Top Banner
The specifications described herein are subject to change without notice. Data sheet no: 5100081 Relay M 8 H.10 1.EI DATA SHEET Relay M 8 H Part no 5100081-01A System: TERRA FIRE www.cnsystem.se 1(2) General Description Relay M 8 provides eight programmable relay contacts. Each of these relay contacts provide a potential free change-over contact. Use Relay M 8 to control units such as sirens, magnets, flashlight, alarms and ventilation fans. For details on assembling a system and definitions of common system terms, refer to the Installation Manual. Data Settings The module is identified by a physical address on the Backbone Bus. The address is set with an 8-pole DIP switch. Address switch The DIP switch value follows the binary system. The address no. can be set from 1 to 126 using DIP-switch poles 1 to 7. Connections Operating voltage range 19-30 VDC Max. DC load (resistive) per channel 5 A /30 VDC Max. AC load (resistive) per channel 5 A /250 VAC Current consumption (at 24 V) 11 mA Max total current consumption 86 mA Cable terminals 2,5 mm 2 Operating temperature range -5°C to +55°C Weight (with housing) 230g Spare part no. (without housing) 5100080-01A 0845-CPD-232.1686
2

Relay M 8 H - System för branddetektorer - Consilium ...consiliumbuildingsafety.com/Commonresources/Files/… · Data sheet no: 5100081 Relay M 8 H.10 1.E I DATA SHEET Relay M 8

Jul 20, 2018

Download

Documents

hoangdieu
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Relay M 8 H - System för branddetektorer - Consilium ...consiliumbuildingsafety.com/Commonresources/Files/… · Data sheet no: 5100081 Relay M 8 H.10 1.E I DATA SHEET Relay M 8

The specifications described herein are subject to change without notice. Data sheet no: 5100081 Relay M 8 H.10 1.EI

DATA SHEET

Relay M 8 HPart no 5100081-01A

System: TERRA FIRE

www.cnsystem.se

1(2)

General DescriptionRelay M 8 provides eight programmable relay contacts. Each of these relay contacts provide a potential free change-over contact.Use Relay M 8 to control units such as sirens, magnets, flashlight, alarms and ventilation fans.For details on assembling a system and definitions of common system terms, refer to the Installation Manual.

Data

SettingsThe module is identified by a physical address on the Backbone Bus. The address is set with an 8-pole DIP switch.

Address switchThe DIP switch value follows the binary system. The address no. can be set from 1 to 126 using DIP-switch poles 1 to 7.

ConnectionsOperating voltage range 19-30 VDC

Max. DC load (resistive) per channel

5 A /30 VDC

Max. AC load (resistive) per channel

5 A /250 VAC

Current consumption (at 24 V) 11 mA

Max total current consumption 86 mACable terminals 2,5 mm2

Operating temperature range -5°C to +55°C

Weight (with housing) 230g

Spare part no.(without housing)

5100080-01A

0845-CPD-232.1686

Page 2: Relay M 8 H - System för branddetektorer - Consilium ...consiliumbuildingsafety.com/Commonresources/Files/… · Data sheet no: 5100081 Relay M 8 H.10 1.E I DATA SHEET Relay M 8

DATA SHEET

The specifications described herein are subject to change without notice. Data sheet no: 5100081 Relay M 8 H.10 1.EI

www.cnsystem.se

2(2)

IndicatorsRelay M 8 indicators display input and output status.

Module Dimensions (mm)

MountingMount the module horizontally on a 35 mm DIN rail.

Indicator Indicator Colour Status

Relay 1 – 8

Green The relay is activated (C and NO terminals connected)

Yellow The relay has an internal faultNone The relay is deactivated (C and NC terminals connected)

PS (Power Supply)

Green OK

Yellow, steady Power FaultYellow, flashing Boot loader mode

COM (Communication)

Green, steady OK

Green, flashing UnconfiguredYellow, steady Faulty communication

Yellow, flashing Major fault

None No communication

PS + COM(both flashing)

PSYellow, flashing

Transferring softwareCOMGreen, flashing