Top Banner
PTCC Protection Features
66

04 ptcc protection feautres

Jul 15, 2015

Download

Documents

duytn1
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: 04 ptcc protection feautres

PTCC Protection Features

Page 2: 04 ptcc protection feautres

Overview

The purpose of this presentation is to explain the operation of the various protection features used with the PTCC.

The following topics will be covered:

Sequence Control Live Load Blocking Dead Lockout High Current Lockout Inrush Restraint Cold Load Pickup Single Shot Work Tag

Page 3: 04 ptcc protection feautres

Objectives

At the end of this training session, you should be able to:

Understand how protection and reclosing operations can be modified by the use of the various protection features that are available on the PTCC.

Page 4: 04 ptcc protection feautres

Sequence Control

Where more than one recloser is installed on a feeder, the upstream device must always be coordinated with the downstream device for faults seen by both.

They can become uncoordinated if the fault is still present when the downstream device trips and recloses.

In this case the downstream device will begin timing to trip according to its Trip 2 settings and if the upstream device has also detected the fault it will calculate the time to trip according to its Trip 1 settings.

For a given fault, the upstream device’s Trip 1 time might be shorter than the downstream device’s Trip 2 time.

This could cause an unnecessary loss of supply to the load connected between the two devices.

Page 5: 04 ptcc protection feautres

Sequence Control OFF

PickupPickupPickup

Active Settings = Trip 1 Active Settings = Trip 1Active Settings = Trip 2

Auto ReclosePickup

Auto Reclose ON Auto Reclose ON

F - S - S - F F - S - S - FF - S - S - F

Page 6: 04 ptcc protection feautres

Sequence Control ON

PickupPickupPickup

Active Settings = Trip 1 Active Settings = Trip 1Active Settings = Trip 2

Auto ReclosePickup

Active Settings = Trip 2

Auto Reclose ON Auto Reclose ON

F - S - S - F F - S - S - FF - S - S - FF - S - S - F

Page 7: 04 ptcc protection feautres

Sequence Control Setting on the Control Panel

Page 8: 04 ptcc protection feautres

PTCC Control Panel Navigation

System Status

Event Log

Measurement

Protection

Page 9: 04 ptcc protection feautres

Protection Menu Navigation

6x Earth Protection Settings

6x NPS Protection Settings

3x Global Protection Settings

2x Protection Features Settings

2x Frequency Protection Settings

6x Phase Protection Settings

Page 10: 04 ptcc protection feautres

Sequence Control setting in WSOS

Page 11: 04 ptcc protection feautres

Live Load Blocking

Page 12: 04 ptcc protection feautres

Live Load Blocking

With Live Load Blocking ON, all close requests will be disregarded if any load side terminal is live.

Load 1Source 2

Page 13: 04 ptcc protection feautres

Determining Live and Load Status in WSOS

Page 14: 04 ptcc protection feautres

Live If and Power Flow settings on the Panel

Page 15: 04 ptcc protection feautres

System Status Menu Navigation

1x Trip Flags

2x Operator and System Settings

8x Switchgear Status and Settings

3x Options

1x Quick Key Selection

1x WSOS Port P8 Communications

1x IOEX Status

13x Communications Setup

Page 16: 04 ptcc protection feautres

Dead Lockout

Page 17: 04 ptcc protection feautres

Dead Lockout

When Dead Lockout is ON, the recloser will not automatically reclose unless one or more of the source side or load side terminals are live.

If all the terminals are dead following a protection trip, the controller will go to lockout.

Dead Lockout

Page 18: 04 ptcc protection feautres

Dead Lockout in WSOS

Page 19: 04 ptcc protection feautres

Dead Lockout On/Off on the Operator Panel

Page 20: 04 ptcc protection feautres

Dead Lockout Summary

Dead Lockout only applies when Auto Reclose is ON.

The controller checks for Source side voltages and load side voltages if they are available immediately prior to the scheduled Auto Reclose event.

Unless at least one of the source or load bushings is live, Auto Reclose is aborted and the recloser goes to lockout.

Dead Lockout cannot be turned ON if the source side voltages are unavailable.

Therefore, a U Series recloser without voltage sensing on the x side cannot use Dead Lockout if the x side is the designated source.

Page 21: 04 ptcc protection feautres

Dead Lockout Events

When Dead Lockout occurs, a Dead Lockout event is logged as well as the usual Lockout event.

Page 22: 04 ptcc protection feautres

High Current Lockout

Page 23: 04 ptcc protection feautres

High Current Lockout

This feature can be used to prevent the recloser from closing onto a large or persistent fault.

Page 24: 04 ptcc protection feautres

High Current Lockout Settings

High Current Lockout operates according to two settings:

Lockout Current

Active Trip No.

Page 25: 04 ptcc protection feautres

High Current Lockout Operation

Auto Reclose ON

High Current Lockout ON

• Lockout current = 500A

• Active Trip = Trip 1

300 A550 A

High Current Lockout

Page 26: 04 ptcc protection feautres

High Current Lockout Summary

Normal Protection Trip occurs with High Current Lockout and Auto Reclose ON.

The controller checks if: The max current measurement for

the most recent protection trip, exceeds the HCL current setting.

The trip number of the most recent protection trip is equal to or greater than the HCL active trip number.

If both of the above conditions are true, the recloser records that the high current setting was exceeded and goes to lockout.

Page 27: 04 ptcc protection feautres

Protection Menu Navigation

6x Earth Protection Settings

6x NPS Protection Settings

3x Global Protection Settings

2x Protection Features Settings

2x Frequency Protection Settings

6x Phase Protection Settings

Page 28: 04 ptcc protection feautres

High Current Lockout setting on the Panel

Page 29: 04 ptcc protection feautres

High Current Lockout setting in WSOS

Page 30: 04 ptcc protection feautres

High Current Lockout and Single Shot

High Current Lockout can occur when Single Shot Mode is active or when closing onto a fault by an operator.

In both of these situations the controller would have gone to lockout anyway without High Current Lockout being triggered.

The difference is that, if High Current Lockout was triggered, an event will be recorded in the Event Log as extra information for fault analysis.

Page 31: 04 ptcc protection feautres

Inrush Restraint

Inrush Restraint works by raising the phase and earth Threshold Currents for a short period of time to allow the inrush current to subside.

Inrush Restraint is armed for operation whenever the load current goes to zero.

When the load at a later time becomes non-zero the Inrush Restraint is activated and the Inrush Multiplier is used in place of the Threshold Current Multiplier for the set time.

Page 32: 04 ptcc protection feautres

Inrush Restraint

Page 33: 04 ptcc protection feautres

Inrush Restraint Operation

Time (s)

0.00

Current

100 A

200 A

300 A

0.10 0.20 0.30 0.40 0.50 0.60 0.70

Trip Setting

Measured Current

At this point, current goes from zero to non-zero.

IR Time = 200ms IR Multiplier = 2

Page 34: 04 ptcc protection feautres

Inrush Restraint Effect on Protection Curve

220A 400A 220A

0.00 Current zero

Time(s) Event

1.00 Current non zero1.10 IR timer expired

Inrush Restraint Settings:

IR Time

IR Multiplier

Protection Settings:

Phase Trip = 200A Threshold Multiplier = 1.1

100ms

X 2

Page 35: 04 ptcc protection feautres

Inrush Restraint – Points to Remember

Inrush Restraint affects phase and earth protection, but does not apply to Definite Time or SEF.

If normal currents are expected to drop below 2.5A, then Inrush cannot be used. In this case Inrush Restraint should be turned off.

Page 36: 04 ptcc protection feautres

Inrush Restraint Settings in WSOS

Page 37: 04 ptcc protection feautres

Protection Menu Navigation

6x Earth Protection Settings

6x NPS Protection Settings

3x Global Protection Settings

2x Protection Features Settings

2x Frequency Protection Settings

6x Phase Protection Settings

Page 38: 04 ptcc protection feautres

Inrush Restraint Settings on Operator Panel

Page 39: 04 ptcc protection feautres

Cold Load Pickup

Page 40: 04 ptcc protection feautres

Cold Load Pickup

When a typical load has been without supply for a period of time (hours) it loses its diversity.

When power is restored the load is higher than usual because all the heater, refrigeration or air conditioner thermostats have turned on.

The longer the period without supply the greater the loss of diversity and the higher the load current will be when supply is restored.

Page 41: 04 ptcc protection feautres

Cold Load Pickup vs Inrush Restraint

Time Inrush Restraint normally operates over 100 – 200ms. Cold Load operates over a number of hours.

Multiple Inrush Restraint applies a set multiple for a set time. Cold Load applies a multiple which changes over time.

Page 42: 04 ptcc protection feautres

1 + Operational Cold Load Time x (User Set Cold Load Multiplier –1)User Set Cold Load Time

Operational Cold Load Multiplier =

Operational Cold Load Time

Time (min)

Current

100 A

200 A

300 A

30 60 90 120 150 180 210

Trip Setting 100A

Load Current 50A

Page 43: 04 ptcc protection feautres

Operational Cold Load Status

Time (min)

Current

100 A

200 A

300 A

60 120 180 240 300 360 420

1 2 3

390

4

Page 44: 04 ptcc protection feautres

Load Off

Cold Load Pickup Effect on Protection Curve

220A 240A 260A 280A 300A 320A 340A 360A 380A 400A 220A

Protection Settings:

Phase Trip = 200A Threshold Multiplier = 1.1

Load OnElapsed Time

10 min20 min30 min40 min50 min60 min70 min80 min90 min

Cold Load Pickup Settings:

CLP Time

CLP Multiplier

90 min

x 2

Page 45: 04 ptcc protection feautres

Cold Load Settings in WSOS

Page 46: 04 ptcc protection feautres

Cold Load Pickup – Points to Remember

The user-set Cold Load Time and Cold Load Multiplier are set on the Protection Settings 5 screen.

On power up, the load is assumed to be diverse, i.e. the Operational Cold Load Time is zeroed and ‘Cold Load IDLE’ will be displayed.

Cold Load affects phase and earth protection thresholds including instantaneous but not SEF.

High Current Lockout and Definite Time settings are not affected.

Cold Load Pickup cannot be used if normal currents are expected to drop below 2.5A, and should be turned off.

When Cold Load protection is turned on the multiplier used for Inrush will always be the higher of the Inrush Multiplier and the Cold Load Multiplier.

Page 47: 04 ptcc protection feautres

Single Shot Mode

Page 48: 04 ptcc protection feautres

Single Shot Mode

Single Shot Mode is used to provide an appropriate protection curve when non-reclosing operation is required, for example, when closing onto a fault.

Page 49: 04 ptcc protection feautres

Single Shot Operation

In Single Shot Mode the controller goes directly to lockout after one trip and will not Auto-Reclose.

Single Shot Mode is activated when:

Auto-Reclose is turned off and Work Tag is not applied. The circuit breaker is closed by operator command

irrespective of the state of Auto-Reclose.

Single Shot is de-activated when:

Auto-Reclose is turned back on. Work Tag is not active, and the Single Shot Timer expires

without a protection pickup ocurring.

Page 50: 04 ptcc protection feautres

Single Shot Timer

This timer starts when the switchgear closes and runs for the preset number of seconds.

This may be disabled by setting the Single Shot reset time to zero.

When set to zero, auto-reclosing will always be enabled while Auto Reclose is ON.

Page 51: 04 ptcc protection feautres

Single Shot Timer Indication

Page 52: 04 ptcc protection feautres

Single Shot Timer initiated by Operator Close

Operator Close

SS Timer

CB Status

t

Single Shot Timer Expires

OPEN CLOSED

Single Shot Timer Setting

Single Shot Mode

Page 53: 04 ptcc protection feautres

Protection Pickup during Single Shot Timing

CB Status

Pickup

t

SS Timer

Operator Close

OPEN OPEN

Protection Pickup

Single Shot

Protection Trip

CLOSED

Time to Trip

Single Shot Timer Setting

Single Shot Mode

Page 54: 04 ptcc protection feautres

Protection Reset during Single Shot Timing

CB Status

Pickup

t

SS Timer

Operator Close

OPEN

Protection Pickup

CLOSED

Single Shot Timer Setting

Protection Reset

Single Shot Mode

Single Shot Timer Expires

Page 55: 04 ptcc protection feautres

Single Shot Settings in WSOS

Page 56: 04 ptcc protection feautres

Protection Menu Navigation

6x Earth Protection Settings

6x NPS Protection Settings

3x Global Protection Settings

2x Protection Features Settings

2x Frequency Protection Settings

6x Phase Protection Settings

Page 57: 04 ptcc protection feautres

Single Shot Protection Settings

Phase

Earth

NPS

Page 58: 04 ptcc protection feautres

Work Tag

Page 59: 04 ptcc protection feautres

Work Tag

Applying the Work Tag ensures that closing cannot take place at all, either by a local operator, a remote operator or automatically.

Page 60: 04 ptcc protection feautres

Protection Operation with Work Tag Applied

The switchgear cannot close while the Work Tag is applied but Work Tag can be applied when the switchgear is closed.

If a protection trip occurs while the Work Tag is applied, the switchgear will always go to lockout even if Auto Reclose is ON.

The protection pickup and time to trip will be determined by the Work Tag protection settings and Work Tag Trip will be recorded in the Event Log.

Page 61: 04 ptcc protection feautres

Selecting Work Tag ON in WSOS

Page 62: 04 ptcc protection feautres

Applying the Work Tag on the Operator Panel

Page 63: 04 ptcc protection feautres

Work Tag Settings in WSOS

Page 64: 04 ptcc protection feautres

Work Tag Protection Settings

Phase

Earth

NPS

Page 65: 04 ptcc protection feautres

Work Tags and Controller Mode

The controller is always in either Local or Remote mode.

Only a local operator can apply/remove the Work Tag when the controller is in Local Mode and only a remote operator can apply/remove the Work Tag when the controller is in Remote Mode.

This means that a local operator can remove the Work Tag applied by a remote operator but they must first put the controller into Local mode.

Page 66: 04 ptcc protection feautres

Questions

In which Operator Panel menu is Sequence Control turned ON? The Protection menu.

Can system voltage on the 1 (i) side prevent a recloser with Live Load Blocking ON from being closed?

Yes, if the Power Direction setting is Source 2 – Load 1 (Source x – Load i).

What could prevent Dead Lockout from being turned on for a U Series ACR? No x side voltage sensing and Power Direction set to Source x – Load i.

An ACR set for 4 trips to lockout recorded Trip 1 max I 1000A, Trip 2 max I 950A, Trip 3 max I 1040A, Trip 4 max I 1050A, Lockout. When would HCL have caused lockout if the settings were: HCL Current 1000A, Trip No 2?

Lockout would have occurred after Trip 3. To which of the following does Inrush Restaint not apply? SEF, Phase Faults, Definite

Time, Earth Faults. SEF and Definite Time.

If the Cold Load status is: 60 min Mult x2 and the user set Cold Load Time is 120 min, what must the user set Cold Load Multiplier be?

3. How can the switchgear be closed when the Work Tag is applied?

It can’t.