Top Banner
Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel
13

Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Dec 26, 2015

Download

Documents

Colin Newman
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Wir schaffen Wissen – heute für morgen

Paul Scherrer Institut

4.2.2010

René Künzi

Safety for equipment & personnel

Page 2: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Electrical Equipment at PSI

X

Plant

Device

(PS)

50kV/16kV 16kV/400V Dist.

UV

Local Power Distribution Electrical Installation PSI Plants

Devices

Experiments

Page 3: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Personnel Safety in General (1)

Page 4: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Personnel Safety in General (1)

No contact lenses

Page 5: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Personnel Safety (Cloths 1)

• Working outside of danger area

– No special requirements, but….

– Long pants

– Closed shoes

Page 6: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Personnel Safety (Cloths 2)

• Working inside of danger area (protection through cover)

– Working cloths Safety class EN 61482-1-2 (ENV 50354) class 1

– Closed shoes

– Leather Gloves (recommended)

– Never work alone!

Page 7: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Personnel Safety (Cloths 3)

• Working inside of danger area (protection through distance, LV Fuse ≤ 200A)

– Working cloths Safety class EN 61482-1-2 (ENV 50354) class 1

– Closed shoes

– Leather Gloves

– Helmet with face shield (case by case)

– Never work alone!

Page 8: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Personnel Safety (Cloths 4)

• Working inside of danger area (protection through distance, LV, Fuse ≥ 200A, MV, HV)

– Working cloths Safety class EN 61482-1-2 (ENV 50354) class 1

– Closed shoes

– Safety Gloves

– Helmet with face shield

– Safety coat EN 61482-1-2 (ENV 50354)

– Never work alone!

Page 9: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Overheating protection (1)

• Water cooling is monitored twice– Detection of low water flow in

outlet– Temperature sensor on

heatsink

• Forced Air cooling needs to be monitored– High failure rate of fans– Direct monitoring with switch in the

airflow– Indirect monitoring with temperature

sensors on heatsink

Page 10: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Overheating protection (2)

• Magnetic Devices (chokes, transformers)

Conservative design withmoderate winding temperatures

Fans must be monitored

Page 11: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Protection against accidental contact (1)

All Power Supply racks are locked!

All hot blank parts must be covered

Page 12: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Protection against accidental contact (2)

Page 13: Wir schaffen Wissen – heute für morgen Paul Scherrer Institut 4.2.2010 René Künzi Safety for equipment & personnel.

Protection against accidental contact (3)

• Door Switches– … are usually no safety elements– … unless certified and directly switching (not via PLC)