TECHNICAL GUIDE SPLIT-SYSTEM AIR CONDITIONERS 13 SEER – R-410A – 1 PHASE MODELS: YCJD18 THRU 60 (1.5 THRU 5 NOMINAL TONS) Due to continuous product improvement, specifications are subject to change without notice. Visit us on the web at www.york.com Additional rating information can be found at www.ahridirectory.org WARRANTY Standard 5-year limited parts warranty. 10-year limited compressor warranty. Extended 10-year limited parts warranty when product is registered online within 90 days of purchase for replace- ment or closing for new home construction. LISTED 561908-YTG-D-0611 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE DESCRIPTION The 13 SEER Series unit is the outdoor part of a versatile cli- mate system. It is designed with a matching indoor coil compo- nent from Johnson Controls Unitary Products. Available for typical applications this climate system is supported with acces- sories and documents to serve specific functions. FEATURES • Quality Condenser Coils - The coil is constructed of alumi- num microchannel tubing and enhanced aluminum fins for increased efficiency. • Protected Compressor - The compressor is internally pro- tected against high pressure, temperature, and externally by a factory installed high pressure switch. This is accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protects the compressor if undesirable operating conditions occur. A liquid line filter- drier further protects the compressor. • Durable Finish - The cabinet is made of pre-painted steel. The pre-treated galvanized steel provides a better paint to steel bond, which resists corrosion and rust creep. Special primer formulas and matted-textured finish insure less fading when exposed to sunlight. • Lower Installed Cost - Installation time and costs are reduced by easy power and control wiring connections. Available in sweat connect models only. The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping. The small base dimension means less space is required on the ground or roof. • Top Discharge - The warm air from the top mounted fan is blown up away from the structure and any landscaping. This allows compact location on multi-unit applications. • Low Operating Sound Level - The upward air flow carries the normal operating noise away from the living area. The rigid top panel effectively isolates any motor sound. Isolator mounted compressor and the rippled fins of the condenser coil muffle the normal fan motor and compressor operating sounds. • Low Maintenance - Long life permanently lubricated motor- bearings need no annual servicing. • Easy Service Access - Fully exposed refrigerant connec- tions, and a single panel covering the electrical controls make for easy servicing of the unit. • Secured Service Valves - Secured re-usable service valves are provided on both the liquid and vapor sweat connections for ease of evacuating and charging. • U.L. and C.U.L. listed - approved for outdoor application. • Agency Listed - U.L. and C.U.L. listed - approved for out- door application. The unit is certified in accordance with the Unitary Small Equipment certification program, which is based on AHRI Standard 210/240.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
TECHNICAL GUIDESPLIT-SYSTEM AIR CONDITIONERS
13 SEER – R-410A – 1 PHASE
MODELS:YCJD18 THRU 60(1.5 THRU 5 NOMINAL TONS)
Due to continuous product improvement, specifications are subject to change without notice.
Visit us on the web at www.york.com
Additional rating information can be found at
www.ahridirectory.org
WARRANTY
Standard 5-year limited parts warranty.10-year limited compressor warranty.
Extended 10-year limited parts warranty when product isregistered online within 90 days of purchase for replace-ment or closing for new home construction.
LISTED
561908-YTG-D-0611
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
The 13 SEER Series unit is the outdoor part of a versatile cli-mate system. It is designed with a matching indoor coil compo-nent from Johnson Controls Unitary Products. Available fortypical applications this climate system is supported with acces-sories and documents to serve specific functions.
FEATURES
• Quality Condenser Coils - The coil is constructed of alumi-num microchannel tubing and enhanced aluminum fins forincreased efficiency.
• Protected Compressor - The compressor is internally pro-tected against high pressure, temperature, and externally bya factory installed high pressure switch. This is accomplishedby the simultaneous operation of high pressure relief valveand a temperature sensor which protects the compressor ifundesirable operating conditions occur. A liquid line filter-drier further protects the compressor.
• Durable Finish - The cabinet is made of pre-painted steel.The pre-treated galvanized steel provides a better paint tosteel bond, which resists corrosion and rust creep. Specialprimer formulas and matted-textured finish insure less fadingwhen exposed to sunlight.
• Lower Installed Cost - Installation time and costs arereduced by easy power and control wiring connections.Available in sweat connect models only. The unit containsenough refrigerant for matching indoor coils and 15 feet ofinterconnecting piping. The small base dimension meansless space is required on the ground or roof.
• Top Discharge - The warm air from the top mounted fan isblown up away from the structure and any landscaping. Thisallows compact location on multi-unit applications.
• Low Operating Sound Level - The upward air flow carriesthe normal operating noise away from the living area. Therigid top panel effectively isolates any motor sound. Isolatormounted compressor and the rippled fins of the condensercoil muffle the normal fan motor and compressor operatingsounds.
• Low Maintenance - Long life permanently lubricated motor-bearings need no annual servicing.
• Easy Service Access - Fully exposed refrigerant connec-tions, and a single panel covering the electrical controlsmake for easy servicing of the unit.
• Secured Service Valves - Secured re-usable service valvesare provided on both the liquid and vapor sweat connectionsfor ease of evacuating and charging.
• U.L. and C.U.L. listed - approved for outdoor application.
• Agency Listed - U.L. and C.U.L. listed - approved for out-door application. The unit is certified in accordance with theUnitary Small Equipment certification program, which isbased on AHRI Standard 210/240.
561908-YTG-D-0611
2 Johnson Controls Unitary Products
All dimensions are in inches. They are subject to change with-out notice. Certified dimensions will be provided upon request.
Charge Per Foot, Oz. 0.58 0.62 0.62 0.62 0.67 0.67 0.67
Operating Weight Lbs. 97 129 131 145 173 173 195
Models with “H” on the end of the model number have a factory installed start kits.
1. Rated in accordance with AHRI Standard 110, utilization range “A”.2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.4. The Unit Charge is correct for the outdoor unit, matched indoor coil, and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet,
add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
PROCEDURES:1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator, and 15 feet of interconnecting
line tubing.2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.3. Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.4. For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator
+ adder for line set.
FC/MC/PC43 – 4 2 0 0 – –
FC/MC/PC48 – – – 8 2 4 –
FC/MC/PC60 – – – – – 0 0
FC/MC62 – – – – – – 4
FC64 – – – – – – 11
UC18 0 – – – – – –
UC36 – 0 – – – – –
UC48 – – – 8 2 4 –
UC60 – – – – – 0 0
FOOTNOTES:
1. For applications requiring a TXV use 1TVM series kit.2. Approved orifice shipped with outdoor unit.3. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.4. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
System Charge for Various Matched Systems (Continued)
Models 12-48 require start kits for TXV matches. Models with “H” on the end of the model number have factory installed start kits. Formodels without an “H” refer to tech guide for kit number reference.
COOLING CAPACITY - With Air Handler Coils (Continued)
UNITMODEL
AIR HANDLERCOIL
MODEL1
COOLING
MODEL WRATED
CFMNET MBH
SEER EERTOTAL SENS.
561908-YTG-D-0611
Johnson Controls Unitary Products 7
— = Not applicable.MA Modular Air Handlers use coil only ratings.
13 SEER AC WITH AHE / AHP / AHR / AHX / F*FP (Continued)
YCJD42S41S1(H)
AHE42 21 – 1385 43.0 30.4 14.50 12.00
AHP42 21 – 1485 41.0 29.2 13.00 11.00
AHR42 21 – 1485 42.5 30.6 13.00 11.00
AHX42 21 – 1395 42.0 29.9 14.50 12.00
F5FP048 24 – 1455 41.0 29.2 13.00 11.00
F6FP042 21 – 1455 42.0 30.1 14.00 11.75
F6FP048 24 – 1380 41.5 29.4 13.50 11.70
YCJD48S41S1(H)
AHE48 24 – 1600 47.0 34.6 13.75 11.50
AHP48 24 – 1675 48.0 34.4 13.00 11.00
AHP60 24 – 1600 48.0 35.0 13.50 11.00
AHR48 24 – 1610 48.0 34.6 13.00 11.00
AHX48 24 – 1660 48.0 35.4 13.50 11.50
F5FP048 24 – 1600 48.0 34.4 13.00 11.00
F5FP060 24 – 1600 48.0 34.4 13.00 11.00
F6FP048 24 – 1625 47.0 34.8 13.00 11.30
YCJD60S41S1
AHE60 24 – 1835 58.5 39.8 13.50 11.50
AHP60 24 – 1850 57.0 38.5 13.00 11.00
AHR60 24 – 1870 57.0 38.5 13.00 11.00
AHX60 24 – 1905 58.5 40.0 13.50 11.50
F5FP060 24 – 1900 57.0 38.5 13.00 11.00
F6FP060 24 – 1710 57.5 39.0 13.50 11.50
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and AHRI Standards 210. Cooling MBH based on 80 °F entering air temperature, 50% RH, and rated air flow.EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95 °F outdoor ambient divided by the total electric power in watt-hours at those conditions.SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
COOLING CAPACITY - With Air Handler Coils (Continued)
UNITMODEL
AIR HANDLERCOIL
MODEL1
COOLING
MODEL WRATED
CFMNET MBH
SEER EERTOTAL SENS.
561908-YTG-D-0611
8 Johnson Controls Unitary Products
COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils
1. Requires a 2FD06700224 Blower Time Delay unless a standard furnace is equipped with one.** Refer to Quick Selection Chart for specific furnace match-up.
561908-YTG-D-0611
Johnson Controls Unitary Products 9
COOLING CAPACITY - With High Efficiency Motor Furnaces
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.2. Variable speed furnaces have B.O.D (Blower on Delay) standard.
COOLING CAPACITY - With High Efficiency Motor Furnaces (Continued)
MODELSFURNACE
MODELCOIL
MODEL1 W
COOLING
RATED CFM
Net MBHSEER EER
TOTAL SENS.
13 SEER HP WITH VARIABLE SPEED FURNACES2
561908-YTG-D-0611
Johnson Controls Unitary Products 13
ACCESSORIES
Refer to Price Manual for specific model numbers.
Off Cycle Timer Delay - Provides a 5-minute off cycle to pre-vent rapid recycling of the compressor.
Hard Start Kit - Required when using TXV indoor coil. Also,provides increased starting torque for areas with low voltage.
Thermostats - Compatible thermostat controls are availablethrough accessory sourcing. For optimum performance andinstallation, refer to the UPGNET “Low Voltage Wiring Diagram”document to select and apply controls.
SOUND POWER RATINGS*
* Rated in accordance with ARI 270-95 Standards.
TYPICAL INSTALLATION
TYPICAL FIELD WIRING
Model Source 1 Kit numbers
18 S1-2SA06708606
24 S1-2SA06721706
30 S1-2SA06705906
36 S1-2SA06708906
42 S1-2SA06708806
48 S1-2SA06708806
60 S1-2SA06707906
UNIT MODEL (dBA)
18 75
24 76
30 76
36 76
42 76
48 77
60 78
THERMOSTAT
SEAL OPENING(S) WITHPERMAGUM OR EQUIVALENT
TO INDOOR COIL
TO FURNACE ORAIR HANDLERTERMINAL BLOCK
NEC CLASS 2 WIRING
NEC CLASS 1 WIRING
ALL OUTDOOR WIRINGMUST BE WEATHERPROOF.
CONTROLACCESSPANEL
WEATHERPROOFDISCONNECTSWITCH
MINIMUM 18” SERVICEACCESS CLEARANCEON ONE SIDE
60” OVERHEADCLEARANCE
10” CLEARANCEAROUND PERIMETER
NOTE:
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES
POWER WIRING
208/230-1-60
CONTACTOR
TERMINALS
COIL
GND.
LUG
C Y R G W
Y R G W
POWER WIRING
CONTROL WIRING
FACTORY WIRING
24 VOLT CONTROL WIRING
MINIMUM 18 GA. WIRE
(NEC CLASS 2)
FURNACE OR AIR HANDLER TERMINAL BLOCK
ROOM THERMOSTATCONDENSING UNIT
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.
TERMINAL W IS ONLY
REQUIRED ON SYSTEMS
WITH HEAT.
*
*
561908-YTG-D-0611
14 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD18S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC18
CONDENSINGENTERING AIRTEMPERATURE
IDCFM 450 600 750
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers Coils T.C. S.C. KW
– UC18 1.00 1.00 1.00
AHE18 – 1.02 1.07 0.92
AHP18 – 1.00 1.00 1.00
AHR18 – 1.02 1.07 1.02
AHX18 – 1.03 1.07 0.94
AV*24 – 1.03 1.05 0.94
MV12B FC/MC18B 1.00 1.03 0.88
MX12B FC/MC/PC18B 1.02 1.05 0.90
F4FP024 – 1.00 1.00 1.00
F6FP018 – 1.02 1.03 0.93
Furnaces Coils T.C. S.C. KW
T*(8,L)X*A12 FC/MC/PC18A 1.01 1.00 0.89
T*(8,L)X*B12 FC/MC/PC18B 1.03 1.04 0.91
T*9X*B12 FC/MC/PC18B 1.03 1.04 0.91
T*(8,L)X*A12 UC18A 1.03 1.04 0.94
T*(8,L)X*B12 UC18B 1.03 1.04 0.94
T*9X*B12 UC18B 1.03 1.04 0.94
(Y*(8,L)C/T*8V)*A12 FC/MC/PC18A 1.00 0.98 0.88
(Y*(8,L)C/T*8V)*B12 FC/MC/PC18B 1.00 0.98 0.92
(Y*9C/T*9V)*B12 FC/MC/PC18B 1.00 0.99 0.88
(Y*(8,L)C/T*8V)*A12 UC18A 1.00 0.98 0.92
(Y*(8,L)C/T*8V)*B12 UC18B 1.00 0.97 0.92
(Y*9C/T*9V)*B12 UC18B 1.00 0.98 0.88
561908-YTG-D-0611
Johnson Controls Unitary Products 15
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD24S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC36
CONDENSINGENTERING AIRTEMPERATURE
IDCFM 600 800 1000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC32 1.00 1.00 1.00
– FC/MC/PC35 1.00 1.00 1.00
– FC/MC/PC37 1.00 1.00 1.00
– FC/MC/PC43 1.00 1.00 1.00
– UC36 1.00 1.00 1.00
AHE24 – 1.02 1.04 0.93
AHE30 – 1.02 1.04 0.93
AHE36 – 1.05 1.11 0.92
AHP30 – 1.00 1.01 1.00
AHR24 – 0.99 0.99 0.99
AHX30 – 1.00 1.01 0.92
AHX36 – 1.00 1.01 0.92
AV*36 – 1.00 1.04 0.92
MV12B FC/MC36B 1.00 1.04 0.92
MV12B FC/MC35B 1.00 1.04 0.92
MV12B FC/MC43B 1.00 1.04 0.92
MX12B FC/MC35B 1.03 1.04 0.91
MX12B FC/MC36B 1.01 1.01 0.91
MX12B FC/MC43B 1.03 1.02 0.90
F4FP36 – 1.00 1.00 1.00
F6FP030 – 1.00 1.01 0.93
F6FP036 – 1.00 1.02 0.92
Furnaces Coils T.C. S.C. KW
T*(8,L)X*A12 FC/MC/PC32A 1.00 1.01 0.96
T*(8,L)X*B12 FC/MC/PC35B 1.00 1.02 0.92
T*9X*C16 FC/MC/PC35C 0.99 0.98 0.91
T*9X*C20 FC/MC/PC35C 1.00 1.02 0.92
T*(8,L)X*A12 FC/MC/PC36A 1.00 1.01 0.92
T*(8,L)X*B12 FC/MC/PC36B 1.00 1.01 0.92
T*9X*B12 FC/MC/PC36B 1.00 1.01 0.92
T*9X*C16 FC/MC/PC36C 1.00 1.01 0.92
T*9X*C20 FC/MC/PC36C 1.00 1.01 0.92
T*(8,L)X*A12 FC/MC/PC37A 1.00 1.02 0.92
T*(8,L)X*B12 FC/MC/PC43B 1.00 1.02 0.92
(Y*(8,L)C/T*8V)*A12 FC/MC/PC32A 1.00 1.02 0.96
(Y*(8,L)C/T*8V)*B12 FC/MC/PC35B 1.00 1.01 0.92
(Y*9C/T*9V)*B12 FC/MC/PC35B 1.00 1.02 0.92
(Y*(8,L)C/T*8V)*A12 FC/MC/PC36A 1.00 1.01 0.92
(Y*(8,L)C/T*8V)*B12 FC/MC/PC36B 1.00 1.02 0.92
(Y*9C/T*9V)*B12 FC/MC/PC36B 1.00 1.01 0.92
(Y*(8,L)C/T*8V)*A12 FC/MC/PC37A 1.00 1.02 0.92
(Y*(8,L)C/T*8V)*B12 FC/MC/PC43B 1.00 1.01 0.92
(Y*9C/T*9V)*B12 FC/MC/PC43B 1.00 1.02 0.92
(Y*(8,L)C/T*8V)*A12 UC36A 0.98 0.99 0.94
(Y*(8,L)C/T*8V)*B12 UC36B 0.98 1.00 0.94
(Y*9C/T*9V)*B12 UC36B 0.98 1.00 0.94
561908-YTG-D-0611
16 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD30S41S1(H)INDOOR COIL MODEL NO. FC/MC/PC32
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD36S41S1(H)INDOOR COIL MODEL NO. FC/MC/PC37
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD42S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC43
CONDENSINGENTERING AIRTEMPERATURE
IDCFM 1200 1400 1600
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers Coils T.C. S.C. KW
– FC/MC/PC48 1.00 1.00 1.00
– UC48 1.00 1.00 1.00
AHE42 – 1.02 1.04 0.94
AHP42 – 0.98 1.00 0.98
AHR42 – 1.01 1.05 1.01
AHX42 – 1.00 1.02 0.92
AV*48 – 1.00 1.02 0.92
AV*60 – 1.00 1.02 0.92
MV16C FC/MC43C 1.00 1.03 0.92
MV16C FC/MC48C 1.00 1.03 0.92
MV20D FC/MC48D 1.00 1.03 0.92
MX16C FC/MC43C 1.01 1.03 0.93
MX16C FC/MC48C 1.02 1.04 0.92
MX20D FC/MC48D 1.02 1.03 0.94
F5FP048 – 0.98 1.00 0.98
F6FP042 – 1.00 1.03 0.94
F6FP048 – 0.99 1.01 0.93
Furnaces Coils T.C. S.C. KW
T*(8,L)X*B12 FC/MC/PC43B 1.00 0.99 0.96
T*(8,L)X*C16 FC/MC/PC43C 1.00 1.02 0.96
T*(8,L)X*C20 FC/MC/PC43C 1.00 1.01 0.96
T*9X*B12 FC/MC/PC43B 1.00 0.99 0.96
T*9X*C16 FC/MC/PC43C 1.00 1.01 1.00
T*9X*C20 FC/MC/PC43C 1.00 1.01 1.00
T*(8,L)X*C16 FC/MC/PC48C 1.00 1.01 0.96
T*(8,L)X*C20 FC/MC/PC48C 1.00 1.03 0.96
T*9X*C16 FC/MC/PC48C 1.00 1.00 0.96
T*9X*C20 FC/MC/PC48C 1.00 1.00 0.96
T*9X*D20 FC/MC/PC48D 1.00 1.02 0.96
T*(8,L)X*C16 UC48C 1.00 1.01 1.00
T*(8,L)X*C20 UC48C 1.00 1.03 1.00
T*9X*C16 UC48C 0.99 1.00 0.99
T*9X*C20 UC48C 1.00 1.01 1.00
T*9X*D20 UC48D 1.00 1.01 1.00
(Y*(8,L)C/T*8V)*C16 FC/MC/PC43C 1.00 1.03 0.96
(Y*(8,L)C/T*8V)*C20 FC/MC/PC43C 1.00 1.04 0.96
(Y*9C/T*9V)*C16 FC/MC/PC43C 1.00 1.01 1.00
(Y*9C/T*9V)*C20 FC/MC/PC43C 1.00 1.01 1.00
(Y*(8,L)C/T*8V)*C16 FC/MC/PC48C 1.00 1.03 0.96
(Y*(8,L)C/T*8V)*C20 FC/MC/PC48C 1.00 1.03 0.96
(Y*9C/T*9V)*C16 FC/MC/PC48C 1.00 1.04 0.96
(Y*9C/T*9V)*C20 FC/MC/PC48C 1.00 1.04 0.96
(Y*9C/T*9V)*D20 FC/MC/PC48D 1.00 1.02 0.96
(Y*(8,L)C/T*8V)*C16 UC48C 0.99 1.03 0.99
(Y*(8,L)C/T*8V)*C20 UC48C 0.99 1.03 0.95
(Y*9C/T*9V)*C16 UC48C 0.99 1.03 0.99
(Y*9C/T*9V)*C20 UC48C 0.99 1.03 0.99
(Y*9C/T*9V)*D20 UC48D 0.99 1.03 0.99
Furnaces Coils T.C. S.C. KW
561908-YTG-D-0611
Johnson Controls Unitary Products 19
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD48S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC48
CONDENSINGENTERING AIRTEMPERATURE
IDCFM 1400 1600 1800
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed tem
COOLING PERFORMANCE DATAAIR CONDITIONER MODEL NO. YCJD60S41S1
INDOOR COIL MODEL NO. FC/MC/PC60
CONDENSINGENTERING AIRTEMPERATURE
IDCFM 1600 1800 2000
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80