VSD Incentives and Applications Amaan Laheri, KEMA
20

VSD Incentives and Applications

Jan 06, 2016

Download

Documents

malia

VSD Incentives and Applications. Amaan Laheri, KEMA. Agenda. Energy efficiency and Variable Speed Drives (VSD) New prescriptive VSD incentive application for : Chillers Fans Pumps Air Compressors Ineligible measures Q & A. Energy Efficiency and VSD. - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: VSD Incentives and Applications

VSD Incentives and Applications

Amaan Laheri, KEMA

Page 2: VSD Incentives and Applications

Agenda

• Energy efficiency and Variable Speed Drives (VSD)• New prescriptive VSD incentive application for :

– Chillers– Fans– Pumps– Air Compressors

• Ineligible measures• Q & A

Page 3: VSD Incentives and Applications

Energy Efficiency and VSD

• How can a VSD improve energy efficiency?

• How is the VSD controlled?

Page 4: VSD Incentives and Applications
Page 5: VSD Incentives and Applications

Total

% of Load kW Hours kW Hours kWh

100%

90%

80%

60%

50%

40%

30%

Base annual kWh =

Total

% of Load kW Hours kW Hours kWh

100%

90%

80%

60%

50%

40%

30%

Propose annual kWh =

Annual kWh Saving =

VSD WORKSHEET

Unit 1 Unit 2

Without Variable Frequency Drive

With Variable Frequency Drive

Unit 1 Unit 2

Page 6: VSD Incentives and Applications

Now Prescriptive – VSDs on:

• Fan or pump motors, 200 HP or less: $60 per HP

• Chillers, $25 per HP

• Air compressors <100 HP, $100 per HP

Page 7: VSD Incentives and Applications

A Look at the New Application

Page 8: VSD Incentives and Applications

Up to 100 HP 101 HP to 200 HP Over 200 HP

Custom Application

Page 9: VSD Incentives and Applications
Page 10: VSD Incentives and Applications

VSDs on Fan, Pump or Air Compressor Motors

ONF 8760 960 1 $25 $24,000

Supply fan 1&2 RFA DD DP 5814

40 2 $60 $4,800

SFA DD BI 5814 60 2 $60 $7,200

$

Return fan 1&2Chiller #7Air Compressor #3 ACP N/A TWS 5814 50 1 $100 $5,000AHU SF#10 SFA IGV BI 8,760 125 1 $60 $7,500

Page 11: VSD Incentives and Applications

Motors Over 100 HP

AHU SF-10Labs, offices, classrooms

Conditioned air in labs, offices, & classroomsB1 – air foil

1259

2%

Acme Fan Co.75,000

cfm

AFC-124b4 in H2OInlet guide

vanes3 in H2O

Page 12: VSD Incentives and Applications

24/7 24/7

N/A N/A

277

128

0.89 54.6

Page 13: VSD Incentives and Applications

Varies

3 in H2O

55.0 87650.6 394247.3 3942

3760Estimated

57.8 87635.2 394223.1 3942

8760

Page 14: VSD Incentives and Applications

Incentive Capping

Page 15: VSD Incentives and Applications

Specifications

• Existing throttling devices such as inlet vanes, bypass dampers, and throttling valves must be permanently removed or disabled.

• VSD must be installed with automatic control technology.

Page 16: VSD Incentives and Applications

Not Eligible for Incentives

• VSDs installed on equipment that operates less than 1,200 hours per year

• Replacements of existing VSDs • VSDs installed on redundant/backup motors• VSDs installed in place of multi-speed flow control equipment (such as

two-speed cooling tower fans)• VSDs installed in place of variable pitch blade flow control equipment• VSDs installed for the purpose of “soft-starting” motors• VSDs installed on pumps where affinity laws are not in effect, such as

positive displacement pumps

Page 17: VSD Incentives and Applications

Where to find the New Application

www.ComEd.com/bizincentives

Page 18: VSD Incentives and Applications

[email protected] • Program questions (888) 806-2273• Fax: 1-630-480-3436• Outreach Team

630-480-3434• www.ComEd.com/bizincentives