Products are produced at af aci l i t y whose qual i t
y-management systems areISO9001 certified.R-410AYCUL0020-YCUL0072
AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITSSTYLE E (50 AND 60 HZ)
15 -80 TON 50-280KWAIR-COOLED SCROLL COMPRESSOR CONDENSING
UNITSINSTALLATION, OPERATION & MAINTENANCESupersedes:
150.63-NM9 Form 150.63-NM9 (913)Issue Date: September 27,
2013035-22896-000JOHNSON CONTROLS 2FORM 150.63-NM9 ISSUE DATE:
9/27/2013Thisequipmentisarelativelycomplicatedapparatus. During
installation, operation maintenance or service, individuals may be
exposed to certain components or
conditionsincluding,butnotlimitedto:refrigerants,
materialsunderpressure,rotatingcomponents,and both high and low
voltage. Each of these items has the
potential,ifmisusedorhandledimproperly,tocause bodily injury or
death. It is the obligation and
respon-sibilityofoperating/servicepersonneltoidentifyand
recognizetheseinherenthazards,protectthemselves,
andproceedsafelyincompletingtheirtasks.Failure to comply with any
of these requirements could result in serious damage to the
equipment and the property in IMPORTANT!READ BEFORE
PROCEEDING!GENERAL SAFETY GUIDELINESwhich it is situated, as well
as severe personal injury or death to themselves and people at the
site.This document is intended for use by owner-authorized
operating/servicepersonnel.Itisexpectedthatthese
individualspossessindependenttrainingthatwillen-able them to
perform their assigned tasks properly and safely. It is essential
that, prior to performing any task on this equipment, this
individual shall have read and
understoodthisdocumentandanyreferencedmate-rials.Thisindividualshallalsobefamiliarwithand
comply with all applicable governmental standards and regulations
pertaining to the task in question.SAFETY SYMBOLSThe following
symbols are used in this document to alert the reader to specific
situations:Indicates a possible hazardous situation which will
result in death or serious injury if proper care is not
taken.Indicatesapotentiallyhazardoussitua-tion which will result in
possible injuries or damage to equipment if proper care is not
taken.Identifesahazardwhichcouldleadto damage to the machine,
damage to other equipmentand/orenvironmentalpollu-tion if proper
care is not taken or instruc-tions and are not followed.Highlights
additional information useful to the technician in completing the
work being performed properly.External wiring, unless specifed as
an optional connection in the manufacturers product line, is not to
be connected inside the control cabinet. Devices such as relays,
switches, transducers and controls and any external wiring must not
be installed inside the micro panel. All wiring must be in
accor-dance with Johnson Controls published specifcations and must
be performed only by a qualifed electrician. Johnson Controls will
NOT be responsible for damage/problems resulting from improper
connections to the controls or application of improper control
signals. Failure to follow this warn-ing will void the
manufacturers warranty and cause serious damage to property or
personal injury.JOHNSON CONTROLS 3FORM 150.63-NM9 ISSUE DATE:
9/27/2013MANUAL DESCRIPTION FORM NUMBERUnit Replacement Parts Guide
150.63-RP7CHANGEABILITY OF THIS DOCUMENTIn complying with Johnson
Controls policy for contin-uous product improvement, the
information contained inthisdocumentissubjecttochangewithoutnotice.
Johnson Controls makes no commitment to update or provide current
information automatically to the man-ual owner. Updated manuals, if
applicable, can be ob-tained by contacting the nearest Johnson
Controls Ser-vice office or accessing the Johnson Controls QuickLIT
website at http://cgproducts.johnsoncontrols.com.Operating/service
personnel maintain responsibility for the applicability of these
documents to the equipment.
Ifthereisanyquestionregardingtheapplicabilityof these documents,
the technician should verify whether the equipment has been
modified and if current litera-ture is available from the owner of
the equipment prior to performing any work on the chiller.CHANGE
BARSRevisions made to this document are indicated with a line along
the left or right hand column in the area the revision was made.
These revisions are to technical in-formation and any other changes
in spelling, grammar or formatting are not included.ASSOCIATED
LITERATUREJOHNSON CONTROLS 4FORM 150.63-NM9 ISSUE DATE:
9/27/2013THIS PAGE INTENTIONALLY LEFT BLANKJOHNSON CONTROLS 5FORM
150.63-NM9 ISSUE DATE: 9/27/2013TABLE OF CONTENTSSECTION 1 GENERAL
EQUIPMENT INFORMATION AND SAFETY
................................................................
15Introduction
.....................................................................................................................................................
15Compressors
..................................................................................................................................................
15Condenser
......................................................................................................................................................
15Coils
......................................................................................................................................................
15Low Sound Fans
...................................................................................................................................
15Motors
...................................................................................................................................................
15Refrigerant Circuit
..........................................................................................................................................
15Warranty
.........................................................................................................................................................
15Safety And Quality
..........................................................................................................................................
16Standards for Safety and Quality
..........................................................................................................
16Responsibility for Safety
........................................................................................................................
16About This
Manual..........................................................................................................................................
16Misuse Of Equipment
.....................................................................................................................................
16Suitability for Application
.......................................................................................................................
16Structural Support
.................................................................................................................................
17Mechanical
Strength.............................................................................................................................
17General Access
.....................................................................................................................................
17Pressure Systems
.................................................................................................................................
17Electrical
................................................................................................................................................
17Rotating Parts
........................................................................................................................................
17Sharp Edges
..........................................................................................................................................
17Refrigerants and Oils
.............................................................................................................................
17High Temperature and Pressure Cleaning
............................................................................................
17Emergency Shutdown
...........................................................................................................................
17SECTION 2 PRODUCT DESCRIPTION
..............................................................................................................
19Introduction
.....................................................................................................................................................
19General System Description
...........................................................................................................................
19Compressors
.........................................................................................................................................
19Condenser
.............................................................................................................................................
19Low Sound Fans
...................................................................................................................................
20Motors
...................................................................................................................................................
20Microcomputer Control Center
.......................................................................................................................
20Display/Print.........................................................................................................................................
20Entry
......................................................................................................................................................
20Setpoints
...............................................................................................................................................
20Unit
........................................................................................................................................................
20Unit On/Off Switch
.................................................................................................................................
20Building Automation SystemInterface
.........................................................................................................................................................
21Communications
.............................................................................................................................................
21Power Panel
...................................................................................................................................................
21Electrical Options
..................................................................................................................................
22Compressor Power Connections
...................................................................................................
22Single-Point Supply Terminal Block (standard on YCUL
models)..........................................................................................................
22Single-Point Non-Fused Disconnect Switch
..................................................................................
22Single-Point Circuit Breaker
...........................................................................................................
22Control Transformer
.......................................................................................................................
22Power Factor Correction Capacitors
..............................................................................................
22JOHNSON CONTROLS 6FORM 150.63-NM9 ISSUE DATE: 9/27/2013TABLE OF
CONTENTS (CONTD)Control Options
.....................................................................................................................................
22Ambient Kit (Low)
...........................................................................................................................
22Ambient Kit (High)
..........................................................................................................................
22Building Automation System Interface
...........................................................................................
22Language LCD and Keypad Display
..............................................................................................
22Discharge Pressure Transducers And Readout Capability
............................................................................
22Suction Pressure Transducers
.......................................................................................................
23Motor Current Module
....................................................................................................................
23Multi-Unit Sequencing
....................................................................................................................
23Compressor and Piping Options
...........................................................................................................
23Chicago Code Relief Valves
..........................................................................................................
23Service Isolation Valve
...................................................................................................................
23Hot Gas By-Pass
...........................................................................................................................
23Condenser and Cabinet Options
....................................................................................................
23Pre-Coated Fin Condenser Coils
...................................................................................................
23Post-Coated Dipped Condenser Coils
...........................................................................................
23Copper Fin Condenser Coils
..........................................................................................................
23Enclosure Panels (Unit)
.................................................................................................................
23Louvered Panels (Full Unit)
...........................................................................................................
23Sound Attenuation
..........................................................................................................................
23Compressor Acoustic Sound Blanket
.............................................................................................
24Ultra Quiet Fan
...............................................................................................................................
24Vibration Isolators
..........................................................................................................................
24Basic Unit
.....................................................................................................................................................
28SECTION 3 HANDLING AND STORAGE
...........................................................................................................
35Delivery And Storage
......................................................................................................................................
35Inspection
.......................................................................................................................................................
35Unit Rigging
....................................................................................................................................................
35Moving the Condensing Unit
.................................................................................................................
36Lifting Weights
.......................................................................................................................................
36SECTION 4 INSTALLATION
................................................................................................................................
37Installation Checklist
.......................................................................................................................................
37Handling
.........................................................................................................................................................
37Location And Clearances
...............................................................................................................................
37Foundation
............................................................................................................................................
37Ground Level Locations
........................................................................................................................
37Rooftop Locations
.................................................................................................................................
37Noise Sensitive Locations
.....................................................................................................................
37Corrosive
Environments.......................................................................................................................
38Spring Isolators (Optional)
..............................................................................................................................
38Compressor Mounting
....................................................................................................................................
38Pipework Arrangement
...................................................................................................................................
38Duct Work Connection
...................................................................................................................................
38Recommendations Of The Building Services Research Association.
............................................................
38General
Requirements.........................................................................................................................
38Wiring
.............................................................................................................................................................
38System Run Contacts
............................................................................................................................
39Alarm Status Contacts
...........................................................................................................................
39Remote Start/Stop Contacts
..................................................................................................................
39JOHNSON CONTROLS 7FORM 150.63-NM9 ISSUE DATE: 9/27/2013TABLE OF
CONTENTS (CONTD)Remote Emergency Cutoff
....................................................................................................................
39Remote Temp Reset Input
.....................................................................................................................
39Load Limit Input
.....................................................................................................................................
39Liquid Line Solenoid Connections
.........................................................................................................
39Discharge Air Sensor
.............................................................................................................................
39Zone Thermostats, Suction Pressure Control Only (Remote
Start/Stop) .............................................. 39Air
Proving Switch/Remote Start-Stop Contacts
...................................................................................
39Evaporator Blower Start
Contacts........................................................................................................
40Relief Valves
...................................................................................................................................................
40High Pressure Cutout
.....................................................................................................................................
40Compressor Heaters
......................................................................................................................................
40Refrigerant Piping
...........................................................................................................................................
40General
..................................................................................................................................................
40Refrigerant Piping Reference
................................................................................................................
41R-410A Copper Line Sizing
............................................................................................................
41YCUL Line Sizing
Notes.................................................................................................................
41Refrigerant Piping Notes
.......................................................................................................................
42Refrigerant Line Sizing
..........................................................................................................................
43Evaporator Below Condensing Unit
......................................................................................................
43Condenser Below Evaporator
...............................................................................................................
43Oil Traps
.......................................................................................................................................................
43Refrigerant Charge
.........................................................................................................................................
43Refrigerant Piping Reference
.........................................................................................................................
43Filter Driers / Sight Glasses/ Txvs
.................................................................................................................
43SECTION 5 TECHNICAL DATA
..........................................................................................................................
47Voltage Limitations
................................................................................................................................
47Electrical Notes
.....................................................................................................................................
51General
..................................................................................................................................................
97One Inch Defection Spring Isolator Cross-reference
..........................................................................
100SECTION 6 COMMISSIONING
..........................................................................................................................
107Preparation Power Off
...............................................................................................................................
107Inspection...........................................................................................................................................
107Refrigerant Charge
..............................................................................................................................
107Service and Oil Line Valves
.................................................................................................................
107Compressor Oil
...................................................................................................................................
107Isolation / Protection
............................................................................................................................
107Control Panel
.......................................................................................................................................
107Power Connections
.............................................................................................................................
107Grounding
............................................................................................................................................
108Supply Voltage
....................................................................................................................................
108Preparation Power On
...............................................................................................................................
108Switch Settings
....................................................................................................................................
108Compressor Heaters
...........................................................................................................................
108Air Flow Switch
....................................................................................................................................
108JOHNSON CONTROLS 8FORM 150.63-NM9 ISSUE DATE: 9/27/2013TABLE OF
CONTENTS (CONTD)SECTION 7 UNIT CONTROLS
..........................................................................................................................
113Introduction
...................................................................................................................................................
113Microprocessor Board
..................................................................................................................................
113Unit Switch
...................................................................................................................................................
114Display
..........................................................................................................................................................
114Keypad
.........................................................................................................................................................
114Battery Back-Up
...........................................................................................................................................
114Transformer.................................................................................................................................................
114Single System Select AndProgramming # Of Compressors
..................................................................................................................
114Unit Status
...........................................................................................................................................
115General Status Messages
...................................................................................................................
115Fault Safety Status Messages
.............................................................................................................
117System Safeties
...........................................................................................................................
117Unit Safeties
.................................................................................................................................
118Unit Warning
........................................................................................................................................
119Oper Data Key
.....................................................................................................................................
121Oper Data Quick Reference List
.........................................................................................................
124Print Key
..............................................................................................................................................
124Operating Data Printout
.......................................................................................................................
124History Printout
....................................................................................................................................
125History Displays
...................................................................................................................................
126Software Version
.................................................................................................................................
128Up and Down Arrow Keys
...................................................................................................................
129Enter/Adv Key
.....................................................................................................................................
129Cooling Setpoints
................................................................................................................................
130Schedule/Advance Day Key
................................................................................................................
132Program Key
.......................................................................................................................................
132460VAC System Trip Volts
..................................................................................................................
134460VAC Unit Trip Volts
........................................................................................................................
134208/230VAC Units
...............................................................................................................................
134Oper Data Quick Reference List
.........................................................................................................
136Options Key
.........................................................................................................................................
137Option 1 Language
...................................................................................................................
137Option 2System Switches(two system units only)
....................................................................
137Option 3 Ambient Control Type
.................................................................................................
137Option 4 Local/Remote Control Type
........................................................................................
138Option 5 Unit Control Mode
......................................................................................................
138Option 6 Display Units
..............................................................................................................
138Option 7 Lead/Lag Type(two system units only)
.....................................................................
138Option 8 Condenser Fan Control
Mode...................................................................................
138Option 9 Manual Override Mode
...............................................................................................
139Option 10 Current Feedback Options Installed
.........................................................................
139Option 11 Power Fail Restart
....................................................................................................
139Option 12 Soft Start Enable/Disable
.........................................................................................
139Option 13 Unit Type
..................................................................................................................
139Option 14 Refrigerant Type
.......................................................................................................
140Option 15 Expansion Valve Type
..............................................................................................
140Option 16 Flash Card Update
...................................................................................................
140Option 17 Remote Temperature Reset
.....................................................................................
140Option 18 Hot Gas Bypass Type
...............................................................................................
141Option 19 Data Logging
.............................................................................................................
141Clock
...................................................................................................................................................
141JOHNSON CONTROLS 9FORM 150.63-NM9 ISSUE DATE: 9/27/2013TABLE OF
CONTENTS (CONTD)SECTION 8 UNIT OPERATION
.........................................................................................................................
143Capacity Control
...........................................................................................................................................
143Suction Pressure Limit Controls
...................................................................................................................
143Discharge Pressure Limit Controls
...............................................................................................................
143Discharge Air Temperature Control
..............................................................................................................
143Suction Pressure Control
.............................................................................................................................
145System Lead/Lag
.........................................................................................................................................
146Compressor Lead/Lag
..................................................................................................................................
146Anti-Recycle Timer
.......................................................................................................................................
146Anti-Coincidence Timer
................................................................................................................................
146Evaporator Blower Control
...........................................................................................................................
146Evaporator Heater Control
...........................................................................................................................
146Pumpdown Control
.......................................................................................................................................
146Load Limiting
................................................................................................................................................
149Compressor Run Status
...............................................................................................................................
149Alarm Status
.................................................................................................................................................
149BAS/EMS Discharge Air Temperature Reset Using A Voltage Or
Current Signal....................................... 150SECTION 9
SERVICE AND TROUBLESHOOTING
..........................................................................................
151Clearing History
Buffers................................................................................................................................
151Service Mode
...............................................................................................................................................
151Service Mode Outputs
...............................................................................................................................
151Service Mode Condensing Unit Configuration
................................................................................................................................................
152Service Mode Analog And DigitalInputs
............................................................................................................................................................
152Control Inputs/Outputs
.................................................................................................................................
153Checking Inputs And Outputs
.......................................................................................................................
155Digital Inputs
........................................................................................................................................
155Discharge Air Temperature Sensor
.....................................................................................................
156Analog Inputs Pressure
....................................................................................................................
156System 1 Discharge Transducer
.........................................................................................................
157System 2 Discharge Transducer
.........................................................................................................
157System 1 Suction Transducer
.............................................................................................................
157System 2 Suction Transducer
.............................................................................................................
157Digital Outputs
.....................................................................................................................................
158Parts
....................................................................................................................................................
159Assembly and Wiring
...........................................................................................................................
159Obtaining a Printout
.............................................................................................................................
159JOHNSON CONTROLS 10FORM 150.63-NM9 ISSUE DATE: 9/27/2013TABLE OF
CONTENTS (CONTD)SECTION 10 MAINTENANCE
...........................................................................................................................
163Important
......................................................................................................................................................
163Compressors
................................................................................................................................................
163Oil Level check
....................................................................................................................................
163Oil Analysis
..........................................................................................................................................
163Condenser Fan Motors
.................................................................................................................................
163Condenser Coils
...........................................................................................................................................
163Operating Parameters
..................................................................................................................................
163On-Board Battery Back-Up
...........................................................................................................................
163Overall Unit Inspection
.................................................................................................................................
163Bacnet, Modbus And Yorktalk 2 Communications
........................................................................................
164BACnet and Modbus Communications
...............................................................................................
167Communications Data Map Notes
.......................................................................................................
167Yorktalk 2 Communications
.................................................................................................................
171Received Data (Control Data)
......................................................................................................
171Transmitted
Data..........................................................................................................................
171JOHNSON CONTROLS 11FORM 150.63-NM9 ISSUE DATE: 9/27/2013LIST OF
FIGURESFIGURE 1 - YCUL Air-Cooled Scroll Compressor Condensing Unit
.......................................................................
17FIGURE 2 - Unit Components
Front........................................................................................................................
23FIGURE 3 - Power Panel Components
...................................................................................................................
24FIGURE 4 - Power Panel / Control Components
....................................................................................................
25FIGURE 5 - Refrigerant Flow Diagram
....................................................................................................................
30FIGURE 6 - Process And Instrumentation Diagram
................................................................................................
31FIGURE 7 - Unit Rigging
.........................................................................................................................................
33FIGURE 8 - Single-Point Supply Connection Terminal Block,
Non-Fused Disconnect Switch Or Circuit Breaker
................................................................................................................................
42FIGURE 9 - Discharge Air Sensor Field Wiring
.......................................................................................................
42FIGURE 10 - Control Wiring
....................................................................................................................................
43FIGURE 11 - Control Wiring Diagram, Single Circuit, Ipu
Ii.....................................................................................
54FIGURE 12 - Control Wiring Diagram, Single Circuit, IPU II
...................................................................................
57FIGURE 13 - Control Wiring Diagram, Dual Circuit, IPU II
......................................................................................
58FIGURE 14 - Control Wiring Diagram, Dual Circuit, IPU II
......................................................................................
60FIGURE 15 - Control Wiring Diagram, Details, Single Circuit
.................................................................................
62FIGURE 16 - Control Wiring Diagram, Details, Dual Circuit
....................................................................................
64FIGURE 17 - Power Wiring, Single Circuit
..............................................................................................................
66FIGURE 18 - Power Wiring, Single Circuit
..............................................................................................................
68FIGURE 19 - Power Wiring, Single Circuit
..............................................................................................................
70FIGURE 20 - Power Wiring, Single Circuit
..............................................................................................................
72FIGURE 21 - Power Wiring, Dual Circuit
.................................................................................................................
75FIGURE 22 - Power Wiring, Dual Circuit
.................................................................................................................
76FIGURE 23 - Connection Wiring, Single Circuit
......................................................................................................
78FIGURE 24 - Connection Wiring, Single Circuit
......................................................................................................
80FIGURE 25 - Connection Wiring, Single Circuit
......................................................................................................
82FIGURE 26 - Connection Wiring, Single Circuit
......................................................................................................
84FIGURE 27 - Connection Wiring, Dual Circuit
.........................................................................................................
87FIGURE 28 - Connection Wiring, Dual Circuit
.........................................................................................................
88FIGURE 29 - Unit Clearances All Models
.............................................................................................................
94FIGURE 30 - Sample Isolator Location Drawing
.....................................................................................................
95FIGURE 31 - Isolator Locations, 60 HZ
...................................................................................................................
96FIGURE 32 - Isolator Locations, 50 HZ
...................................................................................................................
97FIGURE 33 - One Inch Defection Spring Isolator Cross-Reference
.......................................................................
98FIGURE 34 - One Inch Defection Spring Isolators Installation
Instructions............................................................
99FIGURE 35 - Two Inch Defection Seismic Isolator Cross-Reference
...................................................................
100FIGURE 36 - Seismic Isolator Installation And Adjustment
...................................................................................
101FIGURE 37 - Durulene Isolator Cross-Reference
.................................................................................................
102FIGURE 38 - Installation Of Durulene Vibration Isolators
.....................................................................................
103FIGURE 39 - Discharge Air Temperature Control
..................................................................................................
142FIGURE 40 - Suction Pressure Control
.................................................................................................................
143FIGURE 41 - YCUL0045 YCUL0072 Fan Location (Typical)
.............................................................................
145FIGURE 42 - Microboard Layout
...........................................................................................................................
152FIGURE 43 -I/O Board Relay Contact Architecture
.............................................................................................
156FIGURE 44 - Printer To Microboard Electrical Connections
..................................................................................
157FIGURE 45 - Micro Panel Connections
.................................................................................................................
163JOHNSON CONTROLS 12FORM 150.63-NM9 ISSUE DATE: 9/27/2013LIST OF
TABLESTABLE 1 - Fitting Equivalent Lengths
.....................................................................................................................
41TABLE 2 - Refrigerant Piping Charges
...................................................................................................................
41TABLE 3 - Miscellaneous Liquid Line Pressure Drops
...........................................................................................
42TABLE 4 - Refrigerant Line Connections
................................................................................................................
42TABLE 5 - Voltage Limitations
................................................................................................................................
47TABLE 6 - Physical Data (English)
.........................................................................................................................
48TABLE 7 - Physical Data (SI)
..................................................................................................................................
49TABLE 9 - Micro Panel Power Supply
....................................................................................................................
50TABLE 8 - Voltage Range
.......................................................................................................................................
50TABLE 10 - Status Key Messages Quick Reference List
.....................................................................................
120TABLE 11 - Operation Data
..................................................................................................................................
124TABLE 12 - Cooling Setpoints Programmable Limits And Defaults
......................................................................
135TABLE 13 - Program Key Limits And Defaults
......................................................................................................
135TABLE 14 -Setpoints Quick Reference List
........................................................................................................
136TABLE 15 - Options Key Programming Quick Reference List
..............................................................................
142TABLE 16 - Discharge Air Temperature Control For 5 And 6
Compressors (7 And 8 Steps) ................................
144TABLE 17 - Discharge Air Temperature Control For 4 Compressors
(6 Steps) ....................................................
144TABLE 18 -YCUL0045 YCUL0072 Condenser Fan Control Using Outdoor
Ambient Temperature And Dis-charge Pressure (Discharge Pressure
Controls Will Not Function Unless The Optional Discharge Pressure
Transducer Is Installed)
.....................................................................................................
147TABLE 19 - YCUL0045 YCUL0072 Condenser Fan Control Using
Discharge Pressure Only .......................... 147TABLE 20
-YCUL0045 YCUL0072 Low Ambient Condenser Fan Control Discharge
Pressure Control ....... 148TABLE 21 - Compressor Operation Load
Limiting
.............................................................................................
149TABLE 22 -I/O Digital Inputs
...............................................................................................................................
153TABLE 23 -I/O Digital Outputs
............................................................................................................................
153TABLE 24 - I/O Analog Inputs
...............................................................................................................................
153TABLE 25 - I/O analog outputs
.............................................................................................................................
153TABLE 26 -Outdoor Air Sensor Temperature/Voltage/Correlation
.......................................................................
155TABLE 27 -Discharge Air Temp. Sensor
Temperature/Voltage/Resistance
Correlation....................................... 156TABLE 28 -
Pressure Transducers
.......................................................................................................................
157TABLE 29 - Troubleshooting
.................................................................................................................................
160TABLE 30 - Minimum, Maximum And Default Values
...........................................................................................
165TABLE 31 - Values Required For Bas Communication
.........................................................................................
166TABLE 32 - Real Time Error Numbers
..................................................................................................................
166TABLE 33 - Bacnet And Modbus Communications Data Map
..............................................................................
168TABLE 34 - Yorktalk 2 Communications Data Map
...............................................................................................
172JOHNSON CONTROLS 13FORM 150.63-NM9 ISSUE DATE: 9/27/20131SECTION
1 GENERAL EQUIPMENT INFORMATION AND
SAFETYINTRODUCTIONThe15through80Ton(50through280kW)YCUL
modelsareshippedcompletefromthefactoryready for field
installation.The unit is pressure-tested, evacuated and given a
ni-trogen holding charge and includes an initial oil charge (R-410A
refrigerant supplied by others). After assem-bly, an operational
test is performed to assure that each control device operates
correctly.Theunitstructureisheavy-gauge,galvanizedsteel.
Thisgalvanizedsteeliscoatedwithbaked-onpow-der paint which, when
subjected to ASTM B117 1000 hour salt spray testing, yields a
minimum ASTM 1654 ratingof6.Unitsaredesignedinaccordancewith NFPA
70 (National Electric Code), ASHRAE/ANSI 15 Safety code for
mechanical refrigeration, and are cETL listed. All units are
produced at an ISO 9000-registered
facility.COMPRESSORSThecondensingunithassuction-gascooled,hermet-ic,scrollcompressors.Thecompressorsincorporate
acompliantscrolldesigninboththeaxialandradial
direction.Allrotatingpartsofthecompressorsare
staticallyanddynamicallybalanced.Alargeinternal volume and oil
reservoir provides greater liquid toler-ance. Compressor crankcase
heaters are also included for extra protection against liquid
migration.CONDENSERCoilsFinandtubecondensercoilsofseamless,internally-enhanced,high-condensing-coefficient,corrosionre-sistantcoppertubesarearrangedinstaggeredrows,
mechanicallyexpandedintoaluminumfins.Integral
subcoolingisincluded.Thedesignworkingpressure of the coil is 650
psig (45 barg).Low Sound
FansThecondenserfansarecomposedofcorrosionresis-tant aluminum hub
and composite blades molded into a low noise airfoil section. They
are designed for maxi-mum efficiency and are statically and
dynamically bal-ancedforvibration-freeoperation.Theyaredirectly
driven,andpositionedforverticalairdischarge.The fan guards are
constructed of heavy-gauge, rust-resis-tant, PVC (polyvinyl
chloride)-coated steel wire.MotorsThe fan motors are Totally
Enclosed Air-Over, squirrel-cage type, current protected. They
feature ball bearings that are double-sealed and permanently
lubricated.REFRIGERANT CIRCUITAll unit piping will be copper with
brazed joints. The liquid line will include a field connection
shutoff valve withchargingportlocatedoneachcondensercircuit.
Suctionlineconnectionsareprovidedoneachrefrig-eration circuit. A
filter drier and sight glass are shipped loose for field
installation on each refrigerant
circuit.Allexpansionvalves,liquidlinesolenoidvalves, refrigerant,
and refrigerant field piping are supplied by others.WARRANTYJohnson
Controls warrants all equipment and materials against defects in
workmanship and materials for a pe-riod of eighteen months from
date of shipment, unless labor or extended warranty has been
purchased as part of the contract.The warranty is limited to parts
only replacement and shipping of any faulty part, or sub-assembly,
which has failed due to poor quality or manufacturing errors. All
claims must be supported by evidence that the failure
hasoccurredwithinthewarrantyperiod,andthatthe unit has been
operated within the designed parameters specified.All warranty
claims must specify the unit model, serial number, order number and
run hours/starts. Model and serial number information is printed on
the unit identi-fication
plate.Theunitwarrantywillbevoidifanymodification to
theunitiscarriedoutwithoutpriorwrittenapproval from Johnson
Controls.For warranty purposes, the following conditions must be
satisfied:The initial start of the unit must be carried out by
trainedpersonnelfromanAuthorizedJohnson Controls Service Center
(see SECTION 6 COM-MISSIONING).Onlygenuine
YORKapprovedspareparts,oils, coolants, and refrigerants must be
used. JOHNSON CONTROLS 14FORM 150.63-NM9 ISSUE DATE:
9/27/2013SECTION 1 GENERAL EQUIPMENT INFORMATION AND SAFETYAll the
scheduled maintenance operations detailed in this manual must be
performed at the specifed times by suitably trained and qualifed
personnel (see Section 10 MAINTENANCE).Failure to satisfy any of
these conditions will au-tomatically void the warranty (see
Warranty Pol-icy).SAFETY AND QUALITYStandards for Safety and
QualityYCULUNITSaredesignedandbuiltwithinanISO
9002accrediteddesignandmanufacturingorganiza-tion. The condensing
units comply with the applicable sections of the following
Standards and Codes:ANSI/ASHRAEStandard15-SafetyCodefor Mechanical
Refrigeration.ANSI/NFPAStandard70-NationalElectrical Code
(N.E.C.).ASME Boiler and Pressure Vessel Code- Section VIII
Division 1.ARIStandard550/590-PositiveDisplacement Compressors and
Air Cooled Rotary Screw Water Chilling Packages.ASHRAE 90.1- Energy
Effciency compliance.ARI 370- Sound Rating of Large Outdoor
Refrig-eration and Air Conditioning
Equipment.ConformtoIntertekTestingServices,formerly
ETL,forconstructionofcondensingunitsand provide E.T.L./c E.T.L.
Listing label.Inaddition,thecondensingunitsconformtoUnder-writers
Laboratories (U.L.) for construction of chillers and provide
U.L./cU.L. Listing Label.Responsibility for SafetyEvery care has
been taken in the design and
manufac-tureoftheunittoensurecompliancewiththesafety
requirementslistedabove.However,theindividual
operatingorworkingonanymachineryisprimarily responsible
for:Personal safety, safety of other personnel, and the
machinery.Correct utilization of the machinery in accordance with
the procedures detailed in the manuals.ABOUT THIS MANUALThe
following terms are used in this document to alert the reader to
areas of potential hazard.A WARNINGisgiveninthisdocument to
identify a hazard, which could lead to
personalinjury.Usuallyaninstruction will be given, together with a
brief expla-nation and the possible result of ignoring the
instruction.ACAUTIONidentifesahazardwhich
couldleadtodamagetothemachine, damage to other equipment and/or
envi-ronmental pollution. Usually an
instruc-tionwillbegiven,togetherwithabrief
explanationandthepossibleresultof ignoring the
instruction.ANOTEisusedtohighlightadditional
information,whichmaybehelpfulto you but where there are no special
safety implications.Thecontentsofthismanualincludesuggestedbest
working practices and procedures. These are issued for
guidanceonly,andtheydonottakeprecedenceover the above stated
individual responsibility and/or local safety
regulations.Thismanualandanyotherdocumentsuppliedwith
theunitarethepropertyofJohnsonControlswhich
reservesallrights.Theymaynotbereproduced,in
wholeorinpart,withoutpriorwrittenauthorization from an authorized
Johnson Controls representative.MISUSE OF EQUIPMENTSuitability for
ApplicationThe unit is intended for DX cooling applications and is
not suitable for purposes other than those specified in these
instructions. Any use of the equipment other than its intended use,
or operation of the equipment contrary
totherelevantproceduresmayresultininjurytothe operator, or damage
to the
equipment.Theunitmustnotbeoperatedoutsidethedesignpa-rameters
specified in this manual.JOHNSON CONTROLS 15SECTION 1 GENERAL
EQUIPMENT INFORMATION AND SAFETYFORM 150.63-NM9 ISSUE DATE:
9/27/20131Structural SupportStructural support of the unit must be
provided as in-dicated in these instructions. Failure to provide
proper support may result in injury to the operator, or damage to
the equipment and/or building.Mechanical Strength The unit is not
designed to withstand loads or stresses from adjacent equipment,
pipework or structures.Ad-ditional components must not be mounted
on the unit. Any such extraneous loads may cause structural failure
and may result in injury to the operator, or damage to the
equipment.General AccessThere are a number of areas and features,
which may be a hazard and potentially cause injury when working on
the unit unless suitable safety precautions are taken. It is
important to ensure access to the unit is restricted to suitably
qualified persons who are familiar with the
potentialhazardsandprecautionsnecessaryforsafe
operationandmaintenanceofequipmentcontaining high temperatures,
pressures and voltages.Pressure
SystemsTheunitcontainsrefrigerantvaporandliquidunder
pressure,releaseofwhichcanbeadangerandcause injury.The user should
ensure that care is taken during installation, operation and
maintenance to avoid dam-age to the pressure system. No attempt
should be made togainaccesstothecomponentpartsofthepressure system
other than by suitably trained and qualified
per-sonnel.ElectricalTheunitmustbegrounded.Noinstallationormain-tenanceworkshouldbeattemptedontheelectrical
equipmentwithoutfirstswitchingpowerOFF,isolat-ingandlocking-offthepowersupply.Servicingand
maintenanceonliveequipmentmustonlybeper-formed by suitably trained
and qualified personnel.No
attemptshouldbemadetogainaccesstothecontrol panel or electrical
enclosures during normal operation of the unit.Rotating PartsFan
guards must be fitted at all times and not removed unless the power
supply has been isolated. If ductwork
istobefitted,requiringthewirefanguardstobere-moved,alternativesafetymeasuresmustbetakento
protect against the risk of injury from rotating fans.Sharp
EdgesThe fins on the air-cooled condenser coils have sharp
metaledges.Reasonablecareshouldbetakenwhen
workingincontactwiththecoilstoavoidtheriskof
minorabrasionsandlacerations. Theuseofglovesis
recommended.Framerails,brakes,andothercomponentsmayalso
havesharpedges.Reasonablecareshouldbetaken when working in contact
with any components to avoid risk of minor abrasions and
lacerations.Refrigerants and OilsRefrigerants and oils used in the
unit are generally non-toxic, non-flammable and non-corrosive, and
pose no special safety hazards. Use of gloves and safety glasses
is, however, recommended when working on the unit.
Thebuildupofrefrigerantvapor,fromaleakforex-ample, does pose a risk
of asphyxiation in confined or enclosed spaces and attention should
be given to good ventilation.High Temperature and Pressure
CleaningHightemperatureandpressurecleaningmethods
(e.g.steamcleaning)shouldnotbeusedonanypart of the pressure system
as this may cause operation of
thepressurereliefdevice(s).Detergentsandsolvents, which may cause
corrosion, should also be avoided.Emergency ShutdownIn case of
emergency, the control panel is fitted with a Unit Switch to stop
the unit in an emergency. When op-erated, it removes the low
voltage 120 VAC electrical
supplyfromtheinvertersystem,thusshuttingdown the unit.JOHNSON
CONTROLS 16FORM 150.63-NM9 ISSUE DATE: 9/27/2013SECTION 1 GENERAL
EQUIPMENT INFORMATION AND SAFETYTHIS PAGE INTENTIONALLY LEFT
BLANKJOHNSON CONTROLS 17SECTION 2 PRODUCT DESCRIPTIONFORM
150.63-NM9 ISSUE DATE: 9/27/20132SECTION 2 PRODUCT
DESCRIPTIONINTRODUCTIONJohnsonControls YORKSeries40
Air-CooledScroll Condensing Units provide chilled water for all air
con-ditioning applications using central station air handling
orterminalunits.Theyarecompletelyself-contained and are designed
for outdoor (roof or ground level) in-stallation. Each unit
includes hermetic scroll compres-sors, a liquid cooler, air cooled
condenser, and a weath-er resistant microprocessor control center,
all mounted on a pressed steel base.The units are completely
assembled with all
intercon-nectingrefrigerantpipingandinternalwiring,ready for field
installation.The unit is pressure-tested, evacuated and given a
ni-trogen holding charge and includes an initial oil charge (R-410A
refrigerant supplied by others). After assem-bly, a operational
test is performed to assure that each control device operates
correctly.Theunitstructureisheavy-gauge,galvanizedsteel.
Thisgalvanizedsteeliscoatedwithbaked-onpow-der paint which, when
subjected to ASTM B117 1000 hour, salt spray testing, yields a
minimum ASTM 1654 ratingof6.Unitsaredesignedinaccordancewith NFPA
70 (National Electric Code), ASHRAE/ANSI 15 Safety code for
mechanical refrigeration, and are cETL listed. All units are
produced at an ISO 9000-registered
facility.Allexposedpowerwiringisroutedthroughliquid-tight,
non-metallic conduit.GENERAL SYSTEM DESCRIPTIONCompressorsThe
condensing unit has suction-gas cooled, hermetic,
scrollcompressors.The
YCULcompressorsincorpo-rateacompliantscrolldesigninboththeaxialand
radialdirection.Allrotatingpartsarestaticallyand dynamically
balanced. A large internal volume and oil
reservoirprovidesgreaterliquidtolerance.Compres-sorcrankcaseheatersarealsoincludedforextrapro-tection
against liquid migration.An annular discharge check valve and
reverse vent as-semblyprovideslowpressuredrop,silentshutdown, and
reverse rotation
protection.CondenserCoilsFinandtubecondensercoilsofseamless,in-ternally-enhanced,
high-condensing-coefficient,
corro-sionresistantcoppertubesarearrangedinstaggered rows,
mechanically expanded into aluminum fins. Inte-gral subcooling is
included. The design working pres-sure of the coil is 650 PSIG (45
bar).FIGURE 1 - YCUL AIR-COOLED SCROLL COMPRESSOR CONDENSING
UNITJOHNSON CONTROLS 18FORM 150.63-NM9 ISSUE DATE: 9/27/2013SECTION
2 PRODUCT DESCRIPTIONLow Sound
FansThecondenserfansarecomposedofcorrosionresis-tant aluminum hub
and composite blades molded into a low noise airfoil section. They
are designed for maxi-mum efficiency and are statically and
dynamically bal-ancedforvibration-freeoperation.Theyaredirectly
driven,andpositionedforverticalairdischarge.The fan guards are
constructed of heavy-gauge, rust-resis-tant, PVC (polyvinyl
chloride)-coated steel wire.MotorsThe fan motors are Totally
Enclosed Air-Over, squirrel-cage type, current protected. They
feature ball bearings that are double-sealed and permanently
lubricated.MICROCOMPUTER CONTROL
CENTERAllcontrolsarecontainedinaNEMA3R/12cabinet with hinged outer
door and include Liquid Crystal
Dis-play(LCD)withLightEmittingDiode(LED)back-lighting for outdoor
viewing and includes:Two display linesTwenty characters per
lineDisplay/Print Colorcoded12-buttonnon-tactilekeypadwithsec-tions
for display and print of typical information:Suction temperatures
(optional)Ambient temperatureSystem pressures (each
circuit)Operating hours and starts (each compressor)Print calls up
to the liquid crystal displayOperating data for the
systemsHistoryoffaultshutdowndataforuptothelast six fault shutdown
conditions.An RS-232 port, in conjunction with the press-to-print
button, is provided to allow hard copy print-outs via a separate
printer (by others).EntryThis section is used to enter setpoints or
modify system values.SetpointsUpdating can be performed to:Suction
pressure settingSuction pressure control zoneRemote reset
temperature rangeSet daily schedule/holiday for start/stopManual
override for servicingLow and high ambient cutoutsNumber of
compressorsLow suction pressure cutoutHigh discharge pressure
cutoutAnti-recycle timer (compressor start cycle
time)Anti-coincident timer (delay compressor starts) UnitThis
section is used to:Set clockSet optionsSet unit optionSet unit
control for Discharge Air Temperature Control or for Suction
Pressure Control (requires Suction Pres-sure Transducers) is
standard. Unit On/Off
SwitchThemicroprocessorcontrolcenteriscapableof display ing the
following:Suction temperatures (optional)Low ambient temperature
cutout settingEnglish or Metric dataSuction pressure cutout
settingEach system suction pressure System discharge
pressureJOHNSON CONTROLS 19SECTION 2 PRODUCT DESCRIPTIONFORM
150.63-NM9 ISSUE DATE: 9/27/20132Discharge Air Temperature Reset
via a YORKISNDDCorBuildingAutomationSystem(by others)
via:apulsewidthmodulated(PWM)inputas standarda 4 to 20ma or 0 to
10VDC input, or contact closure with the optional B.A.S. interface
op-tionAnti-recycle timer status for each systemAnti-coincident
system start timer conditionCompressor run statusNo cooling load
conditionDay, date and timeDaily start/stop timesHoliday
statusAutomaticormanualsystemlead/lagcontrol (Discharge Air
Temperature control
only)Automaticlead/lagofcompressorswithinasys-temCompressor starts
and operating hours (each com-pressor)Status of hot gas valves, and
fan operationRun permissive statusNumber of compressors
runningLiquid solenoid valve statusLoad and unload timer
statusProvisionsareincludedforpumpdownatshutdown,
optionalremotedischargeairtemperaturereset,and
twostepsofdemandloadlimitingfromanexternal
buildingautomationsystem.Unitalarmcontactsare standard.The
operating program is stored in non-volatile mem-ory (EPROM) to
eliminate condensing unit failure due to AC powered failure/battery
discharge. Programmed
setpointsareretainedinlithiumbattery-backedRTC memory for 5 years
minimum.BUILDING AUTOMATION SYSTEMINTERFACEThe Microprocessor Board
can accept a 4 to 20ma, 0 to 10VDC or contact closure input to
reset the discharge airtemperaturefromaBuilding AutomationSystem.
Only one of the following remote communications op-tions can be
offered on a unit at a time: BAS Interface, Remote Control Panel or
Multi-unit Sequence Control (Factory
Mounted).Thestandardunitcapabilitiesincluderemote
start-stop,remotewatertemperatureresetviaa PWM 4 to 20ma or 0 to
10VDC input signal or up to two stages of demand (load) limiting
depending on model.Thestandardcontrolpanelcanbedirectlycon-nected
to a Johnson Controls Building Automated
System.COMMUNICATIONSNativecommunicationcapabilityforBACnet (MS/TP)
and ModbusOptionalcommunicationavailableforN2and LON via eLink
optionPOWER PANELEach panel contains:Compressor power
terminalsCompressor motor starting contactors per Interna-tional
Electrotechnical Commission
(I.E.C.).Controlpowerterminalstoacceptincomingfor 115-1-60 control
powerFan contactors and overload current
protectionThepowerwiringisroutedthroughliquid-tightcon-duit to the
compressors and fans.JOHNSON CONTROLS 20FORM 150.63-NM9 ISSUE DATE:
9/27/2013SECTION 2 PRODUCT DESCRIPTIONACCESSORIES AND
OPTIONSElectrical OptionsCompressor Power
ConnectionsSingle-pointterminalblockconnection(s)areprovid-edasstandard.Thefollowingpowerconnectionsare
availableasfactorymountedoptions.(SeeElectrical Data for specific
voltage and options availability.)Single-Point Supply Terminal
Block (standard on YCUL models). Includes enclosure, terminal-block
and interconnecting wiring to the compressors. Separate external
protection must be supplied, by others, in the incoming
compres-sor-powerwiring.Thisoptioncannotbeincludedif
eithertheSinglePointNon-FusedDisconnectSwitch or Single-Point
Circuit Breaker options have been in-cluded.Single-Point Non-Fused
Disconnect
SwitchUnit-mounteddisconnectswitchwithexternal,lock-ablehandleincompliancewithArticle440-14of
N.E.C., can be supplied to isolate the unit power
volt-ageforservicing.Separateexternalfusingmustbe
supplied,byothersinthepowerwiring,whichmust comply with the
National Electrical Code and/or local codes.Single-Point Circuit
BreakerA unit mounted circuit breaker with external, lockable
handle(incompliancewithN.E.C.Article440-14),
canbesuppliedtoisolatethepowervoltageforser-vicing.(ThisoptionincludestheSingle-PointPower
connection.)Control
TransformerThistransformerconvertsunitpowervoltageto115-1-60(0.5or1.0KVAcapacity).Factorymounting
includesprimaryandsecondarywiringbetweenthe transformer and the
control panel.Power Factor Correction
CapacitorsThesefactorymountedcapacitorswillcorrectunit compressor
to a power factor between 0.90 and 0.95.Control OptionsAmbient Kit
(Low)Units will operate to 25F (-4C). This factory mounted
accessory includes all necessary components to permit
chilleroperationto0F(-18C). Thisoptionincludes the Discharge
Pressure Transducer / Readout Capabil-ity option. For proper head
pressure control in applica-tions below 25F (-4C), where wind gusts
may exceed five mph, it is recommended that factory mounted
op-tionalCondenserLouveredEnclosurePanelsalsobe included.Ambient
Kit (High)This factory mounted kit is required if units are to
op-eratewhentheambienttemperatureisabove110F
(43C)andincludesdischargepressuretransducers.
ThisoptionincludesthefactorymountedDischarge Pressure Transducer /
Readout Capability option. Building Automation System InterfaceThe
factory addition of a Printed Circuit Board to ac-cept a 4 to 20ma,
0 to10VDC or contact closure input
toresettheleavingchillerliquidtemperaturefroma Building
AutomationSystem.Onlyoneoffollowing
optionscanbeofferedonaunitatatime:BAS,Re-moteControlPanelorMulti-unitSequenceControl.
(Factory-Mounted)Thestandardunitcapabilitiesin-clude remote
start/stop, remote water temperature reset via a PWM input signal
or up to two steps of demand
(load)limitingdependingonmodel.Thestandard
controlpanelcanbedirectlyconnectedtoaJohnson Controls Building
Automated System via the standard onboard RS485 communication
port.Language LCD and Keypad
DisplaySpanish,French,andGermanunitLCDcontrolsand
keypaddisplayareavailable;howeverthestandard language is
English.DISCHARGE PRESSURE TRANSDUCERS AND READOUT CAPABILITYThe
addition of factory mounted pressure transducers allows models to
sense and display discharge pressure.
Thisisrecommendedforbrinechillingapplications. This option is
included with either the low or high am-bient kits.JOHNSON CONTROLS
21SECTION 2 PRODUCT DESCRIPTIONFORM 150.63-NM9 ISSUE DATE:
9/27/20132Suction Pressure
TransducersThistransducerpermitstheunittosenseanddisplay suction
pressure. This capability is standard on YCUL models.Motor Current
ModuleThis option allows the monitoring of compressor motor current
and provides extra protection against
compres-sorreverserotation,phase-lossandphaseimbalance.
Thisfactorymountedoptionconsistsofonemodule per electrical system.
Multi-Unit SequencingAseparatesequencingcontrolcenterisprovidedto
handlesequencingcontrolofuptoeightchillersin
parallelbasedonmixedliquidtemperature(intercon-nectingwiringbyothers).Theonlyoneoffollowing
factory mounted options can be offered on a unit at a
time:BAS,RemoteControlPanelorMulti-UnitSe-quence Control.
Compressor and Piping OptionsChicago Code Relief
ValvesUnitwillbeprovidedwithreliefvalvestomeetChi-cago code
requirements. (Factory-Mounted)Service Isolation
ValveServiceisolationvalvesarestandardtounit.Thisin-cludesasystemhighpressurereliefvalveorinter-nalcompressorreliefmechanismincompliancewith
ASHRAE 15. (Factory-Mounted)Hot Gas
By-PassPermitscontinuous,stableoperationatcapacitiesbe-low the
minimum step of compressor unloading to as
lowas5%capacity(dependingonboththeunitand operating conditions) by
introducing an artificial load on the cooler. Hot gas by-pass is
installed on only
re-frigerantsystem#1ontwo-circuitedunits.(Factory-Mounted)Condenser
and Cabinet
OptionsCondensercoilprotectionagainstcorrosiveenviron-mentsisavailablebychoosinganyofthefollowing
options. For additional application recommendations, refer to Form
150.12-ES1. (Factory-Mounted)Pre-Coated Fin Condenser
CoilsTheunitscoilsareconstructedwithepoxycoated
aluminumfins.Thiscanprovidecorrosionresistance comparable to
copper-fin coils in typical seashore loca-tions. Either these or
the post-coated coils (below) are recommended for units being
installed at the seashore or where salt spray may hit the
unit.Post-Coated Dipped Condenser CoilsThe units coils are
constructed with dipped-cured con-densercoils.
Thisisthechoiceforcorrosiveapplica-tions(withtheexceptionofstrongalkalis,oxidizers
andwetbromine,chlorineandfluorineinconcentra-tions greater than 100
ppm).Copper Fin Condenser CoilsThe units coils are constructed with
copper fins. (This is not recommended for units in areas where they
may be exposed to acid rain.)Enclosure Panels
(Unit)Tamperproofenclosurepanelspreventunauthorized
accesstounits.Enclosurepanelscanprovideanaes-theticallypleasingalternativetoexpensivefencing.
Additionally, for proper head pressure control, Johnson Controls
recommends the use of louvered panels.Louvered Panels (Full
Unit)Louvered panels surround the front, back, and sides of
theunit.Theypreventunauthorizedaccessandvisu-allyscreenunitcomponents.Unrestrictedairflowis
permitted through generously sized louvered openings. This option
is applicable for any outdoor design ambi-ent temperature up to
115F (46C). (Factory-Mount-ed.)Sound
AttenuationOneorbothofthefollowingfactorymountedsound attenuation
options are recommended for residential or other similar
sound-sensitive locations. Louvered Pan-els can be ordered for
winter applications where wind
gustsmayexceedfivemilesperhour.Thefollowing types of enclosure
options are available:JOHNSON CONTROLS 22FORM 150.63-NM9 ISSUE
DATE: 9/27/2013SECTION 2 PRODUCT DESCRIPTIONCompressor Acoustic
Sound BlanketEachfactorymountedcompressorisindividuallyen-closed by
an acoustic sound blanket. The sound
blan-ketsaremadewithonelayerofacousticalabsorbent
textilefiberof5/8(15mm)thickness;onelayerof anti-vibrating heavy
material thickness of 1/8 (3mm).
BothareclosedbytwosheetsofweldedPVC,rein-forced for temperature and
UV resistance. Ultra Quiet FanLower RPM, 8-pole fan motors are used
with steeper-pitch fans on these factory mounted devices. Vibration
IsolatorsLeveladjusting,springtype1"(25.4mm)orseismic deflection or
neoprene pad isolators for mounting un-der unit base rails.
(Field-Mounted)UNIT COMPONENTS FIGURE 2 - UNIT COMPONENTS
FRONTMICROPANEL FANSCOMPRESSORSCONDENSER COILSJOHNSON CONTROLS
23SECTION 2 PRODUCT DESCRIPTIONFORM 150.63-NM9 ISSUE DATE:
9/27/20132FIGURE 3 - POWER PANEL COMPONENTSLD13247COMPRESSOR
CONTACTORSXTBF1FAN CONTACTORSFAN CONTACTORCOMPRESSOR OVERLOADSFAN
FUSESDISCONNECTSWITCHPOWER PANEL COMPONENTSJOHNSON CONTROLS 24FORM
150.63-NM9 ISSUE DATE: 9/27/2013SECTION 2 PRODUCT DESCRIPTIONPOWER
PANEL / CONTROL COMPONENTSFIGURE 4 - POWER PANEL / CONTROL
COMPONENTSCOMPRESSOR OVERLOADSCOMPRESSOR CONTACTORSFAN
CONTACTORSFAN FUSESCONTROL RELAYMICROCOMPUTER CONTROL CENTER
MICROPANELDISPLAYKEYPADXTBC1XTBC2XTBF2MICROBOARDLD13248JOHNSON
CONTROLS 25SECTION 2 PRODUCT DESCRIPTIONFORM 150.63-NM9 ISSUE DATE:
9/27/20132PRODUCT IDENTIFICATION NUMBER (PIN)BASIC UNITBASIC MODEL
NUMBERYCUL0045EE46XEABASE PRODUCT TYPELU : UnitYC :YORK
Condensing:ScrollVOLTAGE/STARTERX1 7 :200 / 3 / 602 8 :230 / 3 /
604 0 :380 / 3 / 604 6 :460 / 3 / 605 8 :575 / 3 / 605 0 :380-415 /
3 / 50:Across the Line DESIGN/DEVELOPMENT LEVELE :Design SeriesA
:Engineering Changeor PIN LevelE :High EfficiencyUNIT DESIGNATORE
:R-410AREFRIGERANT NOMINAL CAPACITYNominal Capacity1 2 3 4 5 6 7 8
9 10 11 1213 14 15FEATURE FEATURE DESCRIPTION OPTION OPTION
DESCRIPTIONMODEL Model (PIN 1-4) YCUL YCULCAP Capacity (PIN
5-8)0020 00200024 00240031 00310035 00350045 00450051 00510055
00550065 00650072 0072UNIT Unit Designator (PIN 9) E High
EffciencyREF Refrigerant (PIN 10) E R-410AVOLTS Voltage (PIN 11
& 12)17 200/3/6028 230/3/6040 380/3/6046 460/3/6050
380-415/3/5058 575/3/60STARTER Starter (PIN 13) X Across The Line
StarterDESIGN Design Series (PIN 14) E Design Series EDEV
Development Level (PIN 15) A Development Level APOWER Power Field
(PIN 16 & 17)SX Single Point Terminal BlockSD Single Point
Non-Fused DisconnectBX Single Point Circuit BreakerQQ Special Power
Option RequiredTRANS Cntrl Transformer (PIN 18)X No Control
Transformer RequiredT Control Transformer RequiredQ Special Control
Transformer RequiredJOHNSON CONTROLS 26FORM 150.63-NM9 ISSUE DATE:
9/27/2013SECTION 2 PRODUCT DESCRIPTIONPRODUCT IDENTIFICATION NUMBER
(PIN) (CONT)FEATURE FEATURE DESCRIPTION OPTION OPTION
DESCRIPTIONPFC Power Factor Capacitor (19)X No Power Capacitor
RequiredC Power Capacitor RequiredQ Special Power Capacitor
RequiredAMB Ambient Kits (PIN 20)H High Ambient (standard)A Both
Low And High Ambient (Low Ambient kit required)Q Special Ambient
Kit RequiredBAS Bas Reset/Offset (PIN 21)X No BAS Reset/Offset
RequiredM ISN Microgateway RequiredT BAS Reset/Offset RequiredQ
Special BAS Reset/Offset RequiredLCD Language (PIN 22)X EnglishS
SpanishF FrenchG GermanQ Special Language RequiredRDOUT Readout
Kits (PIN 23)R Discharge Pressure Readout (standard)Q Special
Pressure Readout RequiredSAFETY Safety Codes (PIN 24) L N American
Safety Code (cUL/cETL)SENSOR PIN 25X No Option RequiredQ Special
QuotePUMP Motor Current Module (PIN 26)X No Motor Current Readout
RequiredC Motor Current ReadoutQ Special QuoteREMOTE Remote Panel
(PIN 27)X No Remote Panel RequiredO Opiview Remote Panel RequiredQ
Special Remote Panel RequiredSEQ Sequence Kit (PIN 28)X No Sequence
Kit RequiredS Sequence Kit Required = {SEQ/S}Q Special Sequence Kit
RequiredTEMP Suction Temp (PIN 29,30)NUM Suction Temp = {TEMP/NUM}
DegreesQQ Special LWT RequirementsCHICAGO Chicago Code Kit (PIN
31)X Service Isolation Valves B Both Chicago Code and Serv
IsolationQ Special Chicago Code Kit RequiredVALVES Valves (PIN 32)X
Standard Valves ReqdQ Special Optional Valves ReqdHGBP Hot Gas
Bypass (PIN 33)X No Hot Gas Bypass Required1 Hot Gas Bypass
Required - 1 Circuit2 Hot Gas Bypass Required - 2 CircuitsQ Special
Hot Gas Bypass Required GAUGE PIN 34X No Option RequiredQ Special
QuoteOVERLOAD PIN 35X No Option RequiredQ Special QuoteJOHNSON
CONTROLS 27SECTION 2 PRODUCT DESCRIPTIONFORM 150.63-NM9 ISSUE DATE:
9/27/20132FEATURE FEATURE DESCRIPTION OPTION OPTION DESCRIPTIONPIN
36 PIN 36X No Option RequiredQ Special QuoteHTR Crankcase Heater
(Pin 37)X Crankcase Heater StandardQ Special Crankcase Heater
RequiredDWP DWP (PIN 38)X No Option RequiredQ Special QuoteINS
Insulation (PIN 39)X No Option RequiredQ Special QuoteFLANGES
Flanges (PIN 40)X No Option RequiredQ Special QuoteFLOW Flow Switch
(PIN 41)X No Option RequiredQ Special QuoteVESSEL Vessel Codes (PIN
42)X No Option RequiredQ Special QuoteCLR Cooler (PIN 43)X No
Option RequiredQ Special QuotePIN44 PIN 44X No Option RequiredQ
Special QuoteCOILS Coils (PIN 45)X Aluminum CoilB Pre-Coated Fin
CoilC Copper CoilP Post-Coated Dipped CoilQ Special CoilPIN46 PIN
46X No Option RequiredQ Special QuoteFANMOTORS Fan Motors (PIN 47)X
TEAO Fan MotorsQ Special Fan Motors RequiredENCL Enclosure Panels
(PIN 48)1 Wire Enclosures - Factory7 Louvered Enclosure - FactoryQ
Special Enclosure PanelsACOUSTIC Acoustic Blanket (PIN 49)X No
Acoustic Blanket RequiredB Acoustic Blanket RequiredQ Special
Acoustic Blanket RequiredSRDOCS SR Documents (PIN 50)X No Documents
RequiredA Base, Material and Witness DocumentsB Base DocumentM Base
and Material DocumentsW Base and Witness DocumentsQ Special
QuotePIN51 PIN 51X No Option RequiredQ Special QuoteFANS Sound Fans
(PIN 52)X Standard Low Sound Fans RequiredL Ultra Low Sound Fans
RequiredQ Special Sound Fans RequiredPRODUCT IDENTIFICATION NUMBER
(PIN) (CONTD)JOHNSON CONTROLS 28FORM 150.63-NM9 ISSUE DATE:
9/27/2013SECTION 2 PRODUCT DESCRIPTIONFEATURE FEATURE DESCRIPTION
OPTION OPTION DESCRIPTIONPAINT PIN 53X No Option RequiredQ Special
QuoteISOL Vibration Isolators (PIN 54)X No Isolators Required1 1"
Defection Isolators RequiredN Neoprene Isolators RequiredS Seismic
Isolators RequiredQ Special Isolators RequiredWARRANTY Warranty
(PIN 55) Marketing Purposes Only!REFWTY Refrigerant Wty (PIN 56)
Marketing Purposes Only!SHIP Ship Instructions (PIN 57)X No
Containerization requiredA Buy American Act ComplianceBBoth Buy
American Act Compliance and Container Shipping Kit (Factory Prep)C
Container Shipping Kit (Factory Load)P Container Shipping Kit
(Factory Prep)Q Special QuotePIN 58 PIN 58 Marketing Purposes
Only!PKG Pump package (PIN 59)X No Option RequiredQ Special
QuotePKGOPT Pump Package Options (PIN 60)X No Option RequiredQ
Special QuoteMFG Plant of Mfg (PIN 61) R Plant Of Manufacture -
MonterreyLOC Mfg locationCUR Curitiba, BrazilMEX Mexico, ESMTY
Monterrey, BESAT San Antonio, TexasYW YorkWorks versionCV Yorkworks
Confguration Version {YW/CV}UV Yorkworks Upload Version {YW/UV}SQ
Special quote Q Special QuotePRODUCT IDENTIFICATION NUMBER (PIN)
(CONTD)JOHNSON CONTROLS 29SECTION 2 PRODUCT DESCRIPTIONFORM
150.63-NM9 ISSUE DATE: 9/27/20132LD04284AREFRIGERANT FLOW
DIAGRAMFIGURE 5 - REFRIGERANT FLOW DIAGRAM2 OR 3 COMPRESSORS PER
SYSTEMOIL EQUALIZINGLINEAIR COOLED CONDENSERSSERVICE VALVEOPTIONAL
DISCHARGEPRESSURE TRANSDUCERHIGH PRESSURECUTOUT SWITCHLOW PRESSURE
SWITCH ORSUCTION PRESSURE TRANSDUCERLIQUID LINE SERVICE VALVELIQUID
LINESOLENOID VALVE** TXVSIGHT GLASS /MOISTURE INDICATORSOLENOID
OPERATEDHOT GAS BYPASS VALVE*YCUL REFRIGERANT FLOW DIAGRAMNOTE:
YCUL0046-0090 HAVE TWO REFRIGERANT SYSTEMS* HOT GAS OPTION - SYSTEM
1 ONLYLIQUID LINEFILTER DRIEREVAP.AIR FLOWDISCHARGE AIRTEMPERATURE
SENSOROPTIONAL SUCTIONTEMP SENSORFACTORY PIPINGFIELD PIPINGTT**One
TXV and Liquid Line Solenoid shown for illustration purposes.
Actual refrigerant piping may vary depending on evaporator
circuiting.(OPTIONAL)SERVICEVALVE(OPTIONAL)YCULYCUL0045-0072DX
COILJOHNSON CONTROLS 30FORM 150.63-NM9 ISSUE DATE: 9/27/2013SECTION
2 PRODUCT DESCRIPTIONFIGURE 6 - PROCESS AND INSTRUMENTATION
DIAGRAMPROCESS AND INSTRUMENTATION DIAGRAMPSZCPR-1 ZCPR-2
ZCPR-3DVHPLHPCPDVLPC PCondenserFans Fans-YLLSVSTSee P.R.V
.OptionsCompressorsControl Functions:DV - Display ValueCHT -
Chilled Liquid TemperatureHPC- High Pressure CutoutLPC- Low
Pressure CutoutHPL - High Pressure Load LimitingLTC- Low
Temperature CutoutSPSTAmbient Air SensorDVHTCLTC585 PSIG650 PSIG450
PSIGEvaporator CoilPressure Relief Valve (ZP180 Scroll Only)
*Service (Ball) ValveExpansion ValveSolenoid ValveSight GlassSensor
Pressure or TemperatureService (Stop) Access ValvePressure
SwitchFilter Drier (Removable Core)Components:* Smaller Compressor
Scrolls Utilize Internal
Reliefs.Lowpressureliquidrefrigerantentersthecoolerand
isevaporatedandsuperheatedbytheheatenergyab-sorbedfromthechilledliquidpassingthroughthe
coolershell.Lowpressurevaporentersthecompres-sorwherepressureandsuperheatareincreased.The
high pressure vapor is fed to the air cooled condenser coil and
fans where the heat is removed. The fully con-densed and subcooled
liquid passes through the expan-sion valve where pressure is
reduced and further cool-ing takes place before returning to the DX
Coil.LD13139JOHNSON CONTROLS 31SECTION 3 HANDLING AND STORAGEFORM
150.63-NM9 ISSUE DATE: 9/27/20133SECTION 3 HANDLING AND
STORAGEDELIVERY AND STORAGETo ensure consistent quality and maximum
reliability, all units are tested and inspected before leaving the
fac-tory.Units are shipped completely assembled and
con-tainingrefrigerantunderpressure.Unitsareshipped
withoutexportcratingunlesscratinghasbeenspeci-fied on the Sales
Order.If the unit is to be put into storage, prior to installation,
the following precautions should be observed:The unit must be
blocked so that the base is not permitted to sag or
bow.Ensurethatallopenings,suchaswaterconnec-tions, are securely
capped.Donotstorewhereexposedtoambientairtem-peratures exceeding
110 F (43 C).Thecondensersshouldbecoveredtoprotectthe fns from
potential damage and corrosion, particu-larly where building work
is in progress.The unit should be stored in a location where there
is minimal activity in order to limit the risk of ac-cidental
physical damage.Topreventinadvertentoperationofthepressure relief
devices the unit must not be steam cleaned.It is recommended that
the unit is periodically in-spected during
storage.INSPECTIONImmediatelyuponreceivingtheunit,itshouldbein-spected
for possible damage which may have occurred during transit. If
damage is evident, it should be noted in the carriers freight bill.
A written request for inspec-tion by the carriers agent should be
made at once. See Instruction manual, Form 50.15-NM for more
infor-mation and details.Majordamagemustbereportedimmediatelytoyour
local Johnson Controls representative.UNIT
RIGGINGUsespreaderbarstoavoidliftingchainshittingthe
unit.Neverlifttheunitusingaforkliftorby
hookingtothetoprails.Useonlythe lifting holes
provided.LiftingInstructionsareplacedonalabelontheunit and on the
shipping bag.Theunitshouldbeliftedbyinserting hooks through the
holes provided in unit base rails. Spreader bars should be used to
avoid crushing the unit frame rails with the lifting chains (See
Figure 7).FIGURE 7 - UNIT RIGGINGLD14326JOHNSON CONTROLS 32FORM
150.63-NM9 ISSUE DATE: 9/27/2013SECTION 3 HANDLING AND
STORAGEMoving the Condensing
UnitPriortomovingtheunit,ensurethattheinstallation
siteissuitableforinstallingtheunitandiseasilyca-pableofsupportingtheweightoftheunitandallas-sociated
services.Theunitsaredesignedtobeliftedusingcables.A
spreaderbarorframeshouldbeusedinordertopre-vent damage to the unit
from the lifting chains.Units are provided with lifting eyes in the
sides of the baseframe,whichcanbeattachedtodirectlyusing shackles
or safety hooks.The unit must only be lifted by the base frame at
the points provided. Never move the unit on rollers, or lift the
unit using a forklift truck.Care should be taken to avoid damaging
the condenser cooling fins when moving the unit.Lifting
WeightsFordetailsofweightsandweightdistribution,refer to the data
shipped in the unit information packet and unit nameplate.JOHNSON
CONTROLS 3