PL01301006E For more information visit: www.eatonelectrical.com
The VacClad-W design PowerModule incorporates individualvertical sections which will enclosea maximum of;
(1) Two VCP-W breakers,
(2) Four auxiliary drawouts, or
(3) Combination of one VCP-Wbreaker and two auxiliarydrawouts.
• A complete structure includingcircuit breaker compartments,auxiliary compartments, controlcompartment, and main buscompartment; plus side and backsheets, roof assembly, ventilationchimney, door hinges, and doorstops.
• Available with Glass Polyester for41 kA to 63kA applications.
• SE up to 41kA
• The circuit breaker can beinserted in the upper or lowercompartment.
• All breaker secondarydisconnects are terminated on aterminal block within the PowerModule.
• Two auxiliary drawers (for PT,CPT, or Fuse) can be located inthe upper or lower compartment.
• The Power Module (blankAuxiliary B-Plane) is pre-punchedwith knock-outs to accept a PT,CPT or Fuse Drawer Kit.
• Auxiliary compartment kits canbe easily installed into any blankauxiliary power modulecompartment to suit any PT, CPT,or Fuse Drawer.
• Exclusive configuration: 3000Ampere Circuit Breaker in theupper compartment with a singleauxiliary drawer in the lowercompartment for additional spacesavings.
• 36” wide, 5 kV through 15 kVdesigns are available in tenconfigurations.
• 26” wide, 5 kV-250 MVA NarrowDesign (ND) is available in fourconfigurations.
• The switchgear assemblerprovides value added items suchas doors, bus, cable areacompartments, instruments,relays, and associated wiring.
5/15 kV Mini Modules
A simple building block approach.Easily configured to any projectspecification, mini modules areavailable as:
• A one-high breaker mini moduleis offered in a 1200A, 2000A or3000A compartment design.
• Different bus terminalconfigurations available for upperor lower compartments.
• Available with Glass Polyesterinsulating tubes up to 63kA andup to 41kA for Porcelainapplications.
• All breaker secondary disconnectsare wired to a terminal block.
• Available for 36” wide standardand narrow design 26” wideswitchgear configurations.
• The switchgear assemblerprovides value-added items suchas doors, bus, cable areacompartment, side sheets, andcontrol panel for instruments,relays and associated wiring.
5/15 kV Breaker Compartment Kits
Breaker compartment kits provide amaximum value added approach tobuilding switchgear. Combiningmaximum design flexibility withcost competitiveness, each CircuitBreaker Compartment Kit includes:
• Breaker levering in assembly withleft and right draw-out rails.
• Primary disconnect supports(upper and lower).
• All breaker secondary disconnectsare wired to a terminal block.
• Current transformer barrierassembly.
• Shutter assembly.
• Available for 36” wide standardand narrow design 26” wideswitchgear configurations.
5/15 kV Auxiliary Compartment Kits
All Potential Transformer (PT),Control Power Transformer (CPT)and Fuse Drawer Compartment Kitsinclude:
• Left and right draw-out rails.
• Primary draw-out contactassemblies.
• Secondary drawout contactassemblies (PT and CPT only).
• Shutter assembly.
• Stand off insulators and cablesupports.
• Hardware for all configurationsincluding mounting, alignmentbrackets and divider pan.
• PT drawer is partially assembled;Potential Transformers, fusemountings and fuses areprovided by switchgearassembler.
VCP-WG Medium Voltage Generator Vacuum Circuit Breakers
ANSI Type VCP-W & VCP-WND Circuit Breaker (5-Cycle interrupting time) Removable Element Only
Circuit Continuous Maximum Voltage ListBreaker Current Voltage Factor PriceType Amperes kV K US$
Circuit Continuous Maximum Voltage ListBreaker Current Voltage Factor PriceType Amperes kV K US$
Identification Rated Values OrderingInformation
Identification Rated Values OrderingInformation
1 For use on VCPW-ND Power Modules, Mini Modules or Component Kits only.2 Order by description.3 SE option available for $3,000 list adder.4 contact C-H for UL listed breaker style numbers.
Tested to ANSI C37.013 -1997.1
4
4
1
1
1
1
1 Requires 63kA Power Module or Mini Module Cell Parts Kit
175VCP-W50 3150 17.5 50 4 50,000 1 Applicable for 50 Hz or 60 Hz applications.2 Also 3 second short time current rating.3 Provisions for capacitor trip only. If a capacitor trip device is required, select the capacitor trip device on page 11.4 Order by description.5 50 Hertz Only.
Table 3 Breaker Control Voltage
Undervoltage Release (48Vdc, 125Vdc, 250Vdc, 120Vac, 240Vac) 1,200Second Shunt Trip 40050 ms Interrupting Time (3-Cycle) Rating 1,200VCP-WSE Special Environment (cycloaliphatic epoxy insulation)-only up to 41kA 3,000
Power Modules 1Identification Ordering Information
1200ACompartment
1200ACompartment
1200ACompartment
2000ACompartment
2000ACompartment
1200ACompartment
1200ACompartment
BlankAuxiliary
BlankAuxiliary
2000ACompartment
BlankAuxiliary
BlankAuxiliary
1200ACompartment
BlankAuxiliary
BlankAuxiliary
2000ACompartment
BlankAuxiliary
BlankAuxiliary
Blank
Blank Auxiliary
3000ACompartment
BlankAuxiliary
BlankAuxiliary
1 41 kA rated modules are applicable for breakers rated 4.76 kV-250 MVA, 8.25 kV-500 MVA, 15 kV-750 MVA. 50 kA rated modules are applicable for breakers rated 4.76 kV-350 MVA and 15 kV-1000 MVA.63kA rated modules are applicable for breakers rated 4.76 kV-500 MVA and 15 kV-1500 MVA.
2 Exclusive Cutler-Hammer design offers 3000A cell and (1) Auxiliary drawer in a common Power Module.
Compartment Upper Compartment/ Width Description Style List PriceConfiguration Lower Compartment Insulation, Interrupting Number US $
Blank/1200A 36" Glass Polyester, 41 kA 69C4063G01 6,200Blank/1200A 36" Porcelain, 41 kA 69C4063G04 6,800Blank/1200A 36" Glass Polyester, 50 kA 69C4063G11 6,500Blank/1200A 36" Porcelain, 50 kA 69C4063G14 7,100Blank/1200A 36" Glass Polyester, 63kA 69C4063G21 12,000
Blank/2000A 36" Glass Polyester, 41 kA 69C4063G02 7,200Blank/2000A 36" Porcelain, 41 kA 69C4063G05 7,800Blank/2000A 36" Glass Polyester, 50 kA 69C4063G12 7,500Blank/2000A 36" Porcelain, 50 kA 69C4063G15 8,100Blank/2000A 36" Glass Polyester, 63 kA 69C4063G22 13,000
Blank/3000A 36" Glass Polyester, 50 kA 69C4063G13 13,600Blank/3000A 36" Porcelain, 50 kA 69C4063G16 14,200Blank/3000A 36" Glass Polyester, 63 kA 69C4063G23 14,000
Power Modules - Direct Roll-In 1Identification Ordering Information
1 41 kA rated modules are applicable for breakers rated 4.76 kV-250 MVA, 8.25 kV-500 MVA, 15 kV-750 MVA. 50 kA rated modules are applicable for breakers rated 4.76 kV-350 MVA and 15 kV-1000 MVA.63kA rated modules are applicable for breakers rated 4.76 kV-500 MVA and 15 kV-1500 MVA.
2 Exclusive Cutler-Hammer design offers 3000A cell and (1) Auxiliary drawer in a common Power Module.
Description Width Compartment Style Number List PriceContinuous Current, Interrupting Location US $
Using glass polyester insulatingtubes for 5 kV & 15 kV breakers:
1200A, 41 kA 26”(ND) upper or lower 7797C59G01 3,600
1200A, 41 kA 36” lower 6510C91G02 3,6001200A, 41 kA 36” upper 6510C91G03 3,6001200A, 41 kA 36” upper or lower 6510C91G10 3,600
2000A, 41 kA 36” lower 6510C91G04 4,3002000A, 41 kA 36” upper 6510C91G05 4,3002000A, 41 kA 36” upper or lower 6510C91G11 4,300
1200A, 50 kA 36” lower 6529C31G02 3,9001200A, 50 kA 36” upper 6529C31G03 3,9001200A, 50 kA 36” upper or lower 6529C31G10 3,900
2000A, 50 kA 36” lower 6529C31G04 4,6002000A, 50 kA 36” upper 6529C31G05 4,6002000A, 50 kA 36” upper or lower 6529C31G11 4,600
3000A, 50 kA 36” upper or lower 6529C32G02 7,600
Using porcelain insulatingtubes for 5 kV & 15 kV breakers:
1200A, 41 kA 36” lower 6510C91G06 4,2001200A, 41 kA 36” upper 6510C91G07 4,2001200A, 41 kA 36” upper or lower 6510C91G12 4,200
2000A, 41 kA 36” lower 6510C91G08 4,9002000A, 41 kA 36” upper 6510C91G09 4,9002000A, 41 kA 36” upper or lower 6510C91G13 4,900
1200A, 50 kA 36” lower 6529C31G06 4,5001200A, 50 kA 36” upper 6529C31G07 4,5001200A, 50 kA 36” upper or lower 6529C31G12 4,500
2000A, 50 kA 36” lower 6529C31G08 5,2002000A, 50 kA 36” upper 6529C31G09 5,2002000A, 50 kA 36” upper or lower 6529C31G13 5,200
3000A, 50 kA 36” upper or lower 6529C32G03 8,200
Using glass polyester insulatingtubes for 5 kV & 15 kV breakers:
1200A, 63KA 36” upper or lower 7819C66G01 7,5002000A, 63KA 36” upper or lower 7819C66G02 7,8003000A, 63KA 36” upper or lower 7819C66G03 8,100
Direct Roll in:
1200 A Glass Polyester lower only 1C18621G01 3,6001200 A Porcelain lower only 1C18621G02 4,2002000 A Glass Polyester lower only 1C18621G03 4,3002000 A Porcelain lower only 1C18621G04 4,9001200 A Glass Polyester 50KA lower only 1C18621G51 3.9001200 A Porcelain 50KA lower only 1C18621G52 4,5002000 A Glass Polyester 50KA lower only 1C18621G53 4,6002000 A Porcelain 50KA lower only 1C18621G54 5,2003000 A Glass Polyester 50KA lower only 1C18621G55 7,6003000 A Porcelain 50KA lower only 1C18621G56 8,2001200 A Glass Polyester 63KA lower only 1C18621G61 7,5001200 A Porcelain 63KA lower only 1C18621G62 7,8002000 A Glass Polyester 63KA lower only 1C18621G63 7,8003000 A Glass Polyester 63KA lower only 1C18621G65 8,100
Mini ModulesIdentification Ordering Information
36" wide Mini Module with Glass Polyester Insulating Tubes
ND Mini Module withGlass Polyester Insulating Tubes
Description Width Stud Style Number List PriceContinuous Current, Interrupting Configuration US $
Using glass polyester insulating tubes:1200A compartment, 41 kA 26”(ND) line and line 1C14700G01 2,9001200A compartment, 41 kA 36” line and bus 7816C75G02 2,9001200A compartment, 41 kA 36” line and line 7816C75G03 2,9002000A compartment, 41 kA 36” line and bus 7816C75G04 3,3002000A compartment, 41 kA 36” line and line 7816C75G05 3,3001200A compartment, 50 kA 36” line and bus 7816C75G12 3,2001200A compartment, 50 kA 36” line and line 7816C75G13 3,2002000A compartment, 50 kA 36” line and bus 7816C75G14 3,6002000A compartment, 50 kA 36” line and line 7816C75G15 3,6003000A compartment, 50 kA 36” line and bus 7816C75G10 6,100
Utilizing porcelain insulating tubes:1200A compartment, 41 kA 36” line and bus 7816C75G06 3,5001200A compartment, 41 kA 36” line and line 7816C75G07 3,5002000A compartment, 41 kA 36” line and bus 7816C75G08 3,9002000A compartment, 41 kA 36” line and line 7816C75G09 3,9001200A compartment, 50 kA 36” line and bus 7816C75G16 4,1001200A compartment, 50 kA 36” line and line 7816C75G17 4,1002000A compartment, 50 kA 36” line and bus 7816C75G18 4,5002000A compartment, 50 kA 36” line and line 7816C75G19 4,5003000A compartment, 50 kA 36” line and bus 7816C75G11 6,700
Using glass polyester insulating tubes:1200A compartment, 63kA 36” line and bus 7819C65G01 6,1002000A compartment, 63kA 36” line and bus 7819C65G02 6,4003000A compartment, 63kA 36” line and bus 7819C65G03 6,700
Breaker Compartment KitsIdentification Ordering Information
Description 26" wide (ND) 36" wide List PriceStyle Number Style Number US $
Auxiliary Compartment KitsIdentification Ordering Information
Potential Transformer Drawer Compartment Kit
Control Power Transformer Drawer Compartment Kit
Fuse Drawer Compartment Kit
36” wide Glass PolyesterBreaker Compartment Kit
Direct Roll-In Cell Part KitsIdentification Ordering Information
Description Style Number List Price US $
Cell Part Kit 1200A 41 kA Glass Polyester 69C4100G01 2,900Cell Part Kit 2000A 41 kA Glass Polyester 69C4100G02 3,300Cell Part Kit 1200A 41 kA Porcelain 69C4100G03 3,500Cell Part Kit 2000A 41 kA Porcelain 69C4100G04 3,900Cell Part Kit 1200A 50 kA Glass Polyester 69C4100G51 3,200 Cell Part Kit 2000A 50 kA Glass Polyester 69C4100G52 3,600 Cell Part Kit 3000A 50 kA Glass Polyester 69C4100G53 6,100 Cell Part Kit 1200A 50 kA Porcelain 69C4100G54 4,100 Cell Part Kit 2000A 50 kA Porcelain 69C4100G55 4,500 Cell Part Kit 3000A 50 kA Porcelain 69C4100G56 6,700 Cell Part Kit 1200A 63 kA Glass Polyester 69C4100G61 6,100 Cell Part Kit 2000A 63 kA Glass Polyester 69C4100G62 6,400 Cell Part Kit 3000A 63 kA Glass Polyester 69C4100G63 6,700
Standard Levering-In CrankExtension Rails (right & left, 1 set)Set of Rail ClampsManual Charging Handle
Portable Lifter (26”/36” convertible) 3A40094H01 2,200Portable Lifter for 2-high Direct Roll In 1C18658G01 2,500Drawout Ramp 1C14163G02 400Docking Transport Dolly 6510C71G11 1,000Electrical Levering-In Device 1A30257G01 1,375Test Jumper 6526C23G11 300Test Cabinet
Any dc Close and Any Trip 8346A28G21 625ac or dc Close and dc Trip 8346A28G22 625120/240 Vac Close and Capacitor Trip 8346A28G23 625
Padlock/Key Provisions with positional Interlock. 6510C48G12 150Includes the padlock assembly plus a positional interlock. This allows for Key locking the levering-in cagewhen the breaker is in the test position.
Wheel Kit (for Direct Roll In) 68C5010G01 Contact C-HBreaker Wheel conversion kit
Accessories for 36" wide Breaker CompartmentsDescription Style Number List Price US $
Optional accessories include (clockwise):lifting yoke, test cabinet, spin-free levering
crank, and test jumper
Portable Lifterfor 2-highDirect Roll-in
= 1.000
SIZE
CPRO DIRECTORY DWG NO
TITLE
SCALE PARTS LIST PRODUCT CODE SHEET NO
REVIS
ION
1 DFTR
APPD
APPD
ENGR REF
NEXT ASSY
TOOL REF
DSPEC
DATE
OF
C
D
A
B
C
D
1234
1234
A
UNLESS OTHERWISESPECIFIED
DIMENSIONS IN INCHES
TWO PLACE DEC ± 0.02THREE PLACE DEC ± 0.005ANGLES ± 0.5ONE PLACE MMTWO PLACE MMVOLTAGERESISTANCEAMPERAGEFORCE,TORQUE,SPEEDTIMETEMPERATURE
2001 Eaton Corporation, All Rights ReservedC
DIMENSIONS TO BE INTERPRETEDIN ACCORDANCE WITH
ASME Y14.5M-1994
B
THE INFORMATION ON THIS DRAWING IS T HE PROPERTY OF EATON CORPORATION. IT IS DISCLOSED IN CONFIDENCEAND IS NOT TO BE REPRODUCED, USED, O R DISCLOSED EXCEPT FOR THE PURPOSE F OR WHICH FURNISHED.
Test CabinetsAny dc Close and Any Trip 8346A28G41 625ac or dc Close and dc Trip 8346A28G42 625120/240 Vac Close and Capacitor Trip 8346A28G43 625
Padlock/Key Provisions with positional interlock. 6510C48G01 150Includes the padlock assembly plus a positional interlock. This allows for Key locking the levering-in cage when the breaker is in the test position.
Narrow Design Accessories for 26” wide Breaker CompartmentsDescription Style Number List Price US $
Top and Bottom Studs 1200/2000A 3777A50G02 13,700Top and Bottom Studs 3000A 3777A50G03 19,600Top Studs only 1200/2000A 3777A50G04 13,700Bottom Studs only 1200/2000A 3777A50G05 13,700Top Studs only 3000A 3777A50G06 19,600Bottom Studs only 3000A 3777A50G07 19,6005kV, 1200A VCP-WND (26” wide gear) 4A35130G01 13,700
Manual Ground and Test DevicesThe manual ground and test device is available in different ampere ratingsand stud combinations.
Description (up to 50kA) Style Number List Price US $
Description Style Number List Price US $
Top and Bottom Studs 1200/2000A 3777A51G12 15,600Top and Bottom Studs 3000A 3777A51G13 21,600Top Studs only 1200/2000A 3777A51G14 15,600Bottom Studs only 1200/2000A 3777A51G15 15,600Top Studs only 3000A 3777A51G16 21,600Bottom Studs only 3000A 3777A51G17 21,600
“Bail Type” Manual Ground and Test DevicesThe ”Bail Type” manual ground and test device is available in different ampere ratingsand stud combinations.
1200/2000A, 48 Vdc 692C950G02 45,2001200/2000A, 125Vdc or 120 Vac 692C950G03 45,2001200/2000A, 250 Vdc or 240 Vac 692C950G04 45,2003000A, 48 Vdc 692C950G05 49,7003000A, 125Vdc or 120 Vac 692C950G06 49,7003000A, 250 Vdc or 240 Vac 692C950G07 49,700
Electrical Ground and Test DevicesAll electrical ground and test devices have top and bottom studs as standard.The close control voltage ratings follow the ampere ratings in the description below.
5 kV, 1200A (up to 50kA) 691C605G03 6,8005 kV, 2000A (up to 50kA) 691C605G04 9,5005 kV, 3000A (up to 63kA) 691C605G05 19,20015 kV, 1200A (up to 50kA) 691C605G06 8,20015 kV, 2000A (up to 50kA) 691C605G07 11,20015 kV, 3000A (up to 63kA) 691C605G08 24,700
Dummy Elements
Top Stud1200/2000A, 48 Vdc 1C94360G12 72,5001200/2000A, 125 Vdc or 120 Vac 1C94360G13 72,5001200/2000A, 250 Vdc or 240 Vac 1C94360G14 72,5003000A, 48 Vdc 1C94360G15 77,8003000A, 125 Vdc or 120 Vac 1C94360G16 77,8003000A, 250 Vdc or 240 Vac 1C94360G17 77,800Bottom Stud 1200/2000A, 48 Vdc 1C94361G12 72,5001200/2000A, 125 Vdc 1C94361G13 72,5001200/2000A, 250 Vdc or 240 Vac 1C94361G14 72,5003000A, 48 Vdc 1C94361G15 77,8003000A, 125 Vdc or 120 Vac 1C94361G16 77,8003000A, 250 Vdc or 240 Vac 1C94361G17 77,800
“Consolidated Edison” User Type Ground and Test DeviceThe close/trip control voltage ratings follow the ampere ratings in the description below.
Description Style Number List Price US $
Description Style Number List Price US $
Description Style Number List Price US $
Ground & Test Device and Dummy Elements for 36" Wide Compartments(63kA Not Available.)
Order EntryOrder entry will consist of a three-stepprocess, outlined below.I. Select the proper VCP-W breaker. II. Select the proper structure.III. Select the proper accessories. All items entered individually musthave the correct style numberassociated with them, followed by adescription. Orders must be enteredby style numbers.
Breaker Ordering Information Specify:1.Type of breaker.2. Voltage, continuous ampere and
short circuit current or MVA rating.3. Control voltage and frequency.4. Accessories.5. Quantity of breakers.6. Enter the 10 digit style number
of the breaker element on Vistasuffix Q20.
I. Select the Proper Breaker Style NumberTo select the correct style number for aVCP-W breaker, the followinginformation must be known: Voltagerating, short circuit current rating(ANSI or IEC), and continuous currentrating. After this information has beendetermined select the first 7 digits ofthe circuit breaker style number fromTable 1 or Table 2.The last 3 digits of a VCP-W circuitbreaker style number can bedetermined from the circuit breakercontrol voltage(s) and interrupting(breaking) time, from Table 3, e.g. thevalid style number for an ANSI 15 kV,500 MVA, 1200A breaker with 125 Vdccontrol and standard 5 cycleinterrupting time would be3A73950G02.Breaker elements should be enteredon Vista order entry suffix Q20.Breakers which require a controlvoltage not available in Table 3 orbreakers which require anundervoltage release or second shunttrip, 3 cycle rating and/or UL labelshould be entered on Vista order entrysuffix Y3 by description.
II. Select the Proper Structure Style NumberPower ModulesTo select the proper power module foryour application, first determine thestructural configuration from page 5.For example, if a 1200A UpperCompartment (U.C.)/1200A LowerCompartment (U.C.) Power Module isrequired and a 36" wide, glasspolyester, 41 kA is needed, obtain itsstyle number (#3A38303G01) and enterit on Vista order entry suffix Q17. Note: 26" wide (ND) is for 5kV-250MVA only. 36"wide is for both 5kV & 15kV Power Modules.
Mini ModulesTo select the proper mini module foryour application, first determine thestructural configuration required, thenselect the appropriate compartmentlocation from page 9. For example, if a1200A, 36" wide, 41 kA glass polyesterlower compartment mini module isrequired, obtain its style number(#6510C91G02) and enter it on Vistaorder entry suffix Q17. Note: 1200A, 26" wide (ND), 41kA is for 5 kV-250 MVA only.
Breaker Compartment KitsEach Circuit Breaker Compartment Kitincludes:• Breaker levering in assembly with left
and right draw-out rails• Primary disconnect supports (upper
and lower)• CT barrier assembly• Shutter assembly• Drawings that include dimensions
and clearancesChoose one of the descriptive modelsfrom page 10. You must know the StudConfiguration, then enter it on Vistaorder entry suffix Q17.Note: Back sheets are not included in breakercompartment kits.
Auxiliary Drawer Compartment KitsWhen selecting a power module withan auxiliary compartment, an AuxiliaryCompartment Kit is needed. Chooseone of the descriptive models frompage 10, then enter it on Vista orderentry suffix Q17.
Main Bus SupportsWhen selecting main bus supports,you must know the voltage class, BILwithstanding, and the continuouscurrent rating. Choose one of thedescriptive models from page 11, thenenter it on Vista order entry suffix Q17.
III. Select the Proper VCP-W 5/15 kVAccessories15 kV VCP-W AccessoriesThere are two different sets ofaccessories for the 5/15 kV breakers.A set for the 36" wide design and aset for the 26" narrow design. Theseaccessories can be found on page 11for the wide design and on page 12 forthe narrow design.A TOC (Truck Operated Cell) Switch isrequired when a customer wishes tohave auxiliary contacts to indicate ifthe breaker is in the connected or disconnected position. A MOC(Mechanism Operated Cell) Switch is ordered when a customer requiresadditional auxiliary contacts to indicatewhen the breaker is in the open orclosed state. An MOC is designed tooperate in the connect position only orboth test and connect positions.A set of standard accessories includes;a left and right removable extensionrail, rail clamps, manual charginghandle, lifting yoke, levering crank,and a primary contact spanner wrenchfor narrow design only.Optional accessories include; a testcabinet, spin-free levering crank,test jumper, portable lifter, dockingtransport dolly, drawout ramp andlifting yoke.Manual Ground and Test Devices, BailType Manual Ground and Test Devices,Electrical Manual Ground and TestDevices, and Dummy Elements stylenumbers can be found on page 13 andentered on Vista Order Entry SuffixQ20.Note: You must order these accessories by theirstyle numbers on Vista order entry suffix Q17.
All drawings referenced in this price listcan be found in the 5/15 kV VCP-WOEM Handbook KT01301001E
Circuit Nominal Nominal Voltage Insulation Level Current Inter- Permis- Maximum Current ValuesBreaker Voltage 3-Phase Maximum Voltage Withstand Contin- Short rupting sible Voltage Maximum Closing ClosingType Class MVA Voltage Range Test Voltage uous Circuit Time Tripping Divided Symmetrical and and
Class Factor Current Current Delay By K Interrupting Latching Latchingat 60 Hz (at Rated Capability Capability Momentary
Max. kV) CapabilityPower Impulse 2 2
Fre- Shortquency Time
2 (1 min.) Current
E K I Y E/K K x 1kV MVA kV rms kV rms kV Peak Amperes kA rms Cycles Seconds kV rms kA rms kA Peak kA rms . . lbs.
ANSI Standard Ratings1VCP-W Vacuum Circuit Breaker Types Rated on Symmetrical Current Rating Basis
Identification Rated Values Weight
1 Applicable ANSI Standards C37.04-1999, C37.06-2000 (including both K>1 and K=1 ratings), and C37.09-1999.2 See Consulting Application Guide for further information.
Circuit Voltage Insulation Level Normal Short Circuit Short CableBreaker Power Impulse Current Breaking Current Circuit ChargingType Frequency Withstand and 3-sec. Making Breaking
Short Time Current Current CurrentkV rms kV Peak kV Peak Amperes kA rms kA Peak Amperes.. kg