Tel : 031-427-8005 E-mail : info @ taehung.co.kr
Features
Ordering Information
AIRTRON
Process Type : FT = Airflow Measurement
PT = Pressure Measurement
Option : MO = RS485 Modbus RTU
AL = Alarm Output (SPDT)
AIRTRON is microprocessor based airflow & pressure
transmitter which measure air velocity with pitot tubes,
and duct static or differential pressure in HVAC control
system applications.
The AIRTRON consist of temperature compensated
low differential pressure sensing module, auto - zeroing
valve & circuit and state of the art digital electronics
in the transmitter which has industry standard output
signal for remote monitoring and control.
Airflow & PressureSmart Transmitter
AIRTRON
▶ R&D center, Hospital
▶ Industrial buildings
▶ Pharmaceutical, etc
▶ AHU fan flow measurement
▶ Duct airflow measurement
▶ Air pressure measurement
Typical Applications
▶ Multi - points linearization
▶ Malfunction diagnostic capability
▶ Auto zeroing capability
Rugged and Reliable
▶ 0 - 6 to 0 - 50 m/s flow range
▶ 0.5% of Accuracy
▶ No position effected
Ultra-low Diff. Pressure Sensor
▶ Simple configuration menus
▶ Long - term stability
▶ No maintenance required
Low Cost of Ownership
▶ Microprocessor based functionality
▶ 4 - 20 mA or 0 -10 Vdc, RS485 Modbus.
▶ Air volume and velocity display
Flexible Functionality
73, Simin - daero, Dongan - gu, Anyang, GY., South KoreaTel : 031 - 427 - 8005 Fax : 031- 427 - 8020E-mail : info @ taehung.co.kr Website : www.taehung.co.kr
Agent :
Airflow & Pressure Transmitter
Technical Specifications
Performance
▶ Diff. Pressure Span : 0 - 2.5 to 0 - 200 mmH2O (± 1.25 to ± 125 mmH2O)
▶ Accuracy : 0.5% of full scale
▶ Temperature Effect : ■ Zero : None-corrected by Auto-zeroing ■ Span : 0.025% of span/℉
▶ Temperature Limits : ■ Operating : -10 to 60℃ ■ Storage : -40 to 80℃
▶ Overpressure Limits : 5 psi
▶ Humidity Limits : 0 to 95% RH, non-condensing
▶ Span Adjustments : Performed by internally mounted push buttons
▶ Zero adjustments : Performed by internally mounted auto-zeroing circuit & valve selectable 1 - 24 hours on 1 hour intervals
▶ Display & Output Low Pass Filter : A step change is adjustable in 8 increments
▶ Malfunction Diagnostics : Self-malfunction diagnostics display
Indication
▶ LCD Display with backlit, selectable engineering units such as m3/h, m3/m, ft3/m, m/s, mmWC, inWC, Pa.
Outputs
▶ Analog Output 4 - 20 mADC, 0 -10 VDC or RS485 Modbus▶ Alarm Outputs : 2 × SPDT Relay contact 1A @ 24VDC
Power
▶ Power Supply : 24 VAC/DC, ±10 %▶ Power Consumption : ■ 2.3 VA at 24 VAC ■ 2.5 VA at 24 VDC
Enclosure
▶ Process Connections : 2 × 1/4”Barbed fittings▶ Material : Painted steel or Stainless steel
Dimension Wiring
102
126
155
49
FRONT
BOTTOM
RS485 Modbus
3 or 4 WIRE (Analog Output)
<FIELD>
<AIRTRON>Internally
Connected
DP/FLOWANALOGSIG IN
24VAC/DCPOWER
PLC / DDC
+ - + -
RS48524VAC/DCPOWER
PLC / DDC
+ - A B
CN3
SIG COM
ANALOGOUT
POWER
+24 COM
CN3
A B
RS485POWER
+24 COM
COM NO COM NO
ALARM2
ALARM1
EXTERNALSWITCH
- +
PLC / DDC
CN4 (Optional)
+24 COM SIG COM
ALARMRELAYOUT 2
ALARMRELAYOUT 1
EXTERNALSWITCH
IN
+24 COM
CN3
+24 COM SIG COM
ALARMRELAYOUT 2
ALARMRELAYOUT 1
EXTERNALSWITCH
IN
+24 COM
COM NO COM NO
ALARM2
ALARM1
EXTERNALSWITCH
- +
PLC / DDC
<FIELD>
<AIRTRON>
Tel : 031-427-8005 E-mail : info @ taehung.co.kr
Operating Principal
Type FP airflow measuring probe consists of multiple sets
of fechheimer pitot total and static pressure sensing ports,
positioned along the length of the probe to traverse the duct
cross-section, average the sensed pressures in separate
internal manifolds, and provide a measurement of velocity
pressure accurate within 2% of actual flow when the quantity
of the probes and the location in the duct are in accordance
with our minimum installation requirements.
Type FP is available in externally mounted, insertable/removable
and Internally mounted versions to fit the needs of both new
installation and retrofit applications.
Airflow Measuring ProbeType FP
Duct Mounting & Dimensions
T.P. & S.P.Takeoffs
TP SP
传感器
Duct Wall
A = Duct I.D.
B = Probe Dia.
MOUNTING PLATE (mm)
102
102
Threaded End SupportGasket, Washer, and Nut
Mounting Platewith Gasket
102 × 102 200 - 1300
1301 - 2700
Mounting Plate
102 × 102
8
D
8
19
B
25
30
C
尺寸 (mm)
A
40 INSERTION HOLE END HOLE
C
D
Airflow
Type FP airflow measuring probe utilize self averaging, multi points
pitot technology which produces differential pressure from a total
and dual offset static pressure ports of air movement of duct or pipe.
Total pressure sensing ports (Pt) are located on the leading surface
of the probe which effects on dynamic pressure to induce total
pressure by velocity of airflow. Static pressure sensing ports (Ps)
are positioned at angles offset from the flow normal vector, minimize
the error including effect of turbulent airflow. i.e.One static sensor is
exposed to a higher pressure, the other static sensor exposed a
lower pressure of the same magnitude, this elimination of the undesired
effect of partial total pressure is assuring the accurate and stable
measurement without airflow straightener upstream.
Figure 1
TotalPressureSensor
StaticPressureSensors
Ps
Ps
Pt
Pt
Ps
TOTAL PRESSURESTATIC PRESSURE
TotalPressureAveragingManifold
Printed Oct. 2016
73, Simin - daero, Dongan - gu, Anyang, GY., South KoreaTel : 031 - 427 - 8005 Fax : 031- 427 - 8020E-mail : info @ taehung.co.kr Website : www.taehung.co.kr
Agent :
the location indicate the minimum clearance required from air tur-
bulence producing source to guarantee measuring performance
Airflow measurement is highly dependent upon the quantity and
pattern of sensing points of the duct crosssectional area in the
airstream, we recommend quantity of airflow senising depend on
within 2% accuracy. the airflow element should be installed
where greater distance of straight duct than shown below.
duct size in accordance with measurement standard (ASHRAE
fundamentals, AMCA publication 203, etc) shown below guide
line for the measurement accuracy within 1-2% of actual airflow.
Sensing Element InstallationMinimum Installation Requirements
Accuracy
Retangular Duct : X =H+W
2(H×W)
Circular Duct : X = Duct Diameter
SWEEP ELBOW
ROUND SWEEPELBOW CENTRIFUGAL
FAN INLETVANE-AXIAL
FAN
TRANSITION ANGLE ≤ 15̊
90̊ UNVANED ELBOW
90̊ VANED ELBOW
TAKEOFFS
ELBOWS DAMPERS
DUCT TRANSITIONS
FANS
Height
Width
FOR SQUARE AND RECTANGULAR DUCT FOR CIRCULAR DUCT
Diameter
Up to 350
> 351 - 760
> 761 - 1400
> 1401 - 2100
> 2101 - 3100
> 3101 +
1
2
3
4
5
6
Height (mm)Height (mm) Recommend Qty. Recommend Qty.
> 200 - 450
> 451 - 1800
> 1801 +
1
2
3
Diameter (mm) Recommend Qty.