293943-XTG-A-0307 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SPLIT-SYSTEM AIR COOLED CONDENSING UNIT H5CE150, H5CE180 AND H5CE240 12-1/2, 15 AND 20 NOMINAL TONS (World 50Hz) ® ISO 9001 Certified Quality Management System DESCRIPTION These outdoor condensing units are completely assembled, piped and wired at the factory to provide one-piece shipment and rig- ging. Each unit is pressurized with a holding charge of Refriger- ant-22 for storage and/or shipping. The compact design, clean styling, and quiet operation make these condensing units suitable for almost any outdoor location. HCE units are easier to install on rooftops because they weigh much less than a single package unit of similar capacity and are much easier to rig and support. At ground level their ample sub- cooling capacity allows them to be located 18 meters (60 feet) below the evaporator coil. All sheet metal parts are constructed of commercial grade galva- nized steel. Before painting, each part is thoroughly cleaned to remove any grease or dirt from its surfaces. The external parts are then coated a desert sand powder paint to assure a quality finish for many years. This coating system has passed the 1000 hour, salt spray test per ASTM Standard B117. All models include a 1-year limited warranty on the complete unit. The compressor carries an additional 4-year warranty. A matching line of Evaporator Blower units is also offered to meet your precise capacity and air handling requirements. FEATURES • Simplicity ® Controls • Two stage single refrigerant circuit design • Tandem scroll compressors • Inherently protected fan motors • High and Low Pressure Controls • Exterior service port connections • Weatherized Casing with powder paint (1000 hour salt spray hours) • Five-minute compressor anti-short cycle delay • Compressor operation to 45°F • Field install Low Ambient control to 0°F • Permanently attached base rails with fork lift slot and lifting holes allowing 3-way fork lift access and overhead rigging • Factory installed service valves • Factory installed crank case heaters • Factory supplied filter-drier for field installation • Optional Technicoat Coils • Optional Pump Out Kit • Optional Coil Guard • Five year limited warranty • One year limited warranty on all other parts FIELD-INSTALLED ACCESSORIES • A decorative coil guard provides and additional level of pro- tection for condenser coils. H5CE150 - 1CG0409 H5CE180 - 1CG0410 H5CE240 - 1CG0410
12
Embed
X-TG, 50 Hz Split System Air Cooled Condensing Unit ... · 293943-xtg-a-0307 for distribution use only - not to be used at point of retail sale split-system air cooled condensing
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
293943-XTG-A-0307
SPLIT-SYSTEM AIR COOLED
CONDENSING UNIT
H5CE150, H5CE180 AND H5CE240
12-1/2, 15 AND 20 NOMINAL TONS
(World 50Hz)
��
ISO 9001
Certified Quality
Management System
DESCRIPTION
These outdoor condensing units are completely assembled, pipedand wired at the factory to provide one-piece shipment and rig-ging. Each unit is pressurized with a holding charge of Refriger-ant-22 for storage and/or shipping.
The compact design, clean styling, and quiet operation makethese condensing units suitable for almost any outdoor location.HCE units are easier to install on rooftops because they weighmuch less than a single package unit of similar capacity and aremuch easier to rig and support. At ground level their ample sub-cooling capacity allows them to be located 18 meters (60 feet)below the evaporator coil.
All sheet metal parts are constructed of commercial grade galva-nized steel. Before painting, each part is thoroughly cleaned toremove any grease or dirt from its surfaces. The external parts arethen coated a desert sand powder paint to assure a quality finishfor many years. This coating system has passed the 1000 hour,salt spray test per ASTM Standard B117.
All models include a 1-year limited warranty on the complete unit.The compressor carries an additional 4-year warranty.
A matching line of Evaporator Blower units is also offered to meetyour precise capacity and air handling requirements.
FEATURES
• Simplicity® Controls• Two stage single refrigerant circuit design• Tandem scroll compressors• Inherently protected fan motors• High and Low Pressure Controls• Exterior service port connections• Weatherized Casing with powder paint (1000 hour salt spray
hours)• Five-minute compressor anti-short cycle delay• Compressor operation to 45°F• Field install Low Ambient control to 0°F• Permanently attached base rails with fork lift slot and lifting
holes allowing 3-way fork lift access and overhead rigging• Factory installed service valves• Factory installed crank case heaters• Factory supplied filter-drier for field installation• Optional Technicoat Coils• Optional Pump Out Kit• Optional Coil Guard• Five year limited warranty• One year limited warranty on all other parts
FIELD-INSTALLED ACCESSORIES
• A decorative coil guard provides and additional level of pro-tection for condenser coils.
1. Refer to Form 24077 for refrigerant piping limitations.
Voltage Variation,380/415-3-50
Min. 342
Max. 456
Ambient Air on Condenser CoilMin./Max.
°C 7/502
2. These units can operate at an ambient temperature of 52°C (125°F) providing the wet bulb temperature of the air entering the evaporator coil does not exceed 23°C (73°F).
°F 45/1251
Suction Pressure at Compressor and Corresponding Temp. at
Saturation Min./Max.
400kPa/625kPa0°C/12°C
57.5 psig/90.0 psig32.0°F/53.5°F
TABLE 2: PHYSICAL DATA
ModelSize
(Mbh)
Compressor1Condenser Unit Weight
(Lbs.)/Kg.Charge, (R-22)Lbs.-Oz./Kg.24” Fan (Propeller) Fan Motor2 Coil
1. Compressor set consists of two Copeland scroll compressors manifolded into a single refrigerant circuit.2. The ball bearing, 48 frame, single phase condenser fan motor have internal protection are directly connected to the condenser fans. Motor rotation
is counterclockwise when viewing the lead end, which is opposite the shaft end.3. Holding charge is the amount in the unit as shipped from the factory.4. Operating refrigerant charge is for the condensing unit and the matching York air handler, but does not include the charge in the interconnecting pip-
1. Power (Kw input) in Tables 6 thru 12 includes compressor(s) and condenser fan motors.
Unitary Products Group 5
293943-XTG-A-0307
NOTE: These capacities are Gross Ratings. For Net capac-ities, determine the Kw requirements of the supplyair blower motor per the published Blower Perfor-mance data. Convert Kw to MBH per the followingequation and deduct this equivalent heat from thegross cooling ratings.
This Note is applicable to all system performance tables ascovered on Pages 6-11.
TABLE 7: GROSS COOLING CAPACITIES & POWER REQUIREMENT H5CE150 WITH K3EU180 IMPERIAL
CFM EWB°F
ENTERING DRY BULB AT 85°F ENTERING DRY BULB AT 95°F
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group 7
293943-XTG-A-0307
TABLE 9: GROSS COOLING CAPACITIES & POWER REQUIREMENT H5CE240 WITH L*EU240 IMPERIAL
Air on Evaporator CoilTemperature of Air on Condenser Coil
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
8 Unitary Products Group
293943-XTG-A-0307
TABLE 10: GROSS COOLING CAPACITIES & POWER REQUIREMENT H5CE150 WITH K3EU180 METRIC
m3/sEWB
°C
ENTERING DRY BULB AT 29°C ENTERING DRY BULB AT 35°C
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
10 Unitary Products Group
293943-XTG-A-0307
TABLE 12: GROSS COOLING CAPACITIES & POWER REQUIREMENT H5CE240 WITH L*EU240 METRIC
Air on Evaporator CoilTemperature of Air on Condenser Coil
1. The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.
2. These ratings include the condensate fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group 11
GUIDE SPECIFICATION - H*CE150 THRU 240
1. Generala. Units shall be manufactured in a facility registered
under the ISO 9002 manufacturing quality standard.b. Unit shall be packaged to allow outdoor storage.c. Warranty shall be a full year limited parts warranty
on the complete unit with an additional 4-year war-ranty on the compressor.
d. Certified in accordance with the Unitary LargeEquipment certification program, which is based onARI Standard 340/360.
2. Unit Cabineta. Cabinet shall be constructed of 18 gauge, zinc-
coated steel, finished with a powder paint processcapable of withstanding a minimum of 750 salt sprayhours according to ASTM B117.
b. Cabinet screws shall comply with the ASTM B117salt spray test for a minimum of 750 hours.
c. Panels shall be removable for easy access to allinternal components during maintenance and ser-vice.
d. Cabinet shall feature a separate access panel forthe controls so that unit airflow need not be dis-turbed during servicing.
e. Permanently attached base rails shall have 3-wayfork lift access and lifting holes for ease of installa-tion.
3. Compressora. Compressors shall be hermetic scroll.b. Compressor shall feature motor overload protection.c. A crankcase heater shall keep refrigerant from dilut-
ing the compressor oil in the sump. Crankcaseheater shall be field replaceable without removal ofthe charge.
d. Neoprene isolators shall be used to minimize thetransmission of sound and vibration.
e. Compressor sets shall have two stages, withunloading accomplished through turning off onecompressor.
4. Condenser and Fansa. Fan motors shall be direct-drive with propeller-type
condenser fans which discharge air verticallyupward.
b. Fan motors shall have permanently lubricated ball-bearings for longer wear during start and stop cyclesand shall have inherent overload protection.
c. Coil shall be constructed of rifled copper tubingmechanically expanded and bonded to louvered alu-minum fins. Coil shall include an integral subcooler.
5. Refrigerations Components - Refrigerationsystem shall contain the following:
a. High and low pressure cut-outs.b. Suction and liquid line service valves to ease instal-
lation and recovery of refrigerant.c. External ports to accommodate gauge lines, allow-
ing for easy servicing.d. Filter drier shipped in unit for field installation.e. Holding charge of R-22.
6. Controls - Unit control shall include:a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resettable circuitbreaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which pro-vides reset capability at the space thermostat orbase unit, should any of the following standardsafety devices trip and shut off compressor:
c. Loss-of-charge/Low-pressure switch. (1) High-pres-sure switch. If any of the above safety devices trip, aLED (light-emitting diode) indicator shall flash adiagnostic code that indicates which safety switchhas tripped.
d. Unit shall incorporate "AUTO RESET" compressorover temperature, over current protection.
e. Unit shall operate with conventional thermostatdesigns and have a low voltage terminal strip foreasy hook-up.
f. Unit control board shall have on-board diagnosticsand fault code display.
g. Standard controls shall include anti-short cycle andlow voltage protection.
h. Control board shall monitor each refrigerant safetyswitch independently.
i. Control board shall retain last 5 fault codes in nonvolatile memory, which will not be lost in the event ofa power loss.
7. Electricala. Units shall be ______ volts, 3 phase, with a single
power point connection.b. Unit control circuit shall have a 24 volt transformer,
sized sufficiently to operate the indoor fan.c. All condenser fan motors and the secondary of each
transformer shall be grounded. 8. Accessories and Options
a. Coil Guard: Field installed decorative grille shall beplaced on the units to provide further coil protection.
b. Phenolic Coating on Condenser Coil: Condensercoils shall be dipped in a four-coat phenolic coatingprocess to provide longer life in corrosive condi-tions.