Winterwarm HR-series The condensing unit air heater which combines efficient heating with energy savings and high comfort. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Characteristics Winterwarm HR: High efficiency (on ECA list) Energysaving (up to 25% compared to conventional heaters) Stainless steel heatexchanger as standard Modulating burner OpenTherm Control
4

Winterwarm HR-Serie, Warmlufterzeuger mit Brennwerttechnik

Jun 12, 2015

Download

Technology

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Winterwarm HR-Serie, Warmlufterzeuger mit Brennwerttechnik

Winterwarm HR-seriesThe condensing unit air heater which combines efficient heating with

energy savings and high comfort.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. . .

. .

Characteristics Winterwarm HR:

• High efficiency (on ECA list)• Energysaving (up to 25% compared to conventional heaters)

• Stainless steel heatexchanger as standard

• Modulating burner• OpenTherm Control

Page 2: Winterwarm HR-Serie, Warmlufterzeuger mit Brennwerttechnik

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

For many years now, suspendedunit air heaters have beenemployed worldwide to heatindustrial buildings. Researchfrom the ‘Gasunie’ (NL) regardingvarious industrial heatingsystems has confirmed thatdirect heated gas-fired air heating is one of the most efficient heating methods.

In general

The Winterwarm HR series (high

system efficiency) combines efficien-

cy, energy savings and total comfort

control through several unique design

characteristics. The OpenTherm con-

trol makes it easy to operate the

heater and realise a comfortable

environment in the room.

Technical features

The HR is a condensing unit air

heater with axial fan. The efficiency

of the heaters is more than 106%.

The premix burner allows the heater

to modulate back to 20% of its

maximum capacity. This implicates

that the heater can very precisely

adjust its heat output to the demand

received through the room thermostat.

Therefore the energy consumption is

as low as possible. As the range of the

HR-series goes up to 150 kW, a lot of

energy can be saved by applying an

HR-heater instead of a conventional

unit air heater. Measurements by the

dutch national gas institute have

proven that these savings can add up

to 25%!

The heat exchanger is made from high

grade stainless steel and has a

guarantee period of 5 years.

Condensation discharge

The HR heaters can realize an output

of 106 %. This high efficiency requi-

res a condensation discharge system

which is located at the bottom of the

heater. For the installation on the

heater unit a siphon is supplied. Any

further required drain pipes are not

supplied. This means that an extra

siphon or gooseneck is required to be

fitted before the sewage.

Suspension

The HR is provided with 4 suspension

points M10 on top of the heater. A set

of solid cantilever brackets can be

ordered along to suspend the heater

from the wall. The heater can be

either suspended from these brackets,

or be placed on top of them. This sus-

pension set consists of 2 U-sections

with 2 supports. For suspension from

the ceiling threaded bar M10 can be

used.

F

CD

H

J

K

øM

Gas

F

P

N

R

S

4xM10

T

U

Measurements

A B C D F G Gas H J K M N P R S T U

40 910 825 770 150 180 110 3/4” 560 470 120 80 137 250 115 190 100 295

60 1155 825 770 150 180 110 3/4” 560 715 140 100 137 240 115 190 100 295

80 1340 825 770 150 180 110 1” 560 890 140 100 137 240 115 190 100 295

100 1630 825 770 150 180 110 1” 560 1180 140 100 137 240 115 190 100 295

150 1890 1000 1000 180 190 175 1” 850 1425 225 130 165 235 140 170 75 295

A

B

G

Page 3: Winterwarm HR-Serie, Warmlufterzeuger mit Brennwerttechnik

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Flue terminal

The installation of the combustion air

supply and the combustion gas

discharge must meet the general

prescriptions for high efficiency flue

terminals. Winterwarm has a complete

range of stainless steel flue terminals

and extra lenghts/bends available.

As the HR is provided with a flue

booster one can apply either a

horizontal (wall) or a vertical (roof)

flue terminal. The length of the flue

should not exceed 10 m taking into

account that each 45˚ elbow counts as

1 m length and each 90˚ elbow counts

as 2 m length. The dimensions of the

flue is 80, 100 or 130 depending on

the type of heater.

Controls

The HR heaters are provided with a

OpenTherm protocol, controled by an

OpenTherm clock thermostat. This is

a low voltage clock thermostat which

is programmable per day and can con-

trol 1 heater. Also it is provided with

frost protection, summer ventilation

position and a reset function.

If desired, a remote sensor can be

attached so that the control can

be placed elsewhere.

Open Therm Thermostat

A B d D HOH

40 1290 660 80 125 120

60 1170 590 100 150 140

80 1170 590 100 150 140

100 1170 590 100 150 140

150 1345 928 130 200 230

A B d D HOH

40 560 250 80 125 120

60 900 400 100 150 140

80 900 400 100 150 140

100 900 400 100 150 140

150 930 400 130 180 265

Roof terminal Wall terminal

Page 4: Winterwarm HR-Serie, Warmlufterzeuger mit Brennwerttechnik

Winterwarm: leadingWinterwarm has been engaged in the development, production and sales of industrial heating in Europe since 1936.

The company not only specialises in indirect fired unit air heaters, but also sells radiant tubes, rooftops,

water heaters, destratification fans and direct fired heaters for the agricultural and horticultural industry.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Famous Winterwarm quality

• 70 years of experience• ISO 9001-2000 certified• Quick delivery• Reliable

Winterwarm BVIndustrieweg 8 Winterswijk The NetherlandsP.O.Box 36 NL-7100 AA Winterswijk The NetherlandsTel. +31 (0)543 54 63 00 Fax +31 (0)543 54 63 10www.winterwarm.nl [email protected]

Winterwarm UK Ltd. Unit H3, Taylor Business Park, Warrington Road, Risley, Warrington, Cheshire WA3 6BLTel. +44 (0)870 90 89 906 Fax +44 (0)192 57 62 996 www.winterwarmuk.com [email protected]

Technical data

Type Unit HR 40 HR 60 HR 80 HR 100 HR 150

Nominal heat input (Hs.) kW 44.4 66.7 88.8 114.4 166.7

Nominal heat input (Hi.) kW 40 60 80 103 150

Efficiency max. heat input 100% % 94.8 94.2 94.3 94.2 94.8

Efficiency partial heat output 30% % 105.7 105.8 105.8 105.6 104.9

Nominal heat output kW 37.9 56.5 75.4 97 142.2

Gas consumption G20 (hi/low) m3/h 4.18-0.88 6.22-1.34 8.16-2.25 10.67-2.94 15.3-3.37

Nominal gas supply pressure mbar 20 20 20 20 20

Gas consumption G31 kg/h 3.17-0.64 4.72-1.04 6.22-1.72 8.03-2.29 11.69-2.57

Nominal gas supply pressure mbar 37/50 37/50 37/50 37/50 37/50

Gas connection G” 3/4” 3/4” 3/4” 3/4” 3/4”

Dimensions flue terminal ø 80 100 100 100 100

Electrical connection V/Hz 230/50 230/50 230/50 230/50 230/50

Electrical consumption W 300 400 650 750 1400

Air flow rate m3/h 5000 6500 10000 12500 18500

Temperature increase T 22.8 26.3 22.8 23.5 23.1

Throw horizontal (max.-min.) m 26-36 26-36 32-46 36-50 48-68

Sound level* dB(A) 48 51 52 52 58

Minimum suspension height m 1.7 1.7 1.7 1.7 1.7

Weight kg 95 111 136 155 230

* measured 5m. in front of heater