8/2/2019 Un Symmetrical Faults
1/201
Un-Symmetrical Faults
Symmetrical components The method of symmetrical components is a powerful
technique for analyzing unbalanced three phase systems.
It is a linear transformation that transforms from phasecomponents to a new set of components called symmetricalcomponents.
The advantage of this transformation for balanced three phasenetworks the equivalent circuit obtained called the sequencenetwork are separated into three uncoupled networks.
For unbalanced three phase systems, the three sequencenetworks are connected only at point of unbalance.
Decoupling a detailed three phase network into three simplersequence networks reveals complicated phenomena.
8/2/2019 Un Symmetrical Faults
2/202
Symmetrical components Assume that a set of three phase voltages designated Va, Vb
and Vc is given.
These phase voltages are resolved into the following threesets of sequence components:
a) Zero sequence components: consisting of three phasors withequal magnitudes and zero phase displacement.
b) Positive sequence components: consisting of three phasorswith equal magnitudes and 120 phase displacement andpositive sequence.
c) Negative sequence components: consisting of three phasors
with equal magnitudes and 120 phase displacement andnegative sequence.
Symmetrical components
Zero sequence
components Positive sequencecomponents
Negative sequence
components
Va0Vb0
Vc0
Va1
Vb1
Vc1
Vb2
Vc2
Va2
Va = Va1 + Va2 + Va0
Vb = Vb1 + Vb2 + Vb0
Vc = Vc1 + Vc2 + Vc0
8/2/2019 Un Symmetrical Faults
3/203
Symmetrical components
Zero sequence
componentsPositive sequencecomponents
Negative sequencecomponents
Va0
Vb0Vc0
Va1
Vb1
Vc1
Vb2
Vc2
Va2
Va
Vb
Vc
Symmetrical components
Va = Va1 + Va2 + Va0 Vb = Vb1 + Vb2 + Vb0 Vc = Vc1 + Vc2 + Vc0
Let us define the following operator a as follows:
1201=a 24012
=a
1
2
1 ab VaV = 11 ac aVV=
22 abaVV =
2
2
2 acVaV =
00 abVV = 00 ac VV =
=
2
1
0
2
2
1
1
111
a
a
a
c
b
a
V
V
V
a a
aa
V
V
V
8/2/2019 Un Symmetrical Faults
4/204
Symmetrical components
=
2
2
1
1
111
a a
aa
A
=
aa
a a
A
2
21
1
1
111
3
1
=
c
b
a
a
a
a
V
V
V
aa
a a
V
V
V
2
2
2
1
0
1
1
111
3
1)(
3
10 cbaa VVVV ++=
)(3
1 21 cbaa VaaVVV ++=
)(3
1 22 cbaa aVVaVV ++=
Symmetrical components
)(3
10 cbaa VVVV ++=
This equation shows that no zero sequence components exists if the sum of
the unbalanced phasors is zero.
Since the sum of the line-line voltage phasors in a three phase system is
always zero (Why?), zero sequence components are never present in the linevoltages regardless of the amount of unbalance.
However, the sum of the three line-neutral voltage phasors is not necessaryzero and hence line-neutral voltages may contain zero sequence components.
8/2/2019 Un Symmetrical Faults
5/205
Symmetrical components
)(3
10 cbaa IIII ++=
)(3
1 21 cbaa IaaIII ++=
)(3
1 22 cbaa aIIaII ++=
The previous set of equations can be written for currents as well as shown below:
021 aaaa IIII ++=
021 bbbb IIII ++=
021 cccc IIII ++=
In a three phase system, the sum of the line currents is equal to the current Inin the return path
ncbaIIII =++ )( 03 an II =
Example 1:
+
=
120277
120277
0277
cn
bn
an
V
V
V
Calculate the sequence components of the following balanced line-neutralvoltages with abc sequence:
Solution:
0)(3
1
0=++=
cbaVVVV
0277)(3
1 21 =++= cba VaaVVV
0)(3
1 22 =++= cba aVVaVV
8/2/2019 Un Symmetrical Faults
6/206
Example 2:
+
=
12010
12010
010
c
b
a
I
I
I
A Y connected load has balanced currents with acb sequence as follows, find thesequence currents:
Solution:
0)(3
10 =++= cba IIII
0)(31 2
1 =++= cba IaaIII
010)(3
1 22 =++= cba aIIaII
Example 3:
=
12010
0
010
c
b
a
I
I
I
A three phase line feeding a balanced Y load has on of its phases (phase b)open. The load neutral is grounded and the unbalanced currents are
Calculate the sequence and neutral currents:
Solution:
6033.3)(3
10 =++= cba IIII
067.6)(3
1 21 =++= cba IaaIII
6033.3)(3
1 22 =++= cba aIIaII
6010)( =++=cban
IIII
60103 0 == IIn
OR
8/2/2019 Un Symmetrical Faults
7/207
21 aaaoIII ++
Representing the unbalance currents withtheir symmetrical components we get:
cban IIII ++=
21 bbboIII ++ 21 ccco III +++= +nI
coboaoIII ++
4434421
0
111
zer
cbaIII ++
4434421
zero
cbaIII
222+++= +nI
aoI3=nI
Since the positive and negative sequence components are add to zero at theneutral point, therefore there is no positive or negative sequence components
flow from the neutral to the ground.
1. The Sequence circuits for Wye
and Delta connected loads
For the star connected load withgrounded neutral point,
YZaI
bI
cI
YZYZ
abV
bcV
caV
aonI3I ====
anV
nV
n
Under unbalance condition:
aoI3=nI
naonnn ZIZIV 3==
The voltage drop between neutraland ground is:
It is very important to distinguish between voltages to neutral and voltages to ground.
naoannana ZIVVVV 3+=+=
=
c
b
a
V
V
V
cn
bn
an
V
V
V
naoZI3+
+
n
n
n
V
V
V
1
1
1
c
b
a
I
I
I
YZ=
For unbalance threephase system, the phase
voltages are:
YZaI
bI
cI
YZYZ
abV
bcV
caV
aon I3I ====
anV
nV
n
8/2/2019 Un Symmetrical Faults
8/208
2
1
a
a
ao
I
I
I
AYZ====
2
1
a
a
ao
V
V
V
A naoZI3++++
1
1
1
Multiplying byA-1
Using the symmetricalcomponents:
2
1
a
a
ao
I
I
I
YZ====
2
1
a
a
ao
V
V
V
naoZI3++++
1
1
1
1A
2
1
a
a
ao
I
I
I
YZ=
2
1
a
a
ao
V
V
V
naoZI3+
0
0
1
aooao
aonYao
IZV
I)Z3Z(V
====
++++====
22
11
aYa
aYa
IZV
IZV
=
=
OREq. 1
Eq. 2
Eq. 3
nYoZZZ 3+=
11 aYa IZV =
aoI
aoV
YZ
nZ3
n
oZ
22 aYaIZV =
1aI
+aV
YZ n
1Z
aonYao IZZV )3( +=
2a
I
aV
YZ n
2Z
Using the three previous
equations (Eqs. 1, 2 and 3)then the Symmetrical circuitsfor a Wye-connected load
with neutral point connectedto ground is:
YZaI
bI
cI
YZYZ
abV
bcV
caV
aon II 3=
anV
nV Positive Sequence Circuit
Negative Sequence Circuit
Zero Sequence Circuit
8/2/2019 Un Symmetrical Faults
9/209
1aI
1aV
YZ n
1Z
2aI
2aV
YZ n
2Z
YZ
aI
bI
cI
YZYZ
abV
bcV
caV anV
If the neutral point of a Y-connected load is notgrounded, therefore, no zero sequence current
can flow, and
Symmetrical circuits for Y-connected load
with neutral point is not connected to groundare presented as shown:
====nZ
aoI
ao
V
YZ n
oZ ====nZ
Y-connected load (Isolated Neutral):
Zero Sequence Circuit
Positive Sequence Circuit
Negative Sequence Circuit
The Delta circuit can not provide a path through neutral. Therefore for a Deltaconnected loador its equivalent Y-connectedcan not contain any zero sequence
components.
Delta connected load:
ZZ
Z
aI
bI
cI
abV
bcV
caVabI
bcI
caI
abab IZV ====
bcbc IZV ====
caca IZV ====
0V)VVV(3
10abcabcab ========++++++++
The summation of the line-to-line voltages
or phase currents are always zero
and
Therefore, for a Delta-connected loadswithout sources or mutual coupling there will be no
zero sequence currents at the lines (There are some cases where a circulating currents maycirculate inside a delta load and not seen at the terminals of the zero sequence circuit).
aoI
aoV
nZ 1aI
1aV
n3/Z
2aI
2aV
n3/Z
0I)III(3
10abcabcab ========++++++++
NegativeSequence
Circuit
PositiveSequence
Circuit
ZeroSequence
Circuit
8/2/2019 Un Symmetrical Faults
10/2010
The Delta circuit have balanced impedances of21 ohms. Determine the sequence impedances.
Example:
The positive- and negative-sequence circuits have per-phase
impedance
==
73/1 ZZ
==
73/2 ZZ
Solution:
ZZ
Z
aI
bI
cI
abV
bcV
caVabI
bcI
caI
The zero-sequence circuit have per-phaseimpedance of 21 ohms. Thezero sequence current is circulating in Delta circuit.
aoI
aoV
nZaoI
aoV
nZ +aI
+aV
n3/Z
+aI
+aV
n3/Z
aI
aV
n3/ZaI
aV
n3/Z
2. Sequence Circuits ofTransmission Lines
Consider a symmetrical transmission
line where,
Zaa: is the self-impedance and is the same for each phase
Zab: is the mutual-impedance between each two phases
Znn: is the self-impedance of the neutral conductor
Zan: is the mutual-impedance between the neutral and each phase
bI
cI
aI
anZabZ
nI
a
b
c
n
a
b
c
n
aaZ
nnZ
aaZ
aaZ
nnncanbanaan
nanancabbabaaaan
IZIZIZIZ
VIZIZIZIZV
++++++++++++++++==== Using KVL
The voltage drop across the line section is:
nnnancanabbanabaanaanaan I)ZZ(I)ZZ(I)ZZ(I)ZZ(VV ++++++++++++====
Similarly, for phases b and c:
nnnancbanabaanaanaan I)ZZ()II)(ZZ(I)ZZ(VV ++++++++++++==== Eq. 1
ccbbaa ZZZ ========
bcacab ZZZ ========
cnbnan ZZZ ========
212111 IMjILjV ++++====
8/2/2019 Un Symmetrical Faults
11/2011
nnnanbaanabcanaanccn I)ZZ()II)(ZZ(I)ZZ(VV ++++++++++++====
nnnancaanabbanaanbbnI)ZZ()II)(ZZ(I)ZZ(VV ++++++++++++====
The neutral current is:)III(I
cban++++++++====
Substituting Eq. 4 intoEqs. 1,2 and 3
Eq. 2
Eq. 3
Eq. 4
)III)(ZZ()II)(ZZ(I)ZZ(VV cbannancbanabaanaanaan ++++++++++++====
cannnabbannnabaannnaanaan I)Z2ZZ(I)Z2ZZ(I)Z2ZZ(VV ++++++++++++++++++++====
cannnabbannnaaaannnabnbbn I)Z2ZZ(I)Z2ZZ(I)Z2ZZ(VV ++++++++++++++++++++====
cannnaabannnabaannnabnccn I)Z2ZZ(I)Z2ZZ(I)Z2ZZ(VV ++++++++++++++++++++====
annnaas Z2ZZZ ++++====
annnabm Z2ZZZ ++++====
Let:
smm
msm
mms
ZZZ
ZZZZZZ
Then, the voltage drops across the lines are
c
b
a
I
II
)ZZ(00
0)ZZ(0
00)ZZ(
ms
ms
ms
====
nccn
nbbn
naan
VV
VVVV
====
cc
bb
aa
V
VV
Using symmetrical components and rearranging the impedance matrix, we get:
=
2
1
0
aa
aa
aa
V
V
V
A
++++
mmm
mmm
mmm
ZZZ
ZZZ
ZZZ
2
1
0
a
a
a
I
I
I
A
++++
111
111
111
Z
100
010
001
)ZZ(A mms1
Multiplying by A-1
2
1
0
a
a
a
I
I
I
A=
2
1
0
aa
aa
aa
V
V
V
8/2/2019 Un Symmetrical Faults
12/2012
Or,
=
2'
1'
0
aa
aa
aa
V
V
V
++++
)ZZ(00
0)ZZ(0
00)Z2Z(
ms
ms
ms
2
1
0
c
b
a
I
I
I
msoZZZ 2+=
msZZZ =1
msZZZ =2
annnaas ZZZZ 2++++====
annnabm ZZZZ 2++++====
Where,
Therefore,
Substituting forms ZandZ
)2(2)2( annnabannnaao ZZZZZZZ ++++++++++++====
msoZZZ 2++++====
annnabaao ZZZZZ 632 ++++++++====
aoIa
n
a
n
0anV 0naV oZ
)2()2(1 annnabannnaa ZZZZZZZ ++=
msZZZ =1
abaaZZZ =
1
msZZZZ == 12
abaaZZZ =2
And
++++Z
++++aI
a
n
a
n
++++anV
++++naV
aI
Z
a
n
a
n
anV
naV
The positive and negative sequence impedances are equal and dont include the neutral
conductor impedances . The return path conductors enter into the zero
sequence impedances only.
)ZorZ( annn
Notes:
The ground wires (above overhead TL) combined with the earth works as a neutral
conductor with impedance parameters that effects the zero sequence
components. Having a good grounding (depends on the soil resistively), then the voltages
to the neutral can be considered as the voltages to ground.
)ZandZ( annn
8/2/2019 Un Symmetrical Faults
13/2013
3. Sequence Circuits of Synchronous Machines
aI
bI
anE
cnE
cI
nInZ
bnE
aI
bI
anE
cnE
cI
nInZ
bnE
3. Sequence Circuits of Synchronous Machines
Positive Sequence Circuit:
The windings of a synchronous machine are
symmetrical.
Thus the generator voltages are of positive
sequence only.
The positive sequence network consists of an
EMF (equal to no-load terminal voltage) in series
with the positive sequence impedance of the
machine.
++++aI
++++bI
anE
cnE
++++cI
bnE
++++Z
++++Z
++++Z
++++aI
++++bI
anE
cnE
++++cI
bnE
++++Z
++++Z
++++Z
++++aV++++Z
Ean ++++aV++++Z
Ean
The neutral impedance (Zn) does not appear in this
circuit because no positive sequence current will
flow through it.
0111=++
cbaIII
8/2/2019 Un Symmetrical Faults
14/2014
aI
aVZ
Negative Sequence Circuit:
The synchronous machine does not generate any negative sequence voltages.
Z
ZZ
aI
bI
cI
Z
ZZ
aI
bI
cI
Zero Sequence Circuit:
No zero sequence voltage is included in a synchronous machine.
goZ
aoI
boI
coI
nZgoZ
goZaoI3
goZ
aoI
boI
coI
nZgoZ
goZaoI3
aoI
aoV
nZ3
goZ
aoI
aoV
nZ3
goZ
aocoboao IIII 3====++++++++
goZ :Zero sequence impedanceper phase.
gono ZZZ ++++==== 3
++++aVEan
++++Z01
aoI
aoV
nZ3
goZ
aI
aVZ
++++aVEan
++++Z01
aoI
aoV
nZ3
goZaoI
aoV
nZ3
goZ
aI
aVZ
aI
aVZ
Zero
Sequence
Negative
Sequence
Positive
Sequence
Symmetrical
Circuits
aI
bI
anE
cnE
cI
nInZ
bnE
aI
bI
anE
cnE
cI
nInZ
bnE
Summary of the threesequence circuits
8/2/2019 Un Symmetrical Faults
15/2015
4. Sequence Circuits of Delta and Wye Transformers
A. Wye-Wye Bank, Both
Neutrals GroundedWith both wyes grounded, zeroWith both wyes grounded, zero
sequence current can flow. Thesequence current can flow. The
presence of the current in onepresence of the current in one
winding means that secondarywinding means that secondary
current exists in the other.current exists in the other.
A
B
C
N
a
b
c
n
NZ nZ
210 AAAAIIII ++=
210 BBBB IIII ++=
210 CCCCIIII ++=
++++++++++++==== aa0aa IIII
0AI3 0aI3
A
N
a
n
NZ nZ
++++++++++++==== AA0AA IIII
++++++++++++==== aa0aa IIII
0AI3 0aI3
ANV anV
A
VaV
TheThe flowflow ofof thethe sequencesequence currentscurrents dependdepend onon thethe windingwinding connectionsconnections.. TheThe differentdifferent
installationsinstallations ofofDeltaDelta--WyeWye windingswindings determinedetermine thethe configurationconfiguration ofof thethezerozero sequencesequence
circuitcircuitandand thethephasephase shiftshift inin thethe positivepositive andand negativenegative sequencesequence circuitscircuits..
NANA VVV ++++====
N0AANAN0ANAA0A ZI3)VVV(VVV ++++++++++++====++++++++ ++++++++
The negative- and positive-sequence
voltages to ground are equal to negative-
and positive-sequence voltages to
neutral.
. Eq. 1
. Eq. 2
Two linked windingsTwo linked windings
Similarly, on the low voltage side
n0aanan0anaa0a ZI3)VVV(VVV ++++++++====++++++++ ++++++++
nana VVV ====
The voltages and currents on both sides of the transformer are related by the turns
ration (N1/ N2). Therefore,Eq. 4 can be written as
0A
2
1nAN
1
2AN
1
20AN
1
2aa0a I)
N
N(Z3)V
N
NV
N
NV
N
N(VVV ++++++++====++++++++
++++++++
MultiplyingEq. 5 by (N1/ N2).
0A
2
2
1nANAN0ANaa0a
2
1 I)N
N(Z3VVV)VVV(
N
N++++++++====++++++++
++++++++
Substituting fromEq. 2 for N0AAA0AANAN0AN ZI3VVV)VVV( ++++++++====++++++++ ++++++++
0A
2
2
1n0ANAA0Aaa0a
2
1 I)N
N(Z3IZ3VVV)VVV(
N
N++++++++====++++++++
++++++++
. Eq. 3
. Eq. 4
. Eq. 5
. Eq. 6
Then,
. Eq. 7
By equating voltages of the same sequence, we can write
The negative sign comesfrom the direction of thezero sequence current
8/2/2019 Un Symmetrical Faults
16/2016
Eq. 9 represents the relation for the zero sequence. This relation can be represented
as shown in the Fig. When the voltages on both sides of the transformer are
expressed in per unit, the turns ratio becomes unity. The zero sequence
impedance of the circuit, (adding the leakage impedanceZ), is:
21N:N 0a
I
0AV 0aV0AI
n
2
2
1 Z)N
N(3
NZ3
unitperZ3Z3ZZ nN0 ++++++++==== . Eq. 10
Z
0A
2
2
1nN0A0a
2
1 I])N
N(Z3Z3[VV
N
N++++==== . Eq. 9
++++++++==== Aa
2
1 VVN
N
==== Aa2
1 VVN
N
This is similar to a regular transformer, and therefore, the positive
and negative sequence circuits for a transformer are applicable.
. Eq. 8and
ZZ++
Reference Bus
ZZ++
Reference Bus
ZZ--
Reference Bus
ZZ--
Reference Bus
Z
Z
Reference Bus
A. WyeA. Wye--Wye bank with both neutrals groundedWye bank with both neutrals grounded,,
zero sequence current can flow. The presence ofzero sequence current can flow. The presence ofthe current in one winding means that secondarythe current in one winding means that secondary
current exists in the other. The equivalent circuit iscurrent exists in the other. The equivalent circuit is
as shown in the Figure.as shown in the Figure.
B.B. WyeWye--wyewye Bank, One Neutral GroundedBank, One Neutral Grounded
With ungroundedWith ungrounded wyewye, no zero sequence current, no zero sequence current
can flow. No current in one winding means that nocan flow. No current in one winding means that no
current exists in the other.current exists in the other.Reference Bus
C.C. WyeWye--delta Bank, Groundeddelta Bank, Grounded WyeWye
Zero sequence currents will pass through theZero sequence currents will pass through the wyewye
winding to ground. As a result, secondary zerowinding to ground. As a result, secondary zero
sequence currents will circulate through the deltasequence currents will circulate through the delta
winding.winding.No zero sequence current will exist on theNo zero sequence current will exist on thelines of the secondarylines of the secondary..
Reference Bus
ZZ =0
ZZ =0
Z
OC
OC
Z
E. DeltaE. Delta--delta Bankdelta Bank
Since for a delta circuit no return path for zero sequenceSince for a delta circuit no return path for zero sequence
current exists,current exists, no zero sequence current can flow into ano zero sequence current can flow into a
deltadelta--delta bankdelta bank, although it can circulate within the, although it can circulate within the
delta windings.delta windings.
Reference Bus
Z
OCOC
8/2/2019 Un Symmetrical Faults
17/2017
Summary of Transformer Sequence Networks
Transformer Zero Sequence Impedance
ExampleExample 44: Draw the sequence circuits for the network.
T1G1
J0.02
T2
220 kV Transmission Line
1
2 34220 kV Transmission Line
G2
J0.03
G1
MVA X+Voltage X - Xo
100 0.2511 kV 0.25 0.05
G2 100 0.2011 kV 0.20 0.05
T1 100 0.0611/220 0.06 0.06
T2 100 0.0711/220 0.07 0.07
Line 100 0.10220kV 0.10 0.30
8/2/2019 Un Symmetrical Faults
18/20
8/2/2019 Un Symmetrical Faults
19/2019
T1G1
J0.02
T2
220 kV Transmission Line
1
2 34220 kV Transmission Line
G2
J0.03
J0.2J0.07J0.25 J0.06
J0.1
J0.1
Negative Sequence Circuit
T1G1
J0.02
T2
220 kV Transmission Line
2 34220 kV Transmission Line
G2
J0.03
1
2 3
1J0.05J0.07
J0.09
J0.06
J0.3
J0.3
J0.05
J0.06
4
Zero Sequence Circuit
8/2/2019 Un Symmetrical Faults
20/20