CASED & UNCASED UPFLOW & DOWNFLOW … & uncased upflow & downflow evaporator coils ... u47/uc47 wet 0.120.160.20 0.240.270.300.34 __ ... • goodman products
Post on 17-May-2018
235 Views
Preview:
Transcript
1
Description / Application• Compact, versatile, right or left horizontal position• May be used in closet, utility room, or basement
Construction• Insulated steel cabinet
Cabinet Finish• No rust galvanized stucco finish
CASED & UNCASEDUPFLOW & DOWNFLOWEVAPORATOR COILS
U/UC SERIES 02/03
Standard Finish• Fully insulated cabinet on cased coils• Equipped with a check flowrator for heat pump and
cooling unit operation• No rust high temperature thermoplastic drain pans for
upflow and downflow application with secondary drain
Accessories• Downflow kit (DFK) used for all multi-position
furnaces for downflow applications
Made in the USA by:Goodman Manufacturing Company, L.P.
2550 North Loop West, Suite 400Houston, TX 77092
www.goodmanmfg.com
SS-208DRev. M
®
2
UNCASED UPFLOW EVAPORATOR COILSUC-18 THRU UC-42, UC-47, UC-49, UC-59, & UC-62
SUCTIONCONNECTION
LIQUIDCONNECTION
“A” SHAPEDSLAB
3/4” FEMALE NPTPRIMARY & SECONDARY
DRAIN CONNECTIONS(IMPORTANT: HAND
TIGHTEN)
SUCTIONCONNECTION
LIQUIDCONNECTION
3/4”FEMALENPT PRIMARY &SECONDARYDRAINCONNECTIONS(IMPORTANT:HAND TIGHTEN)
ACCESS PANEL VIEW
UC-60 & UC-61ACCESS PANEL VIEW
NOTES:1) SEE BACK SHEET FOR INSTALLATION TIPS.2) DO NOT USE THIS COIL ON OIL FURNACES OR ANY APPLICATIONS WHERE THE TEMPERATURE ON DRAIN PAN MAY EXCEED 300°F. USE
THE FOLLOWING METAL DRAIN PANS: 15236-18 (U-18 THRU U-32), 15236-19 (U-36 THRU U-47), 15236-20 (U/UC-60 THRU U-61), AND FIELDFABRICATED METAL PAN FOR (U/UC-49, U/UC-59, AND U/UC-62).
3) * UC-29 COMES WITH 2 TON FLOWRATER B13134-59. IF 2-1/2 TON MATCHING IS REQUIRED, INSTALL PROVIDED PISTON KIT B17898-65.
STATICA B C PRESSURE
WET COIL
UC-18 1 1/2 13 14 1/4 20 1/8 650 0.20 2 3/8 5/8 14
UC-29 *2 - 21/2 13 14 20 1/8 900 0.20 2 3/8 3/4 16
UC-32 2 1/2 13 17 7/8 20 1/8 1000 0.30 3 3/8 3/4 24
UC-35 3 13 18 1/4 20 1/8 1200 0.30 2 3/8 3/4 18
UC-36 3 17 17 1/2 20 1/8 1200 0.25 2 3/8 3/4 19
UC-42 3 1/2 17 17 3/4 20 1/8 1400 0.30 3 3/8 3/4 34
UC-47 4 17 22 1/8 20 1/8 1600 0.30 3 3/8 7/8 31
UC-49 4 19 3/4 21 7/8 20 1/8 1600 0.30 3 3/8 7/8 33
UC-59 5 19 3/4 25 7/8 20 1/8 2000 0.30 3 3/8 7/8 36
UC-60 5 20 1/4 21 1/4 23 2000 0.30 3 3/8 7/8 42
UC-61 5 20 1/4 22 23 2000 0.30 4 3/8 7/8 44
UC-62 5 19 3/4 26 1/8 20 1/8 2000 0.30 4 3/8 7/8 47
SPECIFICATIONS
NOMINALCFM
NOMINALTONS
COILMODEL
DIMENSIONS (INCHES)
LIQUIDCONN.
NO.ROWS
SUCTIONCONN.
SHIPWT.
3
CASED UPFLOW EVAPORATOR COILSU-18 THRU U-42, U-47, U-49, U-59, & U-62
SUCTION LINE
LIQUID CONN.
3/4” FEMALE NPTPRIMARY &
SECONDARY DRAINCONNECTIONS
(IMPORTANT: HANDTIGHTEN)
23 3/8
SUCTION LINE
LIQUIDLINE
20 3/8
21 1/8
F
20 1/4
D
3/4” FEMALENPT PRIMARY &SECONDARYDRAIN CONNECTIONSIMPORTANT:HAND TIGHTEN
NOTE: FOR DRAIN PAN SPECIFICATIONS, REFER TO NOTE 2 ON PAGE 2.
1) * U-29 COMES WITH 2 TON FLOWRATOR B13134-59. IF 2 1/2 MATCHING IS REQUIRED, INSTALL PROVIDED PISTON KIT B17898-65.
ACCESS PANEL VIEW
ACCESS PANEL VIEW
U-60 & U-61
STATICA B C D E F PRESSURE
WET COIL
U-18 1 1/2 14 1/4 12 3/4 14 1/2 13 1/4 - 650 0.20 2 3/8 5/8 24
U-29 *2 - 21/2 14 1/4 12 3/4 14 1/2 13 1/4 - 900 0.20 2 3/8 3/4 26
U-30 2 1/2 18 1/4 17 1/4 16 1/2 17 1/4 - 1000 0.30 2 3/8 3/4 33
U-31 2 1/2 14 1/4 12 3/4 14 1/2 13 1/4 - 1000 0.30 3 3/8 3/4 30
U-32 2 1/2 18 1/4 17 1/4 16 1/2 17 1/4 2 1000 0.25 3 3/8 3/4 41
U-35 3 14 1/4 12 1/4 14 1/2 13 1/4 4 1/8 1200 0.30 2 3/8 3/4 29
U-36 3 18 1/4 17 1/4 16 1/2 17 1/4 1 3/4 1200 0.30 2 3/8 3/4 40
U-42 3 1/2 18 1/4 17 1/4 16 1/2 17 1/4 2 1400 0.30 3 3/8 3/4 48
U-47 4 18 1/4 17 1/4 16 1/2 17 1/4 6 1600 0.30 3 3/8 7/8 50
U-49 4 21 1/8 20 1/8 27 1/2 20 - 1600 0.30 3 3/8 7/8 51
U-59 5 21 1/8 20 1/8 27 1/2 20 - 2000 0.30 3 3/8 7/8 54
U-60 5 24 1/4 23 1/8 20 1/2 1/2 20 1/8 1 2000 0.30 3 3/8 7/8 60
U-61 5 24 1/4 23 1/8 20 1/2 1/2 20 1/8 1 5/8 2000 0.30 4 3/8 7/8 62
U-62 5 21 1/8 20 1/8 27 1/2 20 - 2000 0.30 4 3/8 7/8 68
LIQUIDCONN.
SUCTIONCONN.
SHIPWT.
SPECIFICATIONSDIMENSIONS (INCHES)
NOMINALTONS
COILMODEL
NOMINALCFM
NO.ROWS
4
STATIC PRESSURE DROP ACROSS COILAir Flow Data - Static Pressure Drop Across Coil - Upflow Application
DOWNFLOW APPLICATIONS
NOTE:A. Do not use this coil on oil furnaces or any applications where the temperature on drain pan may exceed 300°F. Use the following metal
drain pans: 15236-18 (U-18 thru U-32), 15236-19 (U-36 thru U-47), and 15236-20 (U/UC-60 thru U-61).B. Due to the rating mix/match of various coils with outdoor units it is important to match the furnace air flow for the total system capacity.
(Refer to furnace spec. sheet & condenser/heat pump spec. sheet.)
UC COIL INSTALLATION RECOMMENDATIONSMINIMUM DISTANCE
BETWEEN FURNACE AND COIL PAN = 2”
COIL MODEL AIR QUANTITY (CFM)
CFM 400 500 600 700 800 900.00 1000 1100
U18/UC18 WET 0.10 0.12 0.18 0.25 __ __ __ __
DRY 0.08 0.10 0.12 0.19 __ __ __ __
U29/UC29 CFM 600 700 800 900 1000 1100 1200 1300
/30 WET 0.12 0.16 0.20 0.25 0.30 __ __ __
DRY 0.08 0.10 0.13 0.16 0.21 __ __ __
U32/UC32 CFM 700 800 900 1000 1100 1200 1300 1400
U31 WET 0.16 0.22 0.24 0.28 0.34 __ __ __
DRY 0.10 0.16 0.18 0.24 0.27 __ __ __
U36/UC36 CFM 800 900 1000 1100 1200 1300 1400 1500
U35/UC35 WET 0.13 0.16 0.20 0.24 0.28 0.30 __ __
DRY 0.10 0.12 0.14 0.18 0.24 0.28 __ __
U42/UC42 CFM 900 1000 1100 1200 1300 1400 1500 1600
U47/UC47 WET 0.12 0.16 0.20 0.24 0.27 0.30 0.34 __
DRY 0.10 0.13 0.15 0.18 0.20 0.22 0.26 __
CFM 1200 1300 1400 1500 1600 1700 1800 1900
U49/UC49 WET 0.14 0.18 0.22 0.26 0.30 0.34 __ __
DRY 0.12 0.14 0.17 0.19 0.22 0.26 __ __
U59/UC59 CFM 1600 1700 1800 1900 2000 2100 2200 2300
U60/UC60 WET 0.17 0.21 0.24 0.27 0.30 0.33 0.36 0.40
DRY 0.13 0.14 0.19 0.22 0.25 0.29 0.32 0.36
U61/UC61 CFM 1600 1700 1800 1900 2000 2100 2200 2300
U62/UC62 WET 0.19 0.22 0.26 0.29 0.32 0.36 0.40 0.45
DRY 0.15 0.17 0.21 0.25 0.28 0.32 0.35 0.39
5
(1) Utilizing factory installed bottom cabinet filler plates.(2) Discard bottom cabinet filler plates(3) Downflow Coil Adapter Kit allows use of U coils in downflow applications.(*) Upflow Application only(ND) Not for Downflow
CASED (U) COIL APPLICATION OPTIONS
GMP050-3 GDT045-3 GMP075-3 GDT090-4 GMP100-5 GDT115-5 GMP150-5
GMP050-32(C) GDT070-3 GMP100-3 GMNT080-4 GMP125-4 GMNT100-4 GMP150-52(C)
GMP075-3 GMNT040-3 GMP100-4 GPD100-4 GMP125-5 GPD125-4 GMPH120-5
GMP075-32(C) GMNT060-3 GMP100-42(C) GMP125-52(C) GMPN120-5
GMPH050-3 GPD050-3 GMPE075-3 GMPE100-4 GMT140-5 (ND)
GMPN040-3 GPD075-3 GMPH075-4 GMPE125-5
GMPN060-3 GMPN080-4 GMPH080-5
GMT045-3 (ND) GMT070-4 (ND) GMPN100-4
GMT070-3 (ND) GMT090-3 (ND) GMT090-5 (ND)
GMTH045-3 (ND) GMT090-4 (ND) GMT115-5 (ND)
GSM060-3 (ND) GMTH070-4 (ND) GMTH115-5 (ND)
GSMS060-3 (ND) GSM080-4 (ND) GSM100-4 (ND)
GSU060-3 (*) GSMS080-4 (ND) GSMS100-4 (ND)
GSU080-4 (*) GSU100-4 (*)
DFKT-17
COIL NOMINAL MODEL COIL
NO. WIDTHU-18 14” X XU-29 14” X XU-30 17 1/2” X(1) X(1) X(2) X(2)U-31 14” X XU-32 17 1/2” X(1) X(1) X(2) X(2)U-35 14” X XU-36 17 1/2” X(1) X(1) X(2) X(2)U-42 17 1/2” X(1) X(1) X(2) X(2)U-47 17 1/2” X XU-49 21” X(1) X(1) X(2) X(2)U-59 21” X(1) X(1) X(2) X(2)U-60 24 1/2” X(1) X(1) X(2) X(2)U-61 24 1/2” X(1) X(1) X(2) X(2)U-62 21” X(1) X(1) X(2) X(2)
FURNACE MODEL
NO.
NOMINAL FURNACE WIDTH
DFK MODEL NO. (3)
24 1/2”
DFK - 14 DFKT-14 DFK - 17 DFK - 21 DFKT - 21 DFK – 24 DFKT – 24
GMNT120-5
14” 14” 17 1/2” 17 1/2” 21” 21” 24 1/2”
Quality Makes the Difference!All of our systems are designed and manufactured with the same high quality standards regardless of size of efficiency. Ourdesigns virtually eliminate the most frequent causes of product failure. They are simple to service and forgiving to operate. We usethe highest quality materials and components available because if a part fails then the unit fails. Finally, every unit is run testedbefore it leaves the factory. That’s why we know...
There’s No Better Quality.
Visit our website at www.goodmanmfg.com for information on:• Goodman Products• Warranties• Customer Services• Parts• Contractor Programs and Training• Financing Options
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN ARE SUBJECT TO CHANGE WITHOUT NOTICE