ACDO-240v DELAY TIMER - Hevac Control Agencies · ACDO-240v SHORT DURATION TIMER 30 Sec. ~ 5 Min. ADJUSTABLE DELAY ON or OFF • 240vAC Powered & Manufactured to Australian Standards.
Post on 15-Aug-2020
1 Views
Preview:
Transcript
ACDO-240v
SHORT DURATION TIMER 30 Sec. ~ 5 Min.ADJUSTABLE DELAY ON or OFF
• 240vAC Powered & Manufactured to Australian Standards.
• Selectable as Delay ON or Delay OFF.
• Selectable default input switch state as N/C or N/O.
• Indication Lamps for Power, Relay & Timer Elapsed Status.
• Potential Free 240v 10 Amp rated SPDT Relay Output.
• Based on R/C Analog Time Delay (ultra reliable no processor to glitch).
• Din rail mount low profile.
^ ^240vacPOWER
INPUTSWITCH
^ ^ ^ Potential free 8A C/O Contacts
HEVAC CONTROL AGENCIES PTY.LTD www.hevac.com.au 613 95627888
V V
DELAYTIMER
(24v version also available)
ADJUSTMENTS & INDICATION LEGENDINPUT TYPE SELECTOR JUMPER N/O > TIMER FUNCTION BEGINS WHEN INPUT SWITCH CLOSES.N/C > TIMER FUNCTION BEGINS WHEN INPUT OPENS
DELAY ON or OFF SELECTOR JUMPERD.ON > RELAY NORMALLY OFF ANDTURNS ON AFTER TIME DELAY.D.OFF > RELAY NORMALLY ON ANDTURNS OFF AFTER TIME DELAY.
RELAY ON/OFF STATUS INDICATION LAMPILLUMINATION=RELAY ON
INPUT SWITCH CONNECTIONTERMINALS. NOTE : DO NOT CONNECT TO A VOLTAGE SOURCE, DRY CONTACTS ONLY.
VOLTAGE FREE RELAYC/O CONTACTS RATED AT MAX 10 AMPS RESISTIVE (3A INDUCTIVE)
MODULE POWER SUPPLY 240VAC
POWER SUPPLYON INDICATION
TIME DELAYADJUSTMENT POTENTIOMETER30 Sec ~5 Minutes
TIMER FUNCTION INDICATION LAMP. ILLUMINATES AFTER TIME DELAY ELAPSED.
DIMENTIONS
HEVAC CONTROL AGENCIES PTY.LTD www.hevac.com.au 613 95627888
Typical Application Use :Adjustable time delay module suitable for short Time Delay ON or OFF applications that are required to respond to the change of state of an input switch or contact. Typical applications include as an interlock with an Air Conditioning System such that the unit is disabled after a short time delay (delay off) if a balcony door or window is left opened (as detected by a suitably mounted switch) or as a fan or pump run on timer (delay off).The ACDO relays delayed operation (turning either on or off) can be set to trigger between 30 seconds to 5 minutes. The ACDO can be set to respond to an input switch changing from normally closed to an open state (to trigger the timing operation) or vice versa via a user selectable jumper. The output relay can also be set to energise (delay on) or de-energise (delay off) after the adjustable time delay has elapsed with another user selectable jumper. Three indication lamps indicate power, relay on/off status & timer elapsed. This timer is designed to respond to a constant on or off change of input state not a momentary input - Use Hevac's universal timer HUDT for applications required to respond to a momentary input ie push button or movement sensor.
240vACPOWERSUPPLY
N/O
INTERLO
CK
S
N/C
INTERLO
CK
S
MONITOREDSWITCH INPUT
RELAY C
OM
MO
N
ELECTRICAL CONNECTIONS
USE RELAY CONTACTSAS SUITS APPLICATION