ELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Post on 11-Feb-2022
3 Views
Preview:
Transcript
ELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Doc Ref: UKDA Revision: A
Page 1 of 5
Please complete all sections of the application form and return to newconnections@ukpowerdistribution.co.uk
Section 1 – Site Details
UKPD Reference Number:
Energisation Date:
Site Name/Address/Postcode:
Project Description:
Section 2 – Independent Connection Provider (ICP) Details
Your Site Reference Number:
Company Name:
Address:
Designer:
Contact Telephone Number:
Email Address:
Section 3 – Land Owner Details
Company Name:
Address:
Contact Name:
Contact Telephone Number:
Email Address:
ELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Doc Ref: UKDA Revision: A
Page 2 of 5
Section 4 – Land Owner Solicitor Details
Company Name:
Address:
Contact Name:
Contact Telephone Number:
Email Address:
Section 5 – Proposed Connection Load Details
Plot Number or Name
Quantity Supply Capacity (kVA) LV
HV Build Phase Per Plot* Total 1Ph 3Ph
Total Load:
*ADMD (After Diversity Maximum Demand)
As a guide for gas heated semi‐detached domestic housing use 1.0 kVA per plot (up to 3 bedrooms) and for detached domestic housing use 1.4 kVA per plot (up to 5 bedrooms).
As a guide for electric heated domestic apartments/housing use 3.4 kVA per plot (up to 2 bedrooms and within a high density of units). For electric heated housing with ‘restricted hours tariffs and all other scenarios please refer to UKPD for guidance.
For electric heated domestic apartments use UKPD ADMD Ready Reckoner to calculate the rating of distribution transformers.
Section 6 – Proposed Generation and Export Details
Maximum power output (phased if appropriate):
Generation set specification type e.g. PV, CHP:
Confirmation of plans to export back to network:
Plans to run in parallel e.g. test back‐up generator:
Completed ENA document e.g. G59, G83:
ELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Doc Ref: UKDA Revision: A
Page 3 of 5
Section 7 – Proposed Materials and Equipment for Adoption
Category Description Specification Supplier
Note: If you need to provide any further materials and equipment details please provide on a separate sheet in the above format
ELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Doc Ref: UKDA Revision: A
Page 4 of 5
Section 8 – Other drawings and documents to be provided as indicated
Please include the information below depending on the type of projects listed on the right.
LV Networks
LV supplies from a
new
standard sub‐
station
LV supplies from a
new
non‐standard
sub‐station
HV M
etered
Supply
1 Site plan to include the following minimum information: ‐
Clearly defined site boundary
North point
Site location detail (can be provided on separate drawing if desired)
Minimum scale 1:500 @ A3
Yes Yes Yes Yes
2 LV design drawing to include the following minimum information: ‐
Size/type and network asset owner of existing cable at the point of connection
Link box and fuse sizes where required
Substation location where required
Proposed LV cable size/type and ducting size/type where required
All joints, pot ends, terminations and earthing
Detailed cross sections along the cable route
Service load, termination, service fuse size, CT ratio and metering arrangements for each supply
Kiosk/cabinet details, where required, including manufacturers specification
For apartments include details of internal mains and service routes, cable ways, containment, multi metering layouts, distribution boards, fusing and service positions
Street lighting connections where required
Single line diagram (can be provided on separate drawing if desired)
North point
Minimum scale 1:500 @ A3
Yes Yes Yes N/A
3 HV design drawing to include the following minimum information: ‐
Size/type and network asset owner of existing cable at the point of connection
Substation location, load and plant specification including manufacturers details
Small power and lighting specification and details
Proposed HV cable size/type and ducting size/type where required
All joints and terminations
Detailed cross sections along the cable route
Customers transformer or HV network details for any HV metered supplies
Emergency trip button and HV meter panel details where required
Kiosk/cabinet details, where required, including manufacturers specification
Single line diagram (can be provided on separate drawing if desired)
HV Protection details and settings
Ancillaries: Tripping battery, automation details, where required
North point
Minimum scale 1:500 @ A3
N/A Yes Yes Yes
4 Substation earthing drawing to include the following minimum information: ‐
Substation layout
Earthing design
N/A Yes Yes Yes
ELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Doc Ref: UKDA Revision: A
Page 5 of 5
Section 9 – Additional information/comments
Section 10 – ICP Declaration
I confirm that by submitting this application we have been appointed as an ICP to design and install electrical networks to the above named development. I understand that failure to supply any of the required information may result in a delay in my application being processed.
ICP Company Name:
Print Name:
Signature:
Date:
UKPD exist to provide customers with a forward thinking, flexible and least hassle approach in the area of adoption of electricity distribution networks, which we will look to deliver through pioneering commercial solutions and the introduction of a more pragmatic and streamlined approach to the whole adoption process. Contact Us: Address: Head Office, 6500 Daresbury Park, Warrington, Cheshire, WA4 4GE Phone number: 0844 74 000 74 E‐mail: newconnections@ukpowerdistribution.co.uk We are open: Main office is open from 8.30am to 5pm Monday to Friday
5 Substation with standard housing drawing to include the following minimum information: ‐
GRP specification and manufacturer or brick built housing specification
Plinth construction details
N/A Yes N/A Yes
6 Substation with non‐standard housing drawing to include the following minimum information: ‐
Architect proposals for substation room
Substation layout including dimensions, doors, joint locking arrangement and ventilation details
N/A N/A Yes Yes
7 IDNO legal drawing to include the following minimum information: ‐
Substation access
Cable easements
Street names
North point
Scale 1:1250 with insert at 1:500 to highlight any substation detail
Yes Yes Yes Yes
8 Volt drop and earth loop impedance calculations for LV network Yes Yes Yes N/A
9 Drawing register confirming the following:‐
Drawing numbers and revision details
Drawing title
Scheme title
Yes Yes Yes Yes