VFDs- My Experience Introduction- AIRAH DA01 AIRAH DA13 Why Install VFDs? What are VFDs, How do they work? Energy saving potential Potential issues to be aware of Lasath Lecamwasam CPEng MAIRAH MCIBSE MASRAE
14

VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

May 11, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

VFDs- My Experience

• Introduction- AIRAH DA01 AIRAH DA13

• Why Install VFDs?

• What are VFDs, How do they work?

• Energy saving potential

• Potential issues to be aware of

Lasath Lecamwasam CPEng MAIRAH MCIBSE MASRAE

Page 2: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Why Install VFDs ?

Compliance with BCA Section JFANS: • In Air conditioning/ Ventilation system: Except PAC units, all

supply air fans should have VFDs where supply air quantity can be varied.

• In Exhaust system: Exhaust system with an air flow rate of more than 1000 L/s must have VFD fan

• Carparks: If more than 40 spaces, must have VFD with CO based control- 30 ppm….

PUMPS:• In Air conditioning system: Pump delivering more than 2 L/s

& rated more than 3kW shall have a VFD

Page 3: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Why Install VFDs

• Efficiency- Beyond Section J– Variable Pumping in CHW and HHW Systems.– Demand Controlled Ventilation. Eg. CO₂ and CO– Control of Cooling Tower Fans- wet bulb tracking

• Performance of HVAC Systems– VAV Systems– Avoid shock of DOL starts-– Avoid voltage sags

• Safety– Stairwell Pressurisation Systems

Page 4: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

What are VFDs

• VSD or VFD?

• VFDs- for 3ɸ motors. 1ɸ??

• Before VFDs-

– Throttling

– Impellor Replacement or Trimming

– Eddy Current Couplings

– Multi Pole Motors

– Variable Inlet Guide Vanes

Page 5: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Variable Inlet Guide Vanes

Page 6: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Variable Inlet Guide Vanes

Page 7: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Induction Motor

Rotor

Stator

𝑆𝑦𝑛𝑐ℎ𝑟𝑜𝑛𝑜𝑢𝑠 𝑠𝑝𝑒𝑒𝑑 𝑁 =60 𝑥 𝑓

𝑃𝑝

N - 𝑆𝑦𝑛𝑐ℎ𝑟𝑜𝑛𝑜𝑢𝑠 𝑠𝑝𝑒𝑒𝑑𝑓 – Frequency (50Hz)𝑃𝑝 – Number of Pole Pairs

Slip- Typically Rotor speed is 97% of synchronous speed (Slip 2.5-3%)

Page 8: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Voltage

Voltage

Voltage

Time

Time

TimeInput

Low Frequency

High Frequency

How does a VFD work?

Page 9: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

𝑄1

𝑄2

=𝑁1

𝑁2

𝐻1

𝐻2

=𝑁1

𝑁2

2

𝑃1𝑃2

=𝑁1

𝑁2

3

With impeller diameter (D) held constant:

Q - Volumetric flow rateD - Impeller diameterN - Shaft rotational speedH - Pressure (head) developed by the pumpP - Shaft power

Pump Affinity Laws

𝑄 ∝ N

𝐻 ∝ N2

𝑃 ∝ N3

𝑃1𝑃2

=𝐷1

𝐷2

5

𝑄1

𝑄2

=𝐷1

𝐷2

3

𝑄 ∝ D3

𝑄 ∝ D5

Impeller trimming:

Page 10: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

100%

100% on 50% Duty Cycle

Capacity

Capacity

Time

Time

50%

Capacity

Time

Energy consumption 100%

Energy consumption 50%

Energy consumption 12.5%

Energy saving potential of VFDs

Page 11: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

ΔP1

ΔP2

Q2 Q1 Q2 Q1

ΔP1 = ΔP2

𝑃𝑜𝑤𝑒𝑟2𝑃𝑜𝑤𝑒𝑟1

=𝑄2

𝑄1

1.9

Is it 1.9??

𝑃𝑜𝑤𝑒𝑟2𝑃𝑜𝑤𝑒𝑟1

=𝑄2

𝑄1

3

Pump and System curves

Page 12: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

RFI

Harmonics

EMC

ActewAGLService Rules

CE Mark

C ✓

AS/NZS61000

AS/NZS61800

Circuit Breaker

Motor

VFD

Isolator!

Page 13: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

And Finally!• Very Good technology, Costs have really come down.• Design for Variable Flow, to get best outcome.• Fitting VFDs to old motors- winding failure, bearing currents.• VFD losses? Parasitic losses?• Beware of EMC- Harmonics/RFI.• Installing VFDs to external rotor motors!• IP Rating? Dust Ingress? Heat Rejection?• Bypass VFD? Safe isolation of VFD, motor.• Sizing: 120%? Maximum Ambient Temperature? Altitude?• Resonance- Fan Blades.• Noise- Can add 10dBA to motor noise. Carrier Frequency?• Fire mode operation- AS/NZS 1668 Part 1• Correct Specification. Good Installation- Segregation, screened cables

(80% screening?). Maximum length <30m? Metal isolators, terminal boxes & cable glands. No pig tales

• Protection- Circuit breaker, Overload, Thermistor.

Page 14: VFDs- My Experience - AIRAH€¦ · Why Install VFDs •Efficiency- Beyond Section J –Variable Pumping in CHW and HHW Systems. –Demand Controlled Ventilation.Eg. CO₂and CO –Control

Any Questions?

• Beyond VFDs? Permanent magnet motors?• ECDC Motors• Ask the experts- at the end.

[email protected]