This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Integrates sensors & actuators into automation systems– Sensor- and actuator-to-boardroom information integration– Field devices become information servers– Expanding the view on the process
Enables significant TCoO reductions– Plant construction - CAPEX
• Cabling, barriers, cabinets
– Plant operation - OPEX• More information, validation
Full digital replacement of the 4-20 mA analogue concept– Multiple devices on a single wire pair – less wiring and
terminations– Unlocking the capabilities of multi-variable devices– Unlocking device diagnostics capabilities
All process in- and output functions reside in field devices– Also control and other functions can reside in field devices– Less marshalling and I/O cabinets - smaller footprint
FOUNDATION™ Fieldbus is open - ”Best-in-Class” devices– Open concept is warranted by interoperability test regime– Unified configuration and device management tools
Full portfolio of physical layer components– Preferred solution for safe as well as hazardous areas– Multi-barier concept solves the segment power limitation
• High current EExe trunk connection
– Safe galvanic isolation between trunk and spurs
Power supply and conditioner (power hub)– Optional redundant power supply and/or conditioner –
Integrated engineering functions– Off-line configuration of field devices and network– Device parameters and function blocks– Optimised function block scheduling– CFF compliant capability files
Integrated device panel– On-line configuration of field devices– Plug & play - automatic address assignment– Detailed device status information
Integrated asset management functions– Plant Resource Manager (PRM) - FieldMate– On-line field device health monitoring– Multi-user concept
Master Stack (LAS) version only – can be set to Basic Stack– Analogue Input (AI) Block (3)
• (Differential) pressure, static pressure and temperature
– Arithmetic (AR) and Integrator (IT)• Flow computation and totalisation, level linearisation
– Signal Selector (IS) and Characteriser (SC) Block– PID block (optionally)
Transducer block functionality– Impulse Line Blocking Detection (ILBD)– Capsule temperature monitoring and alarming– Primary measurement exceeds range limits– Static pressure exceeds static pressure limits– Amplifier temperature monitoring and alarming
Master Stack (LAS) version only – can be set to Basic Stack– Analogue Input (AI) Block (YTA320: 4; YTA:2)
• Sensor 1, sensor 2, difference and average temperature measurement
– Digital Input (DI) Block (YTA320: 4)• Temperature alarms
– PID block (optionally) - (YTA320: 2; YTA80: 1)
Transducer block functionality– Measurement exceeds range limits– Broken sensor - short or open circuit– Amplifier temperature monitoring and alarming– CPU functioning…etc.
Complete range of electro-magnetic flowmeters– Wafer, flanged or threaded connections; sizes 2.5 - 1000 mm– High grade solid ceramic, rubber or pfa-retained lined
flowtube
Unique dual frequency coil excitation– Superior performance - specifically in noisy applications– Excellent zero stability and speed of response
Superior electrode construction - leak tight
Robust, IP67 waterproof execution– Submersible (IP68) version optionally available
Master Stack (LAS) version only – can be set to Basic Stack– Analogue Input (AI) Block (4 optionally 6)
• Mass and volumetric flowrate, density and temperature measurement• Concentration and net mass flow (optional)
– Integrator (IT) Block (2)• Mass and volumetric flow, optionally net mass flow
– PID block (optionally)
Advanced device and process diagnostics– On-line corrosion and abrasion detection– Excessive zero fluctuation– Auto-zero out of range– Slug flow detection– Empty pipe detection
Multi channel oxygen analyser with up to 8 oxygen sensors– Averaging concept eliminates influence of flue gas stratification– Removes failed or “in calibration” sensors from averaging calculation
Excellent performance – 1% full scale; fast response
Optional automatic calibration– Calibration is initiated based on historical data and system accuracy
Remote sensor validation– Checks zero, span and mid point concentration
Intuitive colour touch screen operation– Average, single or all gas concentrations– Trend graph visualisation
Transducer block functionality– Measurement exceeds range limits– Analyser temperature exceeds range limits– Calibration initiation based on historic data
Transducer block functionality– Valve motor air supply monitoring– Signature function using ValveNavi– Total cycle count and valve travel accumulation– Accumulation of time nearly open and close
Local display function for fieldbus devices– Trends data communicated by devices on the bus
Gateway function for analogue measurements– Universal inputs: analogue 4-20mA, RTD, thermocouple etc.
Trending and data logging function - paperless– 2 through 30 channel versions– Mathematical functions and reporting capability– FDA 21CR part 11 compliant batch reporting
Real-time field device maintenance management– On-line field device data collection and health monitoring– Field device maintenance data server– Configuration, calibration and tuning of field devices– Multi-user concept
Vertical and horizontal integration– Interfaces with PAM/EAM systems - Maximo, SAP– Interfaces with PAS/PIMS - Operations