8/13/2019 X80012EN http://slidepdf.com/reader/full/x80012en 1/44
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 1/44
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 2/44
1MDX80012-EN
Page 2
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
1.5 Secondary injection test
.......................................................28
1.5.1 Measurement with the general three-phase
testing equipment....................................................................29
1.5.1.1 Connection of the testing equipment to the
tested terminal ..............................................................................29
1.5.1.2 Measurement of the operating characteristics of
single-phase-to-earth faults..........................................................30
1.5.1.3 Measurement of the operating characteristics of
phase-to-phase faults31
1.5.1.4 Measurement of the operating characteristics of
three-phase faults .........................................................................33
1.5.1.5 Operating time and time delay of the different
distance measuring zones ............................................................34
1.5.2 Instructions for the measurement of operating
characteristics with the test set type RTS 21 (FREJA)...........34
1.5.2.1 Measurement of the operating time of distanceprotection zones ...........................................................................35
1.5.3 Directional test of the distance measuring function ...............36
1.6 Technical data
.......................................................................37
1.7 Appendix
...............................................................................38
1.7.1 Terminal diagram ...................................................................38
1.7.2 Signal list ................................................................................40
1.7.3 Setting table ............................................................................42
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 3/44
Distance protection
ABB Network Partner AB
Version 1.21
1MDX80012-EN
Page 3
September 1997
The distance protection function remains the most widely spread protec-
tion function in transmission and subtransmission networks. It is becom-
ing increasingly important in distribution networks as well. The two main
reasons for this are:
• there is no dependence on communication links between the line
ends, since for its operation it uses information from locally available
currents and voltages
• in the network the distance protection forms a so-called relatively
selective protection system (non-unit protection system). This means
that it is also able to operate as a remote back-up protection for other
units located in the network.
The basic requirements for a modern line protection such as speed, sensi-
tivity and selectivity, together with the high requirements for availability,
are getting increasingly stringent. In addition to this, modern distance pro-
tections must be able to operate in networks together with existing dis-
tance relays, which are mostly designed in a different technology (static or
even electromechanical relays). The flexibility of a modern distance pro-
tection is therefore of utmost importance. This applies especially when it
is used in a complex network configuration on parallel operating multicir-
cuit lines, on multiterminal lines, etc.
A distance protection is not dependent on communication for selective
operation and can detect faults beyond the current transformer in the
remote terminal. This functionality makes a distance protection an ideal
complement to line differential protections that can not detect faults
beyond the current transformer in the opposite terminal.
The distance protection function optional in REL 561, is primary a protec-
tion for faults beyond the current transformer at the opposite terminal.
This protection function is achieved by the time delayed zone 2, coveringat least the adjacent busbar and thus forming a primary or back-up protec-
tion for the busbar. This function shall be continuously in operation.
An underreaching zone 1 can form a back-up to the line differential pro-
tection. There is no need for this function as long as the differential pro-
tection is in operation. To minimise the risk of unwanted operation from
zone 1, this function can be activated when the differential function is out
of operation.
1 DISTANCE PROTECTION
1.1 Application
1.1.1 General application REL 501, REL 511, REL 521
1.1.2 General application REL 561
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 4/44
1MDX80012-EN
Page 4
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Zone 1 can not protect the entire line. A communication scheme of per-
missive or blocking type will, without time delay, protect the entire line.
This function is only of value when the differential protection is out of
operation. Therefore, to minimise the risk of unwanted operation this
function can normally be blocked and activated when the differential
function is lost. The most likely cause to loose of the differential protec-
tion is communication failure. Therefore the communication scheme
should use another communication channel than the one used by the dif-
ferential protection.
To allow a complementary function in the communication scheme as cur-
rent reversal and weak infeed logic, a reverse zone 3 is available. Zone 3
can also be set forward when needed.
The impedance protection is equipped with phase selector for single-pole
tripping.
The distance protection function, as built into the line protection terminals
REL 5xx, is a full scheme distance protection. This means that it com-
prises individual measuring elements for different types of faults and dif-
ferent zones.
Depending on the type of terminal, it consists of up to five (three in
REL 561) independent impedance measuring zones with a quadrilateral
characteristic, as presented for general case in Fig. 1.
The characteristic in reactive direction is a straight line, parallel with the Raxis. The measuring algorithm used for the reactance part of the character-
istic for phase-to-earth faults compensates for the influence of the load
current on the impedance measurement for distance zone 1. Therefore, the
characteristic presented has no declination against the R axis. Setting of
the reach in reactive direction is independent for each separate zone.
A straight line limits the reach of the distance protection zone in resistive
direction. It is parallel with the line impedance characteristic, Z
L
. This
means that with the R axis it forms a line characteristic angle,
ϕ
L
. Setting
of the reach in resistive direction is independent for each separate zone.
Furthermore, different setting values are possible for phase-to-earth faults
(RFNZn) and for phase-to-phase faults (RFZn), where n designates the
corresponding zone.
The directional characteristic in the second quadrant forms, with the X
axis, an angle of 25
°
. In the fourth quadrant, the corresponding part forms
with the R axis an angle of 15
°
, as presented in Fig. 1.
The characteristics of the distance zones are independent on one another
as far as their directionality and reach in different directions is concerned.
The directionality of each distance zone is programmable. Fig. 2 shows a
typical example of a characteristic of an impedance measuring zone when
directed into forward or reverse direction. A polygon, completed with
dashed lines, represents the characteristic of a non-directional zone.
1.1.3 Basic characteristics
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 5/44
Distance protection
ABB Network Partner AB
Version 1.21
1MDX80012-EN
Page 5
September 1997
Fig. 1 Characteristic of an impedance measuring zone
The set value of a reach in resistive direction determines whether the
directional line in the second quadrant meets, as first, the reactive or the
resistive characteristic - see the difference between the characteristics in
Fig. 1 and Fig. 2.
The values of the reaches in reactive and resistive direction for a particular
zone are the same for forward and reverse impedance measuring elements
as well as for the non-directional mode of operation.
The terminal will automatically adapt the line characteristic angle ϕ
L
according to the set value of the line parameters for positive and zero-
sequence reactance and resistance (R1Zn, X1Zn, R0Zn, X0Zn) for each
zone n separately. Thus, the measurement of different faults will follow
the real conditions in a power system. Fig. 3 shows the measuring charac-
teristic of an impedance measuring zone (for the single-phase-to-earth
fault) that faces the forward direction. Here, a phase-to-earth loop measur-
ing impedance, Z
loop
, consists of a line operational impedance Z
L
, an
earth return impedance Z
N
and a fault resistance RFNZn. The characteris-
tic angle of the complete line,
ϕ
line
, will automatically follow the real sys-
tem conditions as well as the loop measuring characteristics.
X
jX
25o
o15
L
LZ
R F FNR
R
(X80012-1.3)
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 6/44
1MDX80012-EN
Page 6
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Fig. 2 Different characteristics of one zone of the impedance measur-
ing function.
In short line applications, the possibility of covering a sufficient fault
resistance will be a major consideration. Load encroachment problems arenot so common. The independent setting possibility of the reach in reac-
tive and resistive direction is a feature that will greatly improve the flexi-
bility of a distance protection.
An optional overreaching scheme communication logic will, for these
short line applications, additionally improve the resistive coverage. The
optimum solution in some applications is to add the optional directional
comparison earth fault overcurrent protection to the distance protection
scheme.
(X80012-2.3)
LZ
jX
25
Forward
Reverse
Lo
o15
FNR
1.1.4 Short line applications
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 7/44
Distance protection
ABB Network Partner AB
Version 1.21
1MDX80012-EN
Page 7
September 1997
In long line applications, the margin to the load impedance, to avoid load
encroachment, is usually a major consideration. Quadrilateral characteris-
tics with independent settings of the reach in reactive (to cover sufficient
length of a line) and resistive (to avoid load encroachment) direction willdiminish, to a great extent, the conflict that is very characteristic for circu-
lar characteristics.
A wide setting range of the reach in reactive direction, settable independ-
ently for each zone, together with a good current sensitivity, down to 20%
of the rated current, is an important factor that will improve the perform-
ances of the distance protection when used on long transmission lines.
Fig. 3 Characteristic of the phase-to-earth impedance measuring ele-
ment, presented for the loop measurement
1.1.5 Long line applications
jX
loop
X
Z N
N
25°
Z L
15°
RFNZn
line
L
Z
Rline
loopZ
RFNZn
(X80012-3.3)
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 8/44
1MDX80012-EN
Page 8
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
High voltage power cables have two main characteristics that make them,
from the distance protection point of view, different from overhead lines:
• they are relatively short, compared to overhead lines
• the value of their zero sequence reactance is very low, in many cases
even lower than the positive sequence reactance. This results in a
negative value of the characteristic angle for the earth return imped-
ance.
The value of the earth return compensation follows automatically, without
any approximation, the parameters of a power cable for positive and zero
sequence reactance and resistance. This makes the impedance measuring
function, as built into the REL 5xx line protection terminals, suitable for
the protection of short HV power cables. The independent setting of the
reach (in reactive and resistive direction, separately and independently foreach distance zone) will only improve these basic performances.
Zero sequence mutual impedance between different circuits of the multi-
circuit parallel operating lines is a factor that particularly influences the
performance of a distance protection during single-phase-to-earth fault
conditions. In addition to this, a distance protection must, to the greatest
possible extent, operate selectively for intersystem faults and simultane-
ous faults.
The separate and independent setting of the parameters that determine the
value of earth return compensation for different distance protection zones,
enables the compensation of the influence of the zero sequence mutual
impedance on the measurement of the impedance measuring elements for
single-phase-to-earth faults.
The use of separate optional phase selectors with their reach setting inde-
pendent of the reach of the zone measuring elements improves, to a great
extent, the performance of a distance protection on the multicircuit paral-
lel operating lines. At the same time, these phase selectors will reduce to
the lowest possible level the influence of the heavy load current, presentduring a fault, on the phase selection function within the terminals.
1.1.6 Distance protection of the power cables
1.1.7 Application to parallel operating multicircuit lines
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 9/44
Distance protection
ABB Network Partner AB
Version 1.21
1MDX80012-EN
Page 9
September 1997
For the selective operation of a distance protection on tied and multitermi-
nal lines, flexibility in scheme communication logics associated with the
distance protection function is a great advantage. Scheme communicationlogic built into the REL 5xx line protection terminals enables the adapta-
tion of any communication scheme to the existing system conditions. The
free selection of overreaching and underreaching zones, together with the
free selection of a conditional zone, and independent settings of the reach
for different zones, makes the REL 5xx line protection terminals
extremely flexible for such applications.
Fault loop equations use the complex values of voltage, current and
changes in the current. Apparent impedances are calculated and checked
with the set limits (R and X represent the line resistance and reactance).
For single-phase-to-earth faults, earth return compensation is applied in a
conventional manner:
For faults without connection to earth, phase-to-phase quantities are used.
This results in the same reach along the line for all types of faults.
Fig. 4 Measuring principle -general presentation of a line, measuring
quantities
1.1.8 Application on tied and multiterminal lines (not applicable for REL 561)
1.2 Measuring principle
Uph Z0 Z1–( ) I0⋅–
Iph
----------------------------------------------- R jX+=
Uph ph–
Iph ph–
------------------ R jX+=
(X80012-4.3)
U
F
IX
Im(U)
Re(U)
R
U
Re
Im
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 10/44
1MDX80012-EN
Page 10
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
The measuring elements receive information about currents and voltages
from the A/D converter. The checksums are calculated and compared, and
the information is distributed into memory locations. For each of the six
supervised fault loops, voltage , current , and changes in current
between samples are brought from the input memory and fed to a
recursive Fourier filter. The Fourier filter provides two orthogonal values
for each input. These values are related to the loop impedance according
to the formula:
or as orthogonal values:
where Re designates the real component, and Im the imaginary component
of current and voltage.
It is possible to calculate resistance R from the equation for the real value
of the voltage and substitute it in the equation for the imaginary part. The
equation for reactance X can then be solved. The final result of measure-
ment is equal to:
The calculated R and X values are updated each millisecond andcompared with the set zone reach. The adaptive tripping counter counts
the number of permissive tripping results. This in order to effectively
remove any influence of errors introduced by the capacitive voltage trans-
formers or by other causes. The algorithm used is insensitive to changes in
frequency, transient dc components and harmonics since a true replica of
the protected line has been implemented in the algorithm.
The directional evaluations are performed in both forward and reverse
direction, and for all six fault loops simultaneously. Positive sequence
voltage and a phase locked positive sequence memory voltage are used as
a reference. This will ensure unlimited directional sensitivity for faults
close to the relaying point. The directional indication for both forwardand reverse faults makes it possible to provide carrier blocking schemes,
current reversal logic, and weak infeed logic.
u( ) i( )∆i( )
U R IX
ω0
------ ∆I
∆t------⋅+⋅=
Re U( ) R Re I( ) X
ω0
------ ∆Re I( )
∆t------------------⋅+⋅=
Im U( ) R Im I( ) X
ω0
------ ∆Im I( )
∆t------------------⋅+⋅=
RIm U( ) ∆Re I( ) Re U( ) ∆Im I( )⋅–⋅∆Re I( ) Im I( ) ∆Im I( ) Re I( )⋅–⋅
------------------------------------------------------------------------------------=
X ω0 ∆tRe U( ) Im I( ) Im U( ) Re I( )⋅–⋅
∆Re I( ) Im I( ) ∆Im I( ) Re I( )⋅–⋅--------------------------------------------------------------------------------⋅ ⋅=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 11/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 11
September 1997
The impedance measurement for the phase to earth faults is performed on
the loop basis by comparing the calculated resistances and reactances withthe set values of the reach in the resistive and reactive direction. If
and represent measured phase voltage and phase current in relay point
and represents the measured residual current in relay point, then the
operating condition for the phase-to-earth fault resistive measurement in
forward direction follows the expression:
The same condition for the measurement in the reverse direction followsthe expression:
Parameter represent in this case line reactance between the relay
point and the location of a fault.
The operating for the phase-to-earth fault reactive measurement in for-
ward direction follows the expression:
Similar expression is valid also for the phase-to-earth measurement in
reverse direction:
The impedance measurement for the phase to phase faults is performed on
the loop basis by comparing the calculated resistances and reactances with
the set values of the reach in the resistive and reactive direction. The oper-
ating condition for the resistive measurement in forward direction follows
the expression:
1.2.1 Measured impedance
1.2.1.1 Phase-to-earth measurement
Uph
Iph
IN
ReUph
Iph
---------
RFNZn X0Zn X1Zn–( ) R0Zn R1Zn–
X0Zn X1Zn–------------------------------------ Re
IN
Iph
-------
⋅ ImIN
Iph
-------
– Re X1m e jϕLine–
⋅( )+⋅+≤
ReUph
Iph
---------
R– FNZn X0Zn X1Zn–( )–R0Zn R1Zn–
X0Zn X1Zn–------------------------------------ Re
IN
Iph
-------
⋅ ImIN
Iph
-------
– Re X1m e jϕLine–
⋅( )+⋅≥
X1m
ImUph
Iph
---------
X1Zn X0Zn X1Zn–( ) R0Zn R1Zn–
X0Zn X1Zn–------------------------------------ Im
IN
Iph
-------
⋅ ReIN
Iph
-------
+⋅+≤
ImUph
Iph
---------
X– 1Zn X0Zn X1Zn–( ) R0Zn R1Zn–
X0Zn X1Zn–------------------------------------ Im
IN
Iph
-------
⋅ Re
IN
Iph
-------
+⋅+≥
1.2.1.2 Phase-to-phase measurement
UL1
UL2
–
IL1 IL2–-------------------------
RFZn Re X1m e j
ϕL–
⋅( )+≤
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 12/44
1MDX80012-ENPage 12
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Similar condition appears also for the operation in reverse direction:
The operating condition for the reactive measurement in forward direction
follows the expression:
Similar condition applies also for reactive measurement in reverse direc-
tion:
The directional measurement is based on the use of a positive sequence
voltage for the respective fault loop. For the L1-N element, the equation
for forward direction is:
The polarising voltage is available as long as the positive sequence
voltage exceeds 4% of Ur . It will thus be usable for all unsymmetrical
faults (single-phase or two-phase) including close-in faults. For three-
phase faults, the memory voltage , based on the same positive
sequence voltage, will ensure correct directional discrimination.
The memory voltage is used for 100 ms, or until the positive sequence
voltage is restored. After 100 ms, the following will take place:
• If the current is still above 20% of Ir , the condition will seal in. If
the fault has caused tripping, the trip will endure. If the fault was
detected in the reverse direction, the measuring element in thereverse direction will remain in operation.
• If the current decreases below 20%, the memory will reset until the
positive sequence voltage exceeds 40 V.
ReUL1 UL2–
IL1 IL2–
-------------------------
R– FZn Re X1m e⋅ jϕL–
( )+≥
ImUL1 UL2–
IL1 IL2–-------------------------
X1Zn≤
ImUL1 UL2–
IL1 IL2–-------------------------
X– 1Zn≥
1.2.1.3 Directional lines
15°0 8, U1L1⋅ 0 2, U1L1M⋅+
IL1
---------------------------------------------------------------- 115°<arg<
U1L1
U1L1M
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 13/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 13
September 1997
Three digital signal processors, depending on the type of the REL 5xx line
protection terminal, execute algorithms for up to five full scheme distance
protection zones. Fig. 5 presents an outline of the different measuring
loops for the basic five impedance measuring zones as built into the lineprotection terminal REL 511.
Fig. 5 Location of different measuring loops within the three digital
signal processors in line protection terminal REL 511
The first digital signal processor (DSP) measures different fault loops for
different single-phase-to-earth faults and for different zones (not includedinto the REL 501 line protection terminal). This way, it forms the resistive
and reactive part of a characteristic for single-phase-to-earth faults. The
second digital signal processor performs the same task for the phase-to-
phase fault loops. The third digital signal processor performs the direc-
tional measurement for all types of faults, separately in forward and
reverse direction.
The parallel execution of measurements in three different DSPs permits
the evaluation of each impedance measuring loop for each zone separately
within each millisecond. This gives the distance protection function the
same features as those known for the full scheme design of conventional
distance relays (REZ 1, RAZFE).
Different internal and external conditions influence the operation of the
distance protection function as shown in a simplified logic diagram for a
distance protection zone 1 in Fig. 6.
1.3 Design
L1-N L2-N L3-N
L1-N L2-N L3-N
L1-N L2-N L3-N
L1-N L2-N L3-N
L1-N L2-N L3-N
L1-N L2-N L3-N
L1-N L2-N L3-N
L1-L2 L2-L3 L3-L1
L1-L2 L2-L3 L3-L1
L1-L2 L2-L3 L3-L1
L1-L2 L2-L3 L3-L1
L1-L2 L2-L3 L3-L1
L1-L2 L2-L3 L3-L1
L1-L2 L2-L3 L3-L1
Z1
Z2
Z3
Z4
Z5
For.
Rev.
(X80012-5 (2))
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 14/44
1MDX80012-ENPage 14
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Fig. 6 Logical diagram of a distance protection function for zone 1
All other zones have the same logical structure. It is possible to influence
the basic operation of each distance measuring zone (ZM1< on Fig. 6) by
setting the “Operation” parameter at “On” (logical 1) or “Off” (logical 0).
&
O p e r a t i o n t 1 =
O n
I M P - - V T S Z
I M P - - B L T Z 1
I M P - - P S B
I M P - - E X T P S B
1
Z B l o c k = O n
O p e r a t i o n = O n
Z M 1 <
U
1
t
&
&
t 1
&
I M P - - Z M 1
I M P - - T R Z 1
I ,
I
(X80012-6.3)
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 15/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 15
September 1997
The second setting parameter “ZBlock” will permit two logical signals,
listed below, either to block the operation of a particular zone (when ZBlock
= On), or not (when ZBlock = Off). These two logical signals are:
• The IMP--PSB signal that comes from the optional power swingdetection element, and has a logical value 1 when a power swing has
been detected in the primary system. The signal will always be equal
to the logical 0 if the power swing detection unit is not installed in the
terminal, or when its operation has been switched off.
• IMP--EXTPSB is a signal, connected to one of the binary input ter-
minal from an external power swing detection unit. Its influence on
the operation of the distance measuring zone is the same as that for
the signal IMP--PSB.
The IMP--VTSZ signal, normally connected from the optional fuse failure
detection function has a logical value 1 when a fuse failure has beendetected in the secondary circuits of the voltage instrument transformers.
The signal will always be equal to the logical 0 if operation of the fuse
failure unit has been switched off.
It is possible to delay the operation of each distance zone by setting the oper-
ation of the timer “Operation t1” equal to On. This way, the operation of each
distance zone is delayed for the time set on the corresponding timer (opera-
tion of the zone will not be delayed, when the setting on a corresponding
timer will be equal to 0).
Presence of the external binary signal IMP--BLTZn (n=1,2,3,4 or 5) will
prevent the distance measuring function of the corresponding zone from
issuing a tripping signal (for example IMP-- BLTZ1 and IMP--TRZ1 in Fig.
6). Different external conditions could be wired to the corresponding input
terminal for these purposes.
The two logical output signals from the distance zone measuring unit will
be:
• IMP--ZMn, which informs that the impedance has been seen by the
distance zone n (IMP--ZM1 for zone 1)
• IMP--TRZn, which represents the tripping order from the zone n
measuring element (IMP--TRZ1 for zone 1)
Both output signals are connectable to the binary outputs and to other built
in functions.
The appendix to this description of the full scheme distance protection
function brings the following information:
• a simplified block diagram of the distance protection function
• a connection diagram for the distance protection function
• a description of the connection and production signals for the distance
protection function
• a table of the setting parameters for the distance protection function.
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 16/44
1MDX80012-ENPage 16
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
The setting values of all parameters belonging to a distance protection
within the line protection terminals REL 5xx, must correspond to the
parameters of the protected line, as well as to the selectivity plan for the
network. The number of the parameters to be set differs, depending on theoptions included.
Before starting the setting activities for the distance protection function,
check that the setting values of the secondary rated current within the ter-
minal correspond to the current transformers used for the same purposes
as a particular REL 5xx terminal.
It is necessary to convert the primary line impedances to the secondary
sides of the current and voltage instrument transformers. The following
relations apply to these purposes:
and
where:
Iprim is a rated primary current of the used current instrument trans-
formers
Isec is a rated secondary current of the used current instrument
transformers
Uprim is a rated primary voltage of the used voltage instrument trans-
formers
Usec is a rated secondary voltage of the used voltage instrumenttransformers
Zprim is a primary impedance
Zsec is a calculated secondary impedance
1.4 Setting Instructions
1.4.1 Reach setting recommendations
1.4.1.1 Positive-sequence impedance
CTratio
Iprim
Isec
------------= VTratio
Uprim
Usec
--------------=
Zsec
CT ratio
VTratio
------------------ Zprim⋅=
Zsec
Usec
Uprim
--------------Iprim
Isec
------------ Zprim⋅ ⋅=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 17/44
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 18/44
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 19/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 19
September 1997
REL 5xx has a built-in memory capacity for four groups of setting param-
eters, all completely independent of one another. It is possible to set and
pre-test all of them during the commissioning. Their activation is possible
at any time, locally with the aid of a local MMI unit, a personal computer,
or remotely via the SMS or/and SCS (depending on whether the optional
remote communication is built into the terminal or not). Control of the
active setting group by the signals connected to the binary inputs of the
terminals is also possible.
This way, a better adaptation of the REL 5xx settings to different system
conditions can be obtained.
A measuring loop at the single-phase-to-earth faults consists of three
impedances, as shown in Fig. 8:
• the positive sequence impedance of phase conductor
• fault resistance Rf
• earth return impedance
Fig. 8 Equivalent circuits for measurement at single-phase-to-earth
faults.
The earth return impedance is equal to the expression:
The complete measuring impedance, according to Fig. 8b, is equal to:
The reach of a distance protection zone is related to the positive sequence
line impedance, Z1. Therefore, an earth return compensation factor KN has
been introduced into the measuring algorithm. Its value is equal to:
for each particular zone n.
1.4.1.2 Earth return compensation
Z1
ZN
L1 I 1Z
U
rsdI
IU
F
L2
L3
NZR
f
(X80012-8.3)
ZN1
3--- Z0 Z1–( )⋅=
Zloop Z1 ZN Rf + +1
3--- 2Z1 Z0+( ) Rf +⋅= =
KNZn1
3---
Z0Zn Z1Zn–
Z1Zn----------------------------------⋅=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 20/44
1MDX80012-ENPage 20
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Impedances in the above equation are dependent on the values of the set-
ting parameters for each particular zone:
and
The impedance measuring algorithm within the REx 5xx line protection
terminals will automatically calculate the complex value of the earth
return compensation factor on the basis of the setting values for
the:
• positive sequence reactance of protected line section X1Zn
• positive sequence resistance of protected line section R1Zn
• zero-sequence reactance of protected line section X0Zn
• zero-sequence resistance of protected line section R0Zn
The performance of the distance protection for single-phase-to-earth
faults is of great importance, since normally more than 70% of the faults
on transmission lines are single-phase-to-earth ones.
At single-phase-to-earth faults, the fault resistance is composed of three
parts: arc resistance, resistance of a tower construction and tower footing
resistance.
The arc resistance can be calculated according to Warrington's well-
known formula:
where:
I the actual fault current in A
l the length of the arc (in meters). The arc resistance depends also on
the speed of the wind. This should be considered for higher, time
delayed distance protection zones. For the first approximation, about2-3 times the arc foot spacing is sufficient to be considered for the
time delayed operation of zone two with time delay of approximately
500 ms.
The tower footing resistance must be calculated or measured for the spe-
cific case, since the variation of this parameter is very large.
The distance protection can not detect very high resistive earth faults, as
the load impedance and load transfer limit its reach. For faults with resist-
ances higher than those that can be detected by the impedance measure-
ment, an optional earth-fault overcurrent protection can be included in the
REL 5xx line protection terminals.
Z0Zn R0Zn jX0Zn+=
Z1Zn R1Zn jX1Zn+=
KNZn
1.4.1.3 Fault resistance
Rarc28707 l⋅
I1 4,
---------------------=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 21/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 21
September 1997
When calculating the settings for a distance protection function, it is nec-
essary to consider zero-sequence mutual coupling between the circuits of
the multicircuit lines. The positive and the negative sequence mutual cou-pling have no significant influence on the operation of the impedance
measuring protection schemes.
The distance protection within the REL 5xx line protection terminals can
compensate for the influence of a zero-sequence mutual coupling on the
measurement at single-phase-to-earth faults in two different ways:
• by using the possibility of different values that influence the earth
return compensation for different distance zones within the same
group of setting parameters
• by using different groups of setting parameters for different operat-
ing conditions of a protected multicircuit line.
Most multicircuit lines are double-circuit ones, operating in parallel, as
shown in Fig. 9. The following text describes more in detail the setting
recommendations for this particular type of lines, but the basic principles
apply to other multicircuit lines as well. The “Application Guide on Pro-
tection of Complex Transmission Network Configurations” describes the
problems more in detail. The guide was prepared by the CIGRE Working
Group 04 of Study Committee 34 (Protection), and published in Novem-
ber 1991.
Fig. 9 Double-circuit parallel operating line.
1.4.1.4 Zero-sequence mutual coupling on multicircuit lines
REL 5xx
Zs
A
BI
Z
AI F
B
m0
(X80012-9 (2))
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 22/44
1MDX80012-ENPage 22
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Fig. 10a represents an equivalent zero-sequence impedance circuit for the
double-circuit parallel operating line. Input terminals A and B are related
to the input terminals of each circuit close to the busbar A in Fig. 9. Ter-
minal C is related to the fault point. Connection between different termi-
nals differs according to the operating conditions of the line, as shown in
Fig. 10a, Fig. 10b and Fig. 10c.
The distance protection will tend to overreach for single-phase-to-earth
faults on the protected line when the parallel circuit is disconnected and
earthed on both ends. The equivalent zero-sequence impedance circuit
gets the configuration as shown in Fig. 10b. In this case, the equivalent
zero-sequence impedance is equal to the value:
This influences the value of the total loop impedance as measured by the
distance protection function, thus causing its overreaching. It is necessary
to compensate for this overreaching by adjusting the setting of the zero-
sequence impedance for the particular underreaching zone.
Instead of setting the real line zero-sequence resistance R0 and reactance
X0, it is necessary to calculate the equivalent values R 0E and X0E accord-
ing to the equations below, and set them for the particular underreaching
zone of a distance protection function. (The following two equations are
presented mostly for the theoretical understanding).
In many cases, the zero-sequence mutual resistance is not known. In most
cases, however, it has no significant influence on the final measurement
and therefore it is possible to ignore it. In this case, the components of the
equivalent zero-sequence mutual impedance will be equal to (the follow-
ing two equations are presented for the practical use):
1.4.1.5 The parallel operating double-circuit line, with one circuit disconnected and earthedat both ends
Z0E
Z0
2Z
m0
2–
Z0----------------------=
R0E R0 1
Xm0
2Rmo
2– 2
X0
R0
------- Rm0 Xm0⋅ ⋅ ⋅–
R0
2X0
2+
-------------------------------------------------------------------------------+
⋅=
X0E X0 1
Xm0
2Rmo
2– 2
R0
X0
------- Rm0 Xm0⋅ ⋅ ⋅+
R0
2X0
2+
--------------------------------------------------------------------------------–
⋅=
R0E R( m0 0 ) R0 1Xm0
2
R0
2X0
2+
--------------------+
⋅= =
X0E R( m0 0 ) X0 1 Xm0
2
R0
2X0
2+
--------------------–
⋅= =
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 23/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 23
September 1997
Fig. 10 Equivalent zero-sequence impedance circuits for the differentoperating conditions of a double-circuit parallel operating line.
(X80012-10C (2))
c) Equivalent zero-sequence impedance circuit for a single-phase-to-earth on the adjacent busbars with the parallel circuit disconnencted andnot earthed.
(X80012-10A (2))
(X80012-10B (2))
a) Equivalent zero-sequence impedance circuit for a single-phase-to-earth fault
b) Equivalent zero-sequence impedance circuit for a single-phase-to-earthfault on the adjacent busbars with the parallel circuit disconnected andearthed at both ends
on the adjacent busbars with both parallel circuits in operation.
m0
0 m0
C
A
0
m0Z
B
Z -Z
Z -Z
0 m0
m0Z I 0C
B 0 m0
Z -Z
Z -Z
I0
A
C
0 m0
m0B 0
m0Z0I
Z -Z
Z -Z
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 24/44
1MDX80012-ENPage 24
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
When the parallel circuit is out of service and not earthed, the equivalent
zero-sequence impedance circuit will be like the one shown in Fig. 10c.
The line zero-sequence mutual impedance will not influence the measure-ment of the distance protection in a faulty circuit. This means that the reach
of the underreaching distance protection zone will be reduced if, due to
operating conditions, the equivalent zero-sequence impedance has been set
with the parallel system out of operation, and earthed at both ends.
The reduction of the reach will be equal to the factor:
This means that the reach will be reduced both in reactive and resistive
direction. If the real and imaginary components of the constant A are
equal to the values:
The real component of the factor is equal to the value (theoretical
presentation):
and the imaginary one to the value (theoretical presentation):
In many cases, the zero-sequence mutual resistance is not known. In most
cases, however, it has no significant influence on the final measurementand therefore it is possible to ignore it. In this case, the components of the
equivalent zero-sequence mutual impedance will be equal to (the follow-
ing two equations are presented for the practical use):
1.4.1.6 The parallel circuit out of service and not earthed
KU
1
3--- 2 Z1 Z0E+⋅( ) Rf +⋅
1
3--- 2 Z1 Z0+⋅( ) Rf +⋅
------------------------------------------------------ 1Zm0( )
2
Z0 2 Z1 Z0 3R f + +⋅( )⋅----------------------------------------------------------–= =
Re A( ) R0 2 R1 R0 3 Rf ⋅+ +⋅( ) X0 2 X1 X0+⋅( )⋅–⋅=
Im A( ) X0 2 R1 R0 3 Rf ⋅+ +⋅( ) R0 2 X1 X0+⋅( )⋅+⋅=
KU
Re KU( ) 1=Re A( ) Xm0
2Rm0
2–( ) 2 Rm0 Xm0 Re A( )⋅ ⋅ ⋅–⋅
Re A( )[ ]2
Im A( )[ ]2
+
------------------------------------------------------------------------------------------------------------------+
Im KU( )Im A( ) Xm0
2Rm0
2–( ) 2 Rm0 Xm0 Im A( )⋅ ⋅ ⋅+⋅
Re A( )[ ]2
Im A( )[ ]2
+
-------------------------------------------------------------------------------------------------------------------–=
Re KU( ) Rm0 0→[ ] 1Re A( ) Xm0
2⋅
Re A( )[ ]2
Im A( )[ ]2
+
------------------------------------------------------+=
Im KU( ) Rm0 0→[ ]Im A( ) Xm0
2⋅
Re A( )[ ]2
Im A( )[ ]2
+
------------------------------------------------------–=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 25/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 25
September 1997
It is necessary to make sure that the underreaching zones from both line
ends will overlap in a sufficient amount (at least 10%) in the middle of the
protected circuit.
The zero-sequence mutual coupling can virtually reduce the reach of a
distance protection on the protected circuit when the parallel circuit is in
normal operation. The reduction of the reach will be most pronounced
with no infeed in the line terminal closest to the fault. This reach reduction
will normally be less than 15%. However, when the reach is reduced at
one line end, it will be proportionally increased at the opposite line end.
Therefore, this 15% reach reduction will not affect the operation of a per-
missive underreach scheme.
Overreaching zones (in general, zones 2 and 3) must overreach the pro-
tected circuit in all cases. The greatest reduction of a reach will occur in
cases when both parallel circuits are in service, and a single-phase-to-
earth fault located at the end of a protected line. The equivalent zero-
sequence impedance circuit for this case is equal to the one presented in
Fig. 10d.
Therefore, the components of the zero-sequence impedance for the over-
reaching zones must be equal to at least:
It is necessary to check the reduction of a reach for the overreaching zones
due to the effect of the zero-sequence mutual coupling. The reach will be
reduced for a factor:
If the real and imaginary components of the B constant are equal to the
values
the real and the imaginary value of the reach reduction factor for the over-
reaching zones is equal to (theoretical presentation):
1.4.1.7 Parallel circuit in service
1.4.1.8 Setting of the overreaching zones
R0E R0 Rm0+=
X0E X0 Xm0+=
K0 1Zm0
2 Z1 Z0 Zm0 3R f + + +⋅-----------------------------------------------------------–=
Re B( ) 2 R1 R0 Rm0 3 Rf ⋅+ + +⋅=
Im B( ) 2 X1 X0 Xm0+ +⋅=
Re K0( ) 1Rm0 Re B( ) Xm0 Im B( )⋅+⋅
Re B( )[ ]2
Im B( )[ ]2
+
---------------------------------------------------------------------–=
Im K0( )Rm0 Im B( ) Xm0 Re B( )⋅–⋅
Re B( )[ ]2
Im B( )[ ]2
+
---------------------------------------------------------------------=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 26/44
1MDX80012-ENPage 26
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
When the zero-sequence mutual resistance is ignored, their values will be
equal to (the following two equations are presented for the practical use):
Each of the REL 5xx line protection terminals has a built-in possibility of
setting four different groups of setting parameters and activating them
according to the system conditions. Different setting groups can also suit
different operating conditions of a multicircuit, parallel operating line.
The advantage of such an approach is a better coverage of the line under
normal operating conditions as well as when the parallel system is out of
operation and not earthed at both ends.
It is necessary to apply the same measures as in the case with a single set
of setting parameters. This means that an underreaching zone must not
overreach the end of a protected circuit for the single-phase-to-earth
faults. The values of the zero-sequence resistance and reactance must
therefore be set equal to (the following two equations are presented for the
practical use):
Normally, the underreaching zone of a distance protection will underreach
for the single-phase-to-earth faults located closer to the opposite end of
the circuit. To overcome this underreaching and trip without a sequential
tripping of the faults along the greatest possible percentage of a line, it is
necessary to increase the value of the equivalent zero-sequence impedance
to the one recommended also for the overreaching zones. This means that
the values of the equivalent zero-sequence resistance and reactance will be
equal to:
Re K0( ) 1Xm0 Im B( )⋅
Re B( )[ ]2 Im B( )[ ]2+
-----------------------------------------------------–=
Im K0( )X– m0 Re B( )⋅
Re B( )[ ]2
Im B( )[ ]2
+
-----------------------------------------------------=
1.4.1.9 Different values of an earth return compensation in different groups of settingparameters
1.4.1.9.1 The parallel circuit switched off with both ends earthed
R0E R( m0 0 ) R0 1Xm0
2
R0
2X0
2+
--------------------+
⋅= =
X0E R( m0 0 ) X0 1Xm0
2
R0
2X0
2+
--------------------–
⋅= =
1.4.1.9.2 Double-circuit parallel line in normal operation
R0E R0 Rm0+=
X0E X0 Xm0+=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 27/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 27
September 1997
The same rules apply to the overreaching zones as in cases with a single
set of setting parameters. It is necessary to assure that they will always
overreach. Therefore, it is essential to increase the setting of the zero-sequence resistance and reactance to the values that correspond to at least:
In many cases it will be sufficient if the influence of the zero-sequence
mutual impedance will be compensated only in the first overreaching zone
(generally, zone 2). The setting of the back-up overreaching zones (zone 3
and higher) is usually so high that no such compensation is necessary.
Instructions for overreaching zones are applicable for normal network configurations. Their settings must always be reconsidered if any special
lines or other elements (cables, power transformers, etc.) follow the dou-
ble-circuit parallel operating line.
It is necessary to pay special attention to the distance protection of double-
circuit parallel operating multiterminal or tapped lines.
The resistive reach is set independently for each zone, and separately for
phase-to-phase, and phase-to-earth loop measurement (see Fig. 1).
It is necessary to set only the expected fault resistance for multiphase
faults (RFZn) and for phase-to-earth faults (RFNZn), since all the line
parameters (R1Zn, X1Zn, R0Zn and X0Zn) are settable independently of
each other for each distance zone n. The terminal automatically performs
a calculation of the complete loop impedance (see Fig. 3 under item
Application).
The final reach in resistive direction for phase-to-earth fault measurement
will automatically follow the values of the line-positive and zero-sequence
resistance, and at the end of the protected zone, it will be equal to:
for the phase measurement
The blinder in the resistive direction will in this case form an angle with
the R axis equal to:
The ratio between the reach in resisitve and the reactive direction should
not exceed the value:
1.4.1.9.3 Overreaching distance protection zones
R0E R0 Rm0+=
X0E X0 Xm0+=
1.4.1.10 Setting of the reach in resistive direction
RNn R1Zn RFNZn+=
ϕLN arcX1Zn
R1Zn---------------tan=
RFNZn
X1Zn------------------- 4 5,≤
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 28/44
1MDX80012-ENPage 28
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
This realtion should always apply for the underreaching zone 1 and for all
overreaching zones, which do not permit any additional overreaching due
to strict selectivity reasons.
The fault resistance for phase-to-phase faults is normally quite low, com-
pared to the fault resistance for phase-to-earth faults. The setting of the
zone 1 reach in resistive direction for phase-to-phase loop measurement
should be limited to the relation
This realtion should always apply for the underreaching zone 1 and for all
overreaching zones, which do not permit any additional overreaching due
to strict selectivity reasons
The maximum permissible resistive reach for any zone should be checked
to ensure that there is a sufficient setting margin between the relay bound-
ary and the minimum load impedance.
The minimum load impedance is calculated as:
[Ω /phase]
where:
U is the minimum phase-to-phase voltage in kV
S is the maximum apparent power in MVA
The load is a three-phase condition and Zload is therefore equally
expressed in ohms per phase or ohms per loop.
The load impedance is a function of the minimum operation voltage and
the maximum load current:
[Ω /phase]
Umin and Imax are related to the same operating conditions. Minimum load
impedance occurs normally under emergency conditions.
Since the safety margin is required to avoid load encroachment under
three-phase conditions, and to guarantee correct healthy phase relay oper-
ation under combined heavy three-phase load and earth faults, both phase-
to-phase and phase-to-earth fault operating characteristics should be con-
sidered.
To avoid load encroachment, the set resistive reach of the distance protec-
tion function should be less than 80% of the minimum load impedance.
This way we get the following two conditions:
RFZn
X1Zn--------------- 3≤
1.4.1.11 Margin between the reach in resistive direction and a load impedance
ZloadU
2
S-------=
Zload
Umin
3 I⋅ max----------------------=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 29/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 29
September 1997
for the phase-to-earth measuring elements
and
for the phase-to-phase measuring elements
This equations are applicable only when the loop characteristic angle for
the single-phase-to-earth faults is more than twice as large as the maxi-
mum expected load impedance angle. On the contrary, more accurate cal-
culations are necessary according to the equations below:
for the phase-to-earth measuring elements and
where:
ϑ is a maximum load impedance angle, related to the minimum load
impedance conditions.
This is valid for all measuring zones when no power swing detection ele-
ment is included in the protection scheme. An additional safety marginshould be used in cases when a power swing detection element is
included in the protection scheme (see item “Power swing detection”,
1MDX80013-EN).
The required time delays for different distance protection zones are inde-
pendent of each other. Distance protection zone 1 can also have a time
delay, if so required for selectivity reasons. The time delays for all zones
(basic and optional) are settable in a range of 0 to 10 seconds. The tripping
function of each particular zone can be inhibited by setting the corre-sponding “Operation” parameter to an “Off” value.
It is necessary to check the operating values of the impedance measuring
elements and corresponding functions during the commissioning as well
as during regular maintenance tests. ABB Network Partner AB recom-
mends, although it does not absolutely request, the use of a testing equip-
ment of type RTS 21 (FREJA) for purposes of the secondary injection
testing.
The test equipment used should be able to provide an independent three-
phase supply of voltages and currents to the tested terminal. Furthermore,
it must be possible to change the values of voltages, currents and phase
angles between the measuring quantities, independent of each other, for
RFNZn 0 8 Zload min⋅,≤
RFZn 1 6 Zload min⋅,≤
RFNZn 0 8 Zl oad min ϑ 1
3---
Zl oad min ϑsin⋅
2 X1Zn X0Zn+⋅-------------------------------------------- 2 R1Zn R0Zn+⋅( )⋅ ⋅–cos⋅ ⋅,≤
RFZn 1 6 Zl oad min ϑZl oad min ϑsin⋅
X1Zn--------------------------------------- R1Zn⋅–cos⋅ ⋅,≤
1.4.1.12 Setting of timers for the distance protection zones
1.5 Secondary injection test
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 30/44
1MDX80012-ENPage 30
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
each phase separately. The test voltages and currents should have a com-
mon source, with a very small content of higher harmonics. If the test
equipment can not indicate the phase angles between the measured quanti-
ties, a separate phase angle meter will be needed.
It is not necessary to switch off or change the setting of the time-lag ele-
ments for the different impedance measuring zones when testing their oper-
ating values. The corresponding binary signals for the operation of each
distance measuring zone (IMP--ZM1, IMP--ZM2, IMP--ZM3, IMP--ZM4and IMP--ZM5) are available on the local MMI unit under the menu:
Service report
Logical Signals
ImpZones
These signals are configurable to the corresponding binary outputs (relay
contacts) under the menu:
Configuration
Binary Outputs
and connectable to the appropriate terminals on the testing equipment, if
the testing equipment is provided with the automatic facilities for the meas-urement of operating values.
Before testing, it is necessary to connect the testing equipment according tothe valid terminal diagram of the particular REL 5xx terminal. Special
attention should be paid to the correct connection of the input and output
current terminals, and to the connection of the residual current.
Measurement of the operating characteristics should preferably run under
constant current conditions. We recommend to keep the measured current
as close as possible to its rated value or lower, but at any rate it should behigher than 30% of the rated current. If the measurement of the operating
characteristics runs under constant voltage conditions, it will be necessary
to make sure that the maximum continuous current of a terminal does not
exceed four times its rated value.
We recommend keeping the measuring current and reactance as a constant
value, when measuring the operating characteristic in the resistive direc-
tion and the directional boundary in the second quadrant. We also recom-mend keeping the measuring current and the resistance constant, when
measuring the reach in reactive direction and the directional boundary in
the fourth quadrant..
We suggest the measuring of two operating points on each line of the oper-
ating characteristic. Only the characteristic in the direction that corre-
sponds to the direction in question, set for future use, should be measured.
The terminal diagram, as presented under item 11 of this User's Guide, is a
general one for the terminal. The same diagram is not necessarily applica-
ble for each particular delivery, especially regarding the configuration of all
1.5.1 Measurement with the general three-phase testing equipment
1.5.1.1 Connection of the testing equipment to the tested terminal
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 31/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 31
September 1997
binary inputs and outputs. It is therefore necessary to check before the test-ing that the available terminal diagram really corresponds to the terminal
itself. The best way to do this is to check the serial number of the terminal
on its front plate, and compare it with the valid serial number on the termi-
nal diagram.
The description of the testing of the operating values of the impedance
measuring zones for single-phase-to-earth faults refers to the testing of
distance zone 1 for the single-phase-to-earth fault L1-N. Testing of other
zones follows the same rules with the corresponding signals and values for
the respective zones. The testing of other phases follows the same rules
with the corresponding changes in the names of the phases.
The necessary operating conditions are presented for the special case,
when the measured residual current has the same value and phase position
as the measured phase current. This corresponds in most cases to the con-
ditions used by different testing equipments when measuring the operat-
ing characteristics for the phase-to-earth faults.
Fig. 11 shows a phasor diagram of the voltages and currents during the
testing of the operating value of an impedance measuring zone under the
single-phase-to-earth fault L1-N in forward and reverse direction.
The procedure for the measurement of one operating point on the operat-
ing characteristic of the zone 1 measuring element is as follows:• Apply to the terminal symmetrical three-phase voltages and the cur-
rent IL1f , which is in phase with the voltage UL1.
• Change the phase angle of the voltage UL1 to an appropriate value
that corresponds to the phase angle at which the measured operating
point is expected.
• Reduce voltage UL1 until the signal IMP--ZM1 appears on the local
MMI unit.
• Record the operating value of the current, voltage and phase angle.
• Compare the measured result with the expected operating value
according to the settings of zone 1. The expected loop measuredoperating values in reactive and resistive direction are equal to (a rep-
resent the relative value of a reactance at which the resistive reach is
measured: 0 on the R axis and 1 at the end of zone reactive reach):
• The measurement of operating points on the directional lines followsthe same procedure, but with constant measuring voltage, and a
changeable phase angle between the voltage and current in phase L1.
The directional lines should form an angle of 15 degrees with the R
1.5.1.2 Measurement of the operating characteristics of single-phase-to-earth faults
Xm
1
3--- 2 X1Zn⋅ X0Zn+( )⋅=
Rm
1
3--- a 2 R1Zn⋅ R0Zn+( ) RFNZn+⋅ ⋅=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 32/44
1MDX80012-ENPage 32
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
axis in fourth quadrant and 25 degrees with the X axis in the second
quadrant.
Fig. 11 Phasor diagram of currents and voltages for measuring of the
impedance operating characteristics of the single-phase-to-
earth fault L1-N in forward or reverse direction.
The description of the testing of the operating values of the impedance
measuring zones for phase-to-phase faults refers to the testing of distance
zone 1 for the phase-to-phase fault L2-L3. The testing of other zones fol-
lows the same rules with the corresponding signals and values for those
zones. The testing of other phases follows the same rules with the corre-
sponding changes in the names of the phases.
Fig. 12 presents a phasor diagram of the voltages and currents during the
testing of operating values of the impedance measuring zone under the
phase-to-phase fault L2-L3 in forward and reverse direction.
o
10
11
-UL1
9
UL3
operating area
14
(changing the U )
12
13
L1
15
7
UL1
1
16
3
655
o
I
15o
L1F
UL2
Loop
4
(changing the U )operating area
L1
2
6
8
165
115o
(X80012-11C.3)
1.5.1.3 Measurement of the operating characteristics of phase-to-phase faults
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 33/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 33
September 1997
The procedure for the measurement of one operating point on the operat-
ing characteristic of the zone 1 measuring element is as follows:
• Apply to the terminal symmetrical three-phase voltages and current
IL2f and IL3f , which lags the voltage UL2-L3 for 90o
.Observe that IL3 = - IL2.
• Change the phase angle of the voltage UL2-L3 to an appropriate value
that corresponds to the phase angle at which the measured operating
point is expected.
• Reduce the voltage UL2-L3 until the signal IMP--ZM1 appears on the
local MMI unit
• Record the operating value of the current, voltage and phase angle.
• Compare the measured result with the expected operating value
according to the settings of zone 1. The expected loop measured
operating values in reactive and resistive direction are equal to (a rep-resent the relative value of reactance at which the resistive reach is
measured: 0 on the R axix and 1 at the end of zone reactive reach):
• A measurement of the operating points on the directional lines fol-lows the same procedure, but with a constant measuring voltage and
changeable phase angle between voltage UL2-L3 and currents IL2f
and IL3f . The directional lines should form an angle of 15 degrees
with the R axis in fourth quadrant and 25 degrees with the X axis in
the second quadrant.
Xm 2 X1Zn⋅=
Rm a 2 R1Zn⋅ RFZn+⋅=
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 34/44
1MDX80012-ENPage 34
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Fig. 12 Phasor diagram of the currents and voltages for the measuring
of the impedance operating characteristics of the phase-to-
phase faults in forward or reverse direction.
9 o 1
(changing the U )operating area
25
16
L3U
4
L
5
IL2
15
o15
3
2
L2-L3
L2
U
(changing the U )operating area
10
L3 L2
147
11
I =-I
L1U
12
L
75
8
25
o
o
13
UL2-L3
6
(X80012-12C.3)
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 35/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 35
September 1997
Fig. 13 Phasor diagram of the currents and voltages for measuring the
impedance operating characteristics of three-phase faults in
forward or reverse direction.
The description of the testing of the operating values of the impedance
measuring zones for three-phase faults refers to the testing of distance
zone 1 for the three-phase faults L1-L2-L3. The testing of other zones fol-
lows the same rules with the corresponding signals and values for those
zones.
Fig. 13 shows a phasor diagram of the voltages and currents during the
testing of the operating value of the impedance measuring zone under the
three-phase fault L1-L2-L3 in forward and reverse direction.
1.5.1.4 Measurement of the operating characteristics of three-phase faults
operating area in
forward direction
(simultaneous changing
of U , U and U ).
L2F
operating area in
reverse direction
(simultaneous changing
of U , U and U ).
UL3
10
L1
11
L3L2
9
15
L
12
o
I
6
IL3F
7
1
8 UL2
L1FI
5
L2
4
L3
2
3
L1
(X80012-13.3)
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 36/44
1MDX80012-ENPage 36
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
The procedure for the measurement of one operating point on the operat-
ing characteristic of zone 1 measuring element is as follows:
• Apply to the terminal symmetrical three-phase voltages and currents,
which are in phase with the corresponding phase voltages.• Change simultaneously the phase angles of all three voltages to
appropriate values that correspond to the phase angle at which the
measured operating point is expected.
• Reduce simultaneously all three voltages until the signal IMP--ZM1
appears on the local MMI unit.
• Record the operating value of the currents, voltages and phase angles.
• Compare the measured results with the expected operating values
according to the zone 1 settings. The expected phase measured oper-
ating values in reactive and resistive direction are equal to (a repre-
sent the relative value of reactance at which the resistive reach ismeasured: 0 on the R axix and 1 at the end of zone reactive reach):
• The measurement of the operating points on the directional lines fol-
lows the same procedure, but with constant measuring voltages and
changeable phase angles between the voltages and currents. The
directional lines should form an angle of 15 degrees with the R axis
in fourth quadrant and 25 degrees with the X axis in the second quad-rant.
The same connection schemes apply to the measurement of the operating
times for different distance zones as for the measurement of their operat-
ing values. Besides this, it is necessary to configure the corresponding
zone tripping signals (IMP--TRZn, where n represents the number of the
particular zone) to some binary outputs (relay contacts). These signals
must then be wired to the STOP terminals of the timer.
In addition, it is possible to use the regular tripping signals (relay contacts)
to stop the time measurement.
The simulated fault impedance shall be within 70% of the zone reach
when measuring the operating time or time delay of the different imped-
ance measuring zones.
The testing procedure for the manual testing of the operating characteris-
tics of different impedance measuring zones and different faults is as fol-
lows:
Xm X1Zn=
Rm a R1Zn RFZn+⋅=
1.5.1.5 Operating time and time delay of the different distance measuring zones
1.5.2 Instructions for the measurement of operating characteristics with the test settype RTS 21 (FREJA)
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 37/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 37
September 1997
1.1 Configure the zone operating signals (IMP--ZMn, where n = 1 to 5,
depending on the number of optional zones included into the termi-
nal) to one of the binary outputs.
1.2 Set up FREJA for three-phase impedance configuration and 3PZ RXdisplay.
1.3 Connect the IMP--ZMn signal to the FREJA binary input No. 1.
1.4 In the 3PZ display, set FREJA at the following parameters:
1.5 Set fault impedance Z and impedance angle ZΦ for the zone under
test at +10% of the zone setting for one of the suggested testing
points (Fig. 11 to 13).
1.6 Supply the terminal with healthy conditions (press key W) for at least
two seconds.
1.7 Apply fault conditions (press key S).
1.8 Slowly decrease the measured impedance Z until the tested zone
operates. Check that the correct signal (IMP--ZMn) appears on the
local MMI unit. Compare the result of the measurement with the set-
ting values.
1.9 Repeat steps 1.5 to 1.8 for other measuring points of the same imped-
ance measuring zone.
1.10 Repeat steps 1.1 to 1.9 for other measuring zones included into the
terminal (3 or 5).
It is necessary to have the same configuration of test equipment FREJAand of the tested terminal, as for the measurement of the distance protec-tion characteristics. The signals IMP--TRZn must be connected to the cor-responding binary inputs of the testing equipment instead of the zonemeasuring signals IMP--ZMn.
The simulated fault impedance should be within 80% of the zone reach,when measuring the operating time or time delay of the different imped-ance measuring zones.
Parameter Condition
I Greater than 30% Ir
DIgoal 1XXXX XXXXX
Healthy conditions U = 63,5 V, I = 0 A, ZΦ = 0o
R, X scale and
position of Origin
Suitable for the relay settings
Impedance Z Test point
Impedance angle ZΦ Test angle
Digital outputs Not used
1.5.2.1 Measurement of the operating time of distance protection zones
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 38/44
1MDX80012-ENPage 38
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
A directional test of the distance protection function within the REx 5xxline protection terminal should always be carried out before it is taken into
service. The directional test can be performed under the menu:
Service Report
Direction
To perform the directional test, the protected line must be in service and
carry at least so much load current that the phase current in the terminal
will be higher than 20% of the terminal rated current Ir .
When the directional test is activated, the display on the local MMI unit
will show whether the current direction in each phase-to-phase measuring
loop is forward or reverse, relative to the direction of zone 1. The displaywill indicate:
• L1L2 = Forward
• L2L3 = Forward
• L3L1 = Forward
if the current flow in the three measuring loops is in forward direction, and
• L1L2 = Reverse
• L2L3 = Reverse
• L3L1 = Reverse
if the current flow in the three measuring loops is in backward direction.
If one of the loops is in the opposite direction than the other two, this indi-cates that the phase sequence of the incoming voltage or current circuits is
incorrect.
In order to perform the directional test, the load impedance must have anangle which is in the range of -15° and +115°, or +165° and 295°, as these
are the sectors supervised by the directional elements.
The actual values of the current and voltage phasors, as seen by the dis-
tance protection function, are available when the optional fault location
function is included in the REx 5xx terminal. Phasors are available on thelocal MMI unit under the menu:
Service ReportPhasors
and they can be used for the directional tests as well.
1.5.3 Directional test of the distance measuring function
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 39/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 39
September 1997
*) Specified values should be devided by 5 for Ir = 5A
Table 1:
Function Value
Typical operating time 28 ms for REL 52132 ms for REL 501 and REL 51130 ms for REL 561
Minimum operating current 0,2⋅Ir
Resetting ratio typical 105%
Resetting time typical 40 ms
Tripping mode three phase or single and threephase (not for REL 501)
Setting accuracy included in the measuring accu-
racy
Number of zonebasic version
optional
3, direction selectable forREL 5215, direction selectable forREL 501 and REL 5112, direction selectable forREL 5213, direction selectable forREL 561
Impedance setting range at Ir = 1 A
reactive reach *)positive-sequence reactance X1zero-sequence rectance X0
line resistive reach *)positive-sequence resistance R1zero-sequence resistance R0
fault resistance *)for phase-phase faultsfor phase-earth faults
(0,1-150) ohm in steps of 0,01(0,1-1200) ohm in steps of 0,01(not in REL 501)
(0,1-150) ohm in steps of 0,01(0,1-1200) ohm in steps of 0,01(not in REL 501)
(0,1-150) ohm in steps of 0,01(0,1-150) ohm in steps of 0,01(not in REL 501)
Setting range of timersfor impedance zones (0 - 10) s in steps of 1 ms
Static accuracy at 0° and 85° and(0,1-1,1)⋅Ur and (0,5-30)⋅Ir ±5%
Static angular accuracy at 0° and 85°and (0,1-1,1)⋅Ur and (0,2-30)⋅Ir ±5°
Maximum dynamic overreach at85° measured with CVTs and0,5<SIR<30 +5%
1.6 Technical data
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 40/44
1MDX80012-ENPage 40
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
Fig. 14 Simplified terminal diagram of the function.
1.7 Appendix
DISTANCE PROTECTION
*2) not in REL 501
IMP--TRZ2
IMP--TRZ4
IMP--TRZ3
IMP--TRZ5
IMP--PSBPOWER SWINGDETECTION(OPTION)
*2)
IMP--EXTPSB
IMP--BLTZ1
IMP-VTSZ
IMP--BLTZ2
IMP--BLTZ3
IMP--BLTZ4
IMP--BLTZ5
*2)
Z5<
*1)
Z4<*1)
Z3<
Z2<
Z1<
IMP--ZM4
IMP--ZM5
IMP--TRZ1
IMP--ZM3
IMP--ZM2
IMP--ZM1
*1) when installed, not available in REL 561
(X80012-14.4)
1.7.1 Terminal diagram
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 41/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 41
September 1997
Fig. 15 Terminal diagram for the function.
(X80012-15a.4)
40ms
t
*2) not for REL 501
IMP--BLTZ4
IMP--BLTZ5
IMP--BLTZ3
&
earth faultdetected by Z<
Operation=On
IMP--IPSB
Z2PSB
Z1PSB
ZONE 5
ZONE 4
ZONE 3
DISTANCE PROTECTION
IMP--EXTPSB
IMP--BLTZ1
IMP--VTSZ
IMP--BLTZ2
Operation=On
& 11
ZONE 2
Z<
ZONE 1
ZBlock=On
U
Operation t1=On
IMP--TRZ2
&
PSB*1) *2)
IMP--PSB
1 &
2s
&
IMP--ZM4
IMP--TRZ4
IMP--ZM5
IMP--TRZ3
IMP--TRZ5
IMP--ZM3
&
t
&IMP--TRZ1
IMP--ZM2
t1
IMP--ZM1I, I
*1) when included (option)
*1) *3)
*1) *3)
*3) not available in REL 561
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 42/44
1MDX80012-ENPage 42
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
1.7.2 Signal list
C O N N E C T I O N S : T O :
S E T T I N G :
D E S C R I P T I O N :
I M
P - - B L T Z 1
B I
E x
t e r n a l b i n a r y s i g n a l t h a t b l o c k s t r i p p i n g o f d i s t a n c e p r o t e c t i o n z o n e
1
I M
P - - B L T Z 2
B I
E x
t e r n a l b i n a r y s i g n a l t h a t b l o c k s t r i p p i n g o f d i s t a n c e p r o t e c t i o n z o n e
2
I M
P - - B L T Z 3
B I
E x
t e r n a l b i n a r y s i g n a l t h a t b l o c k s t r i p p i n g o f d i s t a n c e p r o t e c t i o n z o n e
3
I M
P - - B L T Z 4
B I
E x
t e r n a l b i n a r y s i g n a l t h a t b l o c k s t r i p p i n g o f d i s t a n c e p r o t e c t i o n z o n e
4
( w
h e n i n s t a l l e d )
I M
P - - B L T Z 5
B I
E x
t e r n a l b i n a r y s i g n a l t h a t b l o c k s t r i p p i n g o f d i s t a n c e p r o t e c t i o n z o n e
5
( w
h e n i n s t a l l e d )
I M
P - - E X T P S B
B I
E x
t e r n a l b i n a r y s i g n a l t h a t c a n b e p r o g r a m m e d t o b l o c k o p e r a t i o n o f a
n y
d i s t a n c e m e a s u r i n g z o n e , f o r i n s t a n c e f r o m a n e x t e r n a l p o w e r s w i n g d
e t e c -
t i o
n u n i t , n o r m a l l y c o n n e c t e d t o o n e
o f t h e p r o g r a m m a b l e b i n a r y i n p u t s
I M
P - - V T S Z
F U S E
C o
n n e c t i o n s i g n a l t h a t b l o c k s t h e o p
e r a t i o n o f t h e d i s t a n c e p r o t e c t i o n
f u n c -
t i o
n . N o r m a l l y c o n n e c t e d t o t h e f u s e
f a i l u r e f u n c t i o n , s i g n a l F U S E - V T S
Z
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 43/44
Distance protectionABB Network Partner AB
Version 1.21
1MDX80012-ENPage 43
September 1997
P R O D U
C T I O N :
T O :
S E T T I N G :
D E S C R I P T I O N :
I M P - - T R
Z 1
B O T R I P
T r i p c a u s e d b y o p e r a t i o n o f d i s t a n c e p r o t e
c t i o n z o n e 1 ( c o n t r o l l e d b y t h e
o p e r a t i o n o f t i m e r t 1 )
I M P - - T R
Z 2
B O T R I P
T r i p c a u s e d b y o p e r a t i o n o f d i s t a n c e p r o t e
c t i o n z o n e 2 ( c o n t r o l l e d b y t h e
o p e r a t i o n o f t i m e r t 2 )
I M P - - T R
Z 3
B O T R I P
T r i p c a u s e d b y o p e r a t i o n o f d i s t a n c e p r o t e
c t i o n z o n e 3 ( c o n t r o l l e d b y t h e
o p e r a t i o n o f t i m e r t 3 )
I M P - - T R
Z 4
B O T R I P
T r i p c a u s e d b y o p e r a t i o n o f d i s t a n c e p r o t e
c t i o n z o n e 4 , w h e n i n s t a l l e d
( c o n t r o l l e d b y t h e o p e r a t i o n o f t i m e r t 4 )
I M P - - T R
Z 5
B O T R I P
T r i p c a u s e d b y o p e r a t i o n o f d i s t a n c e p r o t e
c t i o n z o n e 5 , w h e n i n s t a l l e d
( c o n t r o l l e d b y t h e o p e r a t i o n o f t i m e r t 5 )
I M P - - Z M
1
B O
O p e r a t i o
n o f z o n e 1 i m p e d a n c e m e a s u r i n g e l e m e n t
I M P - - Z M
2
B O
O p e r a t i o
n o f z o n e 2 i m p e d a n c e m e a s u r i n g e l e m e n t
I M P - - Z M
3
B O
O p e r a t i o
n o f z o n e 3 i m p e d a n c e m e a s u r i n g e l e m e n t
I M P - - Z M
4
B O
O p e r a t i o
n o f z o n e 4 i m p e d a n c e m e a s u r i n g e l e m e n t , w h e n i n s t a l l e d
I M P - - Z M
5
B O
O p e r a t i o
n o f z o n e 5 i m p e d a n c e m e a s u r i n g e l e m e n t , w h e n i n s t a l l e d
I M P - - P S
B
B O
O p e r a t i o
n o f t h e o p t i o n a l p o w e r s w i n g d e t e c t i o n e l e m e n t , w h e n i n s t a l l e d
t o g e t h e r
w i t h d i s t a n c e p r o t e c t i o n .
8/13/2019 X80012EN
http://slidepdf.com/reader/full/x80012en 44/44
1MDX80012-ENPage 44
Version 1.21
Distance protection
September 1997
ABB Network Partner AB
1.7.3 Setting table
E T E R :
S E T T I N G
R A N G E :
S E T T I N G
A C T U A L
G
r o u p 1
G r o u p 2
G r o u p 3
G r o u p 4
D E S C R I P T I O N :
D i s t a n c e p r o t e c t i o n z o
n e n
o n
O n / O f f
O p e r a t i o n o f d i s t a n c e p r o t e c t i o n z o n e n ( n = 1 - - 5 )
( 0 , 1 - 1 5 0 ) o h m
P o s i t i v e - s e q u e n c e r e a c t a n c e a s d e fi n e d b y t h e d i s t a n c e
p r o t e c t i o n z o n e n r e a c h
( n = 1 - - 5 )
( 0 , 1 - 1 5 0 ) o h m
P o s i t i v e - s e q u e n c e r e s i s
t a n c e a s d e fi n e d b y t h e d i s t a n c e
p r o t e c t i o n z o n e n r e a c h
( n = 1 - - 5 )
( 0 , 1 - 1 2 0 0 ) o h m
Z e r o - s e q u e n c e r e a c t a n c e a s d e fi n e d b y t h e d i s t a n c e
p r o t e c t i o n z o n e n r e a c h
( n = 1 - - 5 )
( 0 , 1 - 1 2 0 0 ) o h m
Z e r o - s e q u e n c e r e s i s t a n
c e a s d e fi n e d b y t h e d i s t a n c e
p r o t e c t i o n z o n e n r e a c h
( n = 1 - - 5 )
( 0 , 1 - 1 5 0 ) o h m
F a u l t r e s i s t a n c e f o r p h a s e - t o - p h a s e a n d
t h r e e - p h a s e f a u l t s a s d e
fi n e d b y t h e
d i s t a n c e p r o t e c t i o n z o n e n r e a c h ( n = 1 - - 5 )
( 0 , 1 - 1 5 0 ) o h m
F a u l t r e s i s t a n c e f o r s i n g
l e - p h a s e - t o - e a r t h f a u l t s a s
d e fi n e d b y t h e d i s t a n c e
p r o t e c t i o n z o n e n r e a c h ( n = 1 - - 5 )
O n / O f f
T i m e r f o r t i m e d e l a y e d o
p e r a t i o n , i f a n y , o f d i s t a n c e p r o -
t e c t i o n z o n e n ( n = 1 - - 5 )
0 , 0 0 0 - 1 0 , 0 0 0 s
T i m e d e l a y f o r o p e r a t i o n
o f
d i s t a n c e p r o t e c t i o n z o n e n ( n = 1 - - 5 )
N o n
F o r w a r d
R e v e r s e
D i r e c t i o n a l i t y o f d i s t a n c e p r o t e c t i o n z o n e n ( n = 1 - - 5 )
O n / O f f
B l o c k i n g o f z o n e n b y i n
t e r n a l p o w e r s w i n g d e t e c t i o n
e l e m e n t o r b y e x t e r n a l s
i g n a l I M P - - E X T P S B ( n = 1 - - 5 )