C lim a 2005 Lausanne |Solothurnstrasse 13 |C H -3322 Schönbühl |Sw itzerland 8 th REHVA W orld C ongress |Phone +41 (31)852 13 00 |Fax +41 (31)852 13 01 | Email:[email protected] www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196 DW@EnergyBooks.com www.EnergyBooks.com
48

Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Dec 15, 2015

Download

Documents

Kenyon Astle
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Clima 2005 Lausanne | Solothurnstrasse 13 | CH-3322 Schönbühl | Switzerland

8th REHVA World Congress | Phone +41 (31) 852 13 00 | Fax +41 (31) 852 13 01 | Email: [email protected]

www.clima2005.ch

Optimized HVAC for the 21st Century

Donald R. Wulfinghoff, P.E.Wulfinghoff Energy Services, Inc.

Wheaton, Maryland USA

301 – 946 – 1196 [email protected]

Page 2: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

A REVOLUTION IN 45 MINUTES

Contemporary HVAC equipment and design practices are obsolete. They cannot satisfy the stringent requirements of the 21st Century for:

The essential changes can be made quickly.

Here is how to do it.

ENERGY EFFICIENCY

HEALTH

RESISTANCE TO TERRORISM

Page 3: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

THE LOGIC

1. HVAC systems are either multiple-zone or single-zone.

2. Multiple-zone air handling systems inherently cannot perform all HVAC functions and operate efficiently. So, they must be abandoned.

3. Single-zone systems can satisfy all HVAC functions efficiently.

4. But, contemporary single-zone HVAC equipment performs poorly because of flaws in design and equipment.

5. We will solve the design problem by introducing a new approach to design that optimizes every function required by the application.

6. We will solve the equipment problem by showing how to correct all the flaws of contemporary single-zone equipment.

Page 4: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Multiple-Zone Air Handling SystemsInherently Cannot Satisfy All HVAC Functions

1. Temperature control of individual spaces forces a 3‑way compromise between COMFORT, VENTILATION, and ENERGY EFFICIENCY.

2. All multiple-zone systems inherently have: INEFFICIENT and/or INADEQUATE VENTILATION HEALTH HAZARDS FIRE HAZARD AIR TRANSPORT LOSSES AIR LEAKAGE into Idle Spaces and Equipment And Now, … VULNERABILITY TO TERRORISM

Page 5: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

These deficiencies of multiple-zone air handling systems are INHERENT.

They cannot be fixed.

So, multiple-zone systems must be ABANDONED.

Page 6: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Footnote: VAV is a Failed Experiment

Ventilation is radically worse than with constant-volume systems.

Improving comfort and ventilation requires a return to reheat.

Discomfort is endemic. Combining heating and cooling is problematic.

An Interesting Trend: Fan-powered VAV terminals are an evolution toward single-zone systems.

Page 7: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

So, …the optimized HVAC of the 21st century will use SINGLE-ZONE systems exclusively.

They can avoid all conflicts between energy efficiency and the HVAC functions.

They can avoid all health hazards.

They cover smaller areas, limiting the spread of fire and noxious agents.

Page 8: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Then, WHY are SINGLE-ZONE Systems Not the Primary Choice for HVAC Today?

DESIGN DEFICIENCIES: Designers neglect to tailor single-zone systems to the functions needed by the application. (Multiple-zone systems tend to be multi-functional, although inefficient.)  

EQUIPMENT DEFICIENCIES: Lack of rational humidity control Ineffective control of ventilation Failure to exploit opportunities for efficiency Generally poor quality

Page 9: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

INTRODUCING

OPTIMIZED-FUNCTION DESIGN

IMPROVING DESIGN PRACTICE

Page 10: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

OPTIMIZED-FUNCTION DESIGN

addresses every function

of each application

in an optimum manner.

Page 11: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Steps of OPTIMIZED-FUNCTION HVAC Design

1. Define all the HVAC functions that are needed for each application in the facility.

2. Define the spatial zones that correspond to each function. (Zones may differ for different functions.)

3. For each zone, select equipment to fulfill each function optimally.

4. Consolidate the equipment.

5. Optimize the control of the equipment.

Page 12: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Steps of OPTIMIZED-FUNCTION HVAC Design

1. Define all the HVAC functions that are needed for each application in the facility.

2. Define the spatial zones that correspond to each function. (Zones may differ for different functions.)

3. For each zone, select equipment to fulfill each function optimally.

4. Consolidate the equipment.

5. Optimize the control of the equipment.

Page 13: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Common Functions of HVAC(More Than You Realize!)

FUNCTIONS NOT INVOLVING O.A. FUNCTIONS INVOLVING O.A.

Raise Space Temperature Select Cleanest Outside Air

Lower Space Temperature Use Outside Air for Cooling

Raise Space Humidity Raise Humidity of Outside Air

Lower Space Humidity Lower Humidity of Outside Air

Distribute Conditioned Air Control Pressure Relative to Outside

Circulate Air for Comfort Remove Outside Air Pollutants

Remove Space Air Pollutants Recover Sensible Heat from Exhaust

Control Pressure Between Spaces Recover Latent Heat from Exhaust

Limit Spread of Fire Prevent Intake of Noxious Agents

Limit Spread of Noxious Agents

… AND perform all these functions with minimum energy!

Page 14: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Steps of OPTIMIZED-FUNCTION HVAC Design

1. Define all the HVAC functions that are needed for each application in the facility.

2. Define the spatial zones that correspond to each function. (Zones may differ for different functions.)

3. For each zone, select equipment to fulfill each function optimally.

4. Consolidate the equipment.

5. Optimize the control of the equipment.

Page 15: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Steps of OPTIMIZED-FUNCTION HVAC Design

1. Define all the HVAC functions that are needed for each application in the facility.

2. Define the spatial zones that correspond to each function. (Zones may differ for different functions.)

3. For each zone, select equipment to fulfill each function optimally.

4. Consolidate the equipment.

5. Optimize the control of the equipment.

Page 16: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Steps of OPTIMIZED-FUNCTION HVAC Design

1. Define all the HVAC functions that are needed for each application in the facility.

2. Define the spatial zones that correspond to each function. (Zones may differ for different functions.)

3. For each zone, select equipment to fulfill each function optimally.

4. Consolidate the equipment.5. Optimize the control of the equipment.

Page 17: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

EQUIPMENT CONSOLIDATION(One Unit is Needed for Each Zone)

(Filters, humidifiers, and controls are omitted for clarity.)

Page 18: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Fulfilling all the functions of the application usually does NOT require a potpourri of equipment.

A high degree of EQUIPMENT CONSOLIDATIONis possible.

A high degree of STANDARDIZATION is possible.

Page 19: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Steps of OPTIMIZED-FUNCTION HVAC Design

1. Define all the HVAC functions that are needed for each application in the facility.

2. Define the spatial zones that correspond to each function. (Zones may differ for different functions.)

3. For each zone, select equipment to fulfill each function optimally.

4. Consolidate the equipment.

5. Optimize the control of the equipment.

Page 20: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Conditioning Mode F1 F2 C1 C2 H D1 D2 D3 D4 D5 D6 D7 D8

Heating: all conditions O O X X O O O X O X O X O

Mechanical cooling: no dehumidification needed

O O O X X X O O O X O X O

Mechanical cooling: low outside humidity, inside moisture requires dehumidification

O O O X O X X X O X O X O

Mechanical cooling: outside humidity requires dehumidification

O O O O O X X X O O X X O

Economizer cooling: mechanical cooling not needed

O X X X X O X O X X X O O

Economizer cooling: supplemental mechanical cooling required, but not dehumidification

O X O X X X O O X X X O O

Economizer cooling: supplemental mechanical cooling and dehumidification

O X O X O X X X X X X O O

Purge Cycle (for cooling or air cleaning) O X X X X O X O X X X O O

Zone Shutdown X X X X X X X X X X X X X

Legend: F – Fan. All fans are variable-speed. C – Cooling coil H – Heating coil D – Damper. All dampers are 2-position (fully open or fully closed) R – Heat recovery (coil or heat exchanger) A – Air flow sensor O – “on” (for fans and coils) or “open” (for dampers) X – “off” (for fans and coils) or “closed” (for dampers)

Provide OPTIMUM CONTROL for ALL Conditions

Page 21: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

ECONOMICS

of Optimized-Function HVAC

COST ISSUE(in order of cost)

PERFORMANCE (Relative to Multiple-Zone Systems)

Human Productivity & Health Major Improvement

Energy Cost Much Lower

Loss of Rentable Space Much Less

Equipment Cost About Same

Insurance Against Hazards Much Less Expensive

Maintenance More Expensive, but Minor

Page 22: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

FIXING THE EQUIPMENT

OPTIMIZING

DEHUMIDIFICATIONIN SINGLE-ZONE SYSTEMS

Page 23: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

ABOLISH

“CHEAP MOTEL SYNDROME”

24 C, 40%

11 C, 100%

DRY BULB TEMPERATURE (F)

80

40

40

6050

50

60

70

70

80 90 100 120

90

.004

.016

.012

.008

.028

.024

.020

32 C, 90%

Page 24: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

The Solution is REHEAT

24 C, 40%

11 C, 100%

32 C, 90%

DRY BULB TEMPERATURE (F)

80

40

40

6050

50

60

70

70

80 90 100 120

90

.004

.016

.012

.008

.028

.024

.020

Page 25: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Isn’t Reheat EXPENSIVE?Not in single-zone systems. It’s FREE.

Reheat is expensive in multiple-zone systems because it is used for temperature control in addition to humidity control.

But, single-zone systems do not need reheat for space temperature control.

A cooling system always rejects enough heat to provide free reheat for humidity control.

Page 26: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

REHEAT for humidity control in single-zone systems is FREE

because it can be done entirely with REJECTED HEAT

1. Heat rejected in any cooling process always exceeds the cooling load.

2. Reheat needed for dehumidification is always less than the cooling load.

3. Single-zone systems do not need reheat for other functions (temperature control).

Page 28: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Reheating with condenser heat is the most efficient method of dehumidification by cooling that is possible:

It INCREASES THE EFFICIENCY of the cooling equipment.

It is even more efficient than using “renewable” energy sources for reheat.

Page 30: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

Reheat coils must be enhanced to exploit the LOW TEMPERATURE of rejected heat (typically ca. 50 C), which is further reduced by hydronic heat transfer.

Condenser cooling water has low energy density, so it is important to MINIMIZE HEAT LOSS and PUMPING ENERGY. Otherwise, pumping energy will add significant cost to dehumidification.

DESIGN CHALLENGES WHEN USING REJECTED HEAT

IN HYDRONIC SYSTEMS

Page 31: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

OTHER DEHUMIDIFICATION IMPROVEMENTS(not explicitly single-zone issues)

Dehumidify where moisture concentration is greatest. Include latent heat recovery. Eliminate moisture retention on cooling coils.

Page 32: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

OTHER DEHUMIDIFICATION IMPROVEMENTS(not explicitly single-zone issues)

Dehumidify where moisture concentration is greatest. Include latent heat recovery. Eliminate moisture retention on cooling coils.

Page 33: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

OTHER DEHUMIDIFICATION IMPROVEMENTS(not explicitly single-zone issues)

Dehumidify where moisture concentration is greatest. Include latent heat recovery. Eliminate moisture retention on cooling coils.

Page 34: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

FIXING THE EQUIPMENT

OPTIMIZING

VENTILATIONIN SINGLE-ZONE SYSTEMS

Page 35: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

NOTORIOUS VENTILATION DEFECTSIN SINGLE-ZONE SYSTEMS

Inability to regulate outside air intake accurately.

Air infiltration into spaces and equipment during idle periods.

Page 36: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

ACCURATE CONTROL OF OUTSIDE AIR ABOLISH CONTROL DAMPERS! This requires 2 steps:

1) Control ventilation air intake with variable-speed fans.

2) Control fans with air flow monitoring.

Page 37: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

PREVENTION OF OUTSIDE AIR LEAKAGE

Install HERMETIC dampers for ISOLATION.

Page 38: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

OTHER SINGLE-ZONE VENTILATION IMPROVEMENTS

Optimize outside air economizer cycle. Incorporate exhaust air heat recovery.

Page 39: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

OTHER SINGLE-ZONE VENTILATION IMPROVEMENTS

Optimize outside air economizer cycle. Incorporate exhaust air heat recovery.

Page 40: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

IMPROVE VENTILATION SYSTEM DESIGNOUTSIDE THE EQUIPMENT BOXES

(not explicitly single-zone issues)

Cleanest air Isolated from wind pressure Inaccessible to mischief Warmest or coolest air source,

depending on requirement

Improve the efficiency of air distribution to the occupants.

Control ventilation rate in response to need.

Select the best air intake source.

Page 41: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

THE FINAL

REFINEMENTSIN OPTIMIZED-FUNCTION SYSTEMS

MINIMIZE AIR MOVEMENT ENERGY

ELIMINATE ALL HEALTH HAZARDS

Page 42: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

MINIMIZE AIR MOVEMENT ENERGY Abolish control dampers (another reason). Bypass idle coils.

Page 43: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

MINIMIZE AIR MOVEMENT ENERGY Abolish control dampers (another reason). Bypass idle coils.

Page 44: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

ELIMINATE ALL HEALTH HAZARDS Sterilize air handling equipment continuously. Include appropriate filtering, biocides, etc.

to eliminate hazards from the air stream.

Page 45: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

ELIMINATE ALL HEALTH HAZARDS Sterilize air handling equipment continuously. Include appropriate filtering, biocides, etc.

to eliminate hazards from the air stream.

Page 46: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

EQUIPMENT MANUFACTURING ISSUES

Optimized HVAC equipment is easy to manufacture, not significantly more difficult than contemporary equipment.

Existing equipment serves as prototypes for optimized equipment.

Much existing equipment can be used in optimized systems as it presently exists.

Page 47: Www.clima2005.ch Optimized HVAC for the 21 st Century Donald R. Wulfinghoff, P.E. Wulfinghoff Energy Services, Inc. Wheaton, Maryland USA 301 – 946 – 1196.

ONWARD TO THE FUTURE!

Design Your HVAC for this Century, Not the Last One

The Survival of Civilization Depends on It