asi-ez.com Branch or Supplemental Circuit Protection? UL489 or UL1077 Circuit Breakers? What You Need to Know to pick the correct circuit protection for your application.
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: UL489 or UL1077 DIN Rail Circuit Breakers

1

UL489 or UL1077What you need to know to ensure you have

the right circuit protection for your application

www.asi-ez.com 877-650-5160

By: Richard Goodhart, Product Manager

Automation Systems Interconnect

[email protected]

Page 2: UL489 or UL1077 DIN Rail Circuit Breakers

2

Branch Protection

UL489 Listed

www.asi-ez.com 877-650-5160

UL489

Page 3: UL489 or UL1077 DIN Rail Circuit Breakers

3

“Branch circuit protection refers

to circuit protection at the panel box”

- Kenneth Cybart,

Electronic Design

www.asi-ez.com 877-650-5160

UL489

Page 4: UL489 or UL1077 DIN Rail Circuit Breakers

4

Applications: Control Panels Panel-Boards Switchboards Motor Control Centers

www.asi-ez.com 877-650-5160

UL489

Page 5: UL489 or UL1077 DIN Rail Circuit Breakers

5

Required for: - Convenience receptacle circuits (internal or external)

- External load circuit leaving the equipment

- Motors in equipment

- HACR equipment (heating, air Conditioning and Refrigeration)

www.asi-ez.com 877-650-5160

UL489

Page 6: UL489 or UL1077 DIN Rail Circuit Breakers

6

Supplemental Protection UL1077 Recognized

www.asi-ez.com 877-650-5160

UL1077

Page 7: UL489 or UL1077 DIN Rail Circuit Breakers

7

“supplementary overcurrent protective device is intended to

provide limited overcurrent protection for specific

applications and equipment” – UL

Reference: Supplementary Protection or

Branch Circuit Overcurrent Device

www.asi-ez.com 877-650-5160

UL1077

Page 8: UL489 or UL1077 DIN Rail Circuit Breakers

8

Applications: Control Circuits Power Transformers Relays PLC I/O Points Lighting Circuits

www.asi-ez.com 877-650-5160

UL1077

Page 9: UL489 or UL1077 DIN Rail Circuit Breakers

9

Applications:

Provides additional protection for sensitive electronics

Load side branch protection: Computers and microprocessors, Communication equipment, Electronic controllers, Power supplies, and Many other types of equipment

Motor control circuit without transformers in circuit per NEC 430-72

www.asi-ez.com 877-650-5160

UL1077

Page 10: UL489 or UL1077 DIN Rail Circuit Breakers

10

Great Replacement for Fuses!

www.asi-ez.com 877-650-5160

UL1077

Page 11: UL489 or UL1077 DIN Rail Circuit Breakers

11

UL1077 Circuit Breaker (Supplemental) Cannot Be Used in Place of a UL489 Circuit Breaker (Branch)

www.asi-ez.com 877-650-5160

UL1077

Page 12: UL489 or UL1077 DIN Rail Circuit Breakers

12www.asi-ez.com 877-650-5160

Feeder Circuit UL489 Miniature Circuit Breaker (MCB)

UL489 MCB

Outlet

UL1077 MCBPower Supply

UL1077 MCBComputer

UL489 MCB ExternalMotor

UL489 MCBHeatingUnit

UL1077 MCB CommunicationEquipment

Application Example