UK PERKINS APS P13 kVA GENERATOR FEATURES ENGINE DATA ALTERNATOR DATA Manufacturer/Model Cylinder Arrangement Displacement Bore And Stroke Compression Ratio Rated Rpm Gross Bhp @ Prime Power Gross Bhp @ S.By Power Governor Type UK Perkins, 403A-15G 3 Vertical In line 1.496 Litres 84 x 91 mm 22.5 : 1 1500 16.5 18.1 Mechanical Manufacturer Number of Phase Power factor Number of pole Insulation Temperature Rise Total Harmonics (TGH/THC) Exciter Type Number Of Bearing Mecc alte UK/ Leroy somer TAL 3 0.8 4 Class H Class F < 2% (AT NO LOAD) Shunt One POWER FEATURES Prime Power – 400/230V @ 50 Hz: 10.4 kW / 13 kVA Stand by Power- 400/230V @ 50 Hz: 11.4 kW / 15 kVA Ÿ Engine (UK Perkins 403A-15G) Ÿ 12v Charge alternator Ÿ Governor: Mechanical Ÿ Alternator (Mecc alte UK / Leroy somer TAL) Ÿ Single bearing alternator IP 23,insulation class H Ÿ Radiator 50° C (122 F) Ÿ Skid and vibration isolators Ÿ Dry type air filter Ÿ Main line circuit breaker Ÿ 12v Battery , Rack and Cable Ÿ Industrial silencer Ÿ User manual OPTIONAL ITEMS Engine & Radiator Ÿ Heat shield protection exhaust Ÿ Oil drain extension Ÿ Lube oil drain pump Ÿ Stone Protection guard Ÿ Battery charger Ÿ Engine Block heater Ÿ Battery Isolator Fuel System Ÿ 12 or 24 Hours day tank Ÿ Bulk fuel tank connections Ÿ Fuel / Water separator filter (Racor) Alternator Ÿ Anti-Condensation Heater Ÿ Alternator Dust Filters Ÿ PMG excitation Ÿ Single phase Exhaust Ÿ Residential, Critical Silencer Ÿ Flexible exhaust connection Enclosure Ÿ EM-1,5 Ÿ 75 dBA @ 1m Ÿ Dimension mm (L x W x H) – 1560 x 760 x 960 Control Panel Ÿ Deep sea Electronics * For more technical information, please refer to the website below. RPP: Prime Power is available for an unlimited number of annual operating hours in variable load applications, in accordance with ISO 8528-1. A 10% overload capability is available for a period of 1 hour within 12hour period of operation, in accordance with ISO 3046-1. ESP: The standby power rating is applicable for supplying emergency power in variable load applications in accordance with ISO 8528-1. Overload is not allowed Picture shown above is only for illustration purpose, May contain optional item. In Line with Our Policy of Continuous Development, We reserve The Right to Change Specification without Notice www.apsuae.com