UL/FM Fire Pump Systems Lunch & Learn

04/18/05

Page 2: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Rules & Regulations

NFPANFPA CEACEAComité Européen Des AssurancesComité Européen Des Assurances

(European)(European)National Fire Protection AssociationNational Fire Protection Association

((North America)North America)

Page 3: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Fire Protection Pumps• End Suction Pumps• Vertical In-line • Horizontal Split Case • Vertical Mounted Split Case• Vertical Turbine

Page 4: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Compliance to NFPA 20

• 100% Flow at 100% Head

• Maximum of 140% of Head at Shutoff

• Minimum of 65% of Head at 150% of Flow

Page 5: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Maximum Allowed Pressure• The pump shutoff pressure plus the maximum

static suction pressure shall not exceed the pressure for which the system components are rated for.

• Pressure relief valves shall not be used as a means to meet this requirement.

• Variable speed pressure limiting control drivers are acceptable in meeting this requirement (new in NFPA 2003).

Page 6: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Fire Pump Drivers• Electric Motors• Diesel Engines• Steam Turbines• Combination of the above

Page 7: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Fire Pump Accessories• Suction pressure/vacuum gauge.• Discharge pressure gauge.• Automatic air release valve• Casing relief valve (electric driven)• Main pressure relief valve (diesel driven

and VFD applications)

Page 8: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Suction Pipe & Fittings• Suction can be either from a city water supply or

a fire water storage tank.• Suction shall be sized so that at 150% of rated

capacity the velocity in the suction pipe located 10 pipe diameters upstream of the pump suction flange shall not exceed 15 ft/sec.

• Concentric reducers are not allowed in the suction piping.

• UL/FM OS&Y gate valve only.

Page 9: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Discharge Pipe & Fittings

Page 10: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Relief Valves• Used on Diesel Engines• Used with Variable speed pressure limiting

control devices• Spring direct acting or pilot operated.• Relief discharges to an open or closed

waste cone.• Discharges to suction source or splash

block

Page 11: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Test Meters• Where water usage or discharge is not permitted

for the duration of the test.• Installed with upstream and downstream pipe

runs per meter manufacturer.• Where meter downstream run goes back to

suction side of pump proper pipe runs must be followed per NFPA-20.

• A throttling valve shall be installed downstream of the flow meter.

Page 12: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Hose Valve Test Header• Hose test valves are rated for 250 GPM.• Hose valves shall be mounted on a test

head.• A UL/FM isolation valve shall be installed

upstream of the test head.• A Ball drip valve shall be installed if the

test head is mounted outside the building to prevent freezing.

Page 13: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Specialty Valves & Accessories• Backflow Preventers• Suction Control Valves• Pressure Regulating Valves• Alarm Check Valves• Siemese Valves• Tamper Switches• Flow Switches

Page 14: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Pressure Sensing Lines

Page 15: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Electric Drive Pumps• Power derived by a reliable power source

or two or more approved independent sources.

• Second power source shall be from a second utility or on-site power generation

• Automatic Transfer switch to be used if two or more power sources are used.

Page 16: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Electric Drive Starting Methods• Across The Line• Part Winding• Wye Delta (open)• Wye Delta (closed)• Primary Resistance• Auto Transformer• Solid State

Page 17: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Electric Driven Power Supply Arrangement

Page 18: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Diesel Engine Driven Accessories

• Cooling System• Fuel system• Raw Water outlet Drain• Battery Racks• Exhaust System• Air Intake Louver for Engine Air Intake

(used with buildings)

Page 19: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Fuel System design

Page 20: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

Pressure Maintenance Pumps• Rated for not less than normal leak load.

(normally 1% of rated fire flow and 10 psig above rated boost pressure.

• Discharge pressure shall be sufficient to maintain desired system pressure.

• Where the shutoff pressure is greater than the pressure ratings of the system components a relief valve shall be installed on the pump discharge.

Page 21: UL/FM Fire Pump Systems - · PPT file · Web viewUL/FM Fire Pump Systems Lunch & Learn 04/18/05 Rules & Regulations Fire Protection Pumps End Suction Pumps Vertical In-line Horizontal

House Utilities (per NFPA-20)• Approved or listed source of heat• Artificial Lighting• Emergency lighting (including fixed and

portable).• Ventilation• Drainage• Convenience outlet