5/4/12 1 Valdez Marine Terminal Status of Crude Oil Storage Tank Inspections OSPR, TOEM Committees PWSRCAC Staff: Tom Kuckertz, Linda Swiss Contractor: Harvey Consulting May 2012 Board Meeting Why Are Internal Tank Inspections Important? 1. Critical Oil Spill Prevention Measure 2. Collects Data that External Inspections Do Not 3. Evaluates Tank Foundation, Bottom, Shell, Structure, Roof, Nozzles, and Fire System 4. Protects Environment 5. Protects Personnel 6. Protects Asset
11
Embed
Valdez Marine Terminal Status of Crude Oil Storage Tank ... · May 2012 Board Meeting ... API 653 Tank Inspection Industry Standard ... Valdez Marine Terminal Status of Crude Oil
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
5/4/12
1
Valdez Marine Terminal Status of Crude Oil Storage Tank Inspections
OSPR, TOEM Committees PWSRCAC Staff: Tom Kuckertz, Linda Swiss Contractor: Harvey Consulting
May 2012 Board Meeting
Why Are Internal Tank Inspections Important?
1. Critical Oil Spill Prevention Measure
2. Collects Data that External Inspections Do Not
3. Evaluates Tank Foundation, Bottom, Shell, Structure, Roof, Nozzles, and Fire System
(1) may be reduced by the department for tanks (A) over 30 years old (B) that is riveted
(C) with demonstrated structural, corrosion or foundation problem, or (D) after a seismic event
5/4/12
7
ADEC Regulations on Tank Inspections Intervals
Meaning that to extend a tank inspection interval beyond 10 years there must be tank floor corrosion data for that tank
18 AAC 75.065
Field-Constructed Aboveground Oil Storage Tank Requirements. (a) Must follow API 653 inspection standard (b) may not be based on similar service
ADEC Regulations on Tank Inspections Intervals
18 AAC 75.065
Inspection intervals for a field constructed aboveground oil storage tank (3) may be based upon risk-based inspection . . . assessment must include
(A) a quantitative risk assessment, signed by a registered engineer and conducted in accordance with the American Petroleum Institute’s Risk Based Inspection . . . (API RP 580).
5/4/12
8
ADEC Regulations on Tank Inspections Intervals
18 AAC 75.015
Waiver. (a) The dept may waive a requirement . . . if the owner . . . demonstrates to the dept’s satisfaction that an equivalent level of protection will be achieved by using a technology or procedure other than the technology or procedure required by 18 AAC 75.005-18 AAC 75.085.
Current Tank Status
5/4/12
9
Table 2-7 VMT C-Plan Sets Inspection Dates
2
Tanks Currently Out of Service
West Tank Farm East Tank Farm
17 15
18 16 13 11 9 7 5 3 1
14 12 10 8 6 4 2
5/4/12
10
2 West Tank Farm East Tank Farm
Tanks with 1 API 653 internal inspections
Tanks with 2 API 653 internal inspections
17 15
18 16 13 11 9 7 5 3 1
14 12 10 8 6 4 2
2
Tanks with 20 year extensions
West Tank Farm East Tank Farm
17 15
18 16 13 11 9 7 5 3 1
14 12 10 8 6 4 2
1
2
3
4612
5/4/12
11
2
Tanks Requiring Inspection in 2012
West Tank Farm East Tank Farm
17 15
18 16 13 11 9 7 5 3 1
14 12 10 8 6 4 2
Recently Extended to 2014 Extension Rejected