Top Banner
- Y.Rama Krishna WELCOME
44

VFD

May 13, 2017

Download

Documents

netygen1
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: VFD

- Y.Rama Krishna

WELCOME

Page 2: VFD

Natural draught system Induced draught system Forced draught system Balanced draught

system

DRAUGHT SYSTEM

“The difference between the atmospheric pressure and the pressure existing in the furnace is called Draught”.

Page 3: VFD

FANS

An essential auxiliary equipment of the boiler.

Supply air for the combustion in the furnace. (FD Fan)

Evacuates the flue gases formed from the combustion. (ID fan)

Evacuation wouldn’t be possible with out using FANS

“Machines moving the gaseous fluids with a pressure ratio up to 1.15 are know as FANS”

Page 4: VFD

Speed control Inlet guide vane control Damper control Blade pitch control

Types Of Controls Employed For The Fans

MAINTAINS THE DESIRED BALANCED DRAUGHT AND

NEGATIVE PRESSURE REQUIREMENT OF A FURNACE

WITH THE HELP OF F.D. FAN

IMPORTANCE of ID FAN

Page 5: VFD

REGULATION

The fan is adapted to changing operating conditions by means of •Adjustable inlet dampers.•Varying the fan speed

Variable Fan Speed•Two speed drive motor with inlet guide vanes•Variable Speed Hydraulic Coupling•Variable speed drives (stepped/step less variation)•Frequency Controlled Variable Speed Drive

Inlet Damper Control• Actuator

Page 6: VFD

VARIABLE TORQUE

Page 7: VFD
Page 8: VFD
Page 9: VFD
Page 10: VFD
Page 11: VFD

BASIC VFD (LCI-VFD) SYSTEM

LCI -Load Commutated InverterVFD -Variable Frequency Drive

Page 12: VFD

SYNCHRONOUS MACHINE

RATING

6-PULSE 12-PULSE

KW 1488 3895

RPM 390 545

Volts (L-L) 1804 2X2300

PF 0.85 0.85

Exc Volts 240 345

Exc Amps 48 64

Stator YY , 10 pole, A.C.

Rotar 8 pole, D.C.

Page 13: VFD

ISOLATION TRANSFORMER

The transformer provides isolation from the ac system bus.

Provides the correct voltage at the terminals of the rectifier i/p.

Internal impedance of the transformer limits the magnitude of any downstream bus faults.

Transformer rating:-

KVA = 3000 CH-1 Δ/ΔVolts HV/LV = 11/2.3 KV CH-2 Δ/YAmps HV/LV = 157.5/753.1

Page 14: VFD

RECTIFIER I/P - CONSTANT a.cO/P- VARIABLE d.c

THYRISTOR FIRING

1 -- 2 2 -- 3 3 -- 4 4 -- 5 5 -- 6

6 -- 1

1 -- 2

Page 15: VFD

RectifierO/p

Page 16: VFD

INVERTER

Page 17: VFD

INVERTER SWITCHING

Page 18: VFD
Page 19: VFD
Page 20: VFD

i2

1

6

5

4

3

Page 21: VFD

LCI Drive

Page 22: VFD
Page 23: VFD

SPACE VECTOR MODULATION

Page 24: VFD

Inverter o/p

Page 25: VFD

LINE NOTCHES & BUMPS

Page 26: VFD

POWER MODULES 2.3 kV FOR VFD

Page 27: VFD

Gate driver module

Page 28: VFD

HPTK MODULE (Gate driver)

Page 29: VFD

Voltage Regulator For Exciter

Page 30: VFD

FIELD EXCITER MODULE

Page 31: VFD

Overall Functional VFD Diagram

Page 32: VFD

2-channel VFD

Page 33: VFD

LINING-UP AND ISOLATION OF ID FAN

LINING-UP1. Charge the cooling water to fan bearings.2. Charge the cooler from water side & ensure the flow in

view glass. 3. Charge the motor cooling water and observe the FLOW4. Line up the lube oil system5. Normalize the power supply of inlet / outlet gates.6. Normalize the supply of IGV.7. Normalize the fan main breaker.8. Check LOP s availability & interlock.9. Release the EPB. (always at the LAST)

Page 34: VFD

STARTING1. Ensure no alarm persists on the source & load Breakers.2. Check all the permissive available.3. Check no fault is persisting.4. Close the SOURCE breakers from OWS.5. Ensure closing of the breakers from Local.6. Close the Load Breakers.7. Wait till the Drive attains a constant speed.8. Then increase the speed as per requirement.9. Use IGV & SPEED control to maintain DRAUGHT.

Page 35: VFD

ISOLATION

1. Ensure that fan is in stopped condition.2. Press EPB.3. Electrically isolate the main breaker.4. Earthing to be done as per the requirement.5. Ensure that inlet / outlet gates are in closed condition.6. Isolate the supply of inlet and outlet gates.7. Isolate IGV supply.8. Isolate LOP-1 & 2 motor power supply after ensuring that fan at standstill.9. Isolate cooling water to Oil coolers,Bearings,Motor coolers.10.Isolate the oil cooler from oil side.

Page 36: VFD

ADVANTAGES OF USING V.F.D.

1. FAST RESPONSE2. HIGH ACCURACY3. HIGH EFFICIENCY4. LOW MAINTENANCE5. NO SUPPLY FLUCTUATION6. SOFT START7. INCREASE IN MOTOR LIFE

Page 37: VFD

FURTHER APPLICATIONS

The success of VFD to the ID fan in the power plant opens new channels for its application in the power plant auxiliaries like

1. MDBFP2. FD FAN3. PA FAN4. GAS TURBINE STARTER5. COMPRESSOR DRIVES6. CENTRALISED AC SYSTEMS

Page 38: VFD

CONCLUSIONS

•Reduction in auxiliary power consumption approximately by 10% at peak generation and by 15% at 60% generation.

Lower order Harmonics can be eliminated by using PWM

Fuzzy Logic, Neural Networks and Genetic Algorithms can be implemented for optimized control.

SUGGESTIONS

Page 39: VFD

REFERENCES

1. NTPC ET course material.2. NPTI training module3. Customer training manual, LCI VFD vol & II -BHEL4. Power Electronics -P.S Bimbhra, Khanna pub.5. Power Electronics converters, applications and design -N.Mohan, Undeland,Robbins6. VFD article, Kilowatt Classroom7. PWM Current Source Converter Induction Machine Drive -Alfons Klönne, Friedrich W. Fuchs Christian-Abrechts-University of Kiel -Power Electronics and Electrical Drives,

8. A Variable Step-Size C-MEX S-Function for Reduced Simulation Times of Variable Speed Drives, Alan Mullane, Gregor Gregor¡ci¡c, Gordon Light body and Robert Yacamini Department of Electrical Engineering, University College Cork, IRELAND

Page 40: VFD
Page 41: VFD
Page 42: VFD

START PERMISSIVES FOR VFD CH-1

ID FAN

1. VFD Source Breaker Not Disturbed AND2. VFD Source Breaker ON AND3. No VFD CH-1 Alarm Persisting AND4. VFD CH-1 Ready AND5. VFD CH-1 Start Permissive Available AND6. (VFD CH-2 ON) OR (Reg Damper Position Min(<2%) AND Fan I/L & O/L Gates Closed) AND7. Fan Either LO P/P ON AND

contd…

Page 43: VFD

8. Fan LO Press OK (>0.8 KSC) AND9. LO Temp. after Cooler Not High (<75 °C) AND10. Fan Motor Brg. Temp. Not High (<85°C) AND11. Fan Brg temp. Not High (< 90°C ) AND12. Fan Motor Winding Temp. Not High(<120 °C ) AND13. Fan VFD Auxiliary Supply OK AND14. FG path Available OR Other ID Fan ON AND

Page 44: VFD

ID FAN

PROTECTIONS FOR VFD CH-1

VFD CH-1 Fault Condition ORMotor Brg. Temp V High (TD 5 sec) >90°C ORFan Brg Temp V High (TD 5 sec) >110°C ORMotor/Fan Brg. Vib V High (TD 15 sec) >9 mm/sec ORPost Purge Trip from FSSS ORBoth ID Fan ON AND FD Fan-A Tripped ORFan ON (>01 min) AND O/L Gates Closed ORFan ON (>01 min) AND I/L Gates Closed ORVFD CH-2 Fault Condition