Washington State Ventilation and Indoor Air Quality Code

Feb 27, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Washington State Ventilation and Indoor Air Quality Code
Page 2: Washington State Ventilation and Indoor Air Quality Code

Page 3: Washington State Ventilation and Indoor Air Quality Code

Page 4: Washington State Ventilation and Indoor Air Quality Code

Page 5: Washington State Ventilation and Indoor Air Quality Code

Page 6: Washington State Ventilation and Indoor Air Quality Code
Page 8: Washington State Ventilation and Indoor Air Quality Code

8

Page 9: Washington State Ventilation and Indoor Air Quality Code
Page 10: Washington State Ventilation and Indoor Air Quality Code

400 F

100 %

RH

Page 11: Washington State Ventilation and Indoor Air Quality Code

40 0F

Page 12: Washington State Ventilation and Indoor Air Quality Code

40 0F

Page 13: Washington State Ventilation and Indoor Air Quality Code

400F

Page 14: Washington State Ventilation and Indoor Air Quality Code

? R H %

40 0F 75 0F

100 %

RH

Page 15: Washington State Ventilation and Indoor Air Quality Code

30 %

R H

40 0F 75 0F

100 %

RH

Page 16: Washington State Ventilation and Indoor Air Quality Code

DEW

POINT

COLD

OUTSIDE

Page 17: Washington State Ventilation and Indoor Air Quality Code

Areas of High RH

COLD

OUTSIDE

Buildings have micro-climates

Page 18: Washington State Ventilation and Indoor Air Quality Code
Page 19: Washington State Ventilation and Indoor Air Quality Code

Page 20: Washington State Ventilation and Indoor Air Quality Code

Page 21: Washington State Ventilation and Indoor Air Quality Code

Page 22: Washington State Ventilation and Indoor Air Quality Code

Page 23: Washington State Ventilation and Indoor Air Quality Code

Page 24: Washington State Ventilation and Indoor Air Quality Code

www.hvi.org

Page 25: Washington State Ventilation and Indoor Air Quality Code

Page 26: Washington State Ventilation and Indoor Air Quality Code

Fan Tested

CFM @ 0.25”

W.G.

Minimum

Flex

Diameter

Maximum

Length Feet

Minimum

Smooth

Diameter

Maximum

Length Feet

Maximum

Elbows1

50 4 inch 25 4 inch 70 3

50 5 inch 90 5 inch 100 3

50 6 inch No Limit 6 inch No Limit 3

80 4 inch2 NA 4 inch 20 3

80 5 inch 15 5 inch 100 3

80 6 inch 90 6 inch No Limit 3

100 5 inch2 NA 5 inch 50 3

100 6 inch 45 6 inch No Limit 3

125 6 inch 15 6 inch No Limit 3

125 7 inch 70 7 inch No Limit 3

Page 27: Washington State Ventilation and Indoor Air Quality Code
Page 28: Washington State Ventilation and Indoor Air Quality Code
Page 29: Washington State Ventilation and Indoor Air Quality Code
Page 30: Washington State Ventilation and Indoor Air Quality Code

Page 31: Washington State Ventilation and Indoor Air Quality Code

House Size Bedrooms

0-1 2-3 4-5 6-7 >7

<1500 30 45 60 75 90

1501-3000 45 60 75 90 105

3001-4500 60 75 90 105 120

4501-6000 75 90 105 120 135

6001-7500 90 105 120 135 150

>7500 105 120 135 150 165

Page 32: Washington State Ventilation and Indoor Air Quality Code

Page 33: Washington State Ventilation and Indoor Air Quality Code

Page 34: Washington State Ventilation and Indoor Air Quality Code

1,501 – 3,000sf 2-3 bedroom home located in Olympia Wa

System

Type

Flow

Rate

Time of

Operation

Fan

Watts

Fan

$1

Heating

Fuel

Heating

System

Efficiency

Heating

$1

Annual

Operation

$1

Exhaust 60 24hr/day 12 $8.94 NG 80 AFUE $111.97 $120.90

Exhaust 60 24hr/day 12 $8.94 Elec 10.2 HSPF $67.87 $76.80

Inline

Exhaust 180 3hrs. 3X/day 51 $14.24 NG 80 AFUE $125.96 $140.20

Inline

Exhaust 180 3hrs. 3X/day 51 $14.24 Elec 10.2 HSPF $76.35 $90.59

Integrated 60 24hr/day 500 $372.30 NG 80 AFUE $111.97 $484.27

Integrated 180 3hrs. 3X/day 500 $139.61 NG 80 AFUE $125.96 $265.57

HRV/ ERV* 60 24hr/day 59 $43.93 NG 80 AFUE $55.98 $99.91

HRV/ ERV* 180 3hrs. 3X/day 59 $16.47 NG 80 AFUE $62.98 $79.46

1PSE Utility Rates of $0.085/kWh and 1.10/Therm

*Assuming 50% total recovery efficiency

Page 35: Washington State Ventilation and Indoor Air Quality Code

TABLE M1507.3.3(2)

INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa, b

RUN-TIME PERCENTAGE IN EACH 4-HOUR SEGMENT

25% 33% 50% 66% 75% 100%

Factora 4 3 2 1.5 1.3 1.0

a. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.

b. Extrapolation beyond the table is prohibited.

Page 36: Washington State Ventilation and Indoor Air Quality Code

• The fan will operate 1 hour every 4 hours

TABLE M1507.3.3(2)

INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa, b

RUN-TIME PERCENTAGE IN EACH 4-HOUR SEGMENT

25% 33% 50% 66% 75% 100%

Factora 4 3 2 1.5 1.3 1.0

a. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.

b. Extrapolation beyond the table is prohibited.

Page 37: Washington State Ventilation and Indoor Air Quality Code

• The fan will operate 3 hours every 4 hours

TABLE M1507.3.3(2)

INTERMITTENT WHOLE-HOUSE MECHANICAL VENTILATION RATE FACTORSa, b

RUN-TIME PERCENTAGE IN EACH 4-HOUR SEGMENT

25% 33% 50% 66% 75% 100%

Factora 4 3 2 1.5 1.3 1.0

a. For ventilation system run time values between those given, the factors are permitted to be determined by interpolation.

b. Extrapolation beyond the table is prohibited.

Page 38: Washington State Ventilation and Indoor Air Quality Code

Page 39: Washington State Ventilation and Indoor Air Quality Code

Page 40: Washington State Ventilation and Indoor Air Quality Code

Whole House Fan

(see instructions)

Don’t forget the label

Page 41: Washington State Ventilation and Indoor Air Quality Code

Page 42: Washington State Ventilation and Indoor Air Quality Code

Through wall air inlet Window vent

Page 43: Washington State Ventilation and Indoor Air Quality Code

Page 44: Washington State Ventilation and Indoor Air Quality Code

Page 45: Washington State Ventilation and Indoor Air Quality Code

Page 46: Washington State Ventilation and Indoor Air Quality Code
Page 47: Washington State Ventilation and Indoor Air Quality Code

Page 48: Washington State Ventilation and Indoor Air Quality Code

Table 403.8.5.2/M1508.6.2

Prescriptive Supply Fan Duct Sizing

Supply Fan Tested cfm at 0.40” w.g.

Specified Volume

From Table 408.1

Minimum Smooth

Duct Diameter

Minimum Flexible

Duct Diameter

50 – 90 cfm 4 inch 5 inch

90 – 150 cfm 5 inch 6 inch

150 – 250 cfm 6 inch 7 inch

250 – 400 cfm 7 inch 8 inch

See Handout

Page 49: Washington State Ventilation and Indoor Air Quality Code
Page 50: Washington State Ventilation and Indoor Air Quality Code

Page 51: Washington State Ventilation and Indoor Air Quality Code

Page 52: Washington State Ventilation and Indoor Air Quality Code

Page 53: Washington State Ventilation and Indoor Air Quality Code

Page 54: Washington State Ventilation and Indoor Air Quality Code

Exhaust Air To Outside

Outside Air

Supply Air To Home

Return Air From Home

Page 55: Washington State Ventilation and Indoor Air Quality Code

Page 56: Washington State Ventilation and Indoor Air Quality Code
Page 57: Washington State Ventilation and Indoor Air Quality Code

Page 58: Washington State Ventilation and Indoor Air Quality Code

Combustion air reduces the

“backdrafting” potential

Page 59: Washington State Ventilation and Indoor Air Quality Code

Page 60: Washington State Ventilation and Indoor Air Quality Code
Page 61: Washington State Ventilation and Indoor Air Quality Code

Combustion Air

Exhaust

Page 62: Washington State Ventilation and Indoor Air Quality Code

o

Page 63: Washington State Ventilation and Indoor Air Quality Code

• Exception:

• Exception:

Page 64: Washington State Ventilation and Indoor Air Quality Code
Page 65: Washington State Ventilation and Indoor Air Quality Code

Page 66: Washington State Ventilation and Indoor Air Quality Code
Page 67: Washington State Ventilation and Indoor Air Quality Code
Page 68: Washington State Ventilation and Indoor Air Quality Code

Page 69: Washington State Ventilation and Indoor Air Quality Code

Page 70: Washington State Ventilation and Indoor Air Quality Code

Page 71: Washington State Ventilation and Indoor Air Quality Code

Page 72: Washington State Ventilation and Indoor Air Quality Code

Page 73: Washington State Ventilation and Indoor Air Quality Code

Page 74: Washington State Ventilation and Indoor Air Quality Code

solid

Page 75: Washington State Ventilation and Indoor Air Quality Code

Page 76: Washington State Ventilation and Indoor Air Quality Code

Page 77: Washington State Ventilation and Indoor Air Quality Code

Page 78: Washington State Ventilation and Indoor Air Quality Code

Page 79: Washington State Ventilation and Indoor Air Quality Code

Page 80: Washington State Ventilation and Indoor Air Quality Code

Page 81: Washington State Ventilation and Indoor Air Quality Code

Page 82: Washington State Ventilation and Indoor Air Quality Code

Page 83: Washington State Ventilation and Indoor Air Quality Code

Page 84: Washington State Ventilation and Indoor Air Quality Code
Page 85: Washington State Ventilation and Indoor Air Quality Code

Page 86: Washington State Ventilation and Indoor Air Quality Code
Page 87: Washington State Ventilation and Indoor Air Quality Code
Page 88: Washington State Ventilation and Indoor Air Quality Code

••

Page 89: Washington State Ventilation and Indoor Air Quality Code

Page 90: Washington State Ventilation and Indoor Air Quality Code

Page 91: Washington State Ventilation and Indoor Air Quality Code