Page 1: Welcome! A trade association wholly supported by members. .

Welcome!

A trade association wholly supported by members.

www.nfsa.org

Page 2: Welcome! A trade association wholly supported by members. .

National Fire Sprinkler Assn

Rhode Island Nightclub Tragedy “Lessons Learned”

Presented by: Dominick G. Kass CFPS

Northeast Regional Manager© Copyright NFSA 2003

Page 3: Welcome! A trade association wholly supported by members. .

National Fire Sprinkler Association National Fire Sprinkler Association (The “(The “NFSA”NFSA”))•Construction Trade AssociationConstruction Trade Association

–Engineering ServicesEngineering Services

–Training and EducationTraining and Education

–Labor RelationsLabor Relations

–Promoting the concept of sprinkler system installationPromoting the concept of sprinkler system installation

•ManufacturersManufacturers

•SuppliersSuppliers

•ContractorsContractors

•Professional (Architects, Engineers)Professional (Architects, Engineers)

•Subscribers (Code Officials, Insurance)Subscribers (Code Officials, Insurance)

Page 4: Welcome! A trade association wholly supported by members. .

What We’ll Look At

What doesn’t (or didn’t) work

Aspects of the “Station Fire”

What does work

Page 5: Welcome! A trade association wholly supported by members. .

What Didn’t Work

The Tragedy

Page 6: Welcome! A trade association wholly supported by members. .
Page 7: Welcome! A trade association wholly supported by members. .

RI Nightclub Fire “The Station” 20 Feb 03

To date, 100 people have perishedPyrotechnics display at a rock concert

Code changesDeadliest fire in Rhode Island's historyNation's worst nightclub fire in 25 yrs.

Page 8: Welcome! A trade association wholly supported by members. .

The Station Nightclub

Constructed in 1950.

An addition was built in 1975.

Town records indicate 4,484 ft2 of rentable space

Total of 6,278 ft2

Value was assessed at $268,400.

Page 9: Welcome! A trade association wholly supported by members. .

The Station Nightclub

Total of four exits;Main entrance facing North to the street1 Northwest portion by the bar 1 located exiting the kitchen1 located Northeast by the Stage.

Page 10: Welcome! A trade association wholly supported by members. .
Page 11: Welcome! A trade association wholly supported by members. .

The Station Nightclub

“Total of four exits”Human nature:

Attempt egress at original entry point,

Main entrance facing North to the street:

handled 80% to 90% of occupants attempting to exit.

Page 12: Welcome! A trade association wholly supported by members. .

Contributing Factors

Unfamiliar with other exits and paths

Darkness

No suppression, automatic or manual

Delayed alert to occupants

These are all typical and identifiable factors

Page 13: Welcome! A trade association wholly supported by members. .

“The Station” Staff

Reported:

Stage exit was blocked by staff;

“for band members only”.

Bar exit used by only a few.

Page 14: Welcome! A trade association wholly supported by members. .

“Great White” Performing at the Station Nightclub

Pyrotechnics were running at the upper leftPyrotechnics were running at the upper left

Page 15: Welcome! A trade association wholly supported by members. .

Simulation and Test Conducted

NFSA member and N.E. R.M. conducted a simulation of the nightclub using similar foam to show the effectiveness of fire sprinklers in an A-2 Occupancy.

3-inch thick uncovered polyether (pure polypropylene oxidepolyol) foam cushions having a density of 1 to 1.25 pounds per cubic foot measuring 36 by 40 inches.

Page 16: Welcome! A trade association wholly supported by members. .

R.I. Fire Simulation

Page 17: Welcome! A trade association wholly supported by members. .

NIST Report

Fire Model

Page 18: Welcome! A trade association wholly supported by members. .

The StationThe Station

Page 19: Welcome! A trade association wholly supported by members. .

Without Sprinklers

Five Foot Level

Page 20: Welcome! A trade association wholly supported by members. .

Without Sprinklers

Page 21: Welcome! A trade association wholly supported by members. .

With Sprinklers

Five Foot Level

Page 22: Welcome! A trade association wholly supported by members. .

With Sprinklers

Page 23: Welcome! A trade association wholly supported by members. .

Unfortunately, History Repeats Itself:

Some of the deadliest U.S. fires in clubs and dance halls:

-491 dead, Cocoanut Grove club, Boston, Nov. 28, 1942. Cause unknown.

-198 dead, Rhythm Night Club dance hall in Natchez, Miss., April 23, 1940. Cause unknown.

Page 24: Welcome! A trade association wholly supported by members. .

Unfortunately, History Repeats Itself:

Some of the deadliest U.S. fires in clubs and dance halls:

-164 dead, Beverly Hills Supper Club in Southgate, Ky., May 28, 1977. Defective wiring.

-87 dead, Happy Land Social Club in The Bronx, New York, March 25, 1990. Arson.

Page 25: Welcome! A trade association wholly supported by members. .

Unfortunately History repeats itself!!

-40 dead, dance hall in West Plains, Mo., April 13, 1928 (explosion). Cause unknown.

-32 dead, Upstairs Bar in New Orleans, June 24, 1973. Cause unknown.

Page 26: Welcome! A trade association wholly supported by members. .

Unfortunately History repeats itself!!

-25 dead, an ethnic Social Club, Bronx, New York, Oct. 24, 1976. Arson.

-24 dead, Gulliver's Discotheque, Port Chester, N.Y., June 30, 1974. Arson fire in nearby bowling alley spread to disco.

Page 27: Welcome! A trade association wholly supported by members. .

What lessens have we learned?

There would have been a major impact on the outcome had the building been fully protected by an automatic Fire Sprinkler system.

We must look at the current Fire and Building Codes being used in all states and determine if the occupancy load thresholds are too high.

Page 28: Welcome! A trade association wholly supported by members. .

What lessens have we learned?Overdue to examine the triggers in which an

automatic fire sprinkler system would be installed such as the square footage, occupancy load, occupancy uses.

Education of architects, engineers, and designers in fire sprinkler “Trade-Ups” available in model building codes.

Page 29: Welcome! A trade association wholly supported by members. .

The obvious…?

NIST- All Places of Assembly should be protected by an automatic sprinkler system regardless of square footage or occupant load.

“Fire cannot read building codes!”

Page 30: Welcome! A trade association wholly supported by members. .

Code Development

Consensus Code Process

Process is a form of negotiating. (Everyone comes out of process giving up something.)

AHJs should remember that codes are “minimal” codes. (But let’s not go nuts here.)

Min/Max state codes tie the hands of local control.

Page 31: Welcome! A trade association wholly supported by members. .

BCNYS/FCNYS

A-2 Nightclub- 903.2.1.2- An automatic Sprinkler System shall be provided for group A-2 occupancies where (1) of the following conditions exist:

1. The fire area exceeds 5,000 Square Feet (464.5 M).

2. The fire area has an occupant load of 100 or more.

3. The fire area is located on a floor other than the level of exit discharge.

Page 32: Welcome! A trade association wholly supported by members. .

Imagine…your day starts out as any typical work day…

“My name is Raymond Mattera. The last time I kissed and hugged my beautiful daughter Tammy, she was in a black body bag. Tammy was 29 years old…..”

Page 33: Welcome! A trade association wholly supported by members. .

...and what did work…

Page 34: Welcome! A trade association wholly supported by members. .

“Fine Line” Night club

7 Fire Sprinklers activated,

2 over fire, 5 “down wind” due to front door left open after egress,

Fire sprinklers were approx 18 inches below ceiling level, why?

Drop ceiling removed months before when new tenant moved in.

Page 35: Welcome! A trade association wholly supported by members. .

“Fine Line” Night club results?

Minimal loss (considering)

No injuries

NO FATALATIES!!!

Page 36: Welcome! A trade association wholly supported by members. .

“Fine Line” Staff

Trained in evacuation

Pointed patrons to exit

Trained in fire extinguishers

Checked to make sure everyone was out.

Occupancy has fire sprinklers throughout!

Page 37: Welcome! A trade association wholly supported by members. .

OverviewIf Codes and general fire safety procedures are unknown, misunderstood or not enforced? Potential…

Trauma (physical and mental)

Fatalities

High Dollar Losses

Vacant buildings

Degradation of neighborhoods

Crime rate increase

Law suits

Page 38: Welcome! A trade association wholly supported by members. .

NFPA

ROP Meetings for 2006 edition

Definition of “bars” modified to include “bars with live entertainment”.

Page 39: Welcome! A trade association wholly supported by members. .

Fire ModelingStudy prepared for NFPA 101 meeting.

Modeling included many factors-

Fire growth, obstructions, speed of occupants, turning rate, smoke layer, 140º F.

Study done for 5,000 sq ft building

Before untenable at 6 ft. above floor

150 people could escape with one 32” exit

300 people- 2 exits

Under the modeled conditions.

Page 40: Welcome! A trade association wholly supported by members. .

Code Updates

NFPA 101

Fire Sprinklers in Assembly Occupancies

New- 50 or more occupants

Existing- 100 or more

Egress issues and egress inspections

Crowd management

Page 41: Welcome! A trade association wholly supported by members. .

NFPA 5000

New Assembly Occupancies- Festival seating changes identical to NFPA 101.

Supervised Automatic Fire Sprinklers

16.3.5.1.1

Page 42: Welcome! A trade association wholly supported by members. .

NFPA 1/UFC

Fire Sprinklers

13.3.2.4.1 New Assembly Occupancies

13.3.2.5.1 Existing

Page 43: Welcome! A trade association wholly supported by members. .

ICC

Group A-2 Fire Sprinkler requirements changed from 300 to 100 occupants.

Proposal to fire sprinkler all existing A-2 was denied.

Multiple proposals to fire sprinkler other occupancies denied, to include Educational.

Page 44: Welcome! A trade association wholly supported by members. .

Changes to State Legislation

Rhode Island

Assy Occup- 100 or more: Sprinkler Retro

Eff. 01 Oct 2004- Employee Training

Massachusetts

Legislation signed 17 Aug 2004

Assy Occup, 100 or more: Sprinkler Retro

Employee Training to start in 2005

Change to Massachusetts Tax Code!!!

Page 45: Welcome! A trade association wholly supported by members. .

Employee TrainingCrowd count- prevent overcrowding

Exits marked and clear

Open flame use (permits, firewatch)

Fire extinguishers

Panic control/egress routes

Area assignments- evac restrooms, etc.

Decorations- only tested flame resistive materials

Page 46: Welcome! A trade association wholly supported by members. .

Changes to State Legislation

New York State?

Was ahead of the game in 2003:

NYSBC Section 903.2.1.2 A-2 Occupancies

Must have fire sprinklers if:

5,000 ft2

Load of 100 occupants or more (A-1,2,3,4)

NYSFC Section 404 Fire Safety & Evac Plans

NYSFC Section 406 Employee Training & Response Procedures

Page 47: Welcome! A trade association wholly supported by members. .

The “3 E”s

Education

Engineering

Enforcement

Consider a 4th-

Evaluation

Page 48: Welcome! A trade association wholly supported by members. .

What’s the answer?

Ya can’t fix “stupid”!

But we can address the results of “stupid”.

Page 49: Welcome! A trade association wholly supported by members. .

Federal Legislation

HR 1131 / SB 512

Fire Sprinkler Incentive Act of 2005

Page 50: Welcome! A trade association wholly supported by members. .
Page 51: Welcome! A trade association wholly supported by members. .

Contact Info

Office (518) 373-9392

Fax (518) 383-3950

[email protected]

www.NFSA.org

Page 52: Welcome! A trade association wholly supported by members. .

“60 Minutes II” investigates…