This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 1
September 1997
Contents Page
1 DIRECTIONAL EARTH-FAULT OVER-
CURRENT PROTECTION FOR SOLIDLY
EARTHED NETWORKS
2
11 Application
2
12 Theory of operation
4
13 Setting
6
14 Testing
8
15 Technical data
11
16 Appendix
12
161 Terminal diagrams 12
162 Signal list 13163 Setting table 14
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 214
1MDX80015-EN
Page 2
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
In case of single-phase earth-faults the primary fault resistance will vary
with the network conditions and location of the fault In many cases thefault resistance is much higher than the resistance that can be covered by
an impedance measuring distance relay
Earth-faults with high fault resistances can be detected by measuring the
residual current (3I
0
) Directional earth-fault protection is obtained by
measuring the residual current and the angle between this current and the
zero-sequence voltage (3U
0
)
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that is
equal to the angle of the zero-sequence source impedance In solidly
earthed networks this angle will be in the range of 40
deg
to nearly 90
deg
where the high value refers to stations with direct earthed transformers
with delta winding To obtain maximum sensitivity under all conditions
the forward measuring element should have a characteristic angle of 65
deg
As a general rule selectivity is more easily obtained by using the direc-
tional instead of the non-directional earth-fault overcurrent protection
High resistive earth-faults can also be detected by the directional protec-
tion the limiting condition being that sufficient polarising voltage must be
available
Measurement of the distance to the fault can not be made using the zero-sequence components of the current and voltage since the zero-sequence
voltage is a product of the zero-sequence components of current and
source impedance Hence the necessary selectivity must be obtained by
current grading or time delay
The best selectivity is generally obtained by using inverse time delay all
relays having the same type of inverse characteristic An earth-fault in a
line will be selectively tripped if the difference between the fault current
in the line and the residual current (3I
0
) in the other lines gives a time dif-
ference of 03-04 seconds A logarithmic characteristic is generally the
most suitable for this purpose since the time difference is constant for a
given ratio between the currents see Fig 2
1 DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION FOR SOLIDLYEARTHED NETWORKS
11 Application
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 3
September 1997
The directional earth-fault overcurrent protection module for relay
REL 5xx has available independent time delay plus four inverse time
characteristics viz
bull Normal inverse (NI) according to IEC 255-3bull Very inverse (VI) according to IEC 255-3
bull Extremely inverse (EI) according to IEC 255-3
bull Logarithmic inverse (IDG) according to the formula
t = 58 - 135 sdot l
n
I I
a (s) where I
a
is
the set characteristic value (3I
0
gt)
In some cases the selectivity can be improved by adding a settable mini-
mum operating current (IMin) and a minimum operating time (tMin) to
the inverse characteristic These functions are included in the protection
The residual inrush current can cause unwanted tripping of the earth-fault
overcurrent relay when energizing a directly earthed power transformer
The earth-fault overcurrent protection is therefore provided with second
harmonic restraint which blocks the operation if the residual current (3I
0
)
contains 20 per cent or more of the second harmonic component
A serial fault can be caused by broken phase conductor(s) with no contact
to earth or pole discrepancy in a circuit-breaker or a disconnector The
most common type of serial fault is pole discrepancy at breaker manoeu-
vring To minimise the operating time the earth-fault overcurrent protec-
tion module is provided with a switch-onto-fault logic which can be
activated at breaker closure which temporarily reduces the tripping timeto 300 ms
Serial faults can be correctly detected if the voltage transformers feeding
the directional earth-fault protection are situated on the bus side of the
breaker
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 414
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 514
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 5
September 1997
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that isequal to the angle of the zero sequence source impedance The forward
measuring element operates when
where
ϕ
is the angle between 3I
0
and -3U
0 (positive if 3I
0
lags -3U
0
)
3I0D is the set operate value
The change in operate value is small when the phase angle deviates moder-ately from 65
deg
A deviation of 20
deg
will increase the operate value by only
65
The polarising voltage normally obtained from the broken delta windings
of the VTs can have a high content of harmonics relative the fundamentalfrequency when the output voltage is low particularly when capacitive VTsare used To secure a correct measurement the directional function must
have an effective bandpass filtering of the voltage In the module the filter-
ing secures a correct function for fundamental frequency polarising volt-
ages down to 1 of rated voltage
In case of an external fault the capacitive current generated on the line will
decrease the current to the earth-fault relay situated at the line end towardsthe fault The reverse direction comparator should therefore have an
increased sensitivity to secure reliable blocking in case of external faults
when a directional comparison or a blocking communication scheme is
used The operate current of the reverse direction measuring element in themodule is as a fixed ratio set at 06 sdot 3I0D
The independent time delay function is activated by setting CurveType= Def
The timer t1 starts when the current 3I
0
to the relay is equal to or higher
than the set operating value for IMin and the content of the second har-
monic in 3I
0
is less than 20
The inverse time calculation starts when 3I
0
is equal to or higher than the
set operating value for IMin and the content of the second harmonic in 3I
0
is less than 20 The inverse time delay is determined by the selection of
the characteristic (NI VI etc) under setting ldquoCurveType =rdquo and the set-ting of the characteristic current 3I
0
gt The timer t1 starts when both the
inverse time characteristic and the timer tMin operate Timer t1 is nor-
mally set at zero It can be used to add a constant time to the inverse time
delay
The effect of the settings IMin and tMin on the inverse characteristic is
shown in Fig 2
3I0 65deg ϕndash( ) 3I0Dgecossdot
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 614
1MDX80015-EN
Page 6
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 2 Normal inverse and logarithmic inverse time characteristics
To detect high resistive earth-faults a low operating current is required
On the other hand a low setting will increase the risk for unwanted opera-
tion due to unbalance in the network and the current transformer circuits
The minimum operating current (IMin) of the earth-fault overcurrent pro-
tection must be set higher than the maximum false earth-fault current
The unbalance in the network that causes false earth-fault currents is
caused mainly by untransposed or not fully transposed parallel lines with
strong zero-sequence mutual coupling This false earth-fault current is
directly proportional to the load current
In a well transposed system the false earth-fault current is normally lower
than 5 of the line current except for extremely short parallel lines (less
than 5 kilometres) where a higher false earth-fault current may be found
In case of extremely short or not fully transposed parallel lines the false
earth-fault current must be measured or calculated when maximum sensi-
tivity is desired Generally 80 A is recommended as a minimum primary
operating value for the earth-fault overcurrent protection
The choice of time delay characteristic independent (definite time) nor-
mal inverse very inverse extremely inverse or logarithmic inverse
depends on the network
(X80056-22)
x 3Iogt
Logarithmic Inverse
1
mint
1
2
52 3
3
4
5
t [s] I min
7 10 20 30 50
Normal Inverse(K=04)
13 Setting
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 214
1MDX80015-EN
Page 2
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
In case of single-phase earth-faults the primary fault resistance will vary
with the network conditions and location of the fault In many cases thefault resistance is much higher than the resistance that can be covered by
an impedance measuring distance relay
Earth-faults with high fault resistances can be detected by measuring the
residual current (3I
0
) Directional earth-fault protection is obtained by
measuring the residual current and the angle between this current and the
zero-sequence voltage (3U
0
)
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that is
equal to the angle of the zero-sequence source impedance In solidly
earthed networks this angle will be in the range of 40
deg
to nearly 90
deg
where the high value refers to stations with direct earthed transformers
with delta winding To obtain maximum sensitivity under all conditions
the forward measuring element should have a characteristic angle of 65
deg
As a general rule selectivity is more easily obtained by using the direc-
tional instead of the non-directional earth-fault overcurrent protection
High resistive earth-faults can also be detected by the directional protec-
tion the limiting condition being that sufficient polarising voltage must be
available
Measurement of the distance to the fault can not be made using the zero-sequence components of the current and voltage since the zero-sequence
voltage is a product of the zero-sequence components of current and
source impedance Hence the necessary selectivity must be obtained by
current grading or time delay
The best selectivity is generally obtained by using inverse time delay all
relays having the same type of inverse characteristic An earth-fault in a
line will be selectively tripped if the difference between the fault current
in the line and the residual current (3I
0
) in the other lines gives a time dif-
ference of 03-04 seconds A logarithmic characteristic is generally the
most suitable for this purpose since the time difference is constant for a
given ratio between the currents see Fig 2
1 DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION FOR SOLIDLYEARTHED NETWORKS
11 Application
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 3
September 1997
The directional earth-fault overcurrent protection module for relay
REL 5xx has available independent time delay plus four inverse time
characteristics viz
bull Normal inverse (NI) according to IEC 255-3bull Very inverse (VI) according to IEC 255-3
bull Extremely inverse (EI) according to IEC 255-3
bull Logarithmic inverse (IDG) according to the formula
t = 58 - 135 sdot l
n
I I
a (s) where I
a
is
the set characteristic value (3I
0
gt)
In some cases the selectivity can be improved by adding a settable mini-
mum operating current (IMin) and a minimum operating time (tMin) to
the inverse characteristic These functions are included in the protection
The residual inrush current can cause unwanted tripping of the earth-fault
overcurrent relay when energizing a directly earthed power transformer
The earth-fault overcurrent protection is therefore provided with second
harmonic restraint which blocks the operation if the residual current (3I
0
)
contains 20 per cent or more of the second harmonic component
A serial fault can be caused by broken phase conductor(s) with no contact
to earth or pole discrepancy in a circuit-breaker or a disconnector The
most common type of serial fault is pole discrepancy at breaker manoeu-
vring To minimise the operating time the earth-fault overcurrent protec-
tion module is provided with a switch-onto-fault logic which can be
activated at breaker closure which temporarily reduces the tripping timeto 300 ms
Serial faults can be correctly detected if the voltage transformers feeding
the directional earth-fault protection are situated on the bus side of the
breaker
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 414
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 514
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 5
September 1997
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that isequal to the angle of the zero sequence source impedance The forward
measuring element operates when
where
ϕ
is the angle between 3I
0
and -3U
0 (positive if 3I
0
lags -3U
0
)
3I0D is the set operate value
The change in operate value is small when the phase angle deviates moder-ately from 65
deg
A deviation of 20
deg
will increase the operate value by only
65
The polarising voltage normally obtained from the broken delta windings
of the VTs can have a high content of harmonics relative the fundamentalfrequency when the output voltage is low particularly when capacitive VTsare used To secure a correct measurement the directional function must
have an effective bandpass filtering of the voltage In the module the filter-
ing secures a correct function for fundamental frequency polarising volt-
ages down to 1 of rated voltage
In case of an external fault the capacitive current generated on the line will
decrease the current to the earth-fault relay situated at the line end towardsthe fault The reverse direction comparator should therefore have an
increased sensitivity to secure reliable blocking in case of external faults
when a directional comparison or a blocking communication scheme is
used The operate current of the reverse direction measuring element in themodule is as a fixed ratio set at 06 sdot 3I0D
The independent time delay function is activated by setting CurveType= Def
The timer t1 starts when the current 3I
0
to the relay is equal to or higher
than the set operating value for IMin and the content of the second har-
monic in 3I
0
is less than 20
The inverse time calculation starts when 3I
0
is equal to or higher than the
set operating value for IMin and the content of the second harmonic in 3I
0
is less than 20 The inverse time delay is determined by the selection of
the characteristic (NI VI etc) under setting ldquoCurveType =rdquo and the set-ting of the characteristic current 3I
0
gt The timer t1 starts when both the
inverse time characteristic and the timer tMin operate Timer t1 is nor-
mally set at zero It can be used to add a constant time to the inverse time
delay
The effect of the settings IMin and tMin on the inverse characteristic is
shown in Fig 2
3I0 65deg ϕndash( ) 3I0Dgecossdot
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 614
1MDX80015-EN
Page 6
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 2 Normal inverse and logarithmic inverse time characteristics
To detect high resistive earth-faults a low operating current is required
On the other hand a low setting will increase the risk for unwanted opera-
tion due to unbalance in the network and the current transformer circuits
The minimum operating current (IMin) of the earth-fault overcurrent pro-
tection must be set higher than the maximum false earth-fault current
The unbalance in the network that causes false earth-fault currents is
caused mainly by untransposed or not fully transposed parallel lines with
strong zero-sequence mutual coupling This false earth-fault current is
directly proportional to the load current
In a well transposed system the false earth-fault current is normally lower
than 5 of the line current except for extremely short parallel lines (less
than 5 kilometres) where a higher false earth-fault current may be found
In case of extremely short or not fully transposed parallel lines the false
earth-fault current must be measured or calculated when maximum sensi-
tivity is desired Generally 80 A is recommended as a minimum primary
operating value for the earth-fault overcurrent protection
The choice of time delay characteristic independent (definite time) nor-
mal inverse very inverse extremely inverse or logarithmic inverse
depends on the network
(X80056-22)
x 3Iogt
Logarithmic Inverse
1
mint
1
2
52 3
3
4
5
t [s] I min
7 10 20 30 50
Normal Inverse(K=04)
13 Setting
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 3
September 1997
The directional earth-fault overcurrent protection module for relay
REL 5xx has available independent time delay plus four inverse time
characteristics viz
bull Normal inverse (NI) according to IEC 255-3bull Very inverse (VI) according to IEC 255-3
bull Extremely inverse (EI) according to IEC 255-3
bull Logarithmic inverse (IDG) according to the formula
t = 58 - 135 sdot l
n
I I
a (s) where I
a
is
the set characteristic value (3I
0
gt)
In some cases the selectivity can be improved by adding a settable mini-
mum operating current (IMin) and a minimum operating time (tMin) to
the inverse characteristic These functions are included in the protection
The residual inrush current can cause unwanted tripping of the earth-fault
overcurrent relay when energizing a directly earthed power transformer
The earth-fault overcurrent protection is therefore provided with second
harmonic restraint which blocks the operation if the residual current (3I
0
)
contains 20 per cent or more of the second harmonic component
A serial fault can be caused by broken phase conductor(s) with no contact
to earth or pole discrepancy in a circuit-breaker or a disconnector The
most common type of serial fault is pole discrepancy at breaker manoeu-
vring To minimise the operating time the earth-fault overcurrent protec-
tion module is provided with a switch-onto-fault logic which can be
activated at breaker closure which temporarily reduces the tripping timeto 300 ms
Serial faults can be correctly detected if the voltage transformers feeding
the directional earth-fault protection are situated on the bus side of the
breaker
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 414
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 514
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 5
September 1997
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that isequal to the angle of the zero sequence source impedance The forward
measuring element operates when
where
ϕ
is the angle between 3I
0
and -3U
0 (positive if 3I
0
lags -3U
0
)
3I0D is the set operate value
The change in operate value is small when the phase angle deviates moder-ately from 65
deg
A deviation of 20
deg
will increase the operate value by only
65
The polarising voltage normally obtained from the broken delta windings
of the VTs can have a high content of harmonics relative the fundamentalfrequency when the output voltage is low particularly when capacitive VTsare used To secure a correct measurement the directional function must
have an effective bandpass filtering of the voltage In the module the filter-
ing secures a correct function for fundamental frequency polarising volt-
ages down to 1 of rated voltage
In case of an external fault the capacitive current generated on the line will
decrease the current to the earth-fault relay situated at the line end towardsthe fault The reverse direction comparator should therefore have an
increased sensitivity to secure reliable blocking in case of external faults
when a directional comparison or a blocking communication scheme is
used The operate current of the reverse direction measuring element in themodule is as a fixed ratio set at 06 sdot 3I0D
The independent time delay function is activated by setting CurveType= Def
The timer t1 starts when the current 3I
0
to the relay is equal to or higher
than the set operating value for IMin and the content of the second har-
monic in 3I
0
is less than 20
The inverse time calculation starts when 3I
0
is equal to or higher than the
set operating value for IMin and the content of the second harmonic in 3I
0
is less than 20 The inverse time delay is determined by the selection of
the characteristic (NI VI etc) under setting ldquoCurveType =rdquo and the set-ting of the characteristic current 3I
0
gt The timer t1 starts when both the
inverse time characteristic and the timer tMin operate Timer t1 is nor-
mally set at zero It can be used to add a constant time to the inverse time
delay
The effect of the settings IMin and tMin on the inverse characteristic is
shown in Fig 2
3I0 65deg ϕndash( ) 3I0Dgecossdot
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 614
1MDX80015-EN
Page 6
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 2 Normal inverse and logarithmic inverse time characteristics
To detect high resistive earth-faults a low operating current is required
On the other hand a low setting will increase the risk for unwanted opera-
tion due to unbalance in the network and the current transformer circuits
The minimum operating current (IMin) of the earth-fault overcurrent pro-
tection must be set higher than the maximum false earth-fault current
The unbalance in the network that causes false earth-fault currents is
caused mainly by untransposed or not fully transposed parallel lines with
strong zero-sequence mutual coupling This false earth-fault current is
directly proportional to the load current
In a well transposed system the false earth-fault current is normally lower
than 5 of the line current except for extremely short parallel lines (less
than 5 kilometres) where a higher false earth-fault current may be found
In case of extremely short or not fully transposed parallel lines the false
earth-fault current must be measured or calculated when maximum sensi-
tivity is desired Generally 80 A is recommended as a minimum primary
operating value for the earth-fault overcurrent protection
The choice of time delay characteristic independent (definite time) nor-
mal inverse very inverse extremely inverse or logarithmic inverse
depends on the network
(X80056-22)
x 3Iogt
Logarithmic Inverse
1
mint
1
2
52 3
3
4
5
t [s] I min
7 10 20 30 50
Normal Inverse(K=04)
13 Setting
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 414
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 514
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 5
September 1997
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that isequal to the angle of the zero sequence source impedance The forward
measuring element operates when
where
ϕ
is the angle between 3I
0
and -3U
0 (positive if 3I
0
lags -3U
0
)
3I0D is the set operate value
The change in operate value is small when the phase angle deviates moder-ately from 65
deg
A deviation of 20
deg
will increase the operate value by only
65
The polarising voltage normally obtained from the broken delta windings
of the VTs can have a high content of harmonics relative the fundamentalfrequency when the output voltage is low particularly when capacitive VTsare used To secure a correct measurement the directional function must
have an effective bandpass filtering of the voltage In the module the filter-
ing secures a correct function for fundamental frequency polarising volt-
ages down to 1 of rated voltage
In case of an external fault the capacitive current generated on the line will
decrease the current to the earth-fault relay situated at the line end towardsthe fault The reverse direction comparator should therefore have an
increased sensitivity to secure reliable blocking in case of external faults
when a directional comparison or a blocking communication scheme is
used The operate current of the reverse direction measuring element in themodule is as a fixed ratio set at 06 sdot 3I0D
The independent time delay function is activated by setting CurveType= Def
The timer t1 starts when the current 3I
0
to the relay is equal to or higher
than the set operating value for IMin and the content of the second har-
monic in 3I
0
is less than 20
The inverse time calculation starts when 3I
0
is equal to or higher than the
set operating value for IMin and the content of the second harmonic in 3I
0
is less than 20 The inverse time delay is determined by the selection of
the characteristic (NI VI etc) under setting ldquoCurveType =rdquo and the set-ting of the characteristic current 3I
0
gt The timer t1 starts when both the
inverse time characteristic and the timer tMin operate Timer t1 is nor-
mally set at zero It can be used to add a constant time to the inverse time
delay
The effect of the settings IMin and tMin on the inverse characteristic is
shown in Fig 2
3I0 65deg ϕndash( ) 3I0Dgecossdot
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 614
1MDX80015-EN
Page 6
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 2 Normal inverse and logarithmic inverse time characteristics
To detect high resistive earth-faults a low operating current is required
On the other hand a low setting will increase the risk for unwanted opera-
tion due to unbalance in the network and the current transformer circuits
The minimum operating current (IMin) of the earth-fault overcurrent pro-
tection must be set higher than the maximum false earth-fault current
The unbalance in the network that causes false earth-fault currents is
caused mainly by untransposed or not fully transposed parallel lines with
strong zero-sequence mutual coupling This false earth-fault current is
directly proportional to the load current
In a well transposed system the false earth-fault current is normally lower
than 5 of the line current except for extremely short parallel lines (less
than 5 kilometres) where a higher false earth-fault current may be found
In case of extremely short or not fully transposed parallel lines the false
earth-fault current must be measured or calculated when maximum sensi-
tivity is desired Generally 80 A is recommended as a minimum primary
operating value for the earth-fault overcurrent protection
The choice of time delay characteristic independent (definite time) nor-
mal inverse very inverse extremely inverse or logarithmic inverse
depends on the network
(X80056-22)
x 3Iogt
Logarithmic Inverse
1
mint
1
2
52 3
3
4
5
t [s] I min
7 10 20 30 50
Normal Inverse(K=04)
13 Setting
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 514
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 5
September 1997
The current 3I
0
lags the polarising voltage (-3U
0
) by a phase angle that isequal to the angle of the zero sequence source impedance The forward
measuring element operates when
where
ϕ
is the angle between 3I
0
and -3U
0 (positive if 3I
0
lags -3U
0
)
3I0D is the set operate value
The change in operate value is small when the phase angle deviates moder-ately from 65
deg
A deviation of 20
deg
will increase the operate value by only
65
The polarising voltage normally obtained from the broken delta windings
of the VTs can have a high content of harmonics relative the fundamentalfrequency when the output voltage is low particularly when capacitive VTsare used To secure a correct measurement the directional function must
have an effective bandpass filtering of the voltage In the module the filter-
ing secures a correct function for fundamental frequency polarising volt-
ages down to 1 of rated voltage
In case of an external fault the capacitive current generated on the line will
decrease the current to the earth-fault relay situated at the line end towardsthe fault The reverse direction comparator should therefore have an
increased sensitivity to secure reliable blocking in case of external faults
when a directional comparison or a blocking communication scheme is
used The operate current of the reverse direction measuring element in themodule is as a fixed ratio set at 06 sdot 3I0D
The independent time delay function is activated by setting CurveType= Def
The timer t1 starts when the current 3I
0
to the relay is equal to or higher
than the set operating value for IMin and the content of the second har-
monic in 3I
0
is less than 20
The inverse time calculation starts when 3I
0
is equal to or higher than the
set operating value for IMin and the content of the second harmonic in 3I
0
is less than 20 The inverse time delay is determined by the selection of
the characteristic (NI VI etc) under setting ldquoCurveType =rdquo and the set-ting of the characteristic current 3I
0
gt The timer t1 starts when both the
inverse time characteristic and the timer tMin operate Timer t1 is nor-
mally set at zero It can be used to add a constant time to the inverse time
delay
The effect of the settings IMin and tMin on the inverse characteristic is
shown in Fig 2
3I0 65deg ϕndash( ) 3I0Dgecossdot
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 614
1MDX80015-EN
Page 6
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 2 Normal inverse and logarithmic inverse time characteristics
To detect high resistive earth-faults a low operating current is required
On the other hand a low setting will increase the risk for unwanted opera-
tion due to unbalance in the network and the current transformer circuits
The minimum operating current (IMin) of the earth-fault overcurrent pro-
tection must be set higher than the maximum false earth-fault current
The unbalance in the network that causes false earth-fault currents is
caused mainly by untransposed or not fully transposed parallel lines with
strong zero-sequence mutual coupling This false earth-fault current is
directly proportional to the load current
In a well transposed system the false earth-fault current is normally lower
than 5 of the line current except for extremely short parallel lines (less
than 5 kilometres) where a higher false earth-fault current may be found
In case of extremely short or not fully transposed parallel lines the false
earth-fault current must be measured or calculated when maximum sensi-
tivity is desired Generally 80 A is recommended as a minimum primary
operating value for the earth-fault overcurrent protection
The choice of time delay characteristic independent (definite time) nor-
mal inverse very inverse extremely inverse or logarithmic inverse
depends on the network
(X80056-22)
x 3Iogt
Logarithmic Inverse
1
mint
1
2
52 3
3
4
5
t [s] I min
7 10 20 30 50
Normal Inverse(K=04)
13 Setting
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 614
1MDX80015-EN
Page 6
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 2 Normal inverse and logarithmic inverse time characteristics
To detect high resistive earth-faults a low operating current is required
On the other hand a low setting will increase the risk for unwanted opera-
tion due to unbalance in the network and the current transformer circuits
The minimum operating current (IMin) of the earth-fault overcurrent pro-
tection must be set higher than the maximum false earth-fault current
The unbalance in the network that causes false earth-fault currents is
caused mainly by untransposed or not fully transposed parallel lines with
strong zero-sequence mutual coupling This false earth-fault current is
directly proportional to the load current
In a well transposed system the false earth-fault current is normally lower
than 5 of the line current except for extremely short parallel lines (less
than 5 kilometres) where a higher false earth-fault current may be found
In case of extremely short or not fully transposed parallel lines the false
earth-fault current must be measured or calculated when maximum sensi-
tivity is desired Generally 80 A is recommended as a minimum primary
operating value for the earth-fault overcurrent protection
The choice of time delay characteristic independent (definite time) nor-
mal inverse very inverse extremely inverse or logarithmic inverse
depends on the network
(X80056-22)
x 3Iogt
Logarithmic Inverse
1
mint
1
2
52 3
3
4
5
t [s] I min
7 10 20 30 50
Normal Inverse(K=04)
13 Setting
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 714
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 7
September 1997
To achieve optimum selectivity the same type of characteristic should be
used for all earth-fault overcurrent protections in the network Therefore
in networks already equipped with earth-fault overcurrent relays the best
selectivity will normally be achieved by using the same type of character-
istic as that in the existing relays
The following formulas for the operating time in seconds apply to the
characteristics used within the REL 5xx line protection terminal
Characteristic Operating time (s)
Normal inverse
Very inverse
Extremely inverse
Logarithmic inverse
where
I is a multiple of set current 3I
0
gt
k is a time multiplying factor settable in the range of 005 to 11
All inverse time characteristic settings will be a compromise between
short fault clearing time and selective operation in a large current range
The main determining factors are the maximum allowed fault clearing
time at the maximum fault resistance to be covered and the selectivity at
maximum fault current
The minimum operating current (IMin) of the earth-fault overcurrent
protection is settable one to four times the set characteristic quantity
(3I
0
gt) of the inverse time delay Hence an inverse characteristic with a
low set 3I
0
gt to get a short operating time at minimum fault current can be
combined with a higher set minimum operating current IMin in order toavoid unwanted operation due to false earth-fault currents
The minimum operate time is set independent of the inverse time charac-
teristic This time is normally set to be longer than the time delay of dis-
tance Zone 2 in REL 5xx in order to avoid interference with the
impedance measuring system in case of earth-faults with moderate fault
resistance within Zone 2
The polarising voltage for directional earth-fault overcurrent protection is
normally obtained from broken delta-connected secondary windings of
instrument voltage transformers or interposing voltage transformers The
voltage contains a certain amount of harmonics especially when the pro-tection is connected to CVTs
t0 14
I0 02
1ndash
--------------------- k sdot=
t13 5I 1ndash------------ k sdot=
t80
I2
1ndash
------------- k sdot=
t 5 8 1 35 Ilnsdotndash=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 814
1MDX80015-EN
Page 8
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Due to the bandpass filtering within REL 5xx a polarising voltage down
to 1 per cent of the rated voltage will provide correct directional function-
ing This is also valid when the protection is connected to CVTs
The minimum polarising voltage to the protection (U
min
) is calculated
from the formula
where
I
Fmin
is the minimum primary operating fault current
Z
0min
is the minimum zero-sequence impedance at the relay site
U
sec
U
prim
are the rated phase voltages of the open delta-connected
CVTs
Observe that when a blocking scheme or a permissive scheme with cur-
rent reversal or weak infeed logic is used I
Fmin
represents the primary
operating current of the reverse looking directional element
To secure operation in unfavourable cases as well U
min
should be equal to
at least 1 volt plus the maximum network frequency false voltage due to
measuring errors in the VT circuits
If not blocked the directional comparator will operate during the dead
time in case of a single-phase autoreclosure Therefore blocking input
EF---BLOCK should be activated during the single-phase autoreclosing
cycle
For testing of the directional protection and the directional comparison
logic functions a test set with a variable current and a variable voltage
output as well as a variable phase angle between the current and voltage
is required Normally the earth-fault overcurrent protection is tested in
conjunction with the testing of the distance protection functions using the
same multiphase test set Fig 3 below shows the connection of a three-
phase test set at the test of a directional relay
Umin
IF min
Z0 min
Usec
Uprim
--------------sdot sdot=
14 Testing
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 914
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-EN
Page 9
September 1997
Fig 3 Connection of the test set to the relay
Make the appropriate settings including the connections to the digital
inputs and outputs The logic diagram of the tested protection function is
suitably considered when performing the test
The impedance measuring zones may need to be blocked depending on
the zone settings to prevent operation of the impedance function when
checking the earth-fault protection
11 Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg the current lagging the voltage Check that
the operating current of the forward directional element is equal to the
setting 3I0D The function 3I0D activates digital output EF---DEFF
Check with angles ϕ = 20deg and 110deg that the measuring element
operates when 3I0 sdot cos (65deg-ϕ) ge 3I0D
12 Reverse the polarising voltage (ϕ = 180deg+65deg=245deg) and check that
the operating current of the reverse directional element is 06 sdot 3I0D
The function activates digital output EF---DEFR
13 activate the directional function by setting Dir = On
Set the polarising voltage to 2 of Ur and the phase angle between
voltage and current to 65deg
Check the operate current of the IMin function The function acti-
vates digital output EF---STEF
IL1
IL2
IL3
IN
U4
TRIP L1
TRIP L2
TRIP L3
L1I
L2I
L3I
NI
L1U
L2U
L3U
NU
R E L A Y
T E S T
S E T
R E L 5 x x
(X80057-4)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1014
1MDX80015-ENPage 10
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 4 Measuring characteristic of the directional element
14 When independent time delay is selected check the operate time of
timer t1 by injecting current two times the set operate value IMin
When inverse time delay is selected check the operate time at three
points on the inverse characteristic The formulas for operate time for
different types of inverse time delay curves are given in item 13 on
page 7
Check also the functions tMin (minimum operating time) and IMin
(minimum operating current)
15 Activate the input EF---BC to check the function of the switch-onto-
fault logic
Check that digital outputs EF---TRSOTF and EF---TREF are acti-
vated with time delay 300 ms when injecting current two times the set
operate value IMin
16 Check the blocking functions from digital inputs EF---BLOCK and
EF---BLKTEF
Input EF---BLKTEF blocks the output from the timers to digital out-
puts EF---TREF EF---TRSOTF and the tripping output
17 Set the phase angle of the polarising voltage to ϕ = 245deg and check that the directional current function and the switch-onto-fault logic
gives no operation when the current is in reverse direction
Upol = -3Uo
Iset
65
3Io Operation
ϕ
(X 80015-4 (2))
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1114
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 11
September 1997
Table 1
Setting range Accuracy
Basic current 3I0 gt(5-300) Ir in stepsof 1
plusmn5 Iset
Operating value for direc-tional current measure-ment
forward 3I0 sdot cos (ϕ-65deg)
reverse
(5-35) Ir in stepsof 1
60 of the setting forforward operation
(5-10) Iset plusmn10(10-35) Iset plusmn5
(5-10) Iset plusmn15(10-35) Iset plusmn10
Independent time delay (0-60) s in steps of001
plusmn05 plusmn10 ms
Normal inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 5
plusmn60 ms
Very inverse characteristic k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Extremely inverse charact k = (005-11) in stepsof 001
IEC 255-3 class 75
plusmn60 ms
Logarithmic characteristic See the formula below plusmn004 sdot [1 - I Iset]at I = (13-29) Iset
tMin for dependent charact (005-60) s in steps of001 s
plusmn05 plusmn10 ms
Start current for independ-ent and minimum operatecurrent for inverse timecharacteristic IMin (100-400) of 3I0 gt in
steps of 1plusmn5 Iset
Rated voltage 110radic3 V -
Minimum polarisingvoltage
1 Ur plusmn5 at 50 Hz
plusmn15 at 60 Hz
Characteristic angle 65deg lag - fixed plusmn5deg at 20 V and3I0D = 35
15 Technical data
t 5 8 1 35 lnsdotI
3I0set
---------------+=
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1214
1MDX80015-ENPage 12
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
Fig 5 Simplified terminal diagram of the function
Fig 6 Terminal diagram of the function
16 Appendix
(X 80015-5 (2) )
EF---BLKTEF
EF---BLOCK
DIRECTIONAL EARTH-FAULT OVERCURRENT PROTECTION
EF---BC
EF---TRSOTF
EF---DEFF
EF---DEFR
EF---STEF
EF---TREF
161 Terminal diagrams
t
t
2fn+-
amp
2fn
Directional
3Uo
EF---BLOCK
EF---BLKTEF
001 Un
EF3IoSTD
3 Io x
50 ms
t
60 REVERSE
100 FORWARD
1
NI
3Io
IDG
EI
VI
Def
EF---BC
3Iogt
EFK
amp
5
Imin
tmin
t
300 ms
amp
1000 ms
amp amp
amp
amp amp
EF---DEFR
EF---DEFF
1
amp
tamp
t1EF
amp
EF---STEF
1 EF---TREF
EF---TRSOTF
cos( -65)φ
(X 80015-62)
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1314
Directional earth-faultovercurrent protection for solidlyearthed networks
ABB Network Partner AB
Version 121
1MDX80015-ENPage 13
September 1997
162 Signal list
C O N N E C T I O N S
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - B L O C K
B I
B l o c k o v e r c u r r e n t E F p r o t e c t i o n
E F - - - B L K T E F
B I
B l o c k o f t r i p t i m e r
E F - - - B C
B I
B r e a k e r c l o s i n g
P R O D U C T I O N
T O
S E T
T I N G
D E S C R I P T I O N
E F - - - S T E F
B O
E F P i c k - u p
E F - - - T R E F
B O
T r i p E F
E F - - - T R S O T F
B O
T r i p E F f o r s w i t c h - o n t o - f a u l t c o n d i t i o n
E F - - - D E F F
B O
D i r e c t i o n a l E F F o r w a r d o p e r a t i o
n
E F - - - D E F R
B O
D i r e c t i o n a l E F R e v e r s e o p e r a t i o
n
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s
0 6 x 3 I 0 D
8132019 X80015EN
httpslidepdfcomreaderfullx80015en 1414
1MDX80015-ENPage 14
Version 121
Directional earth-faultovercurrent protection for solidlyearthed networks
September 1997
ABB Network Partner AB
163 Setting table
P A R A M
E T E R
S E T T I N G R
A N G E
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N
O p e r a t i o
n
O n O f f
A c t i v a t i o n o f t h e p r o t e c t i o n f u n c t i o n
C u r v e T y
p e
D e f N I V I E I I D G
D e f = I n d e p e n d e n t ( d e fi n
i t e ) t i m e d e l a y N I = N o r m a l
i n v e r s e
V I = V e r y i n v e r s e
E I = E x t r e m e l y i n v e r s e
I D G = L o g a r i t h m i c i n v e r s
e
3 I 0 gt
( 5 - 3 0 0 ) o
f I r
S e t t i n g v a l u e o f t h e c h a
r a c t e r i s t i c q u a n t i t y f o r t h e
i n v e r s e t i m e d e l a y
I M i n
( 1 0 0 - 4 0 0 ) o
f 3 I 0 gt
S t a r t i n g c u r r e n t f o r i n d e
p e n d e n t t i m e d e l a y a n d m i n
o p e r a t i n g c u r r e n t f o r i n v
e r s e t i m e d e l a y
t 1
0 0 0 - 6 0 0 s
D e fi n i t e t i m e d e l a y s e t t i n g a l t e r n a t i v e l y s e t t i n g o f a
fi x e d t i m e i n a d d i t i o n t o
t h e i n v e r s e t i m e d e l a y
K
0 0 5 - 1 1 0
T i m e m u l t i p l i e r f o r i n v e r s e t i m e d e l a y
t M i n
0 0 5 - 6 0 0 s
M i n i m u m
o p e r a t e t i m e f o r i n v e r s e t i m e d e l a y
D i r e c t i o n
N o n D i r
D i r e c t i o n a l
S e l e c t i o n o f d i r e c t i o n a l o r n o n - d i r e c t i o n a l E F p r o t e c -
t i o n f u n c t i o n
3 I 0 D gt
( 5 - 3 5 ) o
f I r
O p e r a t i n g c u r r e n t o f t h e
f o r w a r d d i r e c t i o n a l e l e m e n t
O p e r a t i n g c u r r e n t o f t h e r e v e r s e d i r e c t i o n a l e l e m e n t i s