Relay M 8 H - System för branddetektorer - Consilium ...consiliumbuildingsafety.com/Commonresources/Files/… · Data sheet no: 5100081 Relay M 8 H.10 1.E I DATA SHEET Relay M 8

Post on 20-Jul-2018

222 Views

Category:

Documents

0 Downloads

Preview:

Click to see full reader

Transcript

The specifications described herein are subject to change without notice. Data sheet no: 5100081 Relay M 8 H.10 1.EI

DATA SHEET

Relay M 8 HPart no 5100081-01A

System: TERRA FIRE

www.cnsystem.se

1(2)

General DescriptionRelay M 8 provides eight programmable relay contacts. Each of these relay contacts provide a potential free change-over contact.Use Relay M 8 to control units such as sirens, magnets, flashlight, alarms and ventilation fans.For details on assembling a system and definitions of common system terms, refer to the Installation Manual.

Data

SettingsThe module is identified by a physical address on the Backbone Bus. The address is set with an 8-pole DIP switch.

Address switchThe DIP switch value follows the binary system. The address no. can be set from 1 to 126 using DIP-switch poles 1 to 7.

ConnectionsOperating voltage range 19-30 VDC

Max. DC load (resistive) per channel

5 A /30 VDC

Max. AC load (resistive) per channel

5 A /250 VAC

Current consumption (at 24 V) 11 mA

Max total current consumption 86 mACable terminals 2,5 mm2

Operating temperature range -5°C to +55°C

Weight (with housing) 230g

Spare part no.(without housing)

5100080-01A

0845-CPD-232.1686

DATA SHEET

The specifications described herein are subject to change without notice. Data sheet no: 5100081 Relay M 8 H.10 1.EI

www.cnsystem.se

2(2)

IndicatorsRelay M 8 indicators display input and output status.

Module Dimensions (mm)

MountingMount the module horizontally on a 35 mm DIN rail.

Indicator Indicator Colour Status

Relay 1 – 8

Green The relay is activated (C and NO terminals connected)

Yellow The relay has an internal faultNone The relay is deactivated (C and NC terminals connected)

PS (Power Supply)

Green OK

Yellow, steady Power FaultYellow, flashing Boot loader mode

COM (Communication)

Green, steady OK

Green, flashing UnconfiguredYellow, steady Faulty communication

Yellow, flashing Major fault

None No communication

PS + COM(both flashing)

PSYellow, flashing

Transferring softwareCOMGreen, flashing

top related