H L H
Min Max Min Max
I-HE 35 MF 4 m 1.3 m 6 m 8 m 1.2 m 11 m
LIST OF ø 80/125 ACCESSORIES
1 Coaxial duct kit code 80962532a Extension L. 1000 code 80961712b Extension L. 500 code 80961703 Adapter for ø 80/125 code 80931504a Additional 90° curve code 80958704b Additional 45° curve code 80959705 Tile for joint code 80913006 Terminal for roof exit L. 1285 code 8091205
21
APREOPEN
IMPORTANT:- The insertion of each additional 90° bend with a diameter of
60/100 reduces the available section by 1.5 meters.- The insertion of each additional 90° bend with a diameter of
80/125 reduces the available section by 2 meters.- Each additional 45° curve installed reduces the available
length by 1.0 metres.- During assembly it is important to make sure that the kit
with axial pipes. (1) is positioned horizontally.
NOTEBefore connecting accessories, it is always advisable to lubrica-te the internal part of the gaskets with silicon products. Avoidusing oils and greases.
Fig. 4/a
Page 19 of 40
277,567,5
169
148
112
134
CS
236
CA CA
119 22
2
ø 8
0ø
60
Fig. 7
KEYCA InletCS Outlet
OPERAZIONE DA ESEGUIRESOLO NEL MONTAGGIO DELKIT Ø 80 COD. 8089912
A
B
4
13
2
6
4
5
C
ASSEMBLY OF THE KIT ø 80 code 8089912/ø 60 code 8089913
KEY1 ø 125 Gasket2 Fumes exhausts
flange with tap3 Fa stening screw
4 ø 108 Gasket5 Suction collar (only for
kit code 8089913)6 MF ø 60 reduction (only
for kit code 8089913)
TABLE 1 - ACCESSORIES ø 80 / ø 60
80 dia duct 60 dia duct
Accessories item inlet - Pa outlet - Pa inlet - Pa outlet - Pa
Co-axial duct kit -- -- --
90 Elbow MF 3.0 4.0 25.0 5.0
45 Elbow MF 2.5 2.5 6.0 1.4
Extension L 1000 Horizontal 2.5 2.5 6.0 14.0
Extension L 1000 Vertical 2.5 2.5 6.0 8.0
Walk terminal 1.5 5.0 11.0 16.0
Wall co-axial exhaust
Roof outlet terminal 15.0 2.0 15.0 2.0
Example of allowable installation for a I-HE 35 MF. Calculations in that sum of the head losses of a single fitting less than 76 Pa
Inlet Outlet
Total head loss for flue extension
33.5 Pa
9 m horizontal pipe 80 dia x 2.5 Pa 7.5 Pa 7.5 Pa
2 off x 90 elbows 80 dia x 3.0 Pa 6.0 Pa 6.0 Pa
1 off Terminal 80 dia 1.5 Pa 5.0 Pa
OPERATIONS REQUIREDONLY FOR THE ASSEMBLYOF THE ø 80 KIT CODE8089912
Page 20 of 40
Fig. 9
LIST OF ø 80 ACCESSORIES
1 Coaxial duct kit code 80899122 Additional 90° MF curve code 8077450 (6 pz.)
3 a Extension L. 1000 code 8077351 (6 pz.)3 b Extension L. 500 code 8077350 (6 pz.)
4 Exhaust terminal, code 80895015 Kit with internal/external ring nuts, code 80915006 Suction terminal, code 80895007 Additional 45° MF curve code 8077451(6 pz.)9 Manifold, code 8091400
10 Tile for joint code 809130011 Terminal for roof exit L. 1381 code 809120412 --------13 Union suction/exhaust code 809140114 Coaxial exhaust ø 80/125 L. 885 code 8091210
NOTEBefore connecting accessories, it is alwaysadvisable to lubricate the internal part of thegaskets with silicon products. Avoid using oilsand greases.
LIST OF ø 60 ACCESSORIES
1 Coaxial duct kit code 80899132 a Additional 90° MF curve code code 80899212 b MF 90° bend with suction tap, code 8089924
3 Extension L. 1000 code 80899204 Exhaust terminal, code 80895415 Kit with internal/external ring nuts, code 80915106 Suction terminal, code 80895407 Additional 45° MF bend, code 80899229 Manifold, code 8091400
10 Tile for joint code 809130011 Terminal for roof exit L. 1381 code 809120412 ø 60 MF reduction, code 808992313 Union suction/exhaust code 809140114 Coaxial exhaust ø 80/125 L. 885 code 8091210
IMPORTANT:
In type C53 the outlet and
inlet flues must not come
out on opposite walls.
C53
11
10
1
3
6
3
11
10
3
3
62
3
max 0,5 m
max
0,5
m
C13
4
3
2
6
53
1
12
12
Page 21 of 40
2.7 POSITIONING THE
OUTLET TERMINALS
The outlet terminals for forced-draught
appliances may be located in the externalperimeter walls of the building.
To provide some indications of possible solu-
tions, Table 3 gives the minimum distances
to be observed, with reference to the typeof building shown in fig. 10.
2.8 ELECTRICAL CONNECTION
The boiler is supplied with an electric cable.
Should this require replacement, it must bepurchased exclusively from HUNT.
The electric power supply to the boiler mustbe 230V - 50Hz single-phase through afused main switch, with at least 3 mm spa-
cing between contacts.
Respect the L and N polarities and theearth connection.
NOTE: HUNT declines all responsibility for
injury or damage to persons, animals orthings, resulting from the failure to providefor proper earthing of the appliance.
Minimum clearances
(mm) Ref. Item
Natural
draft
Fan
assisted
Below eaves, balconies and other projections:
Appliances up to 50 MJ/h input 300 200
a
Appliances over 50 MJ/h input
500 300
500 300
500 300
c From a return wall or external corner
d From a gas meter (M) (see 4.7.11 for vent terminal location of regulator) 1000 1000
e From an electricity meter or fuse box (P) 500 500
150 75
500 500 g Horizontally from any building structure or obstruction facing a terminal
h From any other flue terminal , cowl, or combustion air intake 500 300
Horizontally from an openable window, door, non-mechanical air inlet, or an y other openin g into a building with the exception of sub-floor ventilation:
Appliances up to 150 MJ/h input 500 300
Appliances over 150 MJ/h input up to 200 MJ/h input 1500 300
Appliances over 200 MJ/h input up to 250 MJ/h input 1500 500
Appliances over 250 MJ/h input 1500 1500
1500 1000
j
All fan-assisted flue appliances, in the direction of discharge - 1500
k From a mechanical air inlet, including a spa blower
Vertically below an openable window, non-mechanical air inlet, or any other opening into a building with the exception of sub-floor ventilation:
Space heaters up to 50 MJ/h input 150 150
Other appliances up to 50 MJ/h input 500 500
Appliances over 50 MJ/h input and up to 150 MJ/h input 1000 1000
n
Appliances over 150 MJ/h input 1500 1500
Unless appliance is certified for closer installation
From the ground, above a balcony or other surface
†
†
f From a drain pipe or soil pipe
Door
M
P
g
See note 3
T
b
d
d
ee
See note 2
h
h
a
g
h
jjj
n
k
k
c
c
T
TI
f
Openablewindow
Shading indicates prohibitedar eas for f lue t er minal s
LEGEND:
T = Flue termin al
M = G as meterl = Mechanical air inlet P = Elec tr ic ity meter or fuse box
Notes1. All distances are to be measured to the nearest part of the
terminal.2. Prohibited area below electricity meter or fuse box extend to
ground level.3. See Clauses 5.13.6.6 for restrictions on a flue terminal under
a covered area.4. See Appendix J figures J2(a) for clearances from a flue
terminal to an LP gas cylinder. A flue terminal is considered to be a source of ignition.
5. For appliances not addressed above acceptances should be obtained from the technical regulator.
NOTEThe following information is an extract from AS 5601-2004. This information is subject to copyright of the AGA and Standards Australia and is supplied only as a reference. Every installer should have a copy and be familiar with this standard before installing this appliance.
MINIMUM CLEARANCES REQUIRED FOR BALANCED FLUE TERMINALS, FAN-ASSISTED FLUE TERMINALS, ROOM-SEALED APPLIANCE TERMINALS OR THE TERMINALS OF OUTDOOR APPLIANCES.
TABLE 3
Fig. 10
Page 22 of 40
2.8.6 Use with different electronic systems
Some examples are given below of boiler
systems combined with different electronicsystems.
Where necessary, the parameters to be
set in the boiler are given.
The electrical connections to the boiler
refer to the wording on the diagrams (fig.11).
Description of the letters indicating thecomponents shown on the system dia-
grams:
M System outputR System return
CR Remote control CR73SE External temperature sensor
TA Room thermostat
RM
SE
TA
CR
TA1
CRSE
2.8.1 Chronothermostat
connection
Connect the chronothermostat as indica-
ted in the boiler electrical diagram (see fig.11) after having removed the existing brid-
ge.
The chronothermostat to be used must beof a class conforming to the standard EN607301 (clean electrical contact).
2.8.2 Climatic regulator CR53
connection (optional)
The boiler is designed for connectio to a cli-
matic regulator, supplied on request (code8092227), for the management of a hea-ting circuit.
The electronic card will continue to manageinformation visualisation, the setting of thesanitary set and the heating of the second
circuit , and the boi ler parameters bymeans of the keys on the control panel.
For installation and use of the climatic regu-
lator, follow the instructions included in thepackaging.NOTE: Reset parameter 10 to 2 (PAR 10
= 2).
2.8.3 Remote control CR73
connection (optional)
The boiler is designed for connection to a
remote control unit (code 8092226).The remote control unit CR73 allows for
complete remote control of the boiler,
except release of the boiler. The boiler display will show the followingmessage:
For installation and use of the remote con-
trol, follow the instructions in the package.NOTE: Ensure PAR 10 set to 1 (PAR 10 =1).
2.8.4 External sensor connection
The boiler is designed for connection to anexternal temperature sensor, supplied on
request (code 8094101), which can auto-
matically regulate the temperature value of
the boiler output according to the externaltemperature. For installation, follow the instruction in the
package. It is possible to make correctionsto the values read by the drill acting on the
PAR 11.
2.8.5 D.H.W. sensor connection
The boiler is provided with a D.H.W. sensor(SB) linked to the connector Cn5. (not connected)
When the boiler is coupled to an externalboiling unit, introduce the sensor into thespecial sleeve in the boiling unit.
ATTENTION: The boiler is designed forconnection to a remote boiling unit, for
use FOR HEATING & DHW it is necessary:
- to connect the D.H.W. sensor (SB);
- set PAR 2 and 4.
Operations must be carried out by
authorised and qualified technicians.
1 BASIC SYSTEMSYSTEM WITH A DIRECT ZONE AND ROOM THERMOSTAT, OR WITH ACLIMATIC REGULATOR CR53 (Code 8092227) OR WITH REMOTE
CONTROL CR73 (Code 8092226) AND EXTERNAL SENSOR (Code8094101)
PARAMETERS SETTINGS
If using CR 53 set parameter10 to 2 (PAR 10 = 2)
Page 23 of 40
2.9 BOILER ELECTRICAL “I-HE 35 MF & E-HE 35 MF”
TPA(5 VDC)FL
(24 VRAC)
SF(5 VDC)
SM(5 VDC)
SE(5 VDC)
TS(24 VDC)
SB(5 VDC)
TA1(24 VRAC)
TA2(24 VRAC)
EXP (24 VRAC)
OP (24 VAC)
Fig. 11
KEYF1-2 Fuse (4 AT)TRA Ignition transformerPI PumpV FanEA Ignition electrodeER Detection electrodeEV1-2 Gas valve coilTS Safety thermostatSF Exhaust fumes probeTFU Thermal fuseVD Diverter valveSM Heating sensorFL Water flow switchVD Diverter valveTPA Pressure transducer
TA1 Zone 1 environment thermostatTA2 Zone 2 environment thermostatSB D.H.W. tank sensorCR Remote control CR 73 (optional)SE External sensor (optional)OP Internal time clock (optional)EXP Expansion cardAR Remote alarmVZ Zone valveAUX Auxiliary connection
NOTE: Boiler control can be by either240v to terminal 14 CN7 and removal ofthe link on terminals 7 & 8 on CN6.A permanent mains supply must bemaintained at all times.
CONNECTOR SPARE PART CODES:CN1 code 6316282CN2 code 6316285CN3 code 6316210CN4 code 6316203CN5 code 6316200CN6 code 6316202CN7 code 6316204CN9 code 6316274CN12 code 6316280CN13 code 6316282CN14 code 6316213
Page 24 of 40
3 CHARACTERISTICS
3.1 CONTROL PANEL
5
3
1
2
4
2 - DESCRIPTION OF CONTROLS
ON/OFF KEYSON = Electricity supply to boiler is onOFF = Electricity supply to boiler is on but nor ready for
functioning. However, the protection functionsare active.
SUMMER MODE KEYWhen this key is pressed, the boiler functions onlywhen D.H.W. is requested.
WINTER MODE KEYWhen this key is pressed, the boiler provides heatingand D.H.W.
D.H.W. TEMP KEYWhen this key is pressed, the temperature of theD.H.W. is shown on the display .
HEATING TEMP KEYThe first time the key is pressed, the temperature ofheating circuit 1 is shown.The second time the key is pressed, the temperatureof heating circuit 2 is shown.
RE-SET KEYThis allows for restoring functioning after a functioninganomaly.
INCREASE AND DECREASE KEYBy pressing this key the set value increases or decrea-ses.
3 - KEYS RESERVED FOR THE INSTALLER
(access to INST and OEM parameters)
4 - LUMINOUS BARBlue = FunctioningRed = Functioning anomaly
Fig. 12
PC CONNECTIONTo be used only with the HUNT programming kit and onlyby authorised personnel. Do not connect other electro-nic devices (cameras, telephones, mp3 players, etc.)Use a tool to remove the cap and reinsert after use.ATTENTION: Communication port sensitive to electrostatic charges.Before use, it is advisable to touch an earthed metallicsurface to discharge static electricity.
INFORMATION KEYThis key can be pressed several times to view the para-meters.
CHIMNEY SWEEP KEYThis key can be pressed several times to view the para-meters.
DECREASE KEYThis key changes the default settings.
INCREASE KEYThis key changes the default settings.
DESCRIPTION OF DISPLAY ICONS
SUMMER MODE ICON
WINTER MODE ICON
D.H.W. MODE ICON
HEATING MODE ICON1 = First circuit heating system2 = Second circuit heating system
GRADED POWER SCALEThe segments of the bar light up in proportion to boiler poweroutput .
BURNER FUNCTIONING AND BLOCK ICON
DESCRIPTION OF DISPLAY ICONS
CHIMNEY SWEEP ICON
SECONDARY DIGITSThe boiler visualises the value of the pressure of thesystem (correct value is between 1 and 1.5 bar)
MAIN DIGITSThe boiler visualises the values set, the stateof anomaly and the external temperature
INTEGRATIVE SOURCES ICON
Page 25 of 40
1. Visualizzazione temperatura esterna solo con sonda esterna collegata
2. Visualizzazione temperatura sonda riscaldamento (SM)
3. Visualizzazione temperatura sonda sanitario (SS) solo per caldaie istantanee
4. Visualizzazione temperatura sonda ausiliaria o sonda bollitore (SB)
6. Visualizzazione temperatura riscaldamento riferita al primo circuito
7. Visualizzazione temperatura riscaldamento riferita al secondo circuito
13. Visualizzazione codice errore penultima anomalia
14. Visualizzazione numero totale delle anomalie
9. Visualizzazione numero giri ventilatore in rpm x 100 (es. 4.800 e 1.850 rpm)
10. Visualizzazione ore di funzionamento del bruciatore in h x 100 (es. 14.000 e 10)
11. Visualizzazione numero di accensioni del bruciatore x 1.000 (es. 97.000 e 500)
12. Visualizzazione codice errore ultima anomalia
15. Contatore accessi parametri installatore (es. 140 accessi)
5. Visualizzazione temperatura sonda fumi
8. V isual izzazione corrente di ionizzazione in µA
16. Contatore accessi parametri OEM (es. 48 accessi)
1. Visualisation of external temperature,only with external sensor connected
2. Visualisation of heating temperature sensor (SM)
3. Visualisation of D.H.W. temperature sensor (SS)
4. Visualisation of auxiliary temperature sensor
6. Visualisation of heating temperature of first circuit
7. Visualisation of heating temperature of second circuit
8. Visualisation of ionisation current in µA
10. Visualisation of hours of functioning of the burner in h x 100 (e.g. 14000 and 10)
11. Visualisation of number of times the burner has ignited x 1000 (e.g. 97000 and 500)
12. Visualisation of error code of last anomaly
14. Visualisation of total number of anomalies
5. Visualisation of smoketemperature sensor
13. Visualisation of error code of penultimate anomaly
15. Parameter access counter– Installer(i.e. 140 accesses)
16. Parameter access counter–OEM (i.e.48 accesses)
9. Visualisation fan speed in rpm x 100 (e.g. 4.800 and 1850 rpm)
3.2 ACCESS TO INSTALLER'S INFORMATION
For access to information for the installer, press the key (3 fig. 14). Every time the key is pressed, the display moves to the next item of
information. If the key is not pressed, the system automatically quits the function. List of information:
Page 26 of 40
18
18. Visualizzazione valore sonda mandata impianto miscelato con schedino ZONA MIX 1 (ingresso S2)
17. Visualizzazione por tata sanitaria flussimetro (es. 18 l/min e 0,3 l/min) o stato f lussostato (rispettivamente ON e OFF)
19. Visualizzazione termostato sicurezza ZONA MIX (ingresso S1) rispettivamente ON e OFF
20. Visualizzazione pompa con schedino ZONA MIX 1 (rispettivamente ON e OFF)
21. Visualizzazione comando aper tura valvola con schedino ZONA MIX 1 (rispettivamente ON e OFF)
22. Visualizzazione comando chiusura valvola con schedino ZONA MIX 1 (rispettivamente ON e OFF)
23. Visualizzazione valore della sonda mandata impianto miscelato con schedino ZONA MIX 2
24. Visualizzazione termostato sicurezza con schedino ZONA MIX 2 (ingresso S1) rispettivamente ON e OFF
25. Visualizzazione pompa con schedino ZONA MIX 2 (rispettivamente ON e OFF)
26. Visualizzazione comando aper tura valvola con schedino ZONA MIX 2 (r ispettivamente ON e OFF)
27. Visualizzazione comando chiusura valvola con schedino ZONA MIX 2 (rispettivamente ON e OFF)
28. Visualizzazione valore temperatura sonda solare S1 con schedino solare INSOL
29. Visualizzazione valore temperatura sonda solare S2 con schedino solare INSOL
30. Visualizzazione valore temperatura sonda solare S3 con schedino solare INSOL
31. Visualizzazione relè solare R1 con schedino solare INSOL (rispettivamente ON e OFF)
32. Visualizzazione relè solare R2 con schedino solare INSOL (rispettivamente ON e OFF)
33. Visualizzazione relè solare R3 con schedino solare INSOL (rispettivamente ON e OFF)
17. Indication of D.H.W. flowmeter load (i.e. 18 l/min and 0.3 l/min) or flowswitch (respectively ON and OFF)
18. Indication of delivery probe value mixed with board Mixed Zone 1 (input S2)
19. Indicator of safety thermostat Mixed Zone (input S1) respectively ON and OFF
20. Indicator of pump with board Mixed Zone 1 (respectively ON and OFF)
21. Indicator of valve opening control with board Mixed Zone 1 (respectively ON and OFF)
22. Indication of valve closing control with board Mixed Zone 1 (respectively ON and OFF)
23. Indication of the delivery probe mixed with board Mixed Zone 2
24. Indicator of safety thermostat with board Mixed Zone 2 (input S1) respectively ON and OFF
25. Indicator of pump with board Mixed Zone 2 (respectively ON and OFF)
26. Indicator of valve opening control with board Mixed Zone 2 (respectively ON and OFF)
27. Indication of valve closing opening control with board Mixed Zone 2 (respectively ON and OFF)
28. Indication of solar probe temperature value S1 with solar board
29. Indication of solar probe temperature value S2 with solar board
30. Indiction of solar probe temperature value S3 with solar board
31. Indication of operation of solar relay R1 with solar board (respectively ON and OFF)
32. Indication of operation of solar relay R2 with solar board(respectively ON and OFF)
33. Indication of operation of solar relay R3 with solar card (respectively ON and OFF)
Page 27 of 40
3.3 ACCESS TO
INSTALLER'S PARAMETERS
For access to the installer's parameters,press simultaneously the keys and
or 5 seconds (3 fig. 12).
For example, the parameter PAR 23 isvisualised on the display of the controlpanel in the following way:
The paramet ers scrol l for wards andbackwards with the key and and
the default parameters can be changedwith the keys and .The standard visualisation returns automa-
tically after 60 seconds, or by pressing oneof the control keys (2 fig. 12).
3.3.1 Replacing the board or RESETTING parameters
If the electronic board is replaced or reset,it is necessary to configure PAR 1 and PAR
2 by associating the following values toeach type of boiler to be able to restart the
boiler:
PARAMETERS INSTALLER
FAST CONFIGURATION
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
1 Combustion configuration -- = ND = = “--”
1 ... 30
2 Hydraulic configuration -- = ND = = “--”
1 ... 6
1 = DHW + Recirc. pump
3 Timetable 2 programmer 2 = DHW = = 1
3 = Recirculation pump
4 Pressure transducer disabler 0 = Disabled = = 1
1 = Enabled
5 Assignment of auxiliary relay AUX 1 = Remote supply = = 1
(D.H.W. tank) 2 = Recirculation pump
6 Luminous bar indicating presence 0 = Disabled = = 1
of voltage 1 = Enabled
0 = Not assigned
7 Allocation of CR73 channels 1 = Circuit 1 = = 1
2 = Circuits 1 and 2
8 Fan rpm Step ignition 0,0 ... 81 rpmx100 0,1da 0,1a19,9 0,0
1da 20 a 81
9 Long chimneys 0 ... 20 % 1 0
1 = CR 73
10 Remote control option setting 2 = CR 53 = = 1
3 = RVS
11 Correction values external sensor -5 ... +5 °C 1 0
-- = Always
12 Backlighting duration 1 = Never sec. x 10 1 3
1 ... 199
0 = Minimum
13 Modulating pump speed 1 = Maximum = = 1
2 = Automatic
D.H.W. - HEATING
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING20 D.H.W. minimum temperature 10 °C ... PAR 21 °C 1 30
21 D.H.W. maximum temperature PAR 20 ... PAR 62 OEM °C 1 60
22 Anti-legionella (only D.H.W. tank) 0 = Disabled = = 0
1 = Enabled
23 Boiler antifreeze 0 ... +20 °C 1 3
24 External sensor antifreeze - 15 ... +5 °C 1 - 2
25 Climatic curve setting Zone 1 3 ... 40 = 1 20
26 Climatic curve setting Zone 2 3 ... 40 = 1 20
27 Minimum temperature Zone 1 PAR 64 OEM ... PAR 28 °C 1 20
28 Minimum temperature Zone 1 PAR 27 ... PAR 65 OEM °C 1 80
29 Minimum temperature Zone 2 PAR 64 OEM ... PAR 30 °C 1 20
30 Maximum temperature Zone 2 PAR 29 ... PAR 65 OEM °C 1 80
31 Maximum heating power 30 ... 100 % 1 100
32 C.H. pump over-run time 0 ... 199 Sec. 10 30
33 Pump activation delay Zone 1 0 ... 199 10 sec. 1 1
34 Re-ignition delay 0 ... 10 Min. 1 3
35 Integrative sources activation threshold -- , 15 ... 80 °C 1 “--”
36 D.H.W. pump over-run time 0 ... 199 Sec. 1 0
39 Saturation zone modulation -- = Enabled % 1 10
D.H.W. flowmeter 0 ... 100
GAS MODELS PAR 1
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- - 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
NAT. GAS (G20) I-HE 35/E-HE 35 24
LP GAS (G31) I-HE 35/E-HE 35 25
- 26
- 27
- - 28
- 29
- 30
Page 28 of 40
NOTE: the inside of the upper door of the
boiler panel has a label with the values
that have to be set for PAR 1 and PAR 2(fig. 19).
BOILER PAR 2
Instantaneous boiler with diverter 1
valve microswitch and flow switch
Instantaneous boiler with
diverter valve microswitch, 2
flow switch and solar combining
25/55 - 30/55 3
I-HE 35 MF / E-HE 35 MF 4
Instantaneous boiler with diverter 5
valve and flowmeter
Instantaneous boiler with diverter 6
valve, flowmeter and solar combining
PARAMETERS INSTALLER
EXPANSION CARD
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULT
MEASUREMENT UNIT SETTING
40 Number of expansion boards 0 ... 3 = 1 0
41 Mix valve stroke time 0 ... 199 10 sec. 1 12
42 Priority of D.H.W. over mixed zone 0 = Paralle = = 11 = Absolute
43 Floor drying 0 = No activated = = 0
1 = Curve A
2 = Curve B
3 = Curve A+B
44 Type of solar system 1 ... 7 = 1 1
45 ?t solar collector pump 1 PAR 74 OEM - 1... 50 °C 1 8
46 Solar integration delay “--”, 0 ... 199 Min. 1 0
47 Tmin solar collector “--”, -30 ... 0 °C 1 - 10
48 Tmax solar collector “--”, 80 ... 199 °C 1 120
PARAMETERS RESTORATION
PAR DESCRIPTION RANGE UNIT OF INC/DEC DEFAULTMEASUREMENT UNIT SETTING
49 * Reset default parameters -- , 1 = = =(par 01 - par 02 = “-“)
* Should the boiler not be operating correctly, the original default values can be reset by
setting PAR 49 = 1 and the PAR 1 and PAR 2 as specified at point 3.3.1.
Page 29 of 40
3.4 EXTERNAL SENSOR
If there is an external sensor, the hea-ting settings SET can be taken from the
climatic curves according to the exter-nal temperature and, in any case, limi-
ted to with the range values described
in point 3.3 (parameters PAR 25 forzone 1 and PAR 26 for zone 2).The climatic curve to be set can be
selected from a value of 3 and 40 (atstep 1). Increasing the steepness of the curves
of fig. 13 will increase the output tem-perature as the external temperature
decreases.
3.5 CARD FUNCTIONING
The electronic card has the following func-tions:
– Antifreeze protection of the heatingand D.H.W. circuits (ICE).
– Ignition and flame detection system.
– Control panel setting for the power andthe gas for boiler functioning.
– Anti-jamming for the pump which is fed
for a few seconds after 24 hours ofinactivity.
– Antifreeze protection for boilers with
D.H.W. storage tank.– Chimney sweep function which can be
activated from the control panel.
– Temperature which can be shifted withthe external sensor connected. It can be set from the control panel and
is active on the heating systems of bothcircuit 1 and circuit 2.
– Management of two independent hea-
ting circuit systems.– Automatic regulation of the ignition
power and maximum heating.
Adjustments are managed automati-cally by the electronic card to guaran-tee maximum flexibility in use of the
system.– Interface with the following electronic
systems: climatic regulator CR 53,
remote control CR 73, thermal regula-tor RVS, connected to a management
card of a ZoneMIX code 8092234 and
card solar INSOL code 8092235. NOTE: If using CR 53 or RVS set para-meter 10 to 2 (PAR 10 = 2).
3.6 TEMPERATURE
DETECTION SENSOR
Table 4 shows the resistance values of the
heating, DHW and exhaust fumes thermi-stors .
If the heating sensor (SM) is faulty or
open circuit, the boiler will not function oneither heating or D.H.W. (ALL 05).
If the exhaust fumes sensor (SF) is faultyor open circuit, the boiler will not function
on either heating or D.H.W. (ALL 14).
3.7 ELECTRONICIGNITION
Ignition and flame detection is controlled
by a single electrode on the burner whichguarantees reaction in the case of acci-dental extinction or lack of gas within one
second.
3.7.1 Functioning cycle
Burner ignition occurs within max. 10
seconds after the opening of the gasvalve. Ignition failure with consequent acti-vation of block can be due to:
– Lack of gas
The ignition electrode persists in
discharging for max. 10 seconds. If theburner does not ignite, the anomaly is
signalled.
This can happen the first time the boi-ler is switched on after a long period of
inactivity due to the presence of air in
the gas pipesIt can be caused by a closed gas tap orby a broken valve coil (the interruption
does not allow for opening).
– The electrode does not discharge.
In the boiler, only the opening of the gasto the burner can be detected. After10 seconds the anomaly is signalled. It
can be caused by an interruption in theelectrode wire or if it is incorrectlyanchored to the connection points. Or
the electrode may be earthed or stron-gly worn: it must be replaced.
Or the electronic card may be defecti-
ve.
– No flame detected
After start-up the electrode continuesto discharge even when the burner is
on. After 10 seconds, the discharge
stops, the burner is switched off and afault is generated.This fault is sometimes caused by the
shorting of the electrode cable or by itsimproper fixing to the connection
points. The electrode is connected to
the earth or badly worn and must bereplaced. The electronic board is faulty.
In the case of a sudden lack of voltage, theburner will immediately switch off. Whenvoltage returns, the boiler will automatically
start up again.
TABLE 4 (SM - SF sensors)
Temperature (°C) Resistance ( ? )
20 12.090
30 8.313
40 5.828
50 4.161
60 3.021
70 2.229
80 1.669
Fig. 13
ATTENTION: curves are calculated at an ambient temperature of 20°C. Theuser can alter the boiler controls to change the environment set for whichcurve has been calculated by ±5°C.
Page 30 of 40
3.8 WATER FLOW SWITCH
The water flow gauge (15 fig. 3) intervenes,blocking burner functioning, if it detects
that there is insufficient water circulating inthe primary circuit (< 450 l/h).
To res tore burner funct ioning, check
system pressure and the functioning of thepump and the flow switch, and the cleaningof the “Aqua Guard Filter System” filter.
N.B. on system boilers it is important
that if the flow switch assembly is chan-ged, it is fitted with the arrow pointing inthe correct direction.
3.9 HEAD AVAILABLE TO SYSTEM
Residual head for the heating system isshown as a function of rate of flow in the
graph in fig. 14.
The speed of the modulating pump is setas default (installation parameter PAR13=1 ).
To obtain the maximum head available tothe system, turn off the by-pass by turning
the union to the vertical position (fig. 15).
A
B
C
RIFERIMENTO POSIZIONE BY-PASS Fig. 15
Fig. 14
REFERENCE BY-PASS POSITION
KEYA By-pass inserted B BY-pass excluded
C Water pressure transducer
I-HE 35 MF & E-HE 35 MF
I-HE 35 MF & E-HE 35 MF
I-HE 35 MF & E-HE 35 MF
Page 31 of 40
4.1 GAS VALVE
The boiler is supplied as standard with a
gas valve, model SIT 848 SIGMA (Fig. 16).
4.2 GAS CONVERSION (fig. 17)
This operation must be performed byauthorised personnel using original HUNT
components.
To convert from natural gas to LPG or vice
versa, perform the following operations:
–Close the gas cock.
–Replace the nozzle (1) and the gasket (2) using those supplied in the conversion kit.
–Test all the gas connection using soapywater or special products.
Do not use open flames.
–Apply the nameplate with the new gasflow layout.
–Calibrate the maximum and minimum
pressures of the gas valve following the
instructions provided in paragraph 4.2.2.
4.2.1 New fuel configuration
For access to the installer's parameters,
press simultaneously keys and for5 seconds (3 fig. 12).
The parameters will scroll up and downwith the keys and .
The display pane will show the values of theparameter PAR 1. If the boiler is a I-HE 35 MF
& E-HE 35 MF methane (G20) model, SET 24
To change the fuel to propane (G31), it is
necessary to set SET 25, by pressing the
key .
The standard display will automaticallyreturn after 10 seconds. The table below shows the SET settings to
enter when the type of gas fuel is changed.
4.2.2 Calibrating the gas valve
pressures
Measure the CO 2 values with a combustion
analyzer.
Sequence of operations:
1) Press and hold the button down for a
few seconds .
2) Press the button for a few seconds .
3) Identify the CO 2 values at max. power by
adjusting the shutter (5 fig. 16):
4) Press the button for a few seconds .
5) Identify the CO 2 values at min. power by
adjusting the OFF-SET regulation screw
(6 fig. 16):
6) Press the buttons several times to
check the pressures and chan-
ge them if required.
7) Press the button once more to quit
the function.
4.4 DISASSEMBLING THE SHELL
To simplify maintenance operations on the
boiler, it is also possible to completely remo-
ve the shell, as shown in Figure 19.
Turn the control panel to move it forward
4 USE AND MAINTENANCE
MAX powerCO
22(Methane) CO (Propane)
9,0 ± 0,3 10,0 ±0,3
MIN powerCO2
2(Methane) CO (Propane)
9,0 ±0,3 10,0 ± 0,3
Fig. 16
KEY1 Upstream pressure intake2 Intermediate pressure intake3 Air signal inlet (VENT)4 Downstream pressure intake5 Capacity step6 OFF-SET
1
2
3
4 5
6
2
1
Fig. 17
GAS MODELS PAR 1
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- 11
- - 12
- 13
- 14
- 15
- 16
- 17
- 18
- 19
- 20
- 21
- 22
- 23
NAT. GAS (G20) I-HE 35/E-HE 35 24
LP GAS (G31) I-HE 35/E-HE 35 25
- 26
- 27
- - 28
- 29
- 30Page 32 of 40
24
and be able to access the internal compo-
nents of the boiler.
4.5 MAINTENANCE
To guarantee functioning and efficiency of
the appliance, in respect of the legal provi-
sions in force, it must be regularly checked;
the frequency of the checks depends onthe type of appliance and the installationand usage conditions (refer to the mainte-
nance schedual).In any case, it should be inspected at least
once a year by a qualified technician.
During maintenance operations, it is
important to verify that the drip-plate
with drain trap contains water (thischeck is particularly important if thegenerator has not been used for exten-
ded periods of time).
If necessary, the drip plate can be filled
using the tap provided (fig. 20).
Fig. 19
ATTENTIONBefore removing or refitting the frontpanel of the boiler, open the smallupper plastic door.
Code 8106380Model MURELLE GREEN PLANET I-HE 35 MFSerial n. 9999999999
PAR 1 = 24 (NG) / 25 (LPG)PAR 2 = 4
Page 33 of 40
4.5.1 Chimney sweep function (fig. 21)
To check boiler combustion, press the
installer's key for a few seconds. Thechimney sweep function will switch on andwill continue for 15 minutes.
From that moment, the boiler will star t
working in heating mode at maximumpower, with cut off at 80°C and re-ignition
at 70°C (ATTENTION! Temperature may
reach excessive values when using unpro-tected low temperature plants. Beforeactivating the chimney sweep function
make sure that the radiator valves oreventual zone valves are open) .
The test can also be carried out with the
boiler working in sanitary water mode. For this, after activating the chimney sweep
function, open one or more hot water taps.
Under these conditions, the boiler will func-tion at maximum power with the D.H.W. cir-cuit kept at between 60°C and 50°C.
During the test, the hot water taps mustremain open.
If the key and are pressed during
the 15 minutes of the chimney sweep func-tion, the boiler will be brought respectively
to maximum and minimum power.
The chimney sweep function will automa-tically switch off after 15 minutes orwhen the key is pressed again.
4.5.2 Cleaning the filter “Aqua Guard
Filter System” (fig. 22)
To clean the filter, close the delivery/return
on/off taps, turn off the power to the con-trol panel, remove the casing and empty theboiler using the drain provided.
Place a container for collection underneaththe filter, unscrew the cap and proceed to
clean the filter, removing impurities and
limestone deposits. Check the seal o-ring before reassembling
the cap with the filter.
Fig. 20
Fig. 22
Fig. 21
CONDENSATE TRAP
CONTROL PANEL
WATER FILTER
Page 34 of 40
Fig. 23/a
50
45
40
35
30
20
5 10 15 18 [Tag ]0
25
55
A B
1 15 7
X
A + B
1 25
[TVw]
Fig. 22/a
TVw Flow temperature setpointTag Period in daysx Start dayA Functional heatingB Floor curing heating
2
17
5
12
56
0
Page 35 of 40
– HIGH WATER PRESSURE
ANOMALY ALARM 03 (fig. 23/b)If the pressure detected by the transdu-cer is more than 2.8 bar, the boiler
stops and the display shows anomaly“ALL 03"
– D.H.W. SENSOR ANOMALY
ALARM 04 (fig. 23/c)If the D.H.W. sensor (SS) is open or
short circuited, the boiler will function
but wil l not modulate the power forD.H.W. The display will show the alarm“ALL 04”.
– HEATING SENSOR ANOMALY
ALARM 05 (fig. 23/d)
If the heating sensor (SM) is open orshort circuited, the boiler will not func-tion and the display will show the alarm
“ALL 05”.
– FLAME BLOCK ALARM 06 (fig. 23/e)If the flame control has not detected the
presence of the flame after a completeignition sequence, or for any other rea-son the card cannot “see” the flame, the
boiler will stop and the display will showthe alarm “ALL 06”.
Press the key of the controls (2)
to start up the boiler again.
– SAFETY THERMOSTAT
ANOMALY ALARM 07(fig. 23/f)If the connection with the safety thermo-stat is interrupted, the boiler will stop;
the flame control will remain waiting tobe switched off for one minute, keeping
the system pump on for that period.
If, the thermostat connection is restoredwithin the minute, the boiler will start upworking normally again, otherwise it will
stop and the display will show the alarm“ALL 07”.Press the key of the controls (2) to
start up the boiler again.
Fig. 23/b
Fig. 23/c
Fig. 23/d
Fig. 23/e
Fig. 23/f
2
2
Page 36 of 40
– FLAME DETECTION
ERROR 08 (fig. 23/g)If the flame control detects aflame whenone should not be detected, the boiler
will stop and display “ALL 08”.
– SYSTEM WATER CIRCULATION ERROR 09 (fig. 23/h)If the system flow switch detects inade-
quate circulation, the boiler will stop andthe display will show “ALL 09”. If the
error persists for more than 1 minute,
the boiler will stop and wait for 6 minu-tes. The boi ler wi l l then attempt torestart. Possible causes of this error
are faulty or jammed pump, blockedAqua Guard filter, closed flow or returnvalve, blocked heating system.
– AUXILIARY SENSOR ANOMALY ERROR 10 (fig. 23/i)
BOILER WITH ACCUMULATION: anomalyof the D.H.W. sensor. When the D:H.W.sensor is open or short circuited, the
display will show anomaly “ALL 10”. Theboiler will function but will not modulate
power for the D.H.W.
BOILER ONLY FOR HEATING: antifreezesensor anomaly for boilers which fore-see the use of antifreeze sensors.
When the sensor is open or short circui-ted, the boiler loses part of its anti-freezefunctions and the display will show ano-
maly “ALL 10".
BOILER COMBINED WITH SUN-PANEL
SYSTEM: anomaly of the D.H.W. inputsensor. When the sensor is open orshort circuited, the boiler loses the sun-
panel function and the display will showanomaly “ALL 10".
– ACTIVATION OF THE EXHAUST FUMESSENSOR ERROR 13 (fig. 23/l)The activation of this probe causes the
boiler to stop and error message “ALL13” to display.Press the key of the controls (2)
to start up the boiler again.
– EXHAUST FUMES SENSORERROR 14 (fig. 23/m)If the exhaust fumes sensor is open or
short circuit, the boiler will stop anddisplay “ALL 14”.
– FAN ERROR 15 (fig. 23/n)
If the fan speed is not within the ratedspeed range,the display will show “ALL15”. If the problem persists for more
than two minutes the boiler will stopthirty minutes, after which it will attempt
to resume operating.
– SAFETY THERMOSTAT INTERVENTIONFIRST MIXED ZONE “ALL 20” (fig. 23/p)
When the mixed zone board is connec-
ted to the boiler, a safety thermostat
intervention switches the mixed zone
pump, the mixed zone valve closes and
the display indicates error ALL 20.During this this error the boiler functionsnormally
– DELIVERY PROBE FAILURE FIRST
MIXED ZONE “ALL 21” (fig. 23/q)
When the mixed zone board is connec-
ted to the boiler. If the delivery probebecomes open or shor t c i r cui t the
display will indicate ALL21. During this
error the boiler continues to functionnormally.
– SAFETY THERMOSTAT INTERVENTIONSECOND MIXED ZONE “ALL 22” (fig. 23/r)
When the mixed zone board is connec-ted to the boiler. An intervention of thesafety thermostat switches the mixed
zone pump , the mixed zone valve closesand the display indicates ALL 22.During this error the boiler functions
normally.
– DELIVERY PROBE BREAKDOWN ANO-MALY SECOND MIXED ZONE “ALL 23” (fig. 23/s)
When the mixed zone board is connec-ted to the boiler. If the delivery probe is
open or short circuited the display indi-
cates error ALL 23. During this errorFig. 23/i
Fig. 23/g
Fig. 23/h
Fig. 23/l
Fig. 23/n
Fig. 23/m
Fig. 23/p
Fig. 23/q
Fig. 23/r
Page 37 of 40
the boiler functions normally.
– SOLAR S1 COLLECTOR PROBE FAILU-
RE “ALL 24” (fig. 23/t)
When the solar board is connected tothe boiler. If the S1 solar collector probebecomes open or shor t c i r cui t the
display indicates ALL 24. During thiserror the boiler functions normally.
– SOLAR S2 BOILER PROBE FAILURE“ALL 25” (fig. 23/u)When the solar board is connected to
the boiler. If the S2 solar collector probebecomes open or shor t c i r cui t thedisplay indicates ALL 25. During this
error the boiler functions normally.
– S3 SOLAR PROBE FAILURE “ALL 26”
(fig. 23/v)When the solar board is connected tothe boiler. If the S3 solar collector probe
becomes open or shor t c i r cui t thedisplay indicates ALL 26. During this
error the boiler functions normally.
– SOLAR APPLICATION CONFIGURATION
“ALL 27” (fig. 23/w)When the solar board is connected tothe boiler. If the hydraulic configuration of
the boiler is incorrect (PAR2), the displayindicates error ALL 27. During this error
the boiler continues to function normally,
and only the antifreeze function on thesolar board is active.
– NUMBER OF CONNECTED BOARDSERROR “ALL 29” (fig. 23/y)
When the number of connected boards
does not correspond to the number ofboards set in the PCB (PAR 40) or thereis a failure of communication with it, on
the display the indicates ALL 29. Duringthis error, the boiler continues to func-tion normally.
ATTENTION: If the display visualizes “ALL01” the anomaly can be caused by anelectric problem (main PCB or wiring).
Fig. 23/s
Fig. 23/t
Fig. 23/u
Fig. 23/v
Fig. 23/w
Fig. 23/y
Page 38 of 40
Page 39 of 40
MU
RE
LLE
I-H
E 3
5 M
F &
E-H
E 3
5 M
F C
ON
DE
NS
ING
BO
ILE
RS
- v
ersi
on 1
Issu
ed D
ecem
ber
2009
HYDRONIC SYSTEMS (Australia) Pty. Ltd.
11 Fiveways Boulevard, Keysborough, Victoria 3173
Telephone 1300 00 1800
Facsimile 9798 5133
www.huntheat.com.au
HUNT HEATING