Underground Distribution Fuse Service Equipment Series 7 House Service Cut-outs (CNE) 240V/415V WT Henley’s glass reinforced Polyester (DMC) material provides strength, durability and excellent tracking resistance. Tamper resistant ‘pin & plug’ protects unused cable entries. Sharply serrated double entry phase and neutral terminals are suitable for either aluminium or copper conductors from 2.5mm 2 up to 35mm 2 and socket headed terminal screws (operated by a custom designed tool) ensure effective and secure connections. Fuse-clips are precision designed to ensure low contact resistance every time. All phase terminal screws are held captive within the base to make installation as simple as possible. The market leading Series 7 range, sets the standard for safety and convenience in House Service Cut-outs. Designed for Combined Neutral and Earth (CNE) systems, rated up to 100A and fully compliant with BS 7657:2010 • Insulated Busbar available for connecting a second Single Pole cut-out / service • Tamper-resistant ‘pin & plug’ protect unused cable entries. • Fully compliant with BS 7657:2010 • Designed to ensure secure connection and low contact resistance throughout • Manufactured from glass reinforced polyester • Close-coupled version interfaces with industry standard meter types to prevent theft of supply WT Henley Church Manorway, Belvedere, Erith, Kent DA8 1EX ENGLAND A Division of Sicame UK Limited Telephone: +44 (0) 1322 444500 - Facsimile: +44 (0) 1322 444502 - Email: [email protected] Website: www.sicameuk.co.uk Registered office: Church Manorway, Erith, Kent DA8 1EX United Kingdom - Registration No 3319466 VAT Registration No GB 683822508
2
Embed
WT Henley 54138-12 Single Pole & Neutral House Service Cutouts 100A
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Sharply serrated double entry phase and neutral terminals are suitable for eitheraluminium or copper conductors from2.5mm2 up to 35mm2 and socket headedterminal screws (operated by a customdesigned tool) ensure effective and secureconnections. Fuse-clips are precisiondesigned to ensure low contact resistanceevery time.
All phase terminal screws are held captivewithin the base to make installation assimple as possible.
The market leading Series 7 range, sets the standard forsafety and convenience in House Service Cut-outs.Designed for Combined Neutral and Earth (CNE) systems,rated up to 100A and fully compliant with BS 7657:2010
• Insulated Busbar available forconnecting a second Single Polecut-out / service
Solid link in red carrier 54365-08(used in place of fuse-link)
FuselinksBS HD 60269-3 2010 BS 88-3 2010
16 x 22 x 57mm 16 x 30 x 57mmto suit 60/80A Carrier to suit 100A Carrier
30A 58332-04 30A 58332-30
60A 58333-07 60A 58333-11
80A 58334-08 80A 58334-04
100A 58334-09 100A 58334-06
Isolator
Single Pole and Neutral and Earth 54361-05(fitted with red solid link carrier)
Maximum Cable Sizes
Phase and Neutral (incoming and outgoing) 35mm2
Earth 25mm2
Time switch 10mm2
Note: For single-pole-and-neutral and triple-pole-and-neutral sets, the Cut-outs and protectionchambers are supplied as separate items for on site assembly
All dimensions in mm
UUnnddeerrggrroouunndd DDiissttrriibbuuttiioonn
Fuse Service Equipment
General Note: The equipment in this publication should be installed by a suitably qualified person. Sicame UK Limited reserves theright to make changes in product specification without notice or liability. All information is subject to Sicame UK’s own data and isconsidered accurate at time this document was created.