WATER SUPPLY AND DRAINAGE IN BUILDINGAbstract
Research on air and water flows in water supply and drainage systems for
buildings has led to a greater understanding of the aspects of design which
contribute to both enhanced public health and pragmatic water conservation
strategies. The study of airflows and the inevitable air pressure transients
generated by naturally occurring phenomena within building drainage systems,
has led to the development of unique surge alleviation devices in order toprotect fixture water trap seals, the main protection between the public sewer
and habitable space. This focus on pressure transient analysis has also
contributed to the development of a sonar like device for assessing the status
of water trap seals and curtailing the possibilities of infection spread via the
building drainage system. While these phenomena affect the safety of peoplefrom sewer borne pathogens, the supply of water still represents a significant
cost and challenge to supply authorities. The contribution of fixtures such as
WCs, baths and showers represent significant usage of potable water delivered
to a building; in the UK, WCs use 1/3 of the total potable water processed.
Numerical modelling of flows has assisted in formulating strategies for good
design practice, and is conducive to whole system modelling to ensure publichealth safety and water supply security is maintained, economically and
efficiently.
CONTENTS
7/27/2019 Water supply and Drainage in Building
2/21
Introduction Water distribution system in building Methods of distribution Drainage system Installation of drains The requirements of a well designed system Venting Maintenance of house drainage system Conclusion Reference
Introduction
7/27/2019 Water supply and Drainage in Building
3/21
Public water supply systems follow the sequence of
collection, conveyance, treatment, disinfection and distribution. Ultimately
water is distributed for various consumption purposes in a building through
internal water distribution.
The waste water is collected from the buildings and
taken to a treatment plant for treatment and disposal. In this seminar, only the
internal water supply and buildingdrainage are discussed.
The water distribution system in a building terminates at
various plumbing fixtures designed to receive water and discharge wastes. The
drainage system in buildings should not cause a nuisance or any hazard to
health.
Water distribution system in building
The layout of water distribution piping may be basicallya horizontal or vertical arrangement of limited height in which underground
7/27/2019 Water supply and Drainage in Building
4/21
mains under pressure supply water to a fixture inlets. Systems, with piping
above the main or pressure tank, are called up feed systems.
Systems from public mains are supplied through a
service main. This starts at a top on the street mains known as a lateral. The sizeof laterals varies from 10 to 22.5 cm. a water meter is connected to the service
main. Service pipes are subjected to expansion and contraction and minor earth
movement. Hence service mains should be connected through a gooseneck or
expansion loop to avoid strain on joints.
Inside a building at the service valve, the building main
extends to each fixture ground in single storey buildings or to the foot of each
up feed riser in taller buildings. The service pipe may supply an up feed system
for as greater a height as the available pressure allows. In addition, it supplies a
sump from which pumps can draw for the elevated house tanks. A house tank
serves down feed risers to a number of flows. The washer and other valves with
stand pressures up to about 5 kg/ cm2 hence, the static head should be restricted
to 50 m of water. Thus, about 15 floors is the maximum height for a down feed
some
7/27/2019 Water supply and Drainage in Building
5/21
7/27/2019 Water supply and Drainage in Building
6/21
7/27/2019 Water supply and Drainage in Building
7/21
METHODS OF DISTRIBUTION
Depending up onthe topography of the country any one ofthe following three methods may be adopted for the distribution of water
1) gravity system2) gravity and pumping system combined3)pumping system4)
Gravity systemIn this system the water is conveyed through pipes by
gravity only. The gravity system is the most reliable method of distribution. But
it is useful only when the source of water supply is situated at a higher level
than that of distribution area.
Gravity and pumping system combined
In this system the treated water is pumped and stored inan elevated distribution reservoir. The excess water during low consumption
remains in the elevated reservoir and it is supplied during the peak period. Thepumps are usually worked at constant rate and this rate of pumping is so
adjusted that the excess quantity of water stored in reservoir during low
consumption is nearly equal to the extra demand of eater during peak period.
Advantages In case of a fire, the motor pumps can be used to develop high pressure or
a fire demand can directly be satisfied from pump house after closing the
inlet valve for elevated reservoir. In this method, the pumps are generally worked at uniform rate. This method is economical. This method is fairly reliable in the sense that some quantity of water is
available from the elevated reservoir even during break down of pumps.
Pumping system
7/27/2019 Water supply and Drainage in Building
8/21
In this system, the water is directly pumped in to the
mains leading to the consumers. The number of pumps required in this system
will depend on the demand of water.
Disadvantages
In case of power failure the entire water distribution system of locality isdisturbed.
It requires constant attendance because of the fact that the pumps are tobe kept in working conditions all the time and sudden failure of pumps
would lead to great hardship.
DRAINAGE
Drainage means the entire system of sewers, plant and
associated machinery, which is owned by or vested in a local authority, and
used for conveyance and treatment of sewage, the reclamation of water and the
disposal of effluents or by-products resulting from the treatment of sewage.
ANTI SIPHONAGE PIPE: A pipe which is installed in the housedrainage to preserve the water seal of traps is known as anti siphonage pipe. It
maintains proper ventilation and does not allow the siphonic action to take
place.
CONSERVACY TANK: means any covered tank without overflow whichis used for the reception and temporary retention of sewage and which requiresemptying at intervals.
INSPECTION CHAMBER: means a chamber not deeper than 750 mmand of such dimensions that access may be obtained to a drain without causing a
person to enter into such chamber for the purpose of inspection.
7/27/2019 Water supply and Drainage in Building
9/21
MAINHOLE: means a chamber of depth greater than 750 mm which allowsaccess to a drain.
ONE-PIPE SYSTEM: means a system of piping between sanitary fixturesand a drain in which both waste and soil water are permitted to flow down acommon stack.
RELIEF VENT: means a vent or ventilating pipe branching from a stackbelow the point of connection there to the lowest branch connection.
SANITARY FIXTURE: means that part of a drainage system which ispermanently connected to a water supply and which is used for the reception
and discharge of waste water.
SEPTIC TANK: means a tank designed to receive sewage and to retain it forsuch a time and in such a manner as to secure adequate decomposition of
organic solids by bacterial action.
SINGLE-STACK SYSTEM: means a system of piping between sanitaryfixtures and a drain, in which both waste and soil water are permitted to flowdown a common stack, and in which the stack and discharge pipes serve also as
vent pipes.
SINGLE-STACK (MODIFIED) SYSTEM: means a single stacksystem in which a relief vent is provided appurtenant to the discharge stack and
connected therewith below the lowest branch connection and at least at every
alternate floor by a cross vent.
SOIL PIPE: The term soil pipe is used to indicate the pipe which carriesdischarge from soil fittings such as urinals, water closets, etc. it should be ofgood materials and workmanship. The soil pips are kept of uniform diameter
and when they are carried above roof level, they will work as vent pipes also.
7/27/2019 Water supply and Drainage in Building
10/21
STACK: means the main vertical discharge pipe or ventilating pipe connectedto a drainage system.
STORM WATER DRAIN: means a pipe or surface channel, which issituated on a site and is used to convey storm water to a sewer or a point of
discharge acceptable to the local authority.
TRAPPED GULLY: means a drain fitting, incorporating a trap into whichwaste water is discharged.
TWO PIPE SYSTEM: means a system of piping between sanitary fixturesand a drain, in which separate stacks are used for waste water and soil water and
each stack is vented and all traps are vented.
VERTICAL: in reference to a discharge pipe means any such pipe inclined at45 degrees or more to the horizontal.
WASTE FIXTURE: means any sanitary fixture which is used for thereception and discharge of waste water, and includes baths, drinking fountains,showers, baths, sinks, wash basins or wash tubs.
COWL: The top of vent pipes is provided with cowls. These are provided withslits or narrow openings.
FRESH AIR INLET: The last man hole which connects the house drainwith the public sewer is provided with an inlet of fresh air. This fresh air inletdilutes the sewage gasses.
VENT PIPE: The pipe installed for the purpose of ventilation is known as thevent pipe. It should be open at top and bottom and such openings should be at
suitable levels for the flow of foul gases. it is generally placed in the chamber or
7/27/2019 Water supply and Drainage in Building
11/21
manhole from which sewage starts its flow sand it is carried at least about one
meter higher than the roof level.
WASTE PIPE: The term waste pipe is used to indicate the pipe which carriesdischarges from sanitary fittings such as bath rooms, kitchens, sinks, etc
TRAPS: A trap is a depressed or bent sanitary fitting which always remainsfull of water. It is technically termed to contain the water seal which is
measured as the vertical distance between crown and dip of a trap.
Function
The function of a trap in a drainage system is to prevent the
passage of foul air or gases through it. But at the same time it allows the sewageto flow through it thus the installation of a trap avoids the nuisance which will
be developed due to entry of bad smelling gasses in to the house.
Requirement of a good trap
1. It should be capable of being easily cleaned.2. It should be easily fixed with the drain.3. It should be of simple construction.4. It should possess self-cleansing property.5. The internal and external surfaces should be of smooth finish.
RAIN WATER PIPES
Down pipes should be discharged into channels, onto
concrete slabs or into pipes; where they are discharged into pipes, they should
be connected direct to the pipe and not through a catch pit.
7/27/2019 Water supply and Drainage in Building
12/21
7/27/2019 Water supply and Drainage in Building
13/21
MATERIAL AND GRADIENTS
The following material should be used for the different pipes:
A.Underground drain pipes-vetrified clay pipes (VCP) except beneathbuildings where they are of cast iron. PVC, glass fibre or other types
or pipe may only be used with approved
B. Surface pipes:
1. Soil stacks and vent pipes - cast iron pipe (CIP) or PVC.
2. Waste pipes - cast iron or galvanized mild steel pipes (GMSP) or
PVC.
3. Anti siphon pipes - galvanized mild steel pipes or PVC.
INSTALLATION OF DRAINS
Drainage Installation means an installation vested in the
owner of a site which is situated on such site and which is intended forthe reception, conveyance, storage or treatment of sewage and includes
sanitary fixtures, traps, discharge piped, drains, ventilating pipes, septic
tanks, conservancy tanks, sewage treatment works, or mechanical
appliances associated therewith.
Drain means that part of a drainage installation which
conveys the sewage from a building to a connecting sewer or to a common drain
or to any other means of sewage disposed on the site concerned, but shall not
include
A. any discharge pipe;
B. that portion of a discharge stack which is below ground level; or
C. the bend at the foot of a discharge stack, whether such bend is exposed
or not.
Where any drain is constructed adjacent to or under or through a
structural part of any building, adequate measures must be taken to ensure that
the trench in which such drain is laid in no way impairs the stability of suchbuilding or the stability of any other building or interferes with or affects any
existing services.
A.Any drain shall be of such strength, having regard to the manner in whichit is bedded or supported, so that the maximum loads and forces to which
7/27/2019 Water supply and Drainage in Building
14/21
it may normally be subjected will be sustained by it and it shall where
necessary be protected against damage.
B.The requirements contained in paragraph shall be deemed to be satisfiedif either of the following is complied with:
(i)The minimum cover over the outside of the drain is not less than 300
mm or
(ii) Precast or cast-in-situ concrete slabs are placed over the drain,
isolated from the crown of the pipe by a soil cushion not less than 100
mm thick and such slabs are wide enough and strong enough to prevent
excessive superimposed loads being transferred directly to the pipes.
Any drain shall;-
A. Be laid in a straight line between any points where changes of
direction or gradients occur.
B. Be laid with approved flexible joints which will permit joint
movement to take place throughout the life of the drainage installation.
C. Withstand root penetration and not deteriorate when in contact with
sewage or water, and will not cause any obstruction in the interior of such
drain.
D. Be laid at a minimum gradient of 1:60 for 100 and 1:100 for 150
pipes. However the Project Manager may in his discretion permit
gradients less than those specified above.
E. Where the gradient exceeds 1:5 it must be provided with anchor blocks
which must securely fix such drain in place.
Where any portion of a drain passes under any building such portion shall:
A .Be of Cast Iron
B. Be laid without change of direction or gradient.C. Not be provided inside such building with any means of access forcleaning.
Where any portion of a drain passed through a building such portion shall be:
A. Cast Iron
B. Supported throughout its length without restricting thermal movement
and such support must be securely attached to the building.
C. So placed that any junction, bend or any point of access into it isreadily accessible.
7/27/2019 Water supply and Drainage in Building
15/21
Where any drain has a branch drain connected to it, such connection shall:-
A. be by means of a junction fitting which shall not be a saddle junction.
B. Enable the flow from such branch drain to enter the drain obliquely inthe direction of flow so that the included angle between the axes of thetwo drains does not exceed 45.
Where drains are to be laid in heaving, unstable or filled in ground, the Project
Manager must be consulted.
PIPES BENEATH BUILDINGS
Where it is necessary for a drain to pass beneath a building it
must be of cast iron and be without change of direction or gradient. It must not
carry any imposed load and provisions should be made for relieving arches onother supports where drains pass beneath the walls.
MINIMUM DEPTH OF DRAIN PIPES
To protect drains with a covering of less than 300mm they
must be encased in concrete.
7/27/2019 Water supply and Drainage in Building
16/21
SEPTIC AND CONSERVANCY TANKS
Where sewage disposal is by means of septic tanks or
conservancy tanks, type drawing of the tanks may be obtained from the ProjectManager. The sizes of the septic tanks are based on the number of contributors
to the tanks and these sizes are shown on the type drawings Septic and
conservancy tanks must be located at least 3m from any building. French drains,
soakage pits or agricultural drains at least 5m from any building. Care should be
taken that underground water supplies are not polluted; where effluent flows
away from any underground water supply the distance should be at least 50m. Ifeffluent flows towards an underground water supply, the distance should be
considerably greater and will depend on such conditions as depth of water
supply, water table and soil or rock formations.
GROUPING
Where possible all toilet facilities should be grouped in abuilding, both horizontally and vertically and low outlet fittings such as baths
and showers should be placed as close as possible to outside or duct walls, to
facilitate drainage.
POSITIONING
WC's and urinals must be placed against outside or duct walls
or in the case of urinals, the drainage points may end against such walls. Urinals
must be adequately screened from passages, windows etc. A wash-hand basin
must be available at all WC's. Walls must be of one brick thickness where morethan 3 wash hand basins or bowl urinals are to be hung and also where the wall
holding any of these fittings is longer than 3m
7/27/2019 Water supply and Drainage in Building
17/21
The requirements of a well designed system
Put simply, the main requirement of a well designed system
is that it should operate without the user being aware of its existence. However,this is a tall order and there is therefore a need to more fully specify some
requirements which can lead to the invisible system. The following
requirements are essential in achieving a safe, usable and reliable drainage
system;
The system should remove all waste as quickly as possible
Long horizontal pipe runs must be self-cleansing
There must be minimal loss of water trap seal to ensure there is a barrier
for the ingress of sewer gasesOther requirements which are less critical are
Minimal noise from the system
Minimal Odor from the appliance side (WC design)
Ease of maintenance
Code regulations were essentially designed in order to
ensure that installations meet these requirements, and to protect inhabitants
against any possible health risks from contact withcontaminated fecal material.
In developed industrialized countries the majority of installations meet thesestandards and the health risks from drainage systems are still very low. As with
most fields of engineering, sanitary equipment and techniques have benefited
from scientific and engineering research which has improved understanding of
system operation and helped develop new innovate and cost-effective ways of
achieving the goal of safe, reliable drainage systems with no increase in healthrisk.
7/27/2019 Water supply and Drainage in Building
18/21
Venting
Usually vent piping is installed to accommodate air flow only. Sometimes largepipes are used as fixture branches and vents. A pipe which functions in this
manner is called a wet vent
Whenever fixtures from more than one floor drain in to a
single soil or waste stack, vents from the fixtures must connect to a vent stack
installed next to the soil or waste stack. It must terminate through the roof or be
connected to the vent extension at the top of the soil or waste stack its base must
connect to the base of the soil or waste stack
Vent terminals through the roof should be three meter away
from windows or other openings and must be 1.5 m above occupied roof decks.
Otherwise vent terminals should be 60 cm above openings or at least 15cm
above a roof. Venting or horizontal drain lines require a vertical connection of a
vent pipe more than 450 from the vertical. The size of vents and vent stacks
depends on the size of the line vented, the fixture unit load, and the developed
length of the vent. No vent can be smaller than 3.1 cm and it can be less than
one - half the diameter of the pipe vented.
7/27/2019 Water supply and Drainage in Building
19/21
MAINTENANCE OF HOUSE DRAINARE SYSTEMThe house drainage system should be properly maintained and cleaned at
regular intervals for its efficient working.
1. Entry of undesired element.The users of house drainage system should take extreme precautions to
avoid the entry of undesired in the system. Such substances include grit,
sand, decayed fruits, prices of cloth, leaves, etc.
2.
Flushing.In order to maintain the house drainage system in proper working order, it
is advisable to flush it once or twice in a day.
3. Inspection.The various units of house drainage system should be inspected at regular
intervals and the obstructions, if any, should be removed. Similarly the
damaged pipes should be replaced.
4. Quality of materials.The materials used in the house drainage system should be of betterquality.
5. Use of disinfectants.To maintain good sanitary condition in the building, the disinfectants
should be freely used in lavatory blocks, bath rooms, etc.
6. Workmanship.The laying of drains and fixing of pipes should be carried out by licensed
or authorized plumbers only in systematic way.
7/27/2019 Water supply and Drainage in Building
20/21
Conclusions
This report has considered the implications for venting
in building drainage systems. The discussion has concentrated on the
fundamental fluid mechanics which so readily describe the unsteady flows
resulting from plumbing fixture discharges. The description of the workings of a
drainage and vent system in these terms is not new, many early innovators were
well aware of this, however, many codes and regulation worldwide seem to
avoid the engineering imperative of a description based on fluid mechanics in
favor of a prescriptive legalistic approach based on the evolution of the industry
rather than the science. The fundamentals of system friction and pressuretransient generation and propagation are central to understanding why ventingis required in the first place. Possible solutions for alleviating pressure transients
were discussed, including the well respected view that in certain circumstances
systems operate perfectly well without venting.
In each vertical waste water pipe longer than 3,5m A vent pipe the same
size as the drain pipe which it ventilates must be provided.
The various units of house drainage system should be inspected atregular intervals and the obstructions, if any, should be removed.
Similarly the damaged pipes should be replaced. The materials used in
the house drainage system should be of better quality.