XGB U TYPE XBM Slim
XBC/XEC H TYPE
XBC/XEC E TYPE XBC/XEC SU TYPE
Programmable Logic Controller
EASINESS
COMPACTNESS
FUNCTIONALITY
CONVENIENCE
HIGH PERFORMANCE2
3
FEFEFEFEATATATATURURURURESESESESFEATURES4 ~ 15
XBC/XEC U16 ~ 23
XBC/XEC H24 ~ 29
XBC/XEC SU30 ~ 33
XBC/XEC E40 ~ 47
XBM Slim48 ~55
XBC//XEC HXBXBXBC/C/C/XEXEXEC CCSUSUSU
XBC/XEC EXBXBM
M
SlSlimimXGXGXGB BBUUU
APPLICATION56 ~ 107
Programmable Logic Controller
Intro
All-In-One PLCWith Next Generation Technology
4
XGB is a micro PLC that offers maximum performance at minimum cost.
With its high functionality, XGB supports from simple control system to complex task.
Strengthening its communication functions, XGB offers user-oriented integrated control.
Based on its strengths, XGB can be used in many application fields.
5
Features
It’s SlimIt’s Powerful
Size(W×H×D) 150×64×90 114×64×90 135×64×90 100×64×90 30×60×90
XBMSlim Type
XBC/XEC E Type
XBC/XEC SU Type
XBC/XEC H Type
XBC/XEC U Type
(Standard)
ItemSize(W×H×D)
Size(W×H×D) 27×63×90
Expansion Communication Module
20×63×90
Special Module
6
It’s Slim
※ The actual size of the product
※ XBC/XEC U Type
Ethernet1 Ch.(Dual Port)
RS-232C1 Ch.
RS-4851 Ch.
WebServer Data Log USB
High speedcounter8 Ch.
Analoginput/output 8 Ch.
Positioning4 axes
PID
Pulse catch
Externalinterrupt
7
It’s Powerful
Features
8
What you have dreamed of, we make it happen.
XGB U sets new standards in Ultimate performance with its many innovationsIoT (Internet of Things) realizes smart factoriesXGB-U is a user-oriented controller
•Compatible with XGB expansion modules•Max. 2 High speed backplane expansion modules•Max. 10 expansion modules•Max. 352 I/O points•Expansion I/O module
- DC24 input, Transistor output, Relay output•Special module
- Analog input, Analog output, RTD, Thermocouple, High-speed counter, Positioning(Line drive 2 axes, EtherCAT network 8 axes)
•Communication modules- RS-232C, RS-422/485, Ethernet, CANopen (Master/Slave), Profibus-DP (Master/Slave),
DeviceNet (Slave), EtherNet/IP, RAPIEnet
Various Expansion
•Easy parameter set up for [General save], [Trigger save], [Event save] without instruction•16GB of operation data storable•Additional function
- SD memory format, FTP link, Diagnosis, Sending email attached with a data log file
- PLC program upload/download- O/S update
Data Log
•Max. 10 expansion modules- Max. 2 High speed backplane modules- Max. 2 Communication modules
Expansion(XBC/XEC U Type)
High speed Backplane I/F
Basic I/FInterface Speed
High speed Backplane I/F
Communication
Basic
9
Features
•2 ports unmanaged Ethernet switch support•Cost saving through simple wiring•FTP server support (Data logging)
Dual Port Ethernet(XBC/XEC U type)
Daisy Chain Topology
Daisy Chain Topology
Existing products
Internet
XGB U
Star Topology
•Monitoring of PLC information and data through web browser (PLC basic info., module info., diagnosis, device monitoring, flag monitoring, data log file download, O/S update, ladder program update, etc.)•Time synchronization by setting basic parameters (SNTP: Simple Network Time Protocol)•Email service through commercial email (SMTP: Simple Mail Transfer Protocol)
Web Server
SNTP client SNTP client SNTP client
SNTP Server
Gmail
XGB Board
ESMTP
ESMTP
ESMTP/TLS
10
Ultimate PerformanceUniversal IoTUser Oriented
11
Features
Built-in high speed counter
Powerful built-in function
Phase
1 Phase
2 Phase
XBM
20kHz100kHz(4Ch)20kHz(4Ch)
8Ch50kHz(4Ch)10kHz(4Ch)
4Ch
100kHz(2Ch)20kHz(6Ch)
8Ch50kHz(1Ch)8kHz(3Ch)
4Ch
4Ch
2 multiplication: 10kHz4 multiplication: 8kHz
2Ch
100kHz(8Ch)
8Ch
50kHz(4Ch)
4Ch
4kHz
4Ch
2kHz
2Ch
XBC/XEC
ESUHU
U will experience the utmost efficiency for your applications with U’s outstanding features
12
•It supports built-in PID control function up to 16 loops. - It provides parameter setting using XG5000, convenient loop state monitoring through trend monitor. - It can simply get a coefficient value by improved auto-tuning algorithm - Control accuracy improvement by using various additional functions such as PWM output, ΔMV, ΔPV, SV Ramp, etc.
- It provides various control modes such as forward/reverse mixed operation, 2-stage SV PID control, cascade control, etc.
-Various alarm functions such as MV high/low limit, PV high/low limit, PV variation
Built-in PID function
•Built-in analog input 4 channels (voltage/current, 14bit) •Built-in analog output 4 channels (voltage/current 14bit)
Built-in analog I/O function (Available for XBC/XEC-DN32UA type only)
•Line drive output positioning function with up to 2Mpps 4-axis•Parameter set up by XG-PM providing operation data edition, divers monitoring and
diagnosis functions.
Built-in position control function (Available for XBC/XEC-DN32UP type only)
RS-232C/485Ethernet
Modbus-RTU/ASCII
PositioningPulse catch/Input filterHigh speed counter
SensorEncoderServo drive
Servo/Stapping motor
13
XBC/XEC H
Features
XBC/XEC U
Max. 10 stage(Including communication 2 stages)
Standard type Max. 10 stages (High speed interface module : Max. 2 stages)
With its high-speed processing and system capability, XGB offers the utmost efficiency for your applications.
14
Option : Max. 2 stages(Only SU/E type)
Option : Max. 2 stages
XBC/XEC SU
XBC/XEC E
XBM Slim XBM H
Max. 7 stage(Expansion + Option), Communication Max. 2 stages
Max. 7 stage(Communicaion Max. 2 stages) Max. 7 stages (High speed interface module : max. 2stages)
XBO-M2MBXBO-RTCA
XBO-DC04AXBO-TN04AXBO-AD02A XBO-DA02A XBO-AH02AXBO-RD01AXBO-TC02A
Option modules
Memory / program READ/WRITE
RTC (Real time clock), Battery
DC 24V, Input 4 points
TR (Sink), Output 4 points
Voltage/Current, Input 2ch
Voltage/Current, Output 2ch
Voltage/Current, Input 1ch / Voltage/Current, Output 1ch
RTD (Resistance temperature detector), Input 1ch
TC (Thermo couple), Input 2ch
15
XGB U Ultimate Performance Universal IoTUser Oriented
General specifications
Performance specifications
Wiring
18
19
23
C o n t e n t s
General specifications
Block type unit(U, H, SU, E)
Item StandardDescriptions
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Operating ambience
Altitude
Pollution level *1)
Cooling
Vibration resistance
Shock resistance
Noise resistance
*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used.Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due tocondensing.
Continuous vibration
10 timeseach
direction(X, Y and Z)
IEC61131-2
IEC61131-2
LSIS Standard
IEC61131-2 IEC61000-4-4
IEC61131-2 IEC61000-4-3
IEC61131- 2IEC61000- 4- 2
Electrostatic discharge
Fast transient / Burst noise
Radiated electromagnetic
field noise
Main unit
2kV
Expansion module
1kV
4kV
80 ~ 1000MHz, 10V/m
Free from corrosive gases and excessive dust
Up to 2,000m
Less than 2
Air-cooling
18
Square waveimpulse noise 500 V
0 ~ 55 C
- 25 ~ + 70 C
5 ~ 95%RH (Non-condensing)
5 ~ 95%RH (Non-condensing)
Occasional vibrationFrequency
10 f < 57Hz
57 f 150Hz
-
9.8m/s2 (1G)
0.075mm
-
10 f < 57Hz
57 f 150Hz
Peak acceleration: 147m/s2 (15g) Duration: 11ms Pulse waveform: Half-sine, 3times each direction per each axis
-
4.9m/s2 (0.5G)
0.035mm
-
Acceleration Pulse width
Frequency Acceleration Pulse width
XBC U
ItemSpecifications
XBC-DN(P)32U XBC-DR28U XBC-DN(P)32UA XBC-DR28UA XBC-DN(P)32UP XBC-DR28UPRemark
Performance specifications
Program control method
I/O control method
Program language
Processing speed(Basic instruction)Program capacity
Operation modeSelf-diagnosis functionProgram portRetain data at power failureInternal consumption currentWeight
File register
Total program
Data area
Initial task
Max. I/O points
BasicApplication
PMKLFTCSDUZN
Initial taskCyclic taskI/O taskInternal device task
Number ofinstructions
Ladder Diagram, Instruction List28
677
P00000 ~ P2047F(32,768 point) M00000 ~ M2047F(32,768 point)K00000 ~ K8191F(131,072 point)L00000 ~ L4095F (65,536 point)F00000 ~ F2047F (32,768 point)
100ms, 10ms, 1ms: T0000 ~ T2047 (2,048 point)C000 ~ C2047 (2,048 point)
S00.00 ~ S127.99 D00000 ~ D19999(20000word)U00.00 ~ U0B.31 (384 word)
Z000~Z127 (128 word)N0000~N10239(10,240 word)
RAM area 2 block (R0 ~ R16,383)FLASH area : 4 block (128Kbyte)
2561
Max 16Max 8
Max 16
RUN, STOP, DEBUGDetects errors of scan time, memory, I/O and power supply
USB 1 channel, EthernetLatch area setting in basic parameter
Cyclic execution of stored program, Time-driven interrupt, Process-driven interrupt
Batch processing by simultaneous scan (Refresh method),Directed by program instruction
60ns/step
32Kstep
Max 8
700mA
571g
990mA
630g
780mA
683g
1,040mA
732g
1,250mA
673g
1,550mA
722g
Input/Ouput
LinkFlag
TimerCounter
StepData registerAnalog Data
High SpeedCounter task
R
*1) Auto-MDIX (Automatic medium-dependent interface crossover) : It is the function to automatically detect whether the cable connected to the Ethernet port is peer-to-peer(straight) or cross cable
19
Performance specifications | Block type unit
XGXGXGB BBUUU
352points 348points 352points 348points 352points 348points Main + 10expansioons
20
Performance specifications | Block type unit
XEC U
ItemSpecifications
XEC-DN(P)32U XEC-DR28U XEC-DN(P)32UA XEC-DR28UA XEC-DN(P)32UP XEC-DR28UPRemark
Performance specifications
MR
FKL
N
Symbolic variable(A)Input variable(I)Output variable(Q)
Initial taskCyclic taskInitial taskCyclic taskI/O taskInternal device task
OperatorBasic function
Flash areaTimerCounterTotal program
Operation modeSelf-diagnosis functionProgram portRetain data at power failureInternal consumption currentWeight
W
Direct variable
Basic function block
Special function block
Flagvariable
High SpeedCounter task
Data area
Number ofinstructions
Program control method
I/O control method
Processing speed(Basic instruction)
Max. I/O points
Program language
Program memory
Initial task
U
Batch processing by simultaneous scan (Refresh method),Directed by program instruction
43
Each special module has own special function blocks
60ns/step
384Kbyte
64KB
768 Byte
20KB4blocks (128Kbyte)
No limit in points (Time range: 0.001~ 4,294,967.295)No limit in points (Counter range: 64 bit range)
2561
Max 161
Max 16Max 8
Max 16
RUN, STOP, DEBUGDetects errors of scan time, memory, I/O and power supply
USB 1 channelLatch area setting in basic parameter
4KB16KB8KB
64KB (Retain setting available)2KB2KB
32KB (Retain setting available)32KB * 2blocks
Ladder Diagram, Instruction List, SFC, ST18
136 + Floating-point Arithmetic Functions
Max 8
Cyclic execution of stored program, Time-driven interrupt, Process-driven interrupt
352points 348points 352points 348points 352points 348points Main + 10expansioons
Same areawith R
System flagKeep relayLink relay
P2P parameterUsing R device
Analog datarefresh area
700mA571g
990mA630g
780mA683g
1,040mA732g
1,250mA673g
1,550mA722g
21
| Built –in function
Built-in functionItem
SpecificationsXBC/XEC- DN(P)32U
XBC/XEC- DR28U
XBC/XEC-DN(P)32UA
XBC/XEC- DR28UA
XBC/XEC-DN(P)32UP
XBC/XEC- DR28UP
Remark
Protocol
Service
Performance
Counter mode
Function
Protocol
Channel
Transfer spec
TopologyDiagnosis
Group Data setExtensionFile size SD memory typeMemory sizeFile system
Datalog
High SpeedCounter
Seria
PID control
Ethernet
Control by instruction, auto-tunning,PWM output, Forced output,Operation scan time setting,
Antiwindup, Delta MV, PV tracking,Hybrid operation,
Cascade operation
Dedicated protocol,Modbus protocol
User defined protocol ,LS bus(inverter protocol)
Embedded00P2P:01
Embedded01P2P:02
High-speedlink:01
RS-232C 1 port and RS-485 1 port
Cable: 100Base-TXSpeed: 100Mbps
Auto-MDIX *1IEEE 802.3
XGT dedicatedModbus TCP/IP
user define frame
P2P, High Speed link,Remote connection
Max 10 group32 per group
csv fileMax 16Mbyte
SD,SDHC type(Recommand: SanDisk,Transcend)Max 16GB
FAT32
Line, starModule information, service condition
1-phase : 100KHz 8 channels2-phase : 50KHz 4 channels
4 counter modes are supported based on input pulse and INC/DEC method1 pulse operation Mode : INC/DEC count by program
1 pulse operation Mode : INC/DEC count by phase B pulse input2 pulse operation Mode : INC/DEC count by input pulse
2 pulse operation Mode : INC/DEC count by difference of phase
Internal/external preset • Latch counterCompare output • No. of rotation per unit time
Programmable Logic Controller
XGXGXGB BBUUU
*1) Auto-MDIX(Automatic medium-dependent interface crossover) : It is the function to automatically detect whether the cable connected to the Ethernet port is peer-to-peer(straight) or cross cable
22
Performance specifications | Built –in function
XEC U
Item Specifications RemarkPositioning
interpolation
Positioning
Basic Function
Homing method
Manual operation
Encoder input
2/3/4 axis linear interpolation2 axis circular interpolation3 axis helical interpolation
Method: Absolute/Incremental methodAddress range: 2,147,483,648~2,147,483,647
Speed: Max 2Mpps(1~2,000,000pps)Acc /Dec process: Trapezoid type, S-type
DOG+HOME(Off), DOG+HOME(On),Upper limit + HOME,DOG, High speed,
Upper/Lower limit, HOME
Jog operation, MPG operation, Inching operation
Line drive(RS-422A) input1Channel(Max 200kpps)
No. of control axi: 4axis Control Method:Position, Speed, Speed/Position,Feed Control
Control Unit: Pulse ,mm, inch, degreePositioning Data: Each axis can have up to 400 data(Step number:1~400)
Operation pattern: End, Keep, Continuous Operation method: Singular, Repeat
AvailableOn
UP type
Item Specifications RemarkAnalogChannels
Channels
Specification
Specification
Anal
og in
put
Anal
og o
utpu
t
0.250mV(1 ~ 5V), 0.3125mV(0 ~ 5V)0.625mV(0 ~ 10V), 1.250mV(±10V)
0.250mV(1 ~ 5V), 0.3125mV(0 ~ 5V)0.625mV(0 ~ 10V), 1.250mV(±10V)
1.0 (4 ~ 20 )1.25 (0 ~ 20 )
1.0 (4 ~ 20 )1.25 (0 ~ 20 )
1 or more(voltage output), 600 or less(current output)1/16000
±0.2% or less (When ambient temperature is 25 )±0.3% or less (When ambient temperature is 0 ~ 55 )
Output ranges are set in user program or I/O parameter per each channel.
Voltage 2 channels ,Current 2 channels
±0.2% or less (When ambient temperature is 25 )±0.3% or less (When ambient temperature is 0 ~ 55 )
4channels (current/voltage)
Input Range
Output Range
Input resistance
Load resistance
Max.Resolution
Max.Resolution
Accuracy
Accuracy
Voltage: 1~5V, 0~5V, 0~10V, -10~10V, Current: 4~20 ,0~20
Voltage: 1~5V, 0~5V, 0~10V, -10~10V, Current: 4~20 ,0~20
1 or more(voltage input), 250 (current iput)1/16000
Current input or Voltage input can be selected through theexternal terminal wiring setting.
AvailableOn
UP type
23
Wiring | XGB U input/output wiringProgrammable Logic Controller
XBC-DN(P)32U(16 point input)
No. Contact
TB1TB2TB3TB4TB5TB6TB7TB8TB1TB2TB3TB4TB5TB6TB7TB8TB9
TB10
0123456789ABCDEF
DC12/24VCOM
TypeCircuit configurationXBC-DN32UTransistor output (Sink type)
TB9
TB10
TB8
TB1
<MZUQVITV]UJMZ
1V\MZVITKQZK]Q\
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZTB1
- TB8TB9
No. Contact
TB1TB2TB3TB4TB5TB6TB7TB8
TB1TB2TB3TB4TB5TB6TB7TB8TB9
TB10
01234567
89ABCDEF
COMCOM
XGXGXGB BBUUU
XBC/XEC H High Performance
Performance specifications
Wiring
26
27
C o n t e n t s
26
Performance specifications | Block type unit
High performance type
XBC/XEC-DR32HXBC-DR32H/ DC*1)
XEC-DR32H/ DIItem
XBC/XEC-DN32HXEC-DP32H*1)
XBC-DN32H/DC
XBC/XEC-DR64HXBC-DR64H/DC*1)
XEC-DR64H/DI
XBC/XEC-DN64HXEC-DP64H*1)
XBC-DN64H/DC
Performance specifications
Control method I /O control methodProgramming languageProcessing speedProgram capacity
Main unit I /O points
Max. I /O points(Main + Expansion 10 stages)Total programOperation modeSelf diagnosisProgram portRetain data at power failure
Built-in functions
Repetitive, cyclic, interrupt, constant scanRefresh mode (Batch processing by scan synchronization), Direct mode by instruction
Ladder diagram or IEC standard (LD, SFC, ST)*1)
83 ns / Step15Kstep (IEC type: 200KB)
128RUN, STOP, DEBUG
Detects errors of scan time, memory error, I/O error, battery error, power error, etc.USB (Rev 1.1), RS-232C 1 channel (Loader)
Latch area setting at basic parameterRS-232C / RS-485(2 ch), Pulse catch, Input filter, External interrupt,
PID control, High-speed counter, Positioning, RTC
32(Input:16, Output:16)
352 points 384 points
32(Input:16, Output:16)
64(Input: 32, Output: 32)
64(Input: 32, Output: 32)
Data memory
XBC XEC (IEC type)PMKLF
T
CSD
U
ZN
AIQMR
W
FKL
N
UR
Symbolic variableInput variableOutput variable
Direct variable
Flag variable
Flash area
P0000 ~ P1023F (16,384 points)M0000 ~ M1023F (16,384 points)K0000 ~ K4095F (65,536 points)L0000 ~ L2047F (32,768 points)F0000 ~ F1023F (16,384 points)100ms, 10ms, 1ms: T0000 ~ T1023(1,024)(Adjustable by parameter setting)C0000 ~ C1023 (1,024)S00.00 ~ S127.99D0000 ~ D10239 (10,240 word)U00.00 ~ U0A.31(Analog data refresh area: 352 word)Z000 ~ Z127 (128 word)N000 ~ N5119 (5,120 word)
32KB (Max. 16KB retain setting available)2KB(%IX 15.15.63)2KB(%QX 15.15.63)16KB (Max. 8KB retain setting available)20KB (1 block)
20KB
2KB8KB4KB
10KB
1KB20KB (2 blocks)
*1) XEC is IEC standard language programming.
Wiring | XBC/XEC H input/output wiring
27
XBC/XEC-DN(R)32HXBC/XEC-DN/DR/DP32HInput wiring(sink/source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
485+485-00020406080A0C0E
COM24V
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
RXTXSG01030507090B0D0F
24G
XBC/XEC-DR32HRelay output wiring type
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PENC21232426
C0M129282C2E
C0M3
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
Power
2022
C0M02527282A
C0M22D2F
XBC/XEC-DN32HTransistor output wiring(sink type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
DC12/24V
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PEDC12/24V
21232426
C0M129282C2E
C0M3
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
2022
C0M02527282A
C0M22D2F
* XBC input : P00~P1F, XEC input : I00~I31 * XBC output : P21~P3F, XEC output : Q00~Q31
Power
XBC//XEC H
28
Wiring | XBC/XEC H input/output wiring
XEC-DP32HTransistor output wiring(source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
DC12/24V
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PEDC12/24V
21232426
C0M129282C2E
C0M3
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
2022
C0M02527282A
C0M22D2F
XBC-DN(R)64HXEC-DN/DR/DP64HInput wiring(sink/source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
8PW\WKW]XTMZ
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
485+485-00020406080A0O0E
C0M010121416181A1C1E
C0M124V
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
RXTXSG01030507090B0D0FMC11131517191B1D1F
24G
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
PENC21232426
COM1292B2C2E
COM231333537383A3C3E
COM5
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
2022
COM02527282A
COM22D2F30323436
COM439383D3F
XBC-DR60HXEC-DR64HRelay output wiring
* XBC input : P00~P1F, XEC input : I00~I31 * XBC output : P21~P3F, XEC output : Q00~Q31
Power
Power
Programmable Logic Controller
29
XBC-DP64HTransistor output wiring(sink type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
DC12/24V
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
PEDC12/24V
21232426
COM1292B2C2E
COM231333537383A3C3E
COM5
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
2022
COM02527282A
COM22D2F30323436
COM439383D3F
* XBC input : P00~P1F, XEC input : I00~I31 * XBC output : P21~P3F, XEC output : Q00~Q31
XBC-DP64HTransistor output wiring(source type)
No. Contact TypeCircuit configuration
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
PEDC12/24V
21232426
COM1292B2C2E
COM231333537383A3C3E
COM5
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
2022
COM02527282A
COM22D2F30323436
COM439383D3F
Power
Power
XBC//XEC H
XBC/XEC SUStandard
Performance specifications
Wiring
32
33
C o n t e n t s
32
Performance specifications | Block type unit
Standard type
Repetitive, cyclic, interrupt, constant scanRefresh mode (Batch processing by scan synchronization), Direct mode by instruction
Ladder diagram, Instruction List94 ns / Step
15Kstep / 200KB
Data memory
XBC XEC
Performance specificationsXBC/XEC-DN20SUXBC/XEC-DR20SUXBC/XEC-DP20SU
ItemXBC/XEC-DN30SUXBC/XEC-DR30SUXBC/XEC-DP30SU
XBC/XEC-DN40SUXBC/XEC-DR40SUXBC/XEC-DP40SU
XBC/XEC-DN60SUXBC/XEC-DR60SUXBC/XEC-DP60SU
*Some products are due in market soon.
Control method I/O control methodProgramming languageProcessing speedProgram capacity
Main unit I/O points
Max. I/O points(Main + Expansion 7 stages)Total programOperation modeSelf diagnosisProgram portRetain data at power failure
Built-in functions
30(Input:18, Output:12)
20(Input:12, Output:8)
40(Input:24, Output:16)
60(Input:36, Output:24)
254 points244 points 264 points 284 points
128RUN, STOP, DEBUG
Detects errors of scan time, memory error, I/O error, battery error, power error, etc.RS-232C 1 channel (Loader), USB 1 channel (U-type model)
Latch area setting at basic parameterRS-232C / RS-485(2 ch), Pulse catch, Input filter, External interrupt,
PID control, High-speed counter, Positioning
P0000 ~ P1023F (16,384 points)M0000 ~ M1023F (16,384 points)K0000 ~ K4095F (65,536 points)L0000 ~ L2047F (32,768 points)F0000 ~ F1023F (16,384 points)
C0000 ~ C1023 (1,024)S00.00 ~ S127.99D0000 ~ D10239 (10,240 word)
Z000 ~ Z127 (128 word)N0000 ~ N10236 (10,240 word)
2KB (%IX 15.15.63)2KB (%QX 15.15.63)
20KB (1 block)20KB2KB8KB4KB1KB20KB (2 block)
100ms, 10ms, 1ms: T0000 ~ T1023 (1,024)(Adjustable by parameter setting)
U00.00 ~ U0A.31(Analog data refresh area: 352 word)
16KB (Max. 16KBretain setting abailable)
8KB(Max. retain setting available)
PMKLF
CSD
ZR
T
U
Dataarea
A
M
IQ
RWFKLU
Symbolicvariable
Directvariable
Flag variable
Input variableOutput variable
Flash area
33
Wiring | XBC/XEC SU input/output wiring
XBC/XEC-DR20SUXBC/XEC-DN20SUXBC/XEC-DP20SUInput wiring(sink/source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
485+485-00020406080ANCNCNC
COM
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
RXTXSG01030507090BNCNCNC
XBC/XEC-DR20SURelay output wiring
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PEC0M0C0M1C0M2
43COM3
4547NCNCNC24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100-240V
404142NC4446NCNCNC24V
XBC/XEC-DN20SUTransistor output wiring(sink type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PECOM0COM1COM2
43COM3
4547NCNCNC24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100-240V
404142P4446NCNCNC24V
* XBC input : P00~P23, XEC input : I00~I35 * XBC output : P40~P57, XEC output : Q00~Q23
XBXBXBC/C/C/XEXEXEC CCSUSUSU
Wiring | XBC/XEC SU input/output wiring
34
XBC/XEC-DP32HTransistor output wiring(source type)
No. Contact TypeCircuit configurationtbPU
tbPT
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbQQ
tbPW
tbPV
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
comP
comQ
comR
PS
comS
PU
PW
nc
nc
nc
RTg
PP
PQ
PR
n
PT
PV
nc
nc
nc
RTv
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PEC0M0C0M1C0M2Q03
COM3Q05Q07NCNCNC24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100-240VQ00Q01Q02
NQ04Q06NCNCNC24V
XBC/XEC-DR30SUXBC/XEC-DN30SUXBC/XEC-DP30SUInput wiring(sink/source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
485+485-00020406080A0C0E10
COM
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
RXTXSG01030507090B0D0F11
XBC/XEC-DR30SURelay output wiring
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PECOM0COM1COM2
43COM3
4547
COM4494B
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100-240V
404142NC4446NC484A
24V
* XBC input : P00~P23, XEC input : I00~I35 * XBC output : P40~P57, XEC output : Q00~Q23
Programmable Logic Controller
35
XBC/XEC-DN30SUTransistor output wiring(sink type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PECOM0COM1COM2
43COM3
4547
COM4494B
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100-240V
404142P4446NC484A
24V
XBC/XEC-DP30SUTransistor output wiring(source type)
No. Contact TypeCircuit configuration
tbPU
tbPT
tbPW
tbPV
tbPY
tbQPtbPX
tbQQ
tbQS
tbQVtbQR
tbQY
tbRRtbQX
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
comP
comQ
comR
PS
comS
PU
PW
comT
PY
RTg
PP
PQ
PR
n
PT
PV
nc
PX
QP
RTv
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PECOM0COM1COM2Q03
COM3Q05Q07
COM4Q09Q1124G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100-240VQ00Q01Q02
NQ04Q06NCQ08Q1024V
XBC/XEC-DR40SUXBC/XEC-DN40SUXBC/XEC-DP40SUDC24 Input wiring(sink/source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30
485+485-00020406080A0C0E10121416
COM
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29
RXTXSG01030507090B0D0F11131517
* XBC input : P00~P23, XEC input : I00~I35 * XBC output : P40~P57, XEC output : Q00~Q23
XBXBXBC/C/C/XEXEXEC CCSUSUSU
Wiring | XBC/XEC SU input/output wiring
36
XBC/XEC-DR40SURelay output wiring
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30
PEC0M0C0M1C0M2
43COM3
4547
COM4494B
COM54D4F
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29
AC100-240V
404142NC4446NC484ANC4C4E
24V
* XBC input : P00~P23, XEC input : I00~I35 * XBC output : P40~P57, XEC output : Q00~Q23
XBC/XEC-DN40SUTransistor output wiring(sink type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30
PEC0M0C0M1C0M2
43COM3
4547
COM4494B
COM54D4F
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29
AC100-240V
404142P4446NC484ANC4C4E
24V
XBC/XEC-DP40SUTransistor output wiring(source type)
No. Contact TypeCircuit configuration
tbPT
tbPW
tbPV
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbQY
tbRR
tbQX
tbRU
tbRX
tbRT
tbQQ
tbPU
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
comP
comQ
comR
PS
comS
PU
PW
comT
PY
comU
QS
QU
RTg
tbR
tbT
tbV
tbX
tbQP
tbQR
tbQT
tbQV
tbQX
tbRP
tbRR
tbRT
tbRV
tbRX
tbSP
tbQ
tbS
tbU
tbW
tbY
tbQQ
tbQS
tbQU
tbQW
tbQY
tbRQ
tbRS
tbRU
tbRW
tbRY
PP
PQ
PR
n
PT
PV
nc
PX
QP
nc
QR
QT
RTv
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30
PEC0M0C0M1C0M2
03COM3
0507
COM40911
COM51315
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29
AC100-240V
000102N0406NC0810NC1214
24V
Programmable Logic Controller
37
XBC/XEC-DR60SUXBC/XEC-DN60SUXBC/XEC-DP60SUInput wiring(sink/source type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
No. Contact
TB2TB4TB6TB8TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
485+485-00020406080A0C0E10121416181A1C1E2022COM
TB1TB3TB5TB7TB9TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
RXTXSG01030507090B0D0F11131517191B1D1F2123
* XBC input : P00~P23, XEC input : I00~I35 * XBC output : P40~P57, XEC output : Q00~Q23
XBC/XEC-DR60SURelay output wiring
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
PEC0M0C0M1C0M2
43COM3
4547
COM4494B
COM54D4F
COM65153
COM75557
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
AC100-240V
404142NC4446NC484ANC4C4ENC5052NC5456
24V
XBXBXBC/C/C/XEXEXEC CCSUSUSU
Wiring | XBC/XEC SU input/output wiring
38
XBC/XEC-DN60SUTransistor output wiring(sink type)
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
cPmP
cPmQ
cPmR
TS
comS
TU
TW
comT
TY
Tb
comU
Td
Tf
comV
UQ
US
comW
UU
UW
RTg
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
PEC0M0C0M1C0M2
43COM3
4547
COM4494B
COM54D4F
COM65153
COM75557
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
AC100-240V
404142P4446NC484ANC4C4ENC5052NC5456
24V
* XBC input : P00~P23, XEC input : I00~I35 * XBC output : P40~P57, XEC output : Q00~Q23
XBC/XEC-DP60SUTransistor output wiring(source type)
No. Contact TypeCircuit configuration
tbPT
tbPW
tbPV
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbQY
tbRR
tbQX
tbSW
tbTP
tbSV
tbQQ
tbPU
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
comP
comQ
comR
PS
comS
PU
PW
comT
PY
comU
QS
QU
comV
QW
QY
comW
RQ
RS
RTg
PP
PQ
PR
n
PT
PV
nc
PX
QP
nc
QR
QT
nc
QV
QX
nc
RP
RR
RTv
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24TB26TB28TB30TB32TB34TB36TB38TB40TB42
PEC0M0C0M1C0M2
03COM3
0507
COM40911
COM51315
COM61719
COM72123
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23TB25TB27TB29TB31TB33TB35TB37TB39TB41
AC100-240V
000102N0406NC0810NC1214NC1618NC2022
24V
Programmable Logic Controller
39
XBXBXBC/C/C/XEXEXEC CCSUSUSU
XBC/XEC EEconomic
Performance specifications
Wiring
42
43
C o n t e n t s
Performance specifications | Block type unit
42
Item
Specifications (‘E’ type)Performance specifications
Economic
XBC/XEC-DR10EXBC/XEC-DN10EXBC/XEC-DP10E
XBC/XEC-DR14EXBC/XEC-DN14EXBC/XEC-DP14E
XBC/XEC-DR20EXBC/XEC-DN20EXBC/XEC-DP20E
XBC/XEC-DR30EXBC/XEC-DN30EXBC/XEC-DP30E
Program control method
Program capacity
Operation ModeTotal number of program block
Program portSelf - diagnostic functions
Reiterative operation, Fixed cycle operation
Ladder Diagram (LD), Sequential Function Chart (SFC)Structured Text (ST), Instruction List (IL)
Scan synchronized batch processing method (Refresh method)Direct method by instruction
240 ns /step
RS-232C or RS-485(1 ch), Pulse catch, Input filter, External interrupt,High-speed counter
Latch area setting at basic parameter
14 point (1 option)
18 point (1 option)
28 point (2 option)
38 point (2 option)
4 Kstep (XBC-D E), 50 KB (XEC-D E)
RUN, STOP, DEBUG128
18
4 (%I 0.0.0~%I 0.0.3)8
RS-232C 1 channel (Loader)Watchdog Timer, Memory error detection I/O error detection, etc.
Task
I /O control method
Program language
Max. I /O points (Main+Option X )
Built -in functions
Retain data at power failure
Processing speed(Basic instruction)
InitializationFixed periodExternal inputInternal device
Wiring | XBC/XEC E input/output wiring
43
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
XBC/XEC-DR10EXBC/XEC-DN10EXBC/XEC-DP10EInput iring(sink/source type)
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
485+
485-
00
02
04
NC
COM
TB1
TB3
TB5
TB7
TB9
TB11
TB13
RX
TX
SG
01
03
05
NC
No. Contact TypeCircuit configurationtbPU
tbPW
tbPV
tbPY
tbQP
tbPX
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
p
comP
comQ
PS
nc
RTg
PP
PQ
PR
nc
RTv
XBC/XEC-DN10ETransistor output wiring(sink type)
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
PE
P
COM0
COM1
03
NC
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
00
01
02
NC
24V
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
PE
XBC/XEC-DR10ERelay output wiring
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
PE
COM0
COM1
COM2
43
NC
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
40
41
42
NC
24V
AC100-240V
AC100-240V
No. Contact TypeCircuit configurationtbPU
tbPW
tbPV
tbPY
tbQP
tbPX
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
n
comP
comQ
PS
nc
RTg
PP
PQ
PR
nc
RTv
XBC/XEC-DP10ETransistor output wiring(source type)
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
PE
N
COM0
COM1
03
NC
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
00
01
02
NC
24V
AC100~240V
* XBC input : P00~P11, XEC input : I00~I17 * XBC output : P40~P4B, XEC output : Q00~Q11
XBC/XEC E
Wiring | XBC/XEC E input/output wiring
44
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
XBC/XEC-DR14EXBC/XEC-DN14EXBC/XEC-DP14EInput iring(sink/source type)
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
485+
485-
00
02
04
06
COM
TB1
TB3
TB5
TB7
TB9
TB11
TB13
RX
TX
SG
01
03
05
07
No. Contact TypeCircuit configurationtbPU
tbPW
tbPV
tbPY
tbQR
tbPX
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
p
comP
comQ
PS
PU
RTg
PP
PQ
PR
PT
RTv
XBC/XEC-DN14ETransistor output wiring(sink type)
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
PE
P
COM0
COM1
03
05
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
00
01
02
04
24V
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
PE
XBC-DR14ERelay output wiring
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
PE
COM0
COM1
COM2
43
NC
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
40
41
42
NC
24V
AC100-240V
AC100-240V
No. Contact TypeCircuit configurationtbPU
tbPW
tbPV
tbPY
tbQR
tbPX
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
n
comP
comQ
PS
PU
RTg
PP
PQ
PR
PT
RTv
XBC/XEC-DP14ETransistor output wiring(source type)
No. Contact
TB2
TB4
TB6
TB8
TB10
TB12
TB14
PE
N
COM0
COM1
03
05
24G
TB1
TB3
TB5
TB7
TB9
TB11
TB13
00
01
02
04
24V
AC100-240V
* XBC input : P00~P11, XEC input : I00~I17 * XBC output : P40~P4B, XEC output : Q00~Q11
Programmable Logic Controller
45
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
XBC/XEC-DR20EXBC/XEC-DN20EXBC/XEC-DP20EInput iring(sink/source type)
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
485+485-00020406080ANCNCNC
COM
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
RXTXSG01030507090BNCNCNC
No. Contact TypeCircuit configurationtbPU
tbPW
tbPV
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
p
comP
comQ
PS
comR
PU
PW
nc
nc
nc
RTg
PP
PQ
PR
nc
PT
PV
nc
nc
nc
RTv
XBC/XEC-DN20ETransistor output wiring(sink type)
No. Contact
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
PE
XBC-DR20ERelay output wiring
No. Contact
No. Contact TypeCircuit configurationtbPU
tbPW
tbPV
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
n
comP
comQ
PS
comR
PU
PW
nc
nc
nc
RTg
PP
PQ
PR
nc
PT
PV
nc
nc
nc
RTv
XBC/XEC-DP20ETransistor output wiring(source type)
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PECOM0COM1COM2
434547NCNCNCNC24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100
-240V
40
41
42
NC
44
46
NC
NC
NC
24V
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
PEP
COM0COM1
03COM2
0507NCNCNC24G
AC100-240V
000102NC0406NCNCNC24V
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
PEN
COM0COM1
03COM2
0507NCNCNC24G
AC100-240V
000102NC0406NCNCNC24V
* XBC input : P00~P11, XEC input : I00~I17 * XBC output : P40~P4B, XEC output : Q00~Q11
XBC/XEC E
Wiring | XBC/XEC E input/output wiring
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
XBC/XEC-DR30EXBC/XEC-DN30EXBC/XEC-DP30EInput iring(sink/source type)
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
485+485-00020406080AOCOE10
COM
TB1TB3TB5TB7TB9TB11TB13TB15TB17TB19TB21TB23
RXTXSG01030507090BODOF11
No. Contact TypeCircuit configurationtbPU
tbPWtbPV
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbQY
tbRR
tbQX
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
p
comP
comQ
PS
comR
PU
PW
comS
PY
RTg
PP
PQ
PR
nc
PT
PV
nc
PX
QP
RTv
XBC/XEC-DN30ETransistor output wiring(sink type)
No. Contact
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
PE
XBC-DR30ERelay output wiring
No. Contact
No. Contact TypeCircuit configurationtbPU
tbPWtbPV
tbPY
tbQP
tbPX
tbQS
tbQV
tbQR
tbQY
tbRR
tbQX
tbT
<MZUQVITJTWKSVW
1V\MZVITKQZK
]Q\
pe
n
comP
comQ
PS
comR
PU
PW
comS
PY
RTg
PP
PQ
PR
nc
PT
PV
nc
PX
QP
RTv
XBC/XEC-DP30ETransistor output wiring(source type)
No. Contact
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
PECOM0COM1COM2
43COM3
4547
COM4494B
24G
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
AC100
-240V
40
41
42
NC
44
46
NC
48
4A
24V
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
PEP
COM0COM1
03COM2
0507
COM30911
24G
AC100-240V
000102NC0406NC0810
24V
TB2TB4TB6TB8
TB10TB12TB14TB16TB18TB20TB22TB24
TB1TB3TB5TB7TB9
TB11TB13TB15TB17TB19TB21TB23
PEN
COM0COM1
03COM2
0507
COM30911
24G
AC100-240V
000102NC0406NC0810
24V
* XBC input : P00~P11, XEC input : I00~I17 * XBC output : P40~P4B, XEC output : Q00~Q11
46
Programmable Logic Controller
47
XBC/XEC E
XBM Slim Slim
General specification
Performance specifications
Wiring
50
51
53
C o n t e n t s
Modular type unit (XBM-DN32H, DN32S, DR16S,
DN16S)
Item StandardDescriptions
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity
Operating ambience
Altitude
Pollution level *1)
Cooling
Vibration resistance
Shock resistance
Noise resistance
*1) Pollution level indicates the degree to which conductive material is generated in the environment where the equipment is used.Pollution level 2 is the condition that only non-conductive pollution occurred but temporary conductivity may be produced due tocondensing.
Continuous vibration
10 timeseach
direction(X, Y and Z)
IEC61131-2
IEC61131-2
LSIS Standard
IEC61131-2 IEC61000-4-4
IEC61131-2 IEC61000-4-3
IEC61131-2IEC61000-4-2
Electrostatic discharge
Fast transient/ Burst noise
Radiated electromagnetic
field noise
Main unit
2kV
Expansion module
1kV
4kV
80 ~ 1000MHz, 10V/m
Free from corrosive gases and excessive dust
Up to 2,000m
Less than 2
Air-cooling
Square waveimpulse noise 500 V
0 ~ 55 C
- 25 ~ + 70 C
5 ~ 95%RH (Non-condensing)
5 ~ 95%RH (Non-condensing)
Occasional vibrationFrequency
10 f < 57Hz
57 f 150Hz
-
9.8m/s2 (1G)
0.075mm
-
10 f < 57Hz
57 f 150Hz
Peak acceleration: 147m/s2 (15g) Duration: 11ms Pulse waveform: Half-sine, 3times each direction per each axis
-
4.9m/s2 (0.5G)
0.035mm
-
Acceleration Pulse width
Frequency Acceleration Pulse width
Slim
General specification
50
Cyclic execution of stored program, Time-driven interrupt, Process-driven interrupt
Batch processing by simultaneous scan (Refresh method),Directed by program instruction
LD(Ladder Diagram), Instruction List, SFC (Sequential Function Chart)ST (Structured Text)
40ns/step
Max 4
1
Max 16
540mA
28677
64kStep256 points (Main + Expansion 7 stages)
P0000 ~ P2047F (32,768 points)M0000 ~ M2047F (32,768 points)K0000 ~ K4095F (65,536 points)L0000 ~ L4095F (65,536 points)F0000 ~ F2047F (32,768 points)
100ms, 10ms, 1ms: T0000 ~ T2047 (set by parameter)C0000 ~ C2047
S00.00 ~ S127.99D0000 ~ D32767
U0.0 ~ U08.31Z000 ~ Z127 (128word)
N0000 ~ N10239 (10,240 word)RAM area 8block (R00000 ~ R32,767)
2561
Max 16Max 8
RUN, STOP, DEBUGDetects errors of scan time, memory, I/O and power supply
USB 1 channelLatch area setting in basic parameter
134g
Input/Ouput
Link
TimerCounter
StepData registerAnalog Data
Common performancespecifications for CPU
SpecificationsXBM-DN32H
RemarkItem
Program control metho
I/O control method
Processing speed(Basic instruction)
Program language
Program capacityMax. I/O points
BasicApplication
Internal device task
High SpeedCounter task
File resister
Number of instructions
PMKLFTCSDUZNP
Initial taskCyclic task
I/O task
Data area
File resister
Initial task
Total program
Operation modeSelf-diagnosis functionProgram portBack-up method
Weight
Internal consumptioncurrent
Performance specifications
51
XBXBM
MSlSlimim
Repetitive, cyclic, fixed cycle operation, constant scanRefresh mode (Batch processing by scan synchronization), Direct mode by instruction
Ladder diagram, Instruction List160 ns/Step
10Kstep
Data memory
XBM
Performance specifications XBM-DR16SItem XBM-DN16S XBM-DN32S
*1) XBM-DR16S does not have built-in positioning function.
Control method I/O control methodProgramming languageProcessing speedProgram capacity
Main unit I/O points
Max. I/O points(Main + Expansion 7 stages)Total programOperation modeSelf diagnosisProgram portRetain data at power failure
Built- in functions
16 points(Input:8, Output:8)
16 points(Input:8, Output:8)
32 points(Input:16, Output:16)
240 points 256 points
128RUN, STOP, DEBUG
Detects errors of scan time, memory error, I/O error, battery error, power error, etc.RS-232C 1 channel (Loader)
Latch area setting at basic parameterRS-232C/RS-485(2 ch), Pulse catch, Input filter, External interrupt,
PID control, High-speed counter, Positioning*1)
P0000 ~ P127F (2,048 points)M0000 ~ M255F (4,096 points)
K0000 ~ K2559F (Special area: K2600~K2559F) (40,960 points)L0000 ~ L1279F (20,480 points)
F000 ~ F255F (4,096 points)100ms, 10ms, 1ms: T000 ~ T255 (256)
(Adjustable by parameter setting) C000 ~ C255 (256)S00.00 ~ S127.99
D0000 ~ D5119 (5,120 word)U00.00 ~ U07.31 (Analog data refresh area: 256 word)
Z000 ~ Z127 (128 word)N0000 ~ N3935 (3,936 word)
PMKLF
T
CSDUZN
Data area
Slim
Performance specifications | Modular type unit
52
Wiring | XGB Slim Input wiring/Transistor output
53
XBXBM
MSlSlimim
No. TypeContactCircuit configurationXBM-DN32HInput wiring(Sink / Source type)
*
*
*
,+>
.
<MZUQVITJTWKSVW
8PW\WKW]XTMZ
*
*!
*
*
*
*
*
*
*
*
*
*!
*
*
*
*
*
*
*
*
)
)!
)
)
)
)
)
)
)
)
)
)!
)
)
)
)
)
)
)
)
A20A19A18A17A16A15A14A13A12A11A10A9A8A7A6A5A4A3
202122232425262728292A2B2C2D2E2FPP
B20B19B18B17B16B15B14B13B12B11B10B09B08B07B06B05B04B03
B02 IN_COM
OUT_COM
OUT_COM
IN_COM
A2
A1B01
000102030405060708090A0B0C0D0E0FNCNC
No. Contact
TypeContactCircuit configuration
1V\MZVITKQZK]Q\
,+>))
))
)
)
,+>
,+>
+WVVMK\WZ6W
*
*!
*
*
*
*
*
*
*
*
*
*!
*
*
*
*
*
*
*
*
)
)!
)
)
)
)
)
)
)
)
)
)!
)
)
)
)
)
)
)
)
A20A19A18A17A16A15A14A13A12A11A10A9A8A7A6A5A4A3
202122232425262728292A2B2C2D2E2FPP
B20B19B18B17B16B15B14B13B12B11B10B09B08B07B06B05B04B03
B02 IN_COM
OUT_COM
OUT_COM
IN_COM
A2
A1B01
000102030405060708090A0B0C0D0E0FNCNC
No.XBM-DN32HTransistor output(Sink type)
Wiring | XGB Slim input/output wiring
54
No. Contact TypeCircuit configurationXBM-DR16SInput wiring(sink/source type) TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
0
1
2
3
4
5
6
7
COM
No. Contact
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
20
21
22
23
24
25
26
27
COM
TypeCircuit configurationXBM-DR16SRelay output wiring
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
No. Contact No. TypeContactCircuit configurationXBM-DN16SInput wiring(sink/source type) A10
A09
A08
A07
A06
A05
A04
A03
A02
A01
NC
NC
NC
NC
NC
NC
NC
NC
NC
NC
B10
B09
B08
B07
B06
B05
B04
B03
B02
B01
0
1
2
3
4
5
6
7
COM
COM
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
Programmable Logic Controller
55
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
B10B09B08B07B06B05B04B03B02B01A10A09A08A07A06A05A04A03A02A01
2021222324252627
DC12/24VNCNCNCNCNCNCNCNC
XBM-DR16STransistor output wiring(sink type)
COM
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
B10B09B08B07B06B05B04B03B02B01A10A09A08A07A06A05A04A03A02A01
2021222324252627
DC12/24V28292A2B2C2D2E2F
XBM-DR16STransistor output wiring(sink type)
COM
No. Contact TypeCircuit configuration
<MZUQVITJTWKSVW
1V\MZVITKQZK]Q\
8PW\WKW]XTMZ
XBM-DN16S Input wiring(sink/source type)
No. Contact
B10B09B08B07B06B05B04B03B02B01
A10A09A08A07A06A05A04A03A02A01
01234567
COMCOM
NCNCNCNCNCNCNCNC
COMCOM
XBXBM
MSlSlimim
Wiring | Modular type unit
Slim
No. TypeContactCircuit configurationInput wiring(XBM-DN32S) A10
A09A08A07A06A05A04A03A02A01
08090A0B0C0D0E0F
COMCOM
B10B09B08B07B06B05B04B03B02B01
0001020304050607
COMCOM
No. Contact
No. TypeContactCircuit configurationTransistor output wiring(XBM-DN16S) B10
B09B08B07B06B05B04B03B02B01A10A09A08A07A06A05A04A03A02A01
2021222324252627
NCNCNCNCNCNCNCNC
DC12/24V
COM
No. TypeContactCircuit configurationTransistor output wiring(XBM-DN32S) B10
B09B08B07B06B05B04B03B02B01A10A09A08A07A06A05A04A03A02A01
2021222324252627
28292A2B2C2D2E2F
DC12/24V
COM
56
Programmable Logic Controller
57
XBXBM
MSlSlimim
ApplicationXGB Series
Input/Output specification
Names and functions
Built-in functions
Expansion
DC Input
Transistor Output
Relay Output
DC Input/Relay Output
Analog Input
Analog Output
Analog Input/Output
RTD
Thermocouple
Temperature controller module
Load Cell input module
Positioning module
EtherCAT positioning module
High Speed counter module
Modular type
Communication
Option modules/Smart link
Software
XGT Panel iXP Series
XGT Panel eXP Series
XGT Panel XP Series
Product list
Dimension
60
67
71
81
81
82
83
84
86
87
88
89
90
91
93
94
95
97
98
99
103
104
105
106
107
109
112
C o n t e n t s
U type
XEC-DN32U/XEC-DN32UP/XEC-DN32UAXEC-DR28U/XEC-DR28UP/XEC-DR28UAItem
Input pointInsulation methodRated input voltageRated input currentOperation voltage rangeOn voltage / On currentOff voltage / Off currentInput resistance
Insulation pressureInsulation resistanceCommon methodProper cable sizeOperation indicatorExternal connection methodWeight
Response time Off OnOn Off
16 pointPhoto coupler insulation
DC24VAbout 4mA (Contact point 0~3: about 7mA)
DC20.4~28.8V (within ripple rate 5%)DC19V or higher / 3mA or higher
DC6V or lower / 1mA or lowerAbout 5.6 (P00~P07: about 4.7 )
AC560Vrms/3 cycle (altitude 2000m)10ms or more by MegOhmMeter
16 point/COM0.3~0.75mm2
LED On when Input On8 point terminal block + 10point terminal connector
571g
1/3/5/10/20/70/100ms (Set by I/O parameter) Default: 3ms
Input specification
XEC-DN32U/XEC-DN32UP/XEC-DN32UAItemOutput pointInsulation methodRated load voltageOperation load voltage rangeMax. load currentOff leakage currentMax. inrush currentMax. voltage drop when OnSurge absorber
Common methodProper wire size
Operation indicatorExternal connection methodWeight
Response time
External power
Off OnOn Off
VoltageCurrent
16 pointPhoto coupler insulation
DC 12/24VDC 10.2 ~ 26.4V
0.5A/1 point, 2A/1COM0.1mA or less
4A/10ms or lessDC 0.4V or less
Zener diode 1ms or less
1ms or less (rated load, resistive load)16 point/COM
Stranded wire 0.3~0.75mm2 (external diameter 2.8mm or less)DC12/24V ± 10% (Ripple voltage 4 Vp-p or less)
10mA or less (When connecting DC24V)LED On when Output On
8 point terminal block connector + 10 point terminal block connector571g
Transistor output specification
Input/Output specification | Block type unit
60
High performance type
XBC/XEC-DR32HItem XBC/XEC-DN32H
XEC-DP32HXBC/XEC-
DR64HXBC/XEC-DN64HXEC-DP64H
XEC-DR32H/D1XEC-DR64H/D1
XBC/XEC-DR32H XBC/XEC-DR64HItemOutput pointInsulation methodRated load voltage / currentMin. load voltage / currentMax. load voltageOff leakage currentMax. On / Off frequency
Mechanical
ElectricalService life
Response time
Common method
Off OnOn Off
Relay insulationDC 24V 2A (Resistive load)/AC 220V 2A (COS = 1), 5A/COM
DC 5V/1mAAC 250V, DC 125V
0.1mA (AC 220V, 60Hz)3,600 times/hr
20millions times or moreRated load voltage/current 100,000 times or more
AC 200V/1.5A, AC 240V/1A (COS = 0.7) 100,000 times or moreAC 200V/1A, AC 240V/0.5A (COS = 0.35) 100,000 times or more
DC 24V/1A, DC 100V/0.1A (L / R = 7ms) 100,000 times or more10ms or less12ms or less
16 points 32 points
Input specification
Relay output specification
Input pointsRated input voltageRated input currentOperation voltage rangeOn voltage / On currentOff voltage / Off currentInput resistanceResponsetime
Off →→ OnOn →→ Off
DC 24V4mA (Contact 0~7: 9mA)
DC 20.4 ~ 28.8V (Ripple rate < 5%)DC 19V or more/3mA or more
DC 6V or less/1mA or less5.6k (P00 ~ P07: 2.7k )
16 points 16 pointsDC 12 / 24V
5 /10mA (Contact 0~7 : 7/15mA)DC 9.5~30V (Ripple rate < 5%)DC 9V or more/3mA or moreDC 5V or less/1mA or less
2.7k (%IX0.0.0~%IX0.0.7:1.8k )
32 points
4 points/COM P20 ~ 2F: 4 points/COMP30 ~ 3F: 8 points/COM
XBC-DN32H/XEC-DN(P)32H XBC-DN64H/XEC-DN(P)64HItemOutput pointInsulation methodRated load voltageLoad voltage rangeMax. load voltageOff leakage currentMax. inrush currentMax. voltage drop (On)Surge absorber
Response time
Common method
External powersupply
Off OnOn Off
VoltageCurrent
Photo coupler insulationDC 12/24V
DC 10.2 ~ 26.4 V0.5A / 1point (P20 ~ 23: 0.1A/point)
0.1mA or less4A/10ms or lessDC 0.4V or less
Zener Diode1ms or less
1ms or less (Rated load, resistive load)
DC 12/24V 10% (Ripple voltage 4 Vp-p or less)10mA or less (DC 24V connection)
16 points 32 points
4 points/COM P20 ~ 2F: 4 points/COMP30 ~ 3F: 8 points/COM
Transistor output specification
1/3/5/10/20/70/100 ms (Setting by CPU parameter) Initial value: 3ms
Programmable Logic Controller
61
APPLICSTION
Standard type
XBC/XEC-DN20SUXBC/XEC-DR20SU
XBC/XEC-DN30SUXBC/XEC-DR30SU
XBC/XEC-DN40SUXBC/XEC-DR40SU
XBC/XEC-DN60SUXBC/XEC-DR60SU
ItemInput specification
Input pointRated input voltageRated input currentOperation voltage rangeOn voltage / On currentOff voltage / Off currentInput resistance
Response time Off →→ OnOn →→ Off
DC 24V4mA (Contact point 0~1:16mA, 2~7 :10mA), DN20SU (DN30SU) : 4mA (Contact point 0~7: 10mA)
DC 20.4 ~ 28.8V (Ripple rate < 5%)DC 19V or more/3mA or more
DC 6V or less/1mA or less5.6k (P00 ~ P07 : 2.7k )
1/3/5/10/20/70/100ms (Setting by CPU parameter) Initial value : 3ms
12 points 18 points 24 points 36 points
Transistor output specification(Sink/Source type)
XBC/XEC-DR20SU XBC/XEC-DR30SU XBC/XEC-DR40SU XBC/XEC-DR60SUItemOutput pointInsulation methodRated load voltage/currentMin. load voltage/currentMax. load CurrentOff leakage currentSurge absorber
Response time
Common method ( / COM)
Life-cycle
Off OnOn Off
Mechanical
Electrical
Relay insulationDC 24V 2A/AC 220V 2A (COS = 1), 5A/COM
DC 5V/1mAAC 250V, DC 125V
0.1mA (AC 220V, 60Hz)-
10ms or less12ms or less
4 points/COM (P40, P41 : 1 point /COM), (P42 P43 : 2 points/COM)Rated load voltage/Current 10 million times or more
AC 220V/1.5A, AC 240V/1A (COS = 0.7) 10 million times or moreAC 200V/1A, AC 240V/0.5A (COS = 0.35) 10 million times or more
DC 24V/1A, DC 100V/0.1A (L / R = 7ms) 10 million times or more
8 points 12 points 16 points 24 points
Relay output specification
ItemOutput pointInsulation methodRated load voltageLoad voltage rangeMax. load voltageOff leakage currentMax. inrush currentMax voltage drop (on)Surge absorbe
Response time Off →→ OnOn →→ Off
Photo coupler insulationDC 12/24V
DC 10.2 ~ 26.4V0.5A/1 point, 2A / 1COM
0.1mA or less4A/10ms or lessDC 0.4V or less
Zener DiodeDC 12/24V± 10% (Ripple voltage 4Vp-p or less)
25mA or less (DC 24V connection)
8 points 12 points 16 points 24 points
XBC/XEC-DN20SUXBC/XEC-DR20SUXBC/XEC-DP20SU
XBC/XEC-DN30SUXBC/XEC-DR30SUXBC/XEC-DP30SU
XBC/XEC-DN40SUXBC/XEC-DR40SUXBC/XEC-DP40SU
XBC/XEC-DN60SUXBC/XEC-DR60SUXBC/XEC-DP60SU
Input/Output specification | Block type unit
62
Economic type
Relay output specification
Input specification
Specification
Modal Main unitXBC/XEC-DR10E XBC/XEC-DN10E
XBC/XEC-DR14EXBC/XEC-DN14E
XBC/XEC-DR20EXBC/XEC-DN20E
XBC/XEC-DR30EXBC/XEC-DN30E
Input pointInsulation methodRated input voltageRated input currentOperation voltage rangeOn voltage / On currentOff voltage / Off currentInput resistance
Insulation pressureInsulation resistanceCommon methodProper cable sizeOperation indicatorExternal connection method
Photo coupler insulationDC 24V
About 4mA (Contact point 0~3: about 7mA)DC 20.4~28.8V (Within ripple rate 5%)
DC 19V or higher / 3mA or higherDC 6V or lower / 1mA or lower
About 5.6k (%I 0.0.0~%I 0.0.3: about 2.7k )
6 points
1 / 3 / 5 / 10 / 20 / 70 / 100ms (Set by I / O parameter) Default: 3ms
14 point terminal block connector (M3 6 screw) 24 point terminal block connector (M3 6 screw)
AC 560Vrms / 3 cycle (Altitude 2000m)10k or more by MegOhmMeter
0.3LED On when Input On
8 points 12 points 18 points
6 points / COM 8 points / COM 12 points / COM 18 points / COM
330g313g
340g315g
450g418g
465g423g
Off OnOn OffResponse time
Weight
SpecificationModal Main unit
XBC/ XEC-DR10E XBC/ XEC-DR14E XBC/ XEC-DR20E XBC/ XEC-DR30EOutput pointInsulation methodRated load voltage / CurrentMin. load voltage/ CurrentMax. load voltageOff leakage currentMax. On / Off frequencySurge absorber
Common methodProper cable sizeOperation indicatorExternal connection method
Relay insulationDC 24V 2A (resistive load) / AC 220V 2A (COSF = 1), 5A / COM
DC 5V / 1mAAC 250V, DC 125V
0.1mA (AC 220V, 60Hz)3,600 times / hour
None20 million times or more
Rated load voltage / Current 100,000 times or moreAC 200V / 1.5A, AC 240V / 1A (CO = 0.7) 100,000 times or more
AC 200V / 1A, AC 240V / 0.5A (CO = 0.35) 100,000 times or moreDC 24V / 1A, DC 100V / 0.1A (L / R = 7ms) 100,000 times or more
10ms or less12ms or less
4 points
14 point terminal block connector (M3 6 screw) 24 point terminal block connector (M3 6 screw)
Stranded cable 0.3~0.75 (External diameter 2.8 or less)LED On when Output On
6 points 8 points 12 points
2 points / COM 4 points / COM 4 points / COM 4 points / COM
Mechanical
ElectricalService life
Response timeOff OnOn Off
Programmable Logic Controller
63
APPLICSTION
Transistor output specification(Sink /Source type)
Specification
Modal Main unit
XBC/XEC-DN10EXBC/XEC-DP10E
XBC/XEC-DN14EXBC/XEC-DP14E
XBC/XEC-DN20EXBC/XEC-DP20E
XBC/XEC-DN30EXBC/XEC-DP30E
Output pointInsulation methodRated load voltageOperation load voltage rangeMax. load currentOff leakage currentMax. inrush currentMax. voltage drop when OnSurge absorber
Common methodProper wire size
Operation indicatorExternal connection method
Photo coupler insulationDC 12/24V
DC 10.2~26.4V0.5A/1 point, 2A/1COM
0.1mA or less4A/10ms or lessDC 0.4V or less
Zener diode 1ms less
1ms less (Rated load, resistive load)4 point / COM
Stranded wire 0.3~0.75 (External diameter 2.8 or less)DC 12/24V 10% (Ripple voltage 4 Vp-p or less)
25mA or less (When connecting DC 24V)LED On when Output On
4 points
14 point terminal block connector (M3 6 screw) 24 point terminal block connector (M3 6 screw)
6 points 8 points 12 points
Response time
External power
Off OnOn Off
VoltageCurrent
Economic type
Input/Output specification | Block type unit
64
Slim type
Transistor output specification
Main unitXBM-DN32HSpecification
Model
Input pointInsulation methodRated input voltageRated input currentOperation voltage rangeOn voltage / On currentOff voltage / Off currentInput resistance
Insulation pressureInsulation resistanceCommon methodProper cable sizeOperation indicatorExternal connection methodWeight
MechanicalOff → OnOn → Off
Response time
16 pointPhoto coupler insulation
DC24VAbout 4mA (Contact point 0~3: about 5mA)
DC20.4~28.8V (within ripple rate 5%)DC19V or higher / 3mA or higher
DC6V or lower / 1mA or lowerAbout 5.6 ⁄ (P00~P03: about 4.7 )
AC560Vrms / 3 cycle (altitude 2000m)10 or more by MegOhmMeter
16 point / COM0.3~0.75
LED On when Input On40point terminal connector
134g
1/3/5/10/20/70/100 (Set by I/O parameter) Default: 3
XBM HInput specification
| Modular type unitProgrammable Logic Controller
65
APPLICSTION
Main unitXBM-DN32HSpecification
Output pointInsulation methodRated load voltageOperation load voltage rangeMax. load currentOff leakage currentMax. inrush currentMax. voltage drop when OnSurge absorber
Common methodProper wire size
Operation indicatorExternal connection methodWeight
Off → OnOn → Off
VoltageCurrent
Response time
External power
16 pointPhoto coupler insulation
DC 12/24VDC 10.2 ~ 26.4V
0.5A / 1 point, position (p00,p01,p02,p03) 0.1A/1 point 2A / 1COM0.1mA or less
4A / 10 or lessDC 0.4V or less
Zener diode 1 or less
1 or less (rated load, resistive load)16 point / COM
Stranded wire 0.3~0.75 (external diameter 2.8mm or less)DC12/24V 10% (Ripple voltage 4 Vp-p or less)
10mA or less (When connecting DC24V)LED On when Output On
4 point terminal block connector134g
Model
Slim type
XBM-DN16S XBM-DN32SItemOutput pointInsulation methodRated load voltageLoad voltage rangeMax. load voltageMax. inrush currentMax. voltage drop (On)
Response time
Common methodExtenal powersupplyExternal connection method
Off OnOn Off
VoltageCurrent
Photo coupler insulationDC 12 /24V
DC 10.2 ~ 26.4V0.2A/1 point (P20 ~ 23: 0.1A/Point)
4A/10ms or lessDC 0.4V or less
1ms or less1ms or less (Rated load, Resistive load)
DC 12/24V 10% (Ripple voltage 4 Vp-p or less)25mA or less (DC 24V connection)
20pin connector
8 point 16 point
Transistor output specification
XBM-DR16SItemOutput pointInsulation methodRated load voltage / currentMin. load voltage / currentMax. load voltageOff leakage currentMax. On / Off frequency
Mechanical
ElectricalService life
Response time
Common method
Off → OnOn → Off
8 pointsRelay insulationDC 24V 2A (Resistive load)/AC 220V 2A (COS = 1), 5A/COMDC 5V/1mAAC 250V, DC 125V0.1mA (AC 220V, 60Hz)3,600 times/hr20 millions times or moreRated load voltage/Current 100,000 times or moreAC 200V/1.5A, AC 240V/1A (COS = 0.7) 100,000 times or moreAC 200V/1A, AC 240V/0.5A (COS = 0.35) 100,000 times or moreDC 24V/1A, DC 100V/0.1A (L / R = 7ms) 100,000 times or more10ms or less12ms or less8 points / COM
Relay output specification
8 point / COM 16 point / COM
Input specification XBM-DN16S XBM-DN32SXBM-DR16SItemInput pointRated input voltageRated input currentOperation voltage range
Response time
Common method
8 pointsDC 24V
4mA (00 ~ 03: 7mA)DC 20.4 ~ 28.8V (Ripple rate < 5%)
1/3/5/10/20/70/100ms(Set by CPU parameter) Default : 3ms
8 points 16 points
16 points/COM8 points/COM
Off → OnOn → Off
Input/Output specification | Modular type unit
66
Names and functionsProgrammable Logic Controller
67
APPLICSTION
DescritpionsName Remark
LED for displaying input, output
Connector for PADT
Input terminal block
Output terminal block
SD card connector
Battery holder
RUN/STOP mode switch
Status display LED
Terminal block for theembedded Enet communication
Terminal block for theembedded communication
Displays the On/Off status of input, output contacts
Connector (USB 1channel) to access to XG5000
Terminal block receiving the actual input signal
Terminal block outputting the actual output signal
Connector with the SD memory card
Battery holder (upper part of the product)
Sets the basic unit’s operation mode.- STOP RUN : Program’s operation is executed.- RUN STOP : Program’s operation is stopped.
(In case of STOP, the remote operation is available.)
Terminal block for the embedded Enet communication
Terminal block (lower part of the product) for the embedded RS-232C/485 communication
Displays the basic unit’s operation status.- PWR (Red light On) : The power is supplied.- RUN (Green light On) : During RUN mode- ERR (Flickering red light) : Occurrence of errors during operation- STATE (Red light On/flickering Red light): When the SD card is
installed, the red light is turned On; when the SD card error occurs, the red light is flickering.
- RD/WR (Flickering red light) : During SD card Write
Block type unit (U)
No.
68
DescritpionsName Descriptions Remark
PADT connector
Mode switchInput terminal block
Output terminal block
Built-in RS-485 connector
Built-in RS-232C connector
Power terminal
Option module slot
Input LED
Output LED
Expansion module connector
Condition LED
Input indication
PWR: Power indication
RUN: RUN indication
ERR: Error indication
Output LED
Expansion module connector
PADT connection
Mode setting
Input wiring connection
Ouput wiring connection
Built-in RS-485 connection
Built-in RS-232C connectionPower supply terminal
Slot for option module
Red On: Input signal OnRed Off: Input signal Off
Red On: Power OnRed Off: Power Off
Green On: PLC RunGreen Off: PLC Stop
Red On-and-Off: PLC ErrorRed Off: PLC Normal condition
On: Output signal OnOff: Output signal Off
Connection of expansion module(I/O, Special function, Communication)
Connector for XG5000/XG-PD connection
Setting Run/Stop mode of PLC
-
-
RS-485 +/- terminal connection
RS-232C T D, R D, SG terminal connection
AC 100-240V power supply
-
Block type unit(High performance, Standard, Economic)
No.
Names and functions
69
APPLICSTION
Programmable Logic Controller
DescritpionsName
LED for displaying input, output
Input connector
Output connector
Power supply connector
Sets the basic unit’s operation mode. - STOP RUN : Program’s operation is executed. - RUN STOP : Program’s operation is stopped.
(In case of STOP, the remote operation is available.)
Displays the On/Off status of input, output contacts
Terminal block receiving the actual input signal
Terminal block outputting the actual output signal
Power supply connector (24V)
PADT connecting connector
Built-in RS-232C/485 connecting connector
Built-in Enet connecting connector
Displays the basic unit’s operation status. - PWR(Red light On) : The power is supplied. - RUN(Green light On) : During RUN mode - ERR(Flickering red light) : Occurrence of errors during operation - STATE(Red light On/flickering Red light): When the SD
card is installed, the red light is turned On; when the SD card error occurs, the red light is flickering.
- RD/WR(Flickering red light) : During SD card Write
Built-in serial communicationconnecting connector
Built-in ethernetconnecting connector
PADT connecting connector
RUN/STOP mode switch
Status display LED
Modular type unit(XBM-DN32H)
No.❶
❷
❸
❹
❺
❻
❼
❽
❾
DescritpionsName Descriptions Remark
PADT connector
Mode switch
Built-in RS-485 connector
Built-in RS-232C connector
Power connector
Input connector/ Terminal block
Output connector/ Terminal block
Expansion moduleconnector
Output LED
Input LED
Condition LED
PADT connection
Mode setting
Built- in RS- 485 connection
Built-in RS- 232C connection
Power supply connection
Input indication
PWR: Power indication
RUN: RUN indication
Input wiring connection
Ouput wiring connection
ERR: Error indication
Output LED
Expansion module connector
Red On: Input signal OnRed Off: Input signal Off
Red On: Power OnRed Off: Power Off
Green On: PLC RunGreen Off: PLC Stop
Red On-and-Off: PLC ErrorRed Off: PLC Normal condition
On: Output signal OnOff: Output signal Off
Connection of expansion module(I/O, Special function, Communication)
-
-
Connector for XG5000/XG-PD connection
Setting Run / Stop mode of PLC
RS- 485 +/ - terminal connection
RS-232C T D, R D, SG terminal connection
DC 24V power supply
Modular type unit(XBM-DR16S, DN16S, DN32S)
No.
70
Names and functions
71
APPLICSTION
Built-in functionsProgrammable Logic Controller
XGB U
SpecificationItems RemarkPerformance specifications
GroupData set Extension File size SD memory typeMemory sizeFile system
Protocol
Transfer spec
Protocol
Service
Performance
Function
Counter mode
Channel
TopologyDiagnosis
PID control
Serial
Ethernet
Datalog
High speedcounter
Control by instruction, auto-tunning,PWM output, Forced output,Operation scan time setting,Antiwindup, Delta MV, PV tracking,Hybrid operation,Cascade operation
Dedicated protocol,Modbus protocolUser defined protocol ,LS bus (inverter protocol)
Embedded00P2P:01
Embedded01P2P:02High-speedlink:01
RS-232C 1 port and RS-485 1 port
Line, starModule information, service condition
Max 10 group32 per groupcsv fileMax 16MbyteSD,SDHC type (Recommand: SanDisk,Transcend)Max 16GBFAT32
Cable: 100Base-TXSpeed: 100MbpsAuto-MDIX*1
IEEE 802.3
XGT dedicatedModbus TCP/IPuser define frame
• Internal/external preset • Latch counter• Compare output • No. of rotation per unit time
P2P, High Speed link,Remote connection
1-phase : 100MHz 8 channels2-phase : 50MHz 4 channels
4 counter modes are supported based on input pulse and INC/DEC method• 1 pulse operation Mode : INC/DEC count by program• 1 pulse operation Mode : INC/DEC count by phase B pulse input• 2 pulse operation Mode : INC/DEC count by input pulse• 2 pulse operation Mode : INC/DEC count by difference of phase
*1 Auto-MDIX (Automatic medium-dependent interface crossover) : It is the function to automatically detect whether the cable connected to the Ethernet port is peer-to-peer (straight) or cross cable
XGB UBuilt-in positioning function(XBC/XEC-DxxxUP)
Built-in functions
72
SpecificationItems Remark
Basic function
Interpolation
Positioning
Homing method
Manual operation
Encoder input
Availavle on Analog
Built-in analog function(XBC/XEC-DxxxUA)
SpecificationItems Remark
Input Range
Output Range
Input resistance
Load resistance
Max.resolution
Max.resolution
Accuracy
Accuracy
Analoginput
Analogoutput
Specification
Channels
Channels
Specification
4channels (current/voltage)
Voltage 2 channels ,Current 2 channels
1/16000
1/16000
Voltage: 1~5V, 0~5V, 0~10V, -10~10VCurrent: 4~20 , 0~20
Voltage: 1~5V, 0~5V, 0~10V, -10~10VCurrent: 4~20 , 0~20Output ranges are set in user program or I/O parameter per each channel.1MΩ or more(voltage output),600Ω or less(current output)
Current input or Voltage input can be selected throughthe external terminal wiring setting.
No. of control axi: 4axisControl Method:Position, Speed, Speed/Position, Feed ControlControl Unit: Pulse ,mm, inch, degreePositioning Data: Each axis can have up to 400 data (Step number:1~400)Operation pattern: End, Keep, ContinuousOperation method: Singular, Repeat2/3/4 axis linear interpolation2 axis circular interpolation3 axis helical interpolation
Jog operation, MPG operation, Inching operation
Line drive (RS-422A) input1Channel (Max 200kpps)
Method: Absolute/Incremental methodAddress range: 2, 147, 483, 648~2, 147, 483, 647Speed: Max 2Mpps (1~2,000,000pps)Acc /Dec process: Trapezoid type, S-typeDOG+HOME (Off),DOG+HOME (On),Upper limit + HOME, DOG, High speed,Upper/Lower limit, HOME
1MΩ or more (voltage input), 250Ω (current iput)
±0.2% or less (When ambient temperature is 25 )±0.3% or less (When ambient temperature is 0 ~ 55 )
±0.2% or less (When ambient temperature is 25 )±0.3% or less (When ambient temperature is 0 ~ 55 )
0.250 (1 ~ 5V)0.3125 (0 ~ 5V)0.625 (0 ~ 10V)1.250 (±10V)
1.0 (4 ~ 20 )1.25 (0 ~ 20 )
0.250 (1 ~ 5V)0.3125 (0 ~ 5V)0.625 (0 ~ 10V)1.250 (±10V)
1.0 (4 ~ 20 )1.25 (0 ~ 20 )
Availavle on Analog
Programmable Logic Controller
73
DescriptionItemInput voltageInput currentOn voltage (min.)Off voltage (max.)
24V DC (20.4V ~ 28.8V)4mA
20.4V6V
Input specification
XGB H/SU/E, XBM S
DescriptionBlock type unit
H SU E XBMModular typeClassification
Performance specifications
A-phase, B-phaseVoltage input (Open collector)
DC 24V
Signed 32bit (-2,147,483,648 ~ 2,147,483,647)Linear count (If 32bit range exceeded, Carry / Borrow occurs)
Ring count (Repeated count within setting range)1-phase input2-phase input
CW/CCW inputVoltage
Increasing/Decreasing operation setting by B-phase inputIncreasing/Decreasing operation setting by program
Automatic setting by difference in phaseA-phase input: increasing operationB-phase input: decreasing operation
1 multiplication4 multiplication1 multiplication
Preset instruction inputDC 24V input type
Voltage
100kpps100kpps 4ch/20kpps 4ch50kpps 2ch/10kpps 2ch50kpps 2ch/8kpps 2ch
100kpps 2ch/20kpps 6ch 4kpps 4ch 20kpps 4ch2 multiplication: 10kpps4 multiplication: 8kpps
100kpps
50kpps 1ch8kpps 3ch
2 point / channel (for each channel):output contact point of basic unit availableSelect program setting, signal-compared (>, >=, =, <=, <) or section compared output (Included or excluded)Relay, Open-collector output (Sink)To be set through programTo be set through terminal (contact) or programCount latch
1 point / channel (for each channel):output contact point of basic unit available
2kpps 2ch
4kpps 20kpps
Count inputSignal
Number ofchannels
Max. count speed
Count range
Signal type
1 phase input
2 phase input
1 phase input2 phase input
CW/CCWSignal
Signal levelSignal type
Type
Output typeCount enable
Preset functionAuxiliary mode
Output points
CW/CCW
Count mode(Program setting)
Input mode(Program setting)
Up /Downsetting
Multiplicationfunction
Control input
Externaloutput
1 phase
2 phase
SignalInput type
Signal level
APPLICSTION
Built-in functions
74
XBM HBuilt in function Specification
XBM-DN32HItems Remark
PID control
Built-in Function
Cnet
Enet
HighSpeedCounte
Position
PID control
Transferspec
Countermode
Basicfunction
Position
Interpolationfunction
Origin returnmethod
Function
Jog operation
Channel
TopologyDiagnosisProtocolServicePerformancechannels
Pulse catchExternal point InterruptInput filter
Control by instruction, auto-tuning, PWM output, Forced output, Operation scan time setting,Antiwindup, Delta MV, SV lamp, Hybrid operation, Cascade operation
StarModule information, Service conditionXGT dedicated, Modbus TCP/IP, user define frameP2P, High Speed link, Remote connection,SMTP,SNTP, Auto scan1 phase: 200 (2 phase: 100 )1phase 4 channels, 2 phase 2 channels
Dedicated protocol(XGT)Modbus protocolUser defined protocol , LS bus(inverter protocol)
Cable: 100Base-TXSpeed: 100Mbps Auto-MDIX*1
IEEE 802.3
4 counter modes are supported based on input pulse andINC/DEC method• 1 pulse operation Mode : INC/DEC count by program • 1 pulse operation Mode : INC/DEC count by phase B pulse input • 2 pulse operation Mode : INC/DEC count by input pulse • 2 pulse operation Mode : INC/DEC count by difference of phase
No. of control axis: 2axisPulse output type : pulse+ directionPosition data: 80 steps for each axis(1~80)Operation mode: end, keep, continuousOperation method: single, repeat
Jog Operation, MPG Operation, Inching Operation10 4point(P0000 ~ P0003), 50 4point(P0004 ~ P0007)10 4point(P0000 ~ P0003), 50 4point(P0004 ~ P0007)1,3,5,10,20,70,100
Absolute method / Incremental method Position address range: -2,147,483,648 ~ 2,147,483,647(Pulse) Speed range: 1~100,000pps(1pps unit) Acc/dec processing: Trapezoid-shaped
2/3/4/5/6 axis linear interpolation(XBMH: 2 axis linear interpolation)2 axis circular interpolation3 axis helical interpolation( not supported in XBMH)
DOG + HOME (Off), DOG + HOME(On), Upper/Lower limit + HOME, DOG, High speed, Upper/Lower limit, HOME
• Internal/external preset • Latch counter• Compare output • No. of rotation per unit time
RS-232C 1 port and RS-485 1 port
*1 Auto-MDIX(Automatic medium-dependent interface crossover) : It is the function to automatically detect whether the cable connected to the Ethernet port is peer-to-peer(straight) or cross cable
Programmable Logic Controller
75
Parts designation | Block type unit
Name UsageTerminalNo.
P000P001P002P003P004P005P006P007P008P009P00AP00BP00CP00DP00EP00FCOM0
Ch0 counter inputCh1 counter inputCh2 counter inputCh3 counter inputCh4 counter inputCh5 counter inputCh6 counter inputCh7 counter inputCh0 preset 24VCh1 preset 24VCh2 preset 24VCh4 preset 24VCh5 preset 24VCh6 preset 24VCh7 preset 24VCh8 preset 24VInput common
Ch0 A-phase inputCh0 B-phase inputCh2 A-phase inputCh2 B-phase inputCh4 A-phase inputCh4 B-phase inputCh6 A-phase inputCh6 B-phase input
Ch0 preset 24V-
Ch2 preset 24V-
Ch4 preset 24V-
Ch6 preset 24V-
Input common
Counter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminal
Input common
A-phase inputB-phase inputA-phase inputB-phase inputA-phase inputB-phase inputA-phase inputB-phase input
Preset input terminalNo use
Preset input terminalNo use
Preset input terminalNo use
Preset input terminalNo use
Input common
1-phase 2-Phase 1-phase 2-Phase
Name UsageTerminalNo.
IX0.0.0IX0.0.1IX0.0.2IX0.0.3IX0.0.4IX0.0.5IX0.0.6IX0.0.7IX0.0.8IX0.0.9IX0.0.10IX0.0.11IX0.0.12IX0.0.13IX0.0.14IX0.0.15COM0
Ch0 counter inputCh1 counter inputCh2 counter inputCh3 counter inputCh4 counter inputCh5 counter inputCh6 counter inputCh7 counter inputCh0 preset 24VCh1 preset 24VCh2 preset 24VCh4 preset 24VCh5 preset 24VCh6 preset 24VCh7 preset 24VCh8 preset 24VInput common
Ch0 A-phase inputCh0 B-phase inputCh2 A-phase inputCh2 B-phase inputCh4 A-phase inputCh4 B-phase inputCh6 A-phase inputCh6 B-phase input
Ch0 preset 24V-
Ch2 preset 24V-
Ch4 preset 24V-
Ch6 preset 24V-
Input common
Counter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminal
Input common
A-phase inputB-phase inputA-phase inputB-phase inputA-phase inputB-phase inputA-phase inputB-phase input
Preset input terminalNo use
Preset input terminalNo use
Preset input terminalNo use
Preset input terminalNo use
Input common
1-phase 2-Phase 1-phase 2-Phase
High performance type(XBC-H)
High performance type (XEC-H)
Standard type(XBC-SU)
Name UsageTerminalNo.
P000P001P002P003P004P005P006P007P008P009P00AP00BP00CP00DP00EP00FCOM0
Ch0 counter inputCh1 counter inputCh2 counter inputCh3 counter inputCh4 counter inputCh5 counter inputCh6 counter inputCh7 counter inputCh0 preset 24VCh1 preset 24VCh2 preset 24VCh4 preset 24VCh5 preset 24VCh6 preset 24VCh7 preset 24VCh8 preset 24VInput common
Ch0 A-phase inputCh0 B-phase inputCh2 A-phase inputCh2 B-phase inputCh4 A-phase inputCh4 B-phase inputCh6 A-phase inputCh6 B-phase input
Ch0 preset 24V-
Ch2 preset 24V-
Ch4 preset 24V-
Ch6 preset 24V-
Input common
Counter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalCounter input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminal
Input common
A-phase inputB-phase inputA-phase inputB-phase inputA-phase inputB-phase inputA-phase inputB-phase input
Preset input terminalNo use
Preset input terminalNo use
Preset input terminalNo use
Preset input terminalNo use
Input common
1-phase 2-Phase 1-phase 2-Phase
APPLICSTION
Built-in functions | High-speed counter
Built-in functions | High-speed counter
76
Parts designation | Block type unit
Wiring
Voltage output encoder Open collector encoder
Name UsageTerminalNo.
P000P001P002P003P004P005P006P007COM0
Ch0 counter inputCh1 counter inputCh2 counter inputCh3 counter inputCh0 preset 24VCh1 preset 24VCh2 preset 24VCh4 preset 24VInput common
Ch0 A-phase inputCh0 B-phase inputCh2 A-phase inputCh2 B-phase input
Ch0 preset 24V-
Ch2 preset 24V-
Input common
Counter input terminalCounter input terminalCounter input terminalCounter input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminal
Common terminal
A-phase inputB-phase inputA-phase inputB-phase input
Preset input terminalNo use
Preset input terminalNo use
Common terminal
1-phase 2-Phase 1-phase 2-Phase
Name UsageTerminalNo.
P000P001P002P003P004P005P006P007COM0
Ch0 counter inputCh1 counter inputCh2 counter inputCh3 counter inputCh0 preset 24VCh1 preset 24VCh2 preset 24VCh3 preset 24VInput common
Ch0 A-phase inputCh0 B-phase inputCh2 A-phase inputCh2 B-phase input
Ch0 preset 24V-
Ch2 preset 24V-
Input common
Counter input terminalCounter input terminalCounter input terminalCounter input terminalPreset input terminalPreset input terminalPreset input terminalPreset input terminal
Common terminal
A-phase inputB-phase inputA-phase inputB-phase input
Preset input terminalNo use
Preset input terminalNo use
Common terminal
1-phase 2-Phase 1-phase 2-Phase
Economic type (XBC-E)
Parts designation | Modular type unit
Modular type(XBM)
Programmable Logic Controller
77
APPLICSTION
Economic block type unit (E-type) dose not support built-in positioning functions
Electrical specification
Output
Input
Signal Rated inputvoltage
Load voltagerange
Max. loadcurrent / Inrush current
Max. voltagedrop (On)
Leakagecurrent (Off)
Responsetime
Signal Rated inputvoltage / Current
Load voltagerange
On voltage /Current
Off voltage /Current
Inputresistance
Responsetime
Output pulse
External high limitExternal low limitApproximate zerozero
DC 24V/7mA DC 20.4 ~28.8V
DC 24V/4mA
DC 19V/5.7mA or more
DC 19V/3.4mA or more
DC 6V/1.8mAor less
DC 6V/1.1mAor less
3.3
5.60.5ms or less
DC 5~24V DC4.75~26.4V
DC 0.3V orless
0.1mA orless 100 or less100mA (1 point)
1A/10ms or less
DescriptionBlock type unit Modular type
H-type SU-type S-typeClassification
No. of control axisInterpolation
Control mode
Control unit
Positioning data
Positioning monitor
Back-up
Positioning
Max. output pulseMax. distance of connection
2 axes2-axis linear interpolationPosition control, Speed control, Speed/Position switching control,Position /Speed switching controlPulse30-step pattern for each axis (XBC: 80step) (operation step number : 1~ 30, XBC : 1~ 80)Dedicated monitoring function for positioning in XG5000Permanent backup of downloaded parameter (FLASH memory)2-month Super Cap.backup of parameter / Data modified during operation(XBM) battery back-up (XBC)Permanent backup of parameter / Data in RAM by instruction (FLASH memory)Absolute/incremental method-2,147,483,648 ~ 2,147,483,6471 100,000 (pulse/sec)
Trapezoidal acceleration/Deceleration
1 10,000 (4 patterns each can be set)
100 Kpps2m
Performance specification
Positioning methodPositioning rangeSpeed rangeAcceleration /Deceleration typeAcceleration /Deceleration time
Built-in functions | Positioning
78
I/O specifications | Block type unit
Standard type
Signal nameXBC pin number
(XEC pin number)X axis Y axis
Operatingcondition
Direction of positioning
signal toexternal
Item
Input
Output
Limit L
Limit H
DOG
Origin
Input COM
Pulse
Direction
DC 12V~24VOutput COM
Low limit
High limit
Near point
Zero signal (+24V)
Common
External power supplyExternal 24V GND
COM
PCOM 0 ~ 3
P00008(%IX0.0.8)P00009(%IX0.0.9)P0000C(%IX0.0.12)P0000D(%IX0.0.13)
P00020(%QX0.0.0)
Pulse/CW(Open collector)
DC 12~24V
4mA /24V
Direction/CCW(Open collector)
P00022(%QX0.0.2)
P00021(%QX0.0.1)P00023(%QX0.0.3)
P0000A(%IX0.0.10)P0000B(%IX0.0.11)P0000E(%IX0.0.14)P0000F(%IX0.0.15)
High performance type (XBC/XEC-H)
XBM pin numberItem
Limit LLimit HDOGOriginInput COMPulseDirectionDC 12/24VOutput COM
EdgeEdgeEdgeEdge
-----
P00000P00001P00004P00005
P00020P00022
P00002P00003P00006P00007
P00021P00023
Low limitHigh limitNear pointZero signal (+24V)CommonPulse/CW (Open collector)Direction/CCW (Open collector)External power supplyExternal 24V GND
Y axisSignal name Operating
conditionDirection of positioning
signal to externalX axis
Input
Output
I/O specifications | Modular type unit
Signal nameXBC pin number
X axis Y axis
Operating condition
Direction of positioning
signal toexternal
Item
Input
Output
Limit L
Limit H
DOG
Origin
Input COM
Pulse
Direction
DC 12V~24VOutput COM
Low limit
High limit
Near point
Zero signal (+24V)
Common
External power supplyExternal 24V GND
COM
COM
12/24VCOM
PCOM 0~3
P00008(%IX0.0.8)P00009(%IX0.0.9)P0000C(%IX0.0.12)P0000D(%IX0.0.13)
P00040(%QX0.0.0)
Pulse/CW(Open collector)
DC 12~24V
4mA /24V
Direction/CCW(Open collector)
P00042(%QX0.0.2)
P00041(%QX0.0.1)P00043(%QX0.0.3)
P0000A(%IX0.0.10)P0000B(%IX0.0.11)P0000E(%IX0.0.14)P0000F(%IX0.0.15)
Standard type (XBC/XEC-SU)
Programmable Logic Controller
| PID/Pulse catch/Input filter/Task/RTC
79
APPLICSTION
Pulse catch When On-condition time of input signal is shorter than 1 scan time (Min. 50 ), Pulse catch processes the inputsignal as normal input.
External input signal
Input image data
Input filter Input filter prevents processing of the input signal that is shorter than the filtering time. (Filtering time is set byparameter) In the application site where noise is frequently generated, input filter prevents wrong input caused by noise.
External input signal
Input image data
DescriptionBlock type unit Modular type
H SU SClassification
Performance specification(PID)
No. of control loopControl modeControl period
Function
16-loop independent controlP control, PI control, PD control, PID control10ms ~ 6,553.5ms (Setting unit: 0.1ms)
Switching control direction automatically when exceeding dead band
Improved control precision by serial connection between master loop and slave loopPreventing overload caused by excessive SV change by setting variation slopeImproved control stability with various alarm function such as MV high limit / Low limit,PV high limit/low limit, PV variation widthAuto tuning with improved auto-tuning algorithmPWM output, PV Tracking, MV, PV, etc
Forward/ReverseMixed controlCascadeSV Ramp
Alarm
Auto tuningAdditional function
Economic block type unit (E-type) dose not support built-in PID functions
DescriptionBlock type unit Modular type
SUH E SItem
Pulse catch
10 : 4 points (P00000~P00003) 50 : 4 points (P00004~P00007)
10 : 2 points (P00000~P00001) 50 : 6 points (P00002~P00007)
50 : 4 points (P00000~P00003)
50 : 8 points (P00000~P00007)
DescriptionBlock type unit Modular type
SUH E SClassification
No. of setting pointsInput filtering time settingSetting range
Every input contactAssigning for each module
1 ~ 100 (1, 3, 5, 10, 20, 70, 100)
Task Task function is the processing method of internal/external signal generated periodically or aperiodically. It stops operation of scan program for the moment and then execute the assigned task.
RTC RTC function is for time management of system and error log. RTC function is executed steadily when power isoff or instantaneous power cut status. Current time of RTC is renewed every scan by system operation statusinformation flag.
DescriptionBlock type unit Modular type
SUH E SClassification
RTC Built-in Option module Option module Not available
DescriptionBlock type unit Modular type
SUH E SClassification
Initial task Cyclic task I /O task Internal device task
External interrupt
1( _INT)8
88 8 4 8
10 : 4 points (P00000~P00003) 50 : 4 points (P00004~P00007)
10 : 2 points (P00000~P00001) 50 : 6 points (P00002~P00007)
50 : 4 points (P00000~P00003)
50 : 8 points (P00000~P00007)
Built-in functions | PID/Pulse catch/Input filter/Task/RTC
80
I/O specifications | Block type unit
Programmable Logic ControllerExpansion | DC Input
81
APPLICSTION
Model XBE-DC08A XBE-DC16A XBE-DC32ASpecificationInput pointRated input voltage/currentOperation voltage rangeInput resistance
Response time
Insulation pressureInsulation resistanceCOMMON methodInternal current consumption
Off → OnOn → Off
DC 24V / 4mADC 20.4 ~ 28.8V (Ripple rate < 5%)
5.6k
1 / 3 / 5 / 10 / 20 / 70 / 100ms (setting by CPU parameter) Initial value: 3ms
AC 560Vrms / 3 Cycle (altitude 2000m)10M or more by megger
8 points 16 points 32 points
8 points / COM 16 points / COM 32 points / COM30mA 40mA 50mA
XBE-DC08A XBE-DC16A8-point DC Input 16-point DC Input
Specification
Wiring (XBE-DC08A/DC16A)
XBE-DC08AXBE-DC16AXBE-DC32A
82
Expansion | Transistor Output
SpecificationXBE-TN08A XBE-TP08A XBE-TN16A XBE-TP16A XBE-TN32A XBE-TP32A
TypeOutput pointRated load voltageLoad voltage rangeMax. load currentOff leakage currentMax. voltage drop (On)
Response time
Common methodInternal current consumption
Externalpower supply
Off → OnOn → Off
DC 12 / 24VDC 10.2 ~ 26.4 V
0.1mA or lessDC 0.4V
1mA or less1mA or less (Rated load, resistive load)
DC 12 / 24V 10% (Ripple voltage 4 Vp-p)
8 point
0.2A / 1point 0.2A / 1point, 2A / COM
16 point 32 point
Voltage
Current
8 points / COM40mA
10mA or less (DC 24V connection)
16 points / COM60mA
32 points / COM120mA
20mA or less (DC 24V connection)
ModelSpecification
XBE-TN08A XBE-TN16A8-point Sink Output 16-point Sink OutputWiring
(XBE-TN08A/TN16A)
XBE-TN08AXBE-TN16AXBE-TN32A
Sink Source Sink Source Sink Source
XBF-AD04CItem
Analog range
DigitalOutput
Resolution
Currentconsumption
Max. conversion speedMax. absolute inputAnalog Input ChannelsInsulation methodConnection terminalOccupied I/O points
Range
Unsigned valueSigned value
Precise value
Percentile value
Item
Range
Type 16bit binary data (Data : 14bit)0 ~ 16000
-8000 ~ 8000
0 ~ 100001/16000
1ms/channel
4 channel/modulePhoto-coupler insulation between input terminal and PLC power (no insulation between channels)
15-point terminal blockFixed type : 64points
110mA100mA
Voltage Current
DC ±15V DC ±3mA
DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V, DC -10 ~ 10V
(Input resistance 1M min )
1000 ~ 5000 (1 ~ 5V), 0 ~ 5000 (0 ~ 5V), 0 ~ 10000 (0 ~ 10V)
0.250mV (1 ~ 5V) 0.3125mV(0 ~ 5V)0.625mV (0 ~ 10V) 1.250mV(±10V)
1.0µA (4 ~ 20mA)1.25µA (0 ~ 20mA)
4000 ~ 20000 (4 ~ 20mA), 0 ~ 20000 (0 ~ 20mA)
DC 4 ~ 20mA DC 0 ~ 20mA
(Input resistance 250M )
DC 5VDC 24V
Programmable Logic Controller
83
| Relay Output
APPLICSTION
Specification Model XBE-RY08A XBE-RY16ASpecificationOutput pointInsulation methodRated input voltage/CurrentMin. load voltage/CurrentMax. load voltage Off leakage currentMax. on/Off frequencySurge absorber
Service life
Response time
COMMON methodInternal current consumptionOperation indicatorExternal connection method
Mechanical
Electrical
Off → OnOn → Off
Relay insulationDC 24V 2A (resisitive load)/AC 220V 2A (COS = 1), 5A /COM
DC 5V 1mAAC 250V, DC 125V
0.1mA (AC 220V, 60Hz)3,600 times / hr
None20million times or more
Rated load voltage/Current 100,000 times or moreAC 200V/1.5A, AC 240V/1A (COS = 0.7) 100,000 times or moreAC 200V/1A, AC 240V/0.5 (COS = 0.35) 100,000 tiems or moreDC 24V/1A, DC 100V/0.1A (L / R = 7ms) 100,000 times or more
10ms or less12ms or less
8 points / 1COM
Output On, LED On
8 points 16 points
230mA 420mA
9-pin terminal block connector 9-pin terminal block connector 2
XBE-RY08AXBE-RY16A
XBF-DV04C XBF-DC04CItem
Analog range
DigitalOutput
Resolution
Currentconsumption
Max. conversion speedAnalog Input ChannelsInsulation methodConnection terminalOccupied I/O points
Range
Unsigned valueSigned value
Precise value
Percentile value
Item
Range
Type 16bit binary data (Data : 14bit)0 ~ 16000
-8000 ~ 8000
0 ~ 100001/16000
1ms/channel4 channel/module
Photo-coupler insulation between output terminal and PLC power (no insulation between channels) 11-point terminal blockFixed type : 64points
75mA170mA
Voltage Current
DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V, DC -10 ~ 10V
(Input resistance 1k or more )
1000 ~ 5000 (1 ~ 5V), 0 ~ 5000 (0 ~ 5V), 0 ~ 10000 (0 ~ 10V)
0.250mV (1 ~ 5V) 0.3125mV (0 ~ 5V)0.625m V(0 ~ 10V) 1.250mV (±10V)
1.0µA (4 ~ 20mA)1.25µA (0 ~ 20mA)
4000 ~ 20000 (4 ~ 20mA), 0 ~ 20000 (0 ~ 20mA)
DC 4 ~ 20mA DC 0 ~ 20mA
(Input resistance 600M or less )
DC 5VDC 24V
84
Expansion | DC Input / Relay Output
DC Input specification Model DC Input (XBE-DR16A)SpecificationInput pointInsulation methodRated input voltageRated input currentOperation voltage rangeOn voltage/On currentOff voltage/Off currentInput resistance
Response time
COMMON methodWeight
Off → OnOn → Off
8 pointsPhotocoupler
DC 24V4mA
DC 20.4 ~ 28.8V (Ripple rate < 5%)DC 19V or more/3mA or more
DC 6V or less/1mA or less5.6k
1/3/5/10/20/70/100ms (setting by CPU parameter) init value: 3ms
8 points/COM81g
Relay output specification Model Relay Output (XBE-DR16A)SpecificationOutput pointInsulation methodRated input voltage/CurrentMin. load voltage/CurrentMax. load volfage Off leakage currentMax. on/Off frequencySurge absorber
Service life
Response time
COMMON methodInternal current consumptionOperation indicatorExternal connection method
Mechanlcal
Electrical
Off → OnOn → Off
8 pointsRelay insulation
DC 24V 2A (resisitive load)/AC 220V 2A (COS = 1), 5A /COMDC 5V 1mA
AC 250V, DC 125V0.1mA (AC 220V, 60Hz)
3,600 times/hrNone
20million times or moreRated load voltage/Current 100,000 times or more
AC 200V/1.5A, AC 240V/1A (COS = 0.7) 100,000 times or moreAC 200V/1A, AC 240V/0.5 (COS = 0.35) 100,000 tiems or moreDC 24V/1A, DC 100V/0.1A (L / R = 7ms) 100,000 times or more
10ms or less12ms or less
8 points/1COM250mA
Output On, LED On9-pin terminal block connector
8-point DC Input 8-point Relay OutputWiring (XBE-DR16A)
XBE-DR16A
Programmable Logic Controller
85
DC Input specification
Transistor specification
16-points DC Input 16-points Transistor OutputWiring (XBE-DN32A)
XBE-DN32A
APPLICSTION
DC input moduleXBE-DN32ASpecification
Model
Input pointInsulation methodRated input voltageRated input currentInput DeratingOperation voltage rangeOn voltage / On currentOff voltage / Off currentInput resistance
Insulation pressureInsulation resistanceCommon methodProper cable sizeCurrent consumptionOperation indicatorExternal connection methodWeight
Off → OnOn → Off
Response time
16 pointPhoto coupler insulation
DC24VAbout 4mA
DC20.4~28.8V (ripple rate < 5%)Refer to Derating diagram
DC 19V or higher / 3 mA or higherDC 6V or less / 1mA or less
About 5.6
AC 560Vrms / 3 Cycle (altitude 2000m)10 or more by Megohmmeter
16 point / COM0.3
60 (When all inputs and outputs are on)Input On, LED On40 pin connector
60g
1/3/5/10/20/70/100 (set by CPU parameter) Default:3
Main unitXBE-DN32ASpecification
Output pointInsulation methodRated voltage Rated currentOperation voltage rangeMax. load voltageOff leakage currentMax. load voltageMax. voltage drop (On)Surge absorber
Common methodProper cable sizeCurrent consumption
Operation indicatorExternal connection methodWeight
Off → OnOn → Off
VoltageCurrent
Response time
External power
8 pointPhoto coupler insulation
DC12/24V About 4mA
DC10.2~26.4V0.2A / 1 point, 2A / 1COM
0.1mA or less0.7A / 10ms or less
DC 0.4V or lessTVS Diode1 or less
1 or less (Rated load, resistive load)32 point / COM
0.360mA (when all point On)
DC12/24V 10% (ripple voltage 4 Vp-p or less)20mA or less (connecting DC24V)
LED On when output On40 pin terminal block connector
60g
Model
*
*
*
,+>
.
<MZUQVITJTWKSVW
8PW\WKW]XTMZ
1V\MZVITKQZK]Q\
,+>))
))
)
)
,+>
,+>
+WVVMK\WZ6W
86
Expansion | Analog Input
Wiring with 2-wire sensor Wiring with 4-wire sensor
XBF-AD04A XBF-AD04C XBF-AD08AItem
Analog range
Digital output
Max. conversion speedMax. absolute inputAnalog Input channels
Insulation method
Connection terminalOccupied I /O pointsCurrentconsumption
Resolution
Item
Range
TypeUnsigned valueSigned value
Precise value
Percentile value
DC 5VDC 24V
Range
Name Descriptions
RUN LED
Input selection S/W
Terminal blockExternal powersupply terminal
Indicates condition of moduleLED On: Normal conditionLED On and Off: FlickeringLED Off: Power Off or module malfunction
Voltage/Current selection switchV: Voltage input selectionI: Current input selection
External device connection
External DC 24V input
Specification
Names and Functions
XBF-AD04AXBF-AD04C
❶
❸
❹
❸
❹
❷
No.
Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and external device.
Wiring
Voltage
0~1000 0~100001/16000
0~1000
1.5ms / channel 1ms / channel 1.5ms / channel
4 channel/module 4 channel/module 8 channel/module
11-point terminal block 11-point terminal block15-point terminal blockFixed type : 64 points
120mA 110mA 105mA62mA 100mA 85mA
Photocoupler insulationbetween I/O terminal and
power supply
Photocoupler insulationbetween I/O terminal and
power supply
Photo-coupler insulationbetween input terminal and PLC power (No insulation
between channels)
15V DC 15V 15V25mA DC 3mA 25mA
2.5mV(1/4000)
5µA(1/4000)
12bit binary data0~4000
-2000~2000
16bit binary data (Data : 14bit)0 ~ 16000
-8000~8000
12bit binary data0~4000
-2000~2000
DC 0~10V(input resistance : 1MΩ min.)
DC 1~5VDC 0~5VDC 0~10V(Input resistance : 250MΩ)
DC 4~20mA,DC 0~20mA(input resistance:250Ω)
0~1000100~500 (DC 1~5V)0~500(DC 0~5V)
0~1000(DC 0~10V)
1.25mV (DC 1~5V, 0~5v)
2.5mV(DC 0~10V)
100~5000 (1~5V)0~5000 (0~5V)0~10000 (0~5V)
-10000~10000( 10V)
4000~20000(4~20mA)0~20000(0~20mA)
0.250mV (1 ~ 5V)0.3125mV (0 ~ 5V)0.625mV (0 ~ 10V)1.250mV (±10V)
1.0µA (4 ~ 20mA)1.25µA (0 ~ 20mA)
5µA (DC 4~20mA,
0~20mA)
4000~2000(DC 4~20mA)
0~2000(DC 0~20mA)
4000~2000/0~2000
DC 4~20mA,DC 0~20mA (input resistance:250Ω)
DC 1 ~ 5VDC 0 ~ 5VDC 0 ~ 10VDC -10 ~ 10V(Input resistance : 1MΩ min)
DC 4 ~ 20mADC 0 ~ 20mA(Input resistance : 250MΩ)
VoltageCurrent Voltage Current Current
Programmable Logic Controller
87
| Analog Output
XBF-DV04A XBF-DV04C XBF-DC04C XBF-DC04AItem
Analog range Selection
Resolution
Max. conversion speedMax. absolute outputAccuracyAnalog output channels
Connection terminalOccupied I /O pointsCurrent consumption
Insulation method
Analog range
Digital data
Output rangeUnsigned valueSigned value
Percentile value
Data format
Precise value
DC 0 ~ 10 V(Load resistance
2k )
DC 1 ~ 5VDC 0 ~ 5V
DC 0 ~ 10VDC -10 ~ 10V
(Input resistance : 1k or more)
1000~5000 (1~5V)0~5000 (0~5V)
0~10000 (0~10V)-1000~10000 ( 10V)
0.250m (1~5V)0.3125m (0~5V)0.625m (0~10V)1.250m ( 10V)
4000~20000 (4~20mA)0~20000 (0~20mA)
1.0µA (4~20mA)1.25µA (0~20mA)
1/1600Resolution (1/4000)
2.5mV 5
Resolution (1/4000)
DC 4 ~ 20mADC 0 ~ 20mA
(Input resistance :600M or less)
0 ~ 1000
0 ~ 10 V0 ~ 4000
2000 ~ 2000
0~1000 0~1000
0 ~160008000 ~ 8000
1ms/channel
4 channel/module
0~10000Data format of digital input is set by user program or I/O parameter
(Setting for each channel is available.)
1ms/channel15V
0.5% or less4 channel/module
1ms/channel25mA
0.5% or less4 channel/module
11-point terminal blockFixed type: 64 points
Photocoupler insulationbetween I/O terminal and
power supply
Photocoupler insulationbetween I/O terminal and
power supplyPhoto-coupler insulation between output terminaland PLC power (no insulation between channels)
110mA70mA
110mA120mA
75mA170mA
4 ~ 20mA / 0 ~ 20mA(Load resistance
510 )
XG 5000 I/O parameter4 ~ 20mA/0 ~ 20mA
0 ~ 40002000 ~ 2000
400 ~ 2000/0 ~ 2000
Name Descriptions
RUN LED
Terminal blockExternal powersupply terminal
Indicates condition of moduleLED On: Normal condition LED On and Off: FlickeringLED Off: Power Off or module malfunction
External device connection
External DC 24V input
Specification
Names and Functions
Wiring
XBF-DV04AXBF-DV04CXBF-DC04C
❶
❷
❸
No.
DC 5VDC 24V
XBF-DV04A
2k or more
2k or more
510 or less
510 or lessXBF-
DC04A
XBF-DV04C
1k or more
1k or more
600 or less
600 or lessXBF-
DC04C
APPLICSTION
Expansion | Analog Input/Analog Output
88
InputXBF-AH04A
OutputItem
Analog range selection
Digital data
Resolution (1/4000)
Max. conversion speedMax. absolute outputAccuracyInsulation methodConnection terminalOccupied I /O pointsCurrent consumption
Analog channel
Analog range
Unsigned valueSigned value
Precise value
Percentile value
XG 5000 I/O parameter and External switch0 ~ 4000
-2000 ~ 2000100 ~ 500 (DC 1 ~ 5V), 0 ~ 500 (DC 0 ~ 5V), 0 ~ 1000 (DC 0 ~ 10V)
400 ~ 2000 (DC 4 ~ 20mA), 0 ~ 2000 (DC 0 ~ 20mA)0 ~ 1000
1.25mV (DC 1~5V, 0~5V), 2.5mV (DC 0~10V)5 (DC 4~20mA, 0~20mA)
15V, 25mA1ms / Channel
0.5% or lessPhotocoupler insulation between I/O terminal and power supply
11-point terminal blockFixed type: 64 points
120mA130mA
2 channels 2 channelsDC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V
(Input resistance: 1 M min.)DC 4 ~ 20mA, DC 0 ~ 20mA
(Input resistance 250 )
DC 1 ~ 5V, DC 0 ~ 5V, DC 0 ~ 10V (Load resistance 2k )
DC 4 ~ 20mA, DC 0 ~ 20mA (Load resistance 510 )
Name Descriptions
INPUT LED
OUTPUT LED
Input selection S/WOutput selection S/ W
Terminal block
External power supply terminalExpansion connector
Indicates input condition of moduleLED On: Normal conditionLED On and Off: FlickeringLED Off: Power Off or module malfunction
Voltage / Current selection switch for inputVoltage / Current selection switch for outputTerminal for external input deviceTerminal for external output deviceTerminal for external DC 24V inputTerminal for expansion
Indicates output condition of moduleLED On: Normal conditionLED On and Off: FlickeringLED Off: Power Off or module malfunction
Specification
Names and Functions
Wiring
No.
DC 5VDC 24V
XBF-AH04A
❶❷
❽
❸
❹
❺
❻
❼
Wiring with 2-wire sensor (for analog input) Wiring with 4 -wire sensor (for analog input)
Use 22AWG, 2 conductor, twist shielded cable when wiring between analog module and external device.
Programmable Logic Controller
89
| RTD
Item XBF-RD04ANumber of channels
Conversion speedWiring method
SensortypeTemperaturerange
Accuracy
Currentconsumption
Digitaloutput
PT 100JPT 100PT 100JPT 100PT 100JPT 100Scaling250 ~ 55
DC 5VDC 24V
4JIS C1804-1997
JIS C1604-1981, KS C1603-1991200 ~ 600200 ~ 6002000 ~ 60002000 ~ 60000 ~ 4000
0.3% or less0.5% or less40ms / Ch
3-wire100mA100mA
NameNo. Descriptions
RUN LED
ALM LED
Terminal blockExternal power terminalExpansion connector
Displays the hardware operation status (Fatal fault)On: Normal statusFlickering: Error (0.2s flickering)Off: hardware error or power off
Displays the status of the channels (Light fault)Flickering: Line disconnection (1s flickering)Off: Normal status
3-wire RTD sensors can be connectedSupplies the external DC 24VConnects the module with an expansion module
Specification
Wiring
XBF-RD04A
❶
❸
❹
❺
❷
Names and Functions
2-wire 3-wire 4 -wire
Terminal Terminal Terminal
APPLICSTION
Expansion | Thermocouple
90
Specification
Names and Functions
Wiring
XBF-TC04S
❶
❸
❹
❺
❷
❻
Item XBF-TC04SNumber of channels
Input sensor type
Temperature input range
Digital output
Accuracy
Max. conversion speedWarming-up timeTerminalI /O points occupiedCurrent consumption
KJTRTemperature display unitScaling display(Defined by user)Normal temperature (25)Temperature coneffcient (0 ~ 55)
DC 5VDC 24V
4Thermocouple K/J/T/R
JIS C1602 1995200.0 ~ 1300.0 (- 328.0 ~ 2372.0 )200.0 ~ 1200.0 (- 328.0 ~ 2192.0 )
200.0 ~ 400.0 (- 328.0 ~ 752.0 )0.0 ~ 1700.0 (32.0 ~ 3092.0 )
Display down to one decimal placeK, J, T: 0.1 R: 0.5
Unsigned scaling (0 ~ 65535)Signed scaling (-32768 ~ 32767)
0.2%100 ppm /
50ms / Channel15 minutes or more
11-point terminal64 points100mA100mA
Name Descriptions
RUN LED
ALM LED
Terminal blockExternal power terminalRJC
Displays the hardware operation status (Fatal fault)On: Normal statusFlickering: Error (0.2s flickering)Off: hardware error or power off
Displays the status of the channels (Light fault)Flickering: Line disconnection (1s flickering)Off: Normal status
Terminals to connect the thermo-couple sensorTerminals to supply the external DC 24VDevice for Reference Junction Compensation
No.
Module Compensationcable Terminals
Shieldcable Sensor
Programmable Logic Controller| Temperature controller module
91
Item XBF-TC04TT
Warm-upMaximum rate of ambient temperature changingAccess terminalIO occupation point
Power supplyCurrent consumed
Sampling periodControl method
Temperature coefficientCompensation methodCompensation degree
Proportional gainIntegral timeDerivative timeOutput pointRated load voltageMax. load currentMax. voltage drop when onLeakage current when off
Control output cycleTime proportional resolution
Input terminal-PLC powerOutput terminal-PLC powerBetween output channelsWeighted averageMoving average
K
J
T
Standard precision
Target value (SV)
Max. no. of installation
Control loopThermocoupletype and inputrange
Precision
Cold junctioncompensation
Control parameter
Insulation
Averagingfunction
Transistor output
4 loop-200.0 ~ 1300.0
0.0 ~ 500.0 -200.0 ~ 1200.0
0.0 ~ 500.0 -200.0 ~ 800
100ppm/ (0.01%/ )Automatic compensation by RJC sensing
2.0 500ms/ 4 loop
PID CONTROL, ON/OFF CONTROL
0: ON/OFF CONTROL, REAL0: Except integral control, REAL
0: Except derivative control, REAL4
DC 24 V0.1 A / Output point
DC 1.2 V or less0.1 mA or less1 ms or less1 ms or less
0.5 ~ 120.0 sec (Setting unit: 0.5 sec.)Larger one of either 10 ms or 0.05% of the full-scale
0 ~ 99% (setting range)0 ~ 99 times (setting range)
20 minutes or above0.5 /min (30 /hour) or less
16 point terminal (10 point terminal 1ea, 6 point terminal 1ea)Fixed: 64 points
5 V, DC 24 VInternal DC 5 V : 120 mA, External DC 24 V : 100 mA
0.2% or less (25 , normal temperature, except -200~-100 for the T type)
Setting within range according to input type (temperature unit setting)
XBM-DxxxS type: 7ea, XB(E)C-DxxxH type: 10ea,XB(E)C-DxxxSU: 7ea, XB(E)C-DxxxU: 10ea
Non-insulation
Photo relay
Photo relay Insulation resistor: 500V DC, 10 M or above
Withstanding voltage: 400V AC, 50/60Hz 1min, leakage current 10mA or less
Specification
XBF-TC04TT
Response time
Between input channels
On => OffOff => On
APPLICSTION
Expansion | Temperature controller module
92
Item XBF-TC04RT
Access terminalIO occupation point
Power supplyCurrent consumed
Sampling periodControl method
Pt100 JPt100Standard precisionTemperature coefficient
Proportional gainIntegral timeDerivative timeOutput pointRated load voltageMax. load currentMax. voltage drop when onLeakage current when off
Control output cycleTime proportional resolution
Input terminal- PLC powerOutput terminal- PLC powerBetween output channelsWeighted averageMoving average
Target value (SV)
Response timeOn => OffOff => On
Between input channels
Control loopRTD type andinput range
Precision
Control parameter
Transistor output
Insulation
Averagingfunction
Max. no. of installation
Non-insulation
4 loop-200.0 ~ 850.0 -200.0 ~ 600.0
0.2% or less (25 , normal temperature)100ppm/ (0.01%/ )
500ms/ 4 loopPID CONTROL, ON/OFF CONTROL
0: ON/OFF CONTROL, REAL0: Except integral control, REAL
0: Except derivative control, REAL4
DC 24 V0.1 A/Output pointDC 1.2 V or less0.1 mA or less1 ms or less1 ms or less
0.5 ~ 120.0 sec (Setting unit: 0.5 sec.)Larger one of either 10 ms or 0.05% of the full-scale
0 ~ 99% (setting range)0 ~ 99 times (setting range)
18 point terminal (12 point terminal 1ea, 6 point terminal 1ea)Fixed: 64 points
5 V, DC 24 VInternal DC 5 V : 120 mA, External DC 24 V : 100 mA
Photo relay
Photo relay
Specification
XBF-TC04RT
Insulation resistor: 500V DC, 10 M or above
Withstanding voltage: 1500V AC, 50/60Hz 1min, leakage current 10mA or less
XBM-DxxxS type: 7ea, XB(E)C-DxxxH type: 10ea,XB(E)C-DxxxSU: 7ea, XB(E)C-DxxxU: 10ea
Setting within range according to input type(temperature unit setting)
Programmable Logic Controller| Load Cell input module
93
Item SpecificationsInput ChannelLoad Cell Input VoltageLoad Cell TypeResolutionAnalog Input RangeLoad Cell Output Sensitivity
Warm-up timeInput ConnectorIO Occupation Points:
Power Supply
Sampling Cycle (per channel)
Input Accuracy
Insulation
Max. no. of installation
Consumption
2 Channel (Insulation between Channels)5VDC 5%, (8 per 350 load cell channel)
Four-wire or Six-wire1/40000
0.0~6.00.125 (when the rated output of the load cell is 0.0 ~ 1.0 / V)
30 minutes or above8 pins Connector(CH0)/10 pins Connector(CH1)
Fixed type:64 points
5V, DC 24Internal DC5V : 110 External DC24V : 280
XBM-DxxxS type: 7ea, XB(E)C-DxxxH type: 10ea, XB(E)C-DxxxSU: 7ea, XB(E)C-DxxxU: 10ea,
5
Specification
XBF-LD02S
0.01% or below (nonlinear accuracy, 25 )Zero Drift: 0.25 Gain Drift: 15ppm//
Input terminal-Internal circuitsBetween input
channelsExternal power-Internal circuits
AC 550 V 50/60 Hz 1 minute,
Leakage 10 mA or below
Isolator
Transformer
DC/DCConverter
DC500 V,10 M or
above
APPLICSTION
Classification Insulation Method
InsulationResistance
Insulation Voltage Resistance(Internal Test Specifications)
Expansion | Positioning module
94
Item XBF-PDO2AN0. of control axisPulse output typeMax. pulse outputMax. connection length
Control mode
InterpolationPositioning dataConfiguration toolBack-up
Positioning
Max. encoder inputError /OperationI/O occupied pointsConnection terminalCurrent consumption (mA)
Positioning methodUnitPositioning rangeSpeed rangeAcceleration/Deceleration typeAcceleration/Deceleration time
2 axisLine drive
2Mpps10m
Position control, Speed control, Speed /Position switching control,Position / Speed switching control
Linear interpolation, Circula interpolation150 operation data for each axis
Built-in function parameter of XG5000Flash memory
Absolute/Incremental methodpulse
2,147,483,648 2,147,483,6481 2,000,000 (pulse/sec)
Trapezoidal acceleration/deceleration0 65,535ms, Asymmetric acceleration/deceleration
200kpps (Line drive)LED
Fixed type: 64 points40pin connector
500
Name Descriptions
Terminal block
RUN LED
1. RUNDisplays the hardware operation status
On: Normal statusOff: Abnormal status
Terminals to connect the MPG, external device anddrive device.
2. X_AXIS, Y_AXISOn: OperationFlickering: Error
No.
Specification
Names and Functions
XBF-PD02A
Pin numberX axis Y axis
Signal name
Manual Pulse Generator/Encoder A inputManual Pulse Generator/Encoder A inputManual Pulse Generator/Encoder B inputManual Pulse Generator/Encoder B input
Forward pulseForward pulseReverse pulseReverse pulse
High limitLow limit
Near point
Common
Inposition signalInposition signal common
Deviation counter clear signalDeviation counter clear signal common
Zero signal (DC 5V)Zero signal Common
B20A20B19A19
A18A17A16A15A14A13A12A11A10A09A08A07A06A05A04A03A02A01
B18B17B16B15B14B13B12B11B10B09B08B07B06B05B04B03B02B01
MPG AMPG AMPG BMPG B
FPFPRPRPOVOVDOG
NC
COMNCINP
INP COMCLR
CLR COMHOME 5VHOME COM
NC
Terminal
❶
❷
Programmable Logic Controller| EtherCAT positioning module
95
Item XBF-PN08B
Communication PeriodMax. transmission distanceCommunication cableError indicationCommunication status indicationConsumable currentWeight
Manual OperationHoming methodSpeed change functionTorque unitAbsolute position system
XG-PM
Position address range
Absolute IncrementalSpeed/Position,Position/Speed
Switching control
ConnectionSetting data Monitor
ChannelMax. InputInput formInput typeConnection connector
Speed range
Acc./Dec. time
Acc./Dec. process
Positioning method
Positioning
ExternalEncoderinput
Control method
Positioning data
Back-up
Control unit
No. of control axisInterpolation function
Specification
XBF-PN08B
Position control, Speed control, Speed/Position control, Position/Speed control,Position/Torque Control, Feed control
Each axis can have up to 400 operation data .(Operation step number : 1~400)Available to set with XG-PM or program
Trapezoid type, S-type
1~2,147,483,647msselection is available from 4 types of acceleration/deceleration pattern
mmInchdegreepulserpm
mmInchdegreepulse
-214748364.8~214748364.7( )-21474.83648~21474.83647-21474.83648~21474.83647-2147483648~21474836470.01~20000000.00(ßÆ/min)0.001~2000000.000(Inch/min)0.001~2000000.000(degree/min)1~20,000,000(pulse/SEC)0.1~100000.0(RPM)
-214748364.8~214748364.7( )-21474.83648~21474.83647-21474.83648~21474.83647-2147483648~2147483647
-214748364.8~214748364.7( )-21474.83648~21474.83647-21474.83648~21474.83647-2147483648~2147483647
Jog Operation, MPG Operation, Inching OperationRefer to the method supported by the servo driver
Speed change (Percent/Absolute value)Rated torque % designation
Available (when using absolute encoder type servo driver)1 channel200 kpps
Line drive input (RS-422A IEC specification), open collector output type encoder CW/CCW, PULSE/DIR, Phase A/B
9-point connector1ms
100mOver CAT.5 STP (Shielded Twisted-pair) cable
Indicated by LEDIndicated by LED
510mA115g
82~8 axes linear interpolation, 2 axes circular interpolation, 3 axes helical interpolation
Pulse, mm, inch, degree
RS-232C port of CPU module or USBCommon, Basic, Extended, Servo parameter, Operation data, Cam data, Command information
Operation information, Trace, Input terminal information, Error informationSave the parameter, operation data in MRAM ROM (No need of Battery)
Absolute method/Incremental method
❶❸❹
❻
❺
❷
APPLICSTION
Expansion | EtherCAT positioning module
96
Name Descriptions
Operation indicator LED(AX1 ~ AX8)
Communication statusindicator LED
TRX status LED
Connector for encoderwiring
RJ-45 connector
Module ready signalOn: Positioning module normal statusOff: Power OFF or CPU module reset statusFlicker: Positioning module abnormal status
On: applicable axis is runningOff: applicable axis is stop statusFlicker: applicable axis is error status
On: communication with servo driver is connectedOff: communication with servo driver is disconnectedFlicker: Error occurs during communicating with servo driver
On: Wiring with servo driver is doneOff: Wiring with servo driver is not doneFlicker: communicating with servo driver
Connector to connect with encoder
RJ-45 connector to connect with servo driver
No.Names and Functions
Signal namePin No.Pin arrangement Signal direction
Encoder A 24V inputEncoder A 5V inputEncoder A input COMEncoder B 24V inputEncoder B 5V inputEncoder B input COMEncoder Z 24V inputEncoder Z 5V inputEncoder Z input COM
A 24VA 5VA COMB 24VB 5VB COMZ 24VZ 5VZ COM
123456789
Input
Terminal
❶
❷
❸
❹
❺
❻
A 24VA 5VA COMB 24VB 5VB COMZ 24VZ 5VZ COM
Programmable Logic Controller| High speed counter module
97
XBF-HO02ASpecification
XGF-HD02AItem
Countinput signal
Up/downsetting
Multiplica-tion function
Control input
Externaloutput
OperationstatusdisplayCount enablePreset function
TerminalI/O occupied pointsCurrent consumption(mA)Weight
Auxiliary mode function
Maximum coefficient speedNumber of channelsCoefficient range
Count mode
Input pulse mode
SignalInput typeSignal level
A-phase, B-phase
2 ChannelsSigned 32-bit (-2,147,483,648 ~ 2,147,483,647)
Linear Count (When 32-bit range exceeded, Carry /Borrow occurs, The count value stopped)Ring Count (Repeated count within setting range)
1-phase input2-phase input
CW/CCW inputIncreasing/Decreasing operation setting by B-phase input
Increasing/Decreasing operation setting by programAutomatic setting by difference in phase
A-phase input: Increasing operationB-phase input: Decreasing operation
1/2 multiplication1/2/4 multiplication
1- multiplicationPreset instruction input, Auxiliary mode instruction input
DC 5V/12V/24V (by terminal selection) input typeVoltage
2-point /channel (for each channel ): Terminal output availableSelect single-compared (>, >=, =, =<, <) or section compared output (Included or excluded)
Open collector output (Sink)A-phase input, B-phase input, Preset instruction input, Auxiliary mode instruction input
External output 0, External output 1Module Ready
To be set through program (Count available only in enable status)To be set through terminal or program
Count clear,Count latch,
Section count(time setting value: 0~60000),Measurement of input frequency(for respective input phase),
Measurement of counts per hour(time setting value: 0~60000)Count prohibited function
40 pin connectorFixed point : 64
90g
Voltage input (Open Collector)DC 5/12/24V
200kpps
200 260
Differential input (Line Drive):RS-422A Line Drive/HTL LEVEL Line Drive
500kpps (HTL input : 250kpps)
1-phase input
1-phase input2-phase inputCW/CCWSignalSignal levelSignal typeOutput pointsTypeOutput typeInput signalOutput signalBusy status
CW/CCW
2-phase input
Specification
XBF-HO02AXBF-HD02A
NameNo. Descriptions
Run LED(ØA,ØB, P, G, 00, 01)
Ready signal (RDY)
External wiring connector
On: Relevant channel pulse inputting, Preset /Auxiliary function signal inputting, OutputtingOff: No input of relevant channel pulse, No input of preset / Auxiliary function signal, No output of comparisonOn: HSC module normalOff: Power off or CPU module reset, HSC module errorFlicker: HSC module error
Connector to conect with external I/O
Names and Functions
❷
❶
APPLICSTION
Expansion | Modular type
98
Pin arrangementB ch1 A ch0
Signal name
2019181716151413121110090807060504030201
2019181716151413121110090807060504030201
A 24VA 12VA 5V
A COMB 24VB 12VB 5V
B COMP 24VP 12VP 5V
P COMG 24VG 12VG 5V
G COMOUT0OUT124V24G
A phase pulse input 24VA phase pulse input 12VA phase pulse input 5V
A phase pulse input COMB phase pulse input 24VB phase pulse input 12VB phase pulse input 5V
B phase pulse input COMPreset input 24VPreset input 12VPreset input 5V
Preset input COMAuxiliary function input 24VAuxiliary function input 12VAuxiliary function input 5V
Auxiliary function input COMComparison output 0Comparison output 1
External power input 24VExternal power input GND
Terminal (XBF-HO02A)
B A
Pin arrangementB ch1 A ch0
Signal name
2019181716151413121110090807060504030201
2019181716151413121110090807060504030201
A +A -A +A -B +B -B +B -
P 24VP 12VP 5V
P COMG 24VG 12VG 5V
G COMOUT0OUT124V24G
A phase differentiation input +A phase differentiation input -A phase differentiation input +A phase differentiation input -B phase differentiation input +B phase differentiation input -B phase differentiation input +B phase differentiation input -
Preset input 24VPreset input 12VPreset input 5V
Preset input COMAuxiliary function input 24VAuxiliary function input 12VAuxiliary function input 5V
Auxiliary function input COMComparison output 0Comparison output 1
External power input 24VExternal power input GND
Terminal (XBF-HD02A)
B A
Programmable Logic Controller
99
| Communication
Item XBL-EMTACommunication spec.Protocol
Service
HS link sending/Receiving data
No. of channel Connectableto upper stage
Service
MediaCurrent consumption (mA)
With LS PLCsWith other devicesApplication
10/100 Base-TXTCP/IP, UDP/IP
High-speed link , P2P serviceP2P service
XGT Dedicated protocol Server/Client, Modbus/TCP Server/Client200words/block (Max.64blocks)
6 channels
Communication with PC (HMI) and external devices, High-speed communication among LSIS PLCs
UTP/STP Category 5300
Ethernet (XBL-EMTA)
Item XBL- EIMT
Transmission standard
Basic standard
Transmission speedTransmission methodMax. extension distancebetween nodesMax. number of nodesMax. protocol sizeAccess method to service zoneFrame error checkNormal communication guaranteeDimension (mm)Current consumption(mA)Weight (g)
100MbpsBase band
100m
641,516 bytesCSMA / CD
CRC 32 = X32+ X26 + X23 + ,,,,, + X2 + X + 1Max. 1,200 (packet /sec)90(H) x 27(W) x 60(D)
290102
RAPIEnet (XBL-EIMT)
Item Built-in RS-232C XBL-C21A Built-in RS-485 XBL-C41AInterfaceMODEM function
Mode
Operation mode
Data format
SynchronousSpeed (bps)Station numberDistanceMODEM communicationNetworkDiagnosticMax. expansion
Dedicated modeXG5000 modeP2P modeServer (slave)Client (master)Start BitData BitStop BitParitySetting
Remote communication via the external MODEM (XBL-C21A Only)1:1 or 1:N via the dedicated protocol
Program download, Upload and control via the remote controlCommunication defined by the protocol using XG-PD XGT/Modbus master
XGT/Modbus server, User-defined communicationXGT/Modbus P2P Master, User-defined communication
17 or 81 or 2
Even / Odd / NoneSetting by XG-PD parameter
Asynchronous1,200/2,400/4,800/9,600/19,200/38,400/57,600/115,200 bps
Setting by XG-PD, Max. 32 stationsRS-232C: Max.15m (Expansion by MODEM), RS-422/485: Max 500m
Via LED and XG-PD
RS-232C 1ch RS-232C 1ch RS-485 1ch RS-422 / 485 1ch
-
1 : 1Support -
1 : N-
Built-in 2 stages Built-in 2 stages
XBL-C21AXBL-C41A
RS-232C, RS-422 / 485
APPLICSTION
Expansion | Communication
100
Item
TCP
Max. setting datasize per block
Basic standard
CIP (IO communication)
Periodic clientAperiodic clientDimension (mm)Current consumption(mA)Weight (g)
Number of Max. services (P2P)Number of Max. installations
The number ofconnections(Client/Server)
XBL- EIPT
Transmission standard
Transmission speedTransmission methodMax. extension distencebetween nodesAccess method to service zone Frame error check
100MbpsBase band
100m
CSMA/CDCRC 32 = X32+ X26 + X23 + ,,,,, + X2 + X + 1
Line, Star16 / 3232 / 64
22
500 bytes512 bytes
90(H) x 27(W) x 60(D)290102
Ethernet/IP (XBL-EIPT)
Topology
Item
Max. number of stations per segmentCable used
Communication Transmission cycleCommunication Receive cycleMax. number of units installedCommunication Parameters to setInternal-consumed current (mA)Weight (g)
Max. Communication size
Max. Communication size per block
Module TypeNetwork TypeStandardInterfaceTopologyModulation TypeProtocol
Max. Distance & Transmission Speed
XBL-PMEC XBL-PSEASlave
Profibus-DPEN501170/DIN19245
RS-485 (Electric)Bus type
NRZ (Non Return to Zero)Profibus DP-V0
32 (including master & repeater)Electric-twist shielded pair cable
10/20/50/100/200/500ms, 1/5/10sMain unit scan 2 + Data receive time + Communication module scan
2 unitsXG5000 (setting station and high-speed link parameter block)
86 (including connector: 122)
Distance (m)1,200400200100
Send Speed (bps)9.6k/19.2k/93.75k/187.5k
500k1.5M
3M/6M/12M
Profibus-DP Module(XBL-PMEC, XBL-PSEA)
300
Input : 122 WordOutpuut : 122 Word
Input : 64 WordOutpuut : 64 Word
250
Programmable Logic Controller
101
Item
Parameter setting
Transmission Specification
XG5000(High-speed link)
Basic Specification
Transmission Speed (kbps)Transmission Type
Thick CableThin Cable
Terminal resistance ( )125 kbps250 kbps500 kbps
Data PacketMessage Access Control
Bus TypeMax. number of nodsSystem FeaturesOperation Voltage
Diagnosis Function
Master/Slave Operation
Data process unit
Max. communication point Max. block number Max. point number per blockMax. modules installedInternal-consumed current (mA)Weight (g)
XBL-DSEA125/250/500
Poll, Bit strobe, COS, Cyclic500 (125kbps)/250 (250kbps)/100 (500kbps)
100 (125/250/500kbps)121 (1%, 1/4W)
6 (Max. extended length 156)6 (Max. extended length 78)6 (Max. extended length 39)
0~8 BytesCSMA/NBA
Poll typeUp to 64 (including master) MAC IDs (MAC Identifier)
Insertion and removal of nod available in voltage On statusDC 24V
Available only in slaveSetting to High-speed link of XG5000 (RS-232C of CPU module or USB port)
Word
Send 2048points, Receive 2048 points, 256 bytes respectively64 (Setting range: 0~63)1024 points (64 Words)
Up to 2100mA
110
ItemTransmission SpeedMax. Tx distanceConnection Cable
Diagnostic functionTerminal resistance ( )Master/Slave operation
Maximum stationsconnected
XG5000(HS Link)
Specification
Network
Tx/Rx cycle
Data Processing unit
Max. Communication points.Max. Block numberMax. points by BlockAuto scanningMax. module mounted
XBL-RMEA1Mbps(Rnet I/F modules common)
Max. 750mTwisted pair shielded cable
XG5000 : High Speed Link Monitoring110 ( 5%), 1/2W
Only available as MasterByte
3,780 Bytes (slave 31stations * 120Bytes/station)64 (setting range : 0~63)
120 Byte (60words)Supported2 modules
Master station 1[station no:0(fixed)] +Slave stations up to 31[station no:1~63], Note 1)
- Only 1 master is available in the network.
Selection among 20ms, 50ms, 100ms,200ms(default), 500ms, 1s, 5s, 10s
Rnet(XBL-RMEA)
DeviceNet Module(XBL-DSEA)
Module: Checks duplicated station/ Checks CRC error SyCon: Detects defective station/Checks BusOff/Auto-scan function
XG5000: Monitors High-speed link
Select among 10ms, 20ms, 50ms, 100ms, 200ms, 500ms, 1s, 5s and 10s- Default : 20ms
Trunk/drop linePower/Signal cable inside the identical network cable
Communicationdistance (m)
Max.drop length (m)
Network Structure
Send/Receive period
APPLICSTION
Expansion | Communication
102
Item
Max. size of data per PDOPDO transfer typeSupport SDOSDO transfer typeAccess methodTopologySYNC ServiceNMT. eode controlEmergencyNMT. error controlNetwork scanSize (mm)Current consumption (mA)Weight (g)
Transmission SpeedNum. of portMax. node
TPDORPDO
PDO
XBL-CSEAXBL-CMEA10, 20, 50, 100, 125, 250, 500, 800, 1000Kbps
1
8ByteSynchronous acyclic (0), synchronous cyclic (1~240), RTR (252~253), time-event trigger (254~255)
CSMA/BA (Carrier Sense Multiple Access/Bitwise Arbitration)BUS
90 (H)X27 (W)X60 (D)
78
32
Total 32
211 202
-6464
ConsumerNMT slave
Save up to last 10Heartbeat
-
Client 127/Server 1Expedited, Normal
Server 1-
Producer Cycle : 20~5000msNMT master
Save the last five per slaveHeartbeat, Life guarding
CANopen Module(XBL-CMEA, XBL-CSEA)
Programmable Logic Controller
103
| Option modules / Smart link
APPLICSTION
Terminal board Connection cable XBM-DN16S
XBM-DN32S XBE-DC32A XBE-TN32A XBE-TP32A Cable length
TG7-1H40S(Terminalboard)
TG7-1H40CA(Terminalboard, Common)
R32C-NS5A-40P(Relayboard : sink)
R32C-PS5A-40P(Relayboard : source)
0.5m1.0m0.5m1.0m1.5m2.0m3.0m0.5m1.0m1.5m2.0m3.0m0.5m1.5m2.0m
R40H/20HH-05S-XBM3R40H/20HH-10S-XBM3
C40HH-05SB-XBIC40HH-10SB-XBIC40HH-15SB-XBIC40HH-20SB-XBIC40HH-30SB-XBI
C40HH-05SB-XBIC40HH-10SB-XBIC40HH-15SB-XBIC40HH-20SB-XBIC40HH-30SB-XBIC40HH-05PH-XBPC40HH-15PH-XBPC40HH-20PH-XBP
Smart link
Connection cable
Terminal board
Option modules Option modules
XBO-RTCAXBO-DC04AXBO-TN04AXBO-RD01A
RTC (Real Time Clock)DC 24V, Input 4 pointsTransistor (Sink), Output 4 pointRTD (Resistance Temperature Detect, Input 1 ch)
XBO- AD02A XBO-DA02A
XBO-AH02A
XBO-TC02A
Voltage/Current, Input 2 chs Voltage/Current, Output 2 chs Voltage/Current, Input 1 chVoltage/Current, Output 1 ch TC (Thermocouple), Input 2 chs
Software
104
Program editing & Engineering softwareWindows-based easy operationMulti-PLC, Multi-programming supportVarious monitoring and diagnosis functionsVista 2000, XP (Limited use in Windows 98, ME)
Convenient network settingExtended monitoring function for network system and communication modulesFast interface with CPU by effective network managementVarious built - in diagnosis, functions(CPU condition, Link conditon, Service condition, Frame monitoring)
Trend monitor Special module monitor
Ladder monitor
Forced I/O
Variable monitor
Parameter setting
Service conditionmonitoring
Network scan
Frame monitoring
XGT Panel
Link monitoring
Fast ethernet
Cnet
Smart I/O
Other PLC
Other net devics
LS Inverter
XG5000(Programming software)
XG -PD(Network setting software)
Programmable Logic ControllerXGT Panel iXP Series
105
APPLICSTION
Main Specification1GHz 32bit RISC Embedded CPU16,777,216 TFT color LCD128MB display data and 1MB back-up memory
Ethernet 1ch, RS-232C 2ch, RS-422/485 1chUSB host 3ch and device 1ch SD memory card interface
Main FunctionsPLC ladder monitoring (XGK/XBC PLC only)Web Server/Data ServerPath through
XP-Remote : Remote controlling and monitoring
16-bit and 24-bit Color (default: 16-bit Color)
LED Type
4-Line type, analogMagnetic buzzer (85dB)
ARM Cortex-A8 Core (32bit RISC), 1GHz
1MBDate/Hour data, Logging/Alarm/Recipe data and nonvolatile device
Approx. 3 years (Operating ambient temperature of 25 )1 channel, 10/100BASE-TX
3 channels, USB 2.0 host (mouse, keyboard, printer* and USB memory driver is available)1 channel, USB 2.0 slave (for download and upload project file)
1 channel1 channel, RS-422/485 mode
1 Slot (SDHC)
LINE-OUT 1 channelFor communication and I/O option module (available later)
4 channels video input (available later)Up to 12 language simultaneously
GIF format is availableavailableavailableavailable
CE, UL(cUL), KCIP65
Item
Display typeScreen sizeDisplay ResolutionColor indication
BacklightBacklight durationBrightnessTouch panelSound OutputProcess
FlashOperating RAMBackup RAM
Backup dataBattery durationEthernet
RS-232CRS-422/485SD Card
Audio outputExpansion moduleVM moduleMulti-languageAnimationRecipeData loggingScript executorCertificationsProtection standardDimension (mm)Panel cut (mm)Rated voltagePower consumption (W)Weight(Kg)
26.4cm (10.4″)800×600 pixel(SVGA)
21.3cm (8.4″)800×600 pixel(SVGA)
30.7cm (12.1″)800×600 pixel(SVGA)
1GB(display 128MB)512MB
512MB(display 128MB)256MB
Detection range: side 1-1.5m, front 40-50cmAngle: high/low 100°, left/right 140° (detecting 5-20 micron infrared light)
Left/Right: 80 deg. Up: 60 deg. Down: 80 deg.Left/Right: 80 deg. Up: 80 deg. Down: 60 deg.
-
-
38.1cm (15″)1,024×768 pixel(SVGA)
270.5×212.5×60.0259.0×201.0
240.5×180.0×54.4228.5×158.5
313.0×239.0×56.0301.5×227.5
395.0×294.0×60.0383.5×282.5
42.32.2
30.81.9
42.32.4
42.33.9
700 cd/500 cd/ 550 cd/70,000 hours 60,000 hours
800 cd/
TFT color LCD
DC12/24V(AC 100-240V)DC24V
iXP70-TTA/DCiXP70-TTA/ACiXP50-TTA/DC iXP80-TTA/DC
iXP80-TTA/ACiXP90-TTA/DCiXP90-TTA/AC
USB Host
Human sensor
Indication degree
Memory
SEWOO printer only
XGT Panel eXP Series
106
Main Specification•TFT LCD-applied wide type•LED Backlight adopted for enhanced contrast ratio and low-power•PLC Ladder monitoring function: Only XGK/XBC supports*•Web Server* / Data Server* / Path-Through Function*•Remote Viewer Function*•Screen editor : XP-Builder
Functions that support only the TTA model
Display TypeDisplay SizeResolutionColorDisplay AngleBacklightBacklight CapacityBrightness(LCD)Touch PanelSoundProcessor
FlashOperation RAMBackup RAM
Backup TypeBattery CapacityRTC FunctionEthernet
RS-232CRS-485RS-422/485Multi-languageAnimationRecipeData loggingScript executorCertificationProtectionSize (mm)Panel Cut (mm)PowerPower Consumption (W)Weight (kg)
Memory
USB Port
TFT color LCD
LED mode, Auto On/Off
4-wire system, AnalogueMagnetic buzzer (85dB)
ARM9 Core (32bit RISC), 454MHz128MB(Screen 64MB)
128MB128KB
Date/Time data, Logging/Alarm/Recipe data, non-volatile deviceAround 3 years (Upon operation at 25)
Built-in
1 channel, USB 2.0 host (mouse, keyboard, printer* and USB memory driver is available)
1 channel
1 channel, 422/485 CombinationUp to 12 language simultaneously
GIF format is availableavailableavailableavailable
0.597.10.3
208.0 154.0 44.0192.0 138.0
128.0 102.0 32.0119.0 93.0
23.10.60
CE, UL(cUL), KCIP65
DC24V
17.7cm (7 inch)800 x 480 (WVGA)
10.9cm (4.3 inch)480 x 272 (WQVGA)
30,000 hr or more550 cd/
25.9cm (10.2 inch)
Left/Right: 60 deg. Up: 40 deg. Down: 60 deg.
20,000 hr or more
Left/Right: 55 deg. Up: 35 deg. Down: 55 deg.
500 cd/ 350 cd/
1.0
1 channel, 10/100BASE-TX1 channel, 10/100BASE-TX
-
- 1 channel
1 channel, USB 2.0 slave (for download and upload project file)
-
65,536 colors16.7M colors
eXP60-TTA/DCItem eXP40-TTE/DCeXP20-TTA/DC eXP40-TTA/DC
SEWOO printer only
276.0 218.0 44.2260.0 202.0
65,536 colors8-column Gray Scale 256 colors 65,536 colors
Programmable Logic ControllerXGT Panel XP Series
107
APPLICSTION
Graphic type XP30/XP40/XP50/XP70/XP80/XP90•High and vivid distinction with 65,536 colors•High quality raster and vector symbols•Various BMP JPG GIF graphic file support: BMP, JPG, GIF, WMF, etc•Simple animation effects: animated GIF•10/100BASE-T Ethernet interface•Convenient and easy screen editing•Strengthened data management: Logging, Recipe, and Alarm•Read function of a controller’s state information: Monitoring and
maintenance•Multi-lingual display: up to 8 languages•Offline and concurrent simulation with XG5000•Easy to change the address of the graphic objects:
Tag function with XGT Panel•USB host for peripheral devices: USB Drive, Mouse, keyboard,
printer, etc•Sufficient memory for screen data: 10MB
Green: Normal RUN (Monitoring & drawing data download) Red: Error (Communication error & drawing data error)
3.9
31.9-
AC100~220V
-
395 x 294 x 73383.5 x 282.5
CE, UL, KCIP65 (Front Water Proof Structure)
CCFL(can be replaced), Auto On/Off
60/5075/75
450cd/Fixed
USB Host X 2
CF card (TAPE-1)×1Optional
2ch(1 port for PC communication)1ch, 422/485 optional mode
--
8-wire system, analogue
1ch, 10/100Base-T
1024×76838cm (15”)
20MB
TFT Color LCD
2.20.62 0.62 0.750.75 2.4DC 24V AC100~220V, DC 24V
MIN 19.2 VDC, MAX 28.8 VDC-
16.9 17.49.69.7 18.79.8 9.821.8 31.920.1 25.7
MIN 85 VAC, MAX 264 VAC
181x140x 56.5 181 x 140 x 56.5181 x 140 x 66.5 181 x 140 x 66.5155.0 x 123.5
20/4045/45
70/70 50/6065/65
50/6065/65
45/6565/65
45/7565/65
Up/Down(Degree)Left/Right(Degree)
240 x 174 x 73228.5 x 158.5
1.4
317 x 243 x 73294.5 x 227.5
2.2 2.4
203.5 x 153.5 x 41.5192 x 138
Display ElementScreen SizeResolutionColor
ContrastBrightness
Touch PanelMovement LED
EthernetUSB Interface
CF Card InterfaceAUX InterfaceCertificationProtectionSize(W××H××D)mmPanel Cut (W××H)mmWeight (kg)
MemoryScreen Data
Backup Data
Serial
PermittedVoltage
PowerConsumption(W)
RS-232CRS-422/485
Power
ViewingAngle
Backlight
Rated Voltage
Model Type
14cm (5.7”)320×240 800×480
80/8080/80
LED mode50,000 hours 60,000 hours 30,000 hours 50,000 hours 60,000 hours
Adjustable230cd/ 280cd/600cd/ 480cd/ 430cd/ 400cd/
640×480
4-wire system, analogue Analog resistive
4MB128KB
-USB Host X 1
--
10MB512KB
1ch, 10/100Base-TUSB Host X 2
CF card (TAPE-1)×1Optional
10MB512KB
1ch, 10/100Base-TUSB Host X 2
CF card (TAPE-1)×1Optional
4MB128KB
-USB Host X 1
--
4MB128KB
-
10MB
-
800×60021cm (8.4”)17.7cm (7”) 26cm (10.4”) 31cm (12.1”)
10MB512KB
ACDCACDC
XP30-BTA/DC XP30-TTA/DC XP40-TTE/DC XP40-TTA/DCXP30-TTE/DC XP50-TTA/DC XP70-TTA/ACXP70-TTA/DC
XP80-TTA/ACXP80-TTA/DCXP30-BTE/DC XP90-TTA/AC
ColorMonoMono Blue LCD
USB Host X 1
XGT Panel XP Series
108
Text type XP10 •Screen: 192×64 Graphic STN LCD•System RAM: 1000 words•Flash memory: Program/Parameter back up•Communication: Half-duplex comm.
- Baud rate: 1200~115200 bps- Master/slave setting available- RS-232C/RS-485 2 CH separate to use
•Power reguirements - 24 V input or 5 V direct input by LS PLC•Various function key - ESC, ALM, SET, ENT, F1~F4, Arrow keys•Panel Editor - Easy programming and H/W setting
❶
❷
❸
❹
❺
❻
❼
❽
❾
❿
Key to control PLC device and screenESC keyAlarm historyData input and Screen changePLC data settingEnter keyDC24V input terminalRS-232C port to download a projectBrightness adjustmentRS-422 port
❶
❷
❼
❽ ❿
❸ ❹ ❺
❻
❿
Item SpecificationsXP10BKA/DC XP10BKB/DC
Inputvoltage
5VDC24VDCConsumptioncurrent
DC 4.9 ~ 5.1 (RS-232C port)DC 21.6 ~ 26.4 (DC Input connector)
Less than 200mA
LED back-light (192 x 64 Dots)RS-232C, RS-422/485
256K bytesDefault: English, Can be switched to Korean/Chinese/Russian
115,200bps12 Keys (F1~F4, ESC, ALM, , , , , SET, ENT)
DisplayCommunication interfaceFlash memoryLanguage RTCDownload specificationKeys
None Supports
Programmable Logic ControllerProduct list
109
APPLICSTION
Product list Item Model Specifications
Block type unit(High performance)
Block type unit(Standard)
Block type unit(Economic)
Block type unit(U)
XBC/XEC-DN(P)32UXBC/XEC-DR28UXBC/XEC-DN(P)32UPXBC/XEC-DR28UPXBC/XEC-DN(P)32UAXBC/XEC-DR28UAXBC/XEC-DN(P)32U/DC XBC/XEC-DR28U/DC XBC/XEC-DN(P)32UP/DC XBC/XEC-DR28UP/DC XBC/XEC-DN(P)32UA/DC XBC/XEC-DR28UA/DCXBC/XEC-DR32HXBC/XEC-DR64HXBC/XEC-DN32HXBC/XEC-DN64HXEC-DP32HXEC-DP64HXBC-DR32H/DCXBC-DR64H/DCXBC-DN32H/DCXBC-DN64H/DCXEC-DR32H/D1XEC-DR64H/D1XBC/XEC-DR20SUXBC/XEC-DR30SUXBC/XEC-DR40SUXBC/XEC-DR60SUXBC/XEC-DN20SUXBC/XEC-DN30SUXBC/XEC-DN40SUXBC/XEC-DN60SUXBC/XEC-DP20SUXBC/XEC-DP30SUXBC/XEC-DP40SUXBC/XEC-DP60SUXBC/XEC-DR10EXBC/XEC-DR14EXBC/XEC-DR20EXBC/XEC-DR30EXBC/XEC-DN10EXBC/XEC-DN14EXBC/XEC-DN20EXBC/XEC-DN30EXBC /XEC-DP10EXBC/XEC-DP14EXBC/XEC-DP20EXBC/ XEC-DP30E
AC 110-220V, 16points DC24V input, 16points transistor sink(source) type outputAC 110-220V, 16points DC24V input, 12points relay outputAC 110-220V, 16points DC24V input, 16points transistor sink(source) type output, 4 axes built-in positioningAC 110-220V, 16points DC24V input, 12points relay output, 4 axes built-in positioningAC 110-220V, DC24V input, 16points transistor sink(source) type output, 8 channel built-in analogAC 110-220V, DC24V input, 12points relay output, 8 channel built-in analogDC 24V, 16points DC24V input, 16points transistor sink(source) type outputDC 24V, 16points DC24V input, 12points relay outputDC 24V, 16points DC24V input, 16points transistor sink(source) type output, 4 axes built-in positioningDC 24V, 16points DC24V input, 12points relay output, 4 axes built-in positioningDC 24V, DC24V input, 16points transistor sink(source) type output, 8 channel built-in analogDC 24V, DC24V input, 12points relay output, 8 channel built-in analogAC 100 - 240V, DC24 input 16 points, relay output 16 pointsAC 100 - 240V, DC24 input 32 points, relay output 32 pointsAC 100 - 240V, DC24 input 16 points, transistor output 16 points (Sink)AC 100 - 240V, DC24 input 32 points, transistor output 32 points (Sink)AC 100 - 240V, DC24 input 16 points, transistor output 16 points (Source)AC 100 - 240V, DC24 input 32 points, transistor output 32 points (Source)DC 24V, DC24 input 16 points, relay output 16 pointsDC 24V, DC24 input 32 points, relay output 32 pointsDC 24V, DC24 input 16 points, transistor output 16 points (Sink)DC 24V, DC24 input 32 points, transistor output 32 points (Sink)DC 12/24V, DC12/24 input 16 points, relay output 16 pointsDC 12/24V, DC12/24 input 32 points, relay output 32 pointsAC 100 - 240, DC24V input 12 points, relay output 8 pointsAC 100 - 240, DC24V input 18 points, relay output 12 pointsAC 100 - 240, DC24V input 24 points, relay output 16 pointsAC 100 - 240, DC24V input 36 points, relay output 24 pointsAC 100 - 240, DC24V input 12 points, transistor output 8 points (Sink)AC 100 - 240, DC24V input 18 points, transistor output 12 points (Sink)AC 100 - 240, DC24V input 24 points, transistor output 16 points (Sink)AC 100 - 240, DC24V input 36 points, transistor output 24 points (Sink)AC 100 - 240, DC24V input 12 points, transistor output 8 points (Source)AC 100 - 240, DC24V input 18 points, transistor output 12 points (Source)AC 100 - 240, DC24V input 24 points, transistor output 16 points (Source)AC 100 - 240, DC24V input 36 points, transistor output 24 points (Source)AC 100 - 240V, 6 points DC24V input, 4 point Relay ouputAC 100 - 240V, 8 points DC24V input, 6 point Relay ouputAC 100 - 240V, 12 points DC24V input, 8 point Relay ouputAC 100 - 240V, 18 points DC24V input, 12 point Relay ouputAC 100 - 240V, 6 points DC24V input, 4 point transistor output (Sink)AC 100 - 240V, 8 points DC24V input, 6 point transistor output (Sink)AC 100 - 240V, 12 points DC24V input, 8 point transistor output (Sink)AC 100 - 240V, 18 points DC24V input, 12 point transistor output (Sink)AC 100 - 240V, 6 points DC24V input, 4 point transistor output (Source)AC 100 - 240V, 8 points DC24V input, 6 point transistor output (Source)AC 100 - 240V, 12 points DC24V input, 8 point transistor output (Source)AC 100 - 240V, 18 points DC24V input, 12 point transistor output (Source)
Product list
110
Item Model SpecificationsXBM-DN32HXBM-DN32HXBM-DR16SXBM-DN16SXBM-DN32SXBE-DC08AXBE-DC16AXBE-DC32AXBE-RY08AXBE-RY16AXBE-TN08AXBE-TN16AXBE-TN32AXBE-TP08AXBE-TP16AXBE-TP32AXBE-DR16AXBE-DN32AXBF-AD04AXBF-AD04CXBF-AH04AXBF-DV04AXBF-DV04CXBF-DC04AXBF-DC04CXBF-RD04AXBF-RD01AXBF-TC04SXBF-TC04TT XBF-TC04RTXBF-LD02SXBF-PD02AXBF-PN08BXBF-PN04BXBF-AD08AXBF-HO02AXBF-HD02AXBL-C41AXBL-C21AXBL-EMTAXBL-EIMTXBL-EIPTXBL-EIMFXBL-EIMHXBL-PMECXBL-PSEAXBL-DSEAXBL-PSEAXBL-RMEAXBL-CMEAXBL-CSEAPMC-310SUSB-301A
DC24V, 16 pts DC24V input, 16 pts TR output, 2 axes built-in positioningDC24V, 16 pts DC24V input, 16 pts TR output, 6 axes built-in positioningDC 24V, 8-point DC24V input, 8-point relay outputDC 24V, 8-point DC24V input, 8-point TR outputDC 24V, 16-point DC24V input, 16-point TR output8-point DC 24V input16-point DC 24V input32-point DC 24V input8-point relay output16-point relay output8-point Transistor (sink) output16-point Transistor (sink) output32-point Transistor (sink) output8-point Transistor (source) output16-point Transistor (source) output32-point Transistor (source) output8-point DC 24V input, 8-point relay output16-point DC24V input, 16point TR output4-channel analog input (current /voltage)4-channel analog input (current / voltage, resolution : 1/16000)2-channel analog input (current /voltage) / 2-channel analog output (current / voltage)4-channel analog output (voltage)4-channel analog input (voltage, resolution : 1/16000)4-channel analog output (current)4-channel analog input (current, resolution : 1/16000)4-channel RTD input1-channel RTD input4-channel Thermocouple inputTemperature controller, ThermocoupleTemperature controller, RTDLoad Cell input moduleLine drive 2 axisEtherCAT Positioning module, 8axes (XBC/XEC “U” only)EtherCAT Positioning module, 4axes (XBC/XEC “U” only)8-channel analog input (Current /voltage)2-channel High-speed counter input (Open collector)2-channel High-speed counter input (Line drive)Cnet (RS-422/485), 1chCnet (RS- 232C), 1chFast Ethernet (100Mbps), 1chRAPIEnet, 2 chEthernet / IP, 2 chRAPIEnet I /F, Max. 2km (Fiber 2ch.), 100MbpsRAPIEnet I / F (Twisted pair 1ch, Fiber 2 ch.), 100MbpsProfibus-DP, Master, RS-485Profibus-DP, Slave, RS-485DeviceNet, SlaveProfibus-DP, Slave, RS-485Rnet, MasterCANopen (10, 20, 50, 100, 125, 250, 500, 800, 1000Kbps, Num of PDO : 32)CANopen (10, 20, 50, 100, 125, 250, 500, 800, 1000Kbps, Num of PDO : 64)Connection cable (PC to PLC), 9pin(PC)-6pin(PLC)Connection cable (PC to PLC), USB
Communication module
Loader cable
Special module
ExpansionI/O module
Modular typeunit
Product list
Programmable Logic Controller
111
APPLICSTION
Download cable diagram
Terminal board Connection cable XBM-DN16S
XBM-DN32S XBE-DC32A XBE-TN32A XBE-TP32A Cable length
XTB-40H(TG7-1H40S)(Terminalboard)
TG7-1H40CA(Terminalboard, Common)
R32C-NS5A-40P(Relayboard: sink)
R32C-PS5A-40P(Relayboard:source)
0.5m1.0m0.5m1.0m1.5m2.0m3.0m0.5m1.0m1.5m2.0m3.0m0.5m1.5m2.0m
R40H/20HH-05S-XBM3R40H/20HH-10S-XBM3
C40HH-05SB-XBIC40HH-10SB-XBIC40HH-15SB-XBIC40HH-20SB-XBIC40HH-30SB-XBI
C40HH-05SB-XBIC40HH-10SB-XBIC40HH-15SB-XBIC40HH-20SB-XBIC40HH-30SB-XBIC40HH-05PH-XBPC40HH-15PH-XBPC40HH-20PH-XBP
Product list Item Model Specifications
Option modules
Memory module XBO-M2MBXBO-AD02AXBO-DA02AXBO-AH02AXBO-TC02AXBO-RTCAXBO-DC04AXBO-TN04AXBO-RD01A
MemoryVoltage/Current, Input 2 chVoltage/Current, Output 2 chVoltage/Current, Input 1ch/Voltage/Current, Output 1chTC (Thermo couple), Input 2 chRTC (Real time clock), BatteryDC 24V, Input 4 pointsTR (Sink), Output 4 pointsRTD (Resistance temperature detector), Input 1ch
Dimension
112
XBC/XEC-SU
Block type unitXBC/XEC-U (Standard)
XBC/XEC-H
Programmable Logic Controller
113
XBM-S
Modular type unit
XBC/XEC-E
APPLICSTION
Dimension
114
Modular type unit XBM-H
!
-@8)6;176
+766-+<7:
Programmable Logic ControllerMEMO
115
APPLICSTION
Worldwide Network
Head OfficeLS Tower, 127, LS-ro, Dongan-gu, Anyang-si, Gyeonggi-Do, 431-848, KoreaTel : 82-2-2034-4870 Fax : 82-2-2034-3660-7021Cheongju Factory1 Songjeong-dong, Cheongju-si, Chungbuk-do, 361-720, KoreaTel : 82-43-261-6114 Fax : 82-43-261-6602Cheonan Factory56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnam-do, 31226, Republic of KoreaTel : 82-41-550-8114 Fax : 82-41-566-8408Busan Factory 1-19 Block Hwajeon-dong, Gangseo-gu,Busan, 618-280, KoreaTel : 82-51-795-6114 Fax : 82-51-795-6169
Domestic Factories
R&D Campus in Anyang40, LS-ro 116beon-gil, Dongan-gu, Anyang-si, Gyeonggi-do, 14118, KoreaTel: 82-31-8090-7011Electric Technology R&D Center in Cheongju95, Baekbong-ro, Heungdeok-gu, Cheongju-si, Chungcheongbuk-do, 28439, KoreaTel: 82-43-261-6114Automation R&D Center in Cheonan56, Samseong 4-gil, Mokcheon-eup, Dongnam-gu, Cheonan-si, Chungcheongnam-do, 31226, KoreaTel: 82-41-550-8272Power Testing & Technology Institute in Cheongju95, Baekbong-ro, Heungdeok-gu, Cheongju-si, Chungcheongbuk-do, 28439, KoreaTel: 82-43-261-6114
R&D Center
Wuxi Factory, CHINA 102-A. National High & New Tech Industrial Development Area.Wuxi. Jiangsu. 214028. P.R. ChinaTel : 86-510-8534-6666 Fax : 86-510-8534-4078Dalian Factory, CHINA No. 15. Liaohexi 3-Road. Economic and Technical Development zone. Dalian 116600. ChinaTel : 86-411-273-7777 Fax : 86-411-8730-7560Hanoi Factory, VIETNAMRoom 1311, 13th Floor, M3-M4 Building91 Nguyen Chi Thanh street, Hanoi, Vietnam.Tel : 84-4-6275-8055 Fax : 84-4-6275-8056
Overseas Factories
Dalian, Wuxi (China), Hanoi (Vietnam), Dubai (U.A.E.), Amsterdam (Netherlands), Tokyo (Japan), Chicago (U.S.A.)Shanghai, Beijing, Guangzhou, Qingdao, Chengdu, ShenYang, Jinan (China), Tokyo (Japan), Rep. (Vietnam), Moscow (Russia), Jakarta (Indonesia)
Barcelona (Spain), Rosbach (Germany), Praha (Czech), Glozan (Serbia),Bucharest (Romania), Dyachenko (Ukraine), Stanbul (Turkey), Chonburi Province, Bangkok, Bangkok (Thailand), Karachi (Pakistan),Banten (Indonesia), Calcutta (India), Selangor, Pinang (Malaysia), Henderson (Singapore), Ha Noi, Hochiminh (Viet Nam), Amarillo, NorcrossFranklin Park, Tualatin, Southgate (USA), Sao Paulo, Curitina (Brazil), Nuevo Leon (Mexico)
77 Countries
Overseas SubsidiariesLSIS(Dalian) Co., Ltd._Dalian, China No. 15, Liaohexi 3-Road, Economic and Technical Development Zone, Dalian 116600, ChinaTel: 86-411-8730-7510 Fax: 86-411-8730-7560 E-Mail: [email protected]
LSIS(Wuxi) Co., Ltd._Wuxi, China No. 1, Lexing Road, Wuxi National High &New Tech Industrial Development Area, Wuxi214028, Jiangsu, P.T.ChinaTel: 86-510-8534-6666-8005 Fax: 86-510-8534-4078 E-Mail: [email protected]
LS-VINA Industrial Systems Co., Ltd._Hanoi, Vietnam Nguyen Khe, Dong Anh, Hanoi, VietnamTel: 84-4-6275-8055 Fax: 84-4-3882-0220 E-Mail: [email protected]
LSIS(ME) FZE_Dubai, U.A.E. LOB 19-205, JAFZA View Tower, Jebel Ali Free Zone, Dubai, United Arab EmiratesTel: 971-4-886-5360 Fax: 971-4-886-5361 E-Mail: [email protected]
LSIS Europe B.V._Netherlands 1st. Floor, Tupolevlaan 48, 1119NZ,Schiphol-Rijk, The NetherlandsTel: 31-20-654-1420 Fax: 31-20-654-1429 E-Mail: [email protected]
LSIS Japan Co., Ltd._Tokyo, JapanTokyo Club Building 13F, 2-6, Kasumigaseki 3-chome, Chiyoda-ku, Tokyo, 100-0013Tel: 81-3-6268-8241 Fax: 81-3-6268-8240 E-Mail: [email protected]
LSIS USA Inc._ Chicago, U.S.A. 980 Woodlands Pkwy, Vernon Hills, IL 60061 USATel: 1-800-891-2941 or 1-224-352-2265 Fax: 1-847-383-6543 E-Mail: [email protected]
LSIS Beijing Office, China Room 2306, Building B Landgent Center, No.24 Middle Road, East 3rd Ring Road, Chaoyang District, Beijing, P.R. ChinaTel: 86-10-5761-3127 Fax: 86-10-5761-3128 E-Mail: [email protected]
LSIS Shanghai Office, China 32nd Floor, International Corporate City, No.3000 NorthZhongshan Road, Putuo District, Shanghai, China, 200063Tel: 86-21-5237-9977(609) Fax: 86-21-5237-7189 E-Mail: [email protected]
LSIS Guangzhou Office, ChinaRoom 1818-1820, Xinyuan Building,NO.898 Tianhe North Road, Tianhe District, Guangzhou, P.R ChinaTel: 86-20-8326-6784 Fax: 86-20-8326-6287 E-Mail: [email protected]
LSIS Qingdao Office, ChinaRoom 2001, Galaxy Building, 29 ShanDong Road, ShiNan District, QingDao, ShanDong, P.R. ChinaTel: 86-532-8501-6058 Fax: 86-532-8501-6057 E-Mail: [email protected]
LSIS Chengdu Office, ChinaRoom1710, 17/F Huamin Empire Plaza, NO.1 Fuxin Road, Chengdu, P.R. ChinaTel: 86-28-8670-3200 Fax: 86-28-8670-3203 E-Mail: [email protected]
LSIS ShenYang Office, ChinaRoom 803, Hongyuan Building, 52 South Nanjing Road,Heping District, Shenyang, P.R. ChinaTel 86-24-2321-9050 Fax 86-24-8386-7210 E-Mail: [email protected]:LSIS Jinan Office, ChinaRoom 317, Chuangzhan Center, No. 201, Shanda Road, Lixia District, Jinan, Shandong, P. R. ChinaTel: 86-531-8699-7826 Fax: 86-531-8697-7628 E-Mail: [email protected]
LSIS Co., Ltd. Tokyo Office, JapanTokyo Club Building 13F, 2-6, Kasumigaseki 3-chome, Chiyoda-ku, Tokyo, 100-0013Tel: 81-3-6268-8241 Fax: 81-3-6268-8240
LSIS Co., Ltd. Rep. Office, VietnamGema Dept Tower 18F, 6 Le Thanh Ton, District 1, HCM, VietnamTel: 84-8-3823-7890 E-Mail: [email protected]
LSIS Moscow Office, Russia123610, Moscow, Street. Barclay 6, Building 5, Office no.322, RussiaTel: 7-499-682-6130 E-Mail: [email protected]
LSIS Jakarta Office, IndonesiaAPL TOWER lantai 10 unit 3, Jl. Letjen S. Parman kav. 28, 11470, Jakarta Barat, IndonesiaTel: 62-21-293-7614 E-Mail: [email protected]
Overseas Branches
2016. 12 2006. 06 LSIS Co., Ltd. All Rights Reserved. / (27) 2016. 12 Human Power
VECTOR MOTOR CONTROL IBÉRICA (VMC)C/Mar del Carib, 10 - P.I. La Torre del Rector08130 - Santa Perpètua de Mogoda BARCELONA (SPAIN)Tel. (+34) 935 748 206 - Fax (+34) 935 748 248e-mail: [email protected] - www.vmc.es