Northern California: 7977 Capwell Drive, Suite 100 • Oakland, CA 94621 • (510) 638-8400 • Fax (510) 638-8404 Southern California: 1055 Wilshire Blvd., Suite 1450, Los Angeles, CA 90017 • (213) 353-1240 • Fax (213) 353-1244 November 25, 2013 Mr. Greg Secor Transmitted via email:[email protected] University of California at Davis Design & Construction Management 255 Cousteau Place Davis, CA 95618 Re: Asbestos and Lead Surveys for Seismic V Project University of California at Davis, Central Plant, Med Sci 1B, Olson Hall and Wright Hall One Shields Avenue, Davis, California ACC Project #: 3028-067.00 Dear Mr. Secor: Per your request, ACC Environmental Consultants, Inc. (ACC) performed limited asbestos surveys of The Central Plant, Med Sci 1B, Olson Hall and Wright Hall, located at University of California, One Shields Avenue, Davis, California, in October and November of 2013. The surveys of the referenced sites were performed to identify suspect asbestos-containing building materials and loose & peeling lead-containing paint that may be impacted during the planned preliminary investigation project. Common suspect asbestos-containing building materials that may be impacted by typical projects may include but are not limited to, the following materials: Flooring & Associated Adhesives Baseboard & Associated Adhesives Gypsum Wallboard, Taping/Joint Compounds, & Texturing Compounds Plaster Wall & Ceiling Systems Spray Applied Acoustical Material Fireproofing Pipe, Pipe Elbows & Pipe Fitting Insulation Boiler & Flue Insulation HVAC Duct Insulation HVAC Joint Mudding & Duct Tape Sink Undercoating Asbestos-cement (Transite) Flues, Panels & Shingles Ceramic Tile Grout and Underlayment Interior & Exterior Stucco Brick Mortar Roofing Materials Building components not associated with the planned investigation project were not sampled. Furthermore, limited lead sampling was conducted to identify suspect lead-containing coatings that may be disturbed by project activities for the purpose of compliance with Cal-OSHA’s Lead in Construction Standard and is not intended to
97

UC Davis Asbestos Analysis

Jan 12, 2016

Download

Documents

Harvey Ward

Documents detail some of the asbestos and lead paint testing results and recommendations for the UC Davis campus
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: UC Davis Asbestos Analysis

Northern California: 7977 Capwell Drive, Suite 100 • Oakland, CA 94621 • (510) 638-8400 • Fax (510) 638-8404 Southern California: 1055 Wilshire Blvd., Suite 1450, Los Angeles, CA 90017 • (213) 353-1240 • Fax (213) 353-1244

November 25, 2013 Mr. Greg Secor Transmitted via email:[email protected] University of California at Davis Design & Construction Management 255 Cousteau Place Davis, CA 95618 Re: Asbestos and Lead Surveys for Seismic V Project University of California at Davis, Central Plant, Med Sci 1B, Olson Hall and Wright Hall

One Shields Avenue, Davis, California ACC Project #: 3028-067.00

Dear Mr. Secor: Per your request, ACC Environmental Consultants, Inc. (ACC) performed limited asbestos surveys of The Central Plant, Med Sci 1B, Olson Hall and Wright Hall, located at University of California, One Shields Avenue, Davis, California, in October and November of 2013. The surveys of the referenced sites were performed to identify suspect asbestos-containing building materials and loose & peeling lead-containing paint that may be impacted during the planned preliminary investigation project. Common suspect asbestos-containing building materials that may be impacted by typical projects may include but are not limited to, the following materials:

• Flooring & Associated Adhesives • Baseboard & Associated Adhesives • Gypsum Wallboard, Taping/Joint Compounds, & Texturing Compounds • Plaster Wall & Ceiling Systems • Spray Applied Acoustical Material • Fireproofing • Pipe, Pipe Elbows & Pipe Fitting Insulation • Boiler & Flue Insulation • HVAC Duct Insulation • HVAC Joint Mudding & Duct Tape • Sink Undercoating • Asbestos-cement (Transite) Flues, Panels & Shingles • Ceramic Tile Grout and Underlayment • Interior & Exterior Stucco • Brick Mortar • Roofing Materials

Building components not associated with the planned investigation project were not sampled. Furthermore, limited lead sampling was conducted to identify suspect lead-containing coatings that may be disturbed by project activities for the purpose of compliance with Cal-OSHA’s Lead in Construction Standard and is not intended to

Page 2: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 2 of 18 be a “Lead Inspection” or “Lead Risk Assessment” as defined by the California Department of Public Health (DPH).

Asbestos Bulk Sample Results

Mr. Chris Yama, a Cal/OSHA Certified Asbestos Consultant (CAC #98-2356) with ACC, performed bulk sampling of suspect asbestos-containing materials during October and November of 2013. Two Hundred ninety-eight (298) samples of suspect materials were submitted for analysis. Copies of the laboratory results are attached. The samples were delivered to Forensic Analytical Laboratories, of Hayward, California; an independent laboratory that participates in the bulk sample proficiency analysis program conducted by the United States Environmental Protection Agency (EPA) and is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP). The samples were analyzed using Polarized Light Microscopy (PLM) with dispersion staining to estimate percent composition by volume. Samples with less than 1% (<1%) asbestos are designated as “Trace asbestos.” Samples with no observable asbestiform minerals are designated as “no asbestos detected.”

Summary of Asbestos Bulk Sample Results Central Plant

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

RC-1-1 Tar and Gravel Roofing

Southwest Roof

Felt: 10% Chrysotile Asbestos Off White Canvas: No Asbestos Detected Tar: 10% Chrysotile Asbestos

9,200 SF Category 1 Class 2

RM-2-1 Perimeter Roofing Southwest Roof Tar: 10% Chrysotile Asbestos

2,100 SF Category 1 Class 2

RP-3-1 Roof Patching Mastic Southwest Roof Mastic: No Asbestos Detected N/Q N/A N/A

JC-5-1, 2, 3, 4, 5

Drywall & Joint Compound

Throughout Building B

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

3,200 SF Unclassifi

ed Class 2

WT-6-1 Wall Texture on Drywall Throughout Building A Wall Texture: No Asbestos Detected

N/Q N/A N/A

JC-7-1, 2, 3, 4, 5

Drywall & Joint Compound

Throughout Building A Drywall: No Asbestos Detected Joint Compound: No Asbestos Detected

N/Q N/A N/A

PI-8-1, 2, 3

Hardpack Pipe Insulation

Throughout Plant Complex

Insulation: 10% Amosite Asbestos

1,410 LF Friable RACM

Class 1

PI-9-1 Fiberglass Pipe Insulation

Throughout Plant Complex

Insulation: No Asbestos Detected

N/Q N/A N/A

TG-10-1 Ceramic Tile on Drywall

Throughout Building B

Grout: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Drywall: No Asbestos Detected

240 SF Unclassified

Class 2

CT-11-1 2’ X 4’ White Ceiling Tile with Fissures

Building A Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

MI-12-1, 2, 3

Concrete Throughout Plant Complex

Concrete: No Asbestos Detected

N/Q N/A N/A

RP-13-1, 2

Roof Patch Parapet Walls and Penetrations Bldg A

Tar: 15% Chrysotile Asbestos

420 SF Cat I Class 2

CT-14-1 2’ X 4’ White Ceiling Tile - Textured

Building A Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

Page 3: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 3 of 18

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

CT-15-1 2’ X 4’ White Ceiling Tile with Fissures

Building A Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

ES-16-1, 2, 3

Exterior Stucco At VFD Room Stucco: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

RC-17-1, 2

White Painted Rolled Roofing Bldg A

Felt: 35% Chrysotile Asbestos Tar: No Asbestos Detected

420 SF Cat I Class 2

BA-18-1, 2

Brown Base Adhesive Throughout Plant Complex

Adhesive: No Asbestos Detected N/Q N/A N/A

MI-19-1, 2 Epoxy Floor and Red Concrete

Bathroom Epoxy: No Asbestos Detected Red Concrete: No Asbestos Detected

N/Q N/A N/A

FA-20-1 12” X 12” Grey Floor Tile and Yellow Adhesive

Old Control Room Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

GC-21-1, 2

1’ X 1’ White Ceiling Tile Large Fissures with Brown Mastic

Old Control Room Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

WT-22-1, 2, 3

Wall Texture on Concrete

Bathroom Texture: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

GC-23-1, 2

1’ X 1’ White Ceiling Tile Small Fissures with Brown Mastic

VFD Room Hallway Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

CK-24-1, 2, 3

Beige/Tan Caulk Perimeter of Windows and Louvers

Caulk: No Asbestos Detected

N/Q N/A N/A

MI-25-1, 2 Concrete Throughout Plant Complex-Exterior

Concrete: No Asbestos Detected

N/Q N/A N/A

DB-26-1 Debris Insulation Throughout Plant Complex

Debris: <1% Amosite Asbestos

2,250 SF Friable RACM

Class 1

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions. Med Sci 1B

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

ES-1-1, 2, 3, 4, 5, 6, 7, 8, 9

Exterior Stucco At Soffits and Roof Wells

Stucco: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

MI-2-1, 2 Terrazzo Floor Bathrooms Terrazzo: No Asbestos Detected N/Q N/A N/A

MI-3-1, 2, 3

Concrete Throughout Building Concrete: No Asbestos Detected N/Q N/A N/A

CK-4-1, 2 Grey Caulking Roof Wells Caulking: No Asbestos Detected N/Q N/A N/A

BA-5-1, 2 Brown Base Adhesive Throughout Building Adhesive: No Asbestos Detected N/Q N/A N/A

FA-6-1, 2 12” X 12” Beige Floor Tile and Black Adhesive

Throughout Building Tile: 2% Chrysotile Asbestos Mastic: No Asbestos Detected 700 SF Cat I Class 2

TG-7-1, 2 Ceramic Tile Grout and Adhesive

Bathrooms Grout: No Asbestos Detected Adhesive: No Asbestos Detected

N/Q N/A N/A

PI-8-1 Fiberglass Pipe Insulation

Throughout Building Insulation: No Asbestos Detected

N/Q N/A N/A

Page 4: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 4 of 18

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

PE-9-1, 2, 3, 4

Insulation at Pipe Racks Throughout Building Insulation: No Asbestos Detected

N/Q N/A N/A

JC-10-1, 2, 3, 4, 5, 6, 7, 8, 9

Drywall & Joint Compound

Throughout Building Drywall: No Asbestos Detected Joint Compound: No Asbestos Detected

N/Q N/A N/A

CT-11-1, 2

2’ X 4’ White Ceiling Tile with Pinholes

Store #135 Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-12-1 2’ X 4’ White Ceiling Tile with Fissures

Store #135 Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-13-1, 2

2’ X 2’ White Ceiling Tile with Pinholes

Throughout Building Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

RP-14-1 Roof Patching Mastic Mechanical Wells Mastic: No Asbestos Detected N/Q N/A N/A

GC-15-1 1’ X 1’ White Ceiling Tile Fiberglass with Brown Mastic

Library Bathrooms Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

CT-16-1, 2

1’ X 1’ White Ceiling Tile Cellulose with Brown Mastic

Library Bathrooms Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

CM-17-1, 2

Brown Ceiling Tile Mastic

Library Bathrooms Mastic: No Asbestos Detected N/Q N/A N/A

RC-18-1, 2

Tar and Gravel Roofing

Mechanical Wells Tar: 10% Chrysotile Asbestos Felt: 40% Chrysotile Asbestos

980 SF Cat I Class 2

RM-19-1 Membrane Roofing Mechanical Well, SW Membrane: No Asbestos Detected N/Q N/A N/A

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions.

Olson Hall Sample

No. Material Description Location Description Results Approx.

Quantity* NESHAPS Category1

OSHA Class2

A-PL-1-1, 2, 3

Plaster 2nd Floor Shop at Chase

Plaster: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

A-RM-2-1, 2

Membrane Roofing, Felt and Tar

Middle of Main Roof Membrane Roofing: No Asbestos Detected Tar: No Asbestos Detected

N/Q N/A N/A

WT-1-1, 2, 3, 4, 5, 6, 7

Wall Texture on Concrete Throughout Building

Wall Texture: 2% Chrysotile Asbestos 52,000 SF

Friable RACM Class 2

CK-2-1, 2, 3

Grey Caulking Around Windows and at Expansion Joints

Caulking: No Asbestos Detected N/Q N/A N/A

CK-3-1, 2 Tan Caulking Top of Roof Seams Caulking: No Asbestos Detected N/Q N/A N/A

WP-4-1, 2, 3, 4

Grey Window Putty Rooftop Windows Putty: No Asbestos Detected N/Q N/A N/A

AD-5-1, 2, 3

Silver Foil with Brown/Yellow Mastic

Above Ceiling Throughout Building

Mastic: No Asbestos Detected N/Q N/A N/A

RP-6-1, 2 Roof Patching Mastic Roof Walkways Mastic: No Asbestos Detected N/Q N/A N/A

PI-7-1, 2, 3

Hardpack Pipe Insulation

Throughout Building Insulation: 10% Amosite Asbestos

1,700 LF Friable RACM

Class 1

PE-8-1, 2, 3

Pipe Elbows on Fiberglass Lines

Throughout Building Insulation: 2% Chrysotile Asbestos

900 EA Friable RACM

Class 1

Page 5: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 5 of 18

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

SA-9-1, 2, 3, 4, 5, 6, 7

Acoustic Plaster with Metal Lath

Stairwells and Center Lobbies

Plaster: 2% Chrysotile Asbestos 4,000 SF

Friable RACM Class 1

MI-10-1, 2 Terrazzo Floor Center Lobbies Terrazzo: No Asbestos Detected N/Q N/A N/A

FA-11-1, 2

12” X 12” Beige Floor Tile over 9” X 9” and Black Adhesive

Throughout Building Bottom Tile: 5% Chrysotile Asbestos Bottom Mastic: 5% Chrysotile Asbestos 2,400 SF Cat I Class 2

WP-12-1, 2, 3

Brown Window Putty Lower Windows Putty: No Asbestos Detected N/Q N/A N/A

BA-13-1, 2, 3

Beige and Brown Base Adhesive

Throughout Building Adhesive: No Asbestos Detected N/Q N/A N/A

MI-14-1 Wall Covering Throughout Building Glue: No Asbestos Detected N/Q N/A N/A

FA-15-1, 2, 3, 4

12” X 12” Green and Purple Floor Tile Black and Yellow Adhesive

Throughout Building, Hallways

Tile: No Asbestos Detected Mastic: 2% Chrysotile Asbestos

15,400 SF Cat I Class 2

TG-16-1 Ceramic Wall Tile Grout and Adhesive

Bathrooms Grout: No Asbestos Detected Adhesive: No Asbestos Detected

N/Q N/A N/A

TG-17-1 Ceramic Tile Grout and Underlayment

Janitor Closets Grout: No Asbestos Detected Underlayment: No Asbestos Detected

N/Q N/A N/A

TG-18-1, 2

Ceramic Floor Tile Grout and Adhesive

Bathrooms Grout: No Asbestos Detected Adhesive: No Asbestos Detected

N/Q N/A N/A

GC-19-1, 2

1’ X 1’ White Ceiling Tile Fiberglass with Brown Mastic

2nd Floor South Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

CT-20-1, 2

1’ X 1’ White Ceiling Tile Cellulose

Throughout Building Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

CM-22-1, 2

Ceiling Tile Mastic, Yellow

Throughout Building Mastic: No Asbestos Detected N/Q N/A N/A

CM-23-1, 2

Ceiling Tile Mastic, Brown

Throughout Building Mastic: No Asbestos Detected N/Q N/A N/A

MI-24-1, 2 Tan Epoxy Flooring Rooms 230 and 250 Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

MI-25-1, 2 Concrete Exterior Throughout Exterior Concrete: No Asbestos Detected

N/Q N/A N/A

MI-26-1, 2 Concrete Interior Throughout Building Concrete: No Asbestos Detected

N/Q N/A N/A

AD-27-1 Black Adhesive on Ductwork

Basement Mechanical Room

Mastic: 2% Chrysotile Asbestos 1,200 SF Cat II Class 2

DB-28-1, 2

Insulation Debris

Mechanical Rooms and Mechanical Closets Throughout Building

Debris: 2% Amosite Asbestos 20,400 SF Friable RACM

Class 2

PL-29-1, 2, 3, 4, 5, 6, 7

Plaster Throughout Building Plaster: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

DI-30-1, 2 Fiberglass Duct Insulation with Silver Cover

Throughout Building Insulation: No Asbestos Detected

N/Q N/A N/A

DI-31-1 Fiberglass Duct Insulation with Canvas Cover

Throughout Building Insulation: No Asbestos Detected Cover: No Asbestos Detected

N/Q N/A N/A

Page 6: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 6 of 18

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

FA-32-1 12” X 12” Beige Floor with Yellow Mastic

Room 206 on Elevated Floor. Note FA-33 is below elevated Floor

Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

FA-33-1, 2

9” X 9” Tan Floor Tile and Black Adhesive

Throughout Building, Partially Concealed by various Floor Coverings and Elevated Floors

Bottom Tile: 5% Chrysotile Asbestos Bottom Mastic: 5% Chrysotile Asbestos 48,000 SF Cat I Class 2

JC-34-1, 2, 3, 4, 5, 6, 7, 8

Drywall & Joint Compound Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

16,200 SF Unclassifi

ed Class 2

CM-35-1 Ceiling Tile Mastic, Tan Throughout Building Mastic: No Asbestos Detected N/Q N/A N/A

CT-36-1, 2

2’ X 2’ White Ceiling Tile With Pinholes

Throughout Building Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

FA-37-1 12” X 12” Tan Floor with Yellow Mastic

Rooms 248 and 248A on Elevated Floor. Note FA-33 is below elevated Floor

Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

FA-38-1 12” X 12” Tan Floor Tile and Yellow Adhesive

Elevator Tile: 2% Chrysotile Asbestos Mastic: No Asbestos Detected 30 SF Cat I Class 2

AD-39-1, 2, 3

Tan/Brown Adhesive on Perimeter of Ceiling Grids

Throughout Building Mastic: 2% Chrysotile Asbestos 9,400 LF Cat II Class 2

AD-40-1 Yellow Wall Panel Adhesive

Throughout Building Mastic: No Asbestos Detected N/Q N/A N/A

CT-41-1, 2

2’ X 4’ White Ceiling Tile With Fissures

Throughout Building Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

FD-42 Fire Doors Throughout Building Assumed Asbestos 16 Each Friable RACM

Class 2

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions. Wright Hall

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

RM-1-1, 2, 3

Membrane Roofing, Felt, Tar and Lightweight Concrete

Middle of West Lower Roof

Membrane Roofing: No Asbestos Detected Tar: No Asbestos Detected Lightweight Concrete: No Asbestos Detected

N/Q N/A N/A

SA-3-1, 2, 3

Acoustic Plaster with Metal Lath

Throughout Theatre and Theatre Lobby

Plaster: 10% Chrysotile Asbestos

900 SF Friable RACM

Class 1

PI-4-1, 2, 3

Hardpack Pipe Insulation

Throughout Building Insulation: 15% Amosite Asbestos

2,200 LF Friable RACM

Class 1

PL-5-1, 2, 3, 4, 5, 6, 7, 8

Plaster Throughout Building Plaster: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

TG-6-1 Brown Ceramic Tile Grout and Underlayment

Bathrooms Grout: No Asbestos Detected Underlayment: No Asbestos Detected

N/Q N/A N/A

Page 7: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 7 of 18

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

TG-7-1 Tan Ceramic Tile Grout and Underlayment

Bathrooms Grout: No Asbestos Detected Underlayment: No Asbestos Detected

N/Q N/A N/A

PL-9-1, 2, 3

Plaster on Drywall Above Ceiling on Second Floor

Plaster: No Asbestos Detected

N/Q N/A N/A

MI-10-1, 2, 3

Tan and Beige Waterproofing Paint

Throughout Exterior Waterproofing: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

SV-11-1 Tan Sheet Vinyl Restrooms at Lobby Sheet Vinyl: No Asbestos Detected Backing: No Asbestos Detected

N/Q N/A N/A

MI-12-1, 2 Lightweight Concrete Above Ceiling on Second Floor

Concrete: No Asbestos Detected

N/Q N/A N/A

BA-13-1, 2 Brown Base Adhesive Throughout Building

Adhesive: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos

900 LF Cat II Class 2

MI-14-1, 2 Firestop Throughout Building Firestop: No Asbestos Detected

N/Q N/A N/A

JC-15-1, 2, 3, 4, 5, 6, 7, 8

Drywall & Joint Compound Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

2,600 SF Unclassifi

ed Class 2

FA-16-1, 2, 3

9” X 9” Tan Floor Tile and Black Adhesive

Throughout Building Tile: <1% Chrysotile Asbestos Mastic: 5% Chrysotile Asbestos

800 SF Cat I Class 2

MI-17-1, 2 Concrete Throughout Building Concrete: No Asbestos Detected

N/Q N/A N/A

CT-18-1 2’ X 4’ White Ceiling Tile Fiberglass

Throughout Building Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

MI-19-1, 2, 3

Concrete Throughout Building Concrete: No Asbestos Detected

N/Q N/A N/A

TP-20-1 Transite Panels Above Showers in Basement Bathroom

Assumed Asbestos 100 SF Cat II Class 2

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions. Fire/Police

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

MI-1-1, 2 Concrete Exterior Concrete: No Asbestos Detected

N/Q N/A N/A

RM-2-1 Membrane Roof Lower Roof Membrane: No Asbestos Detected

N/Q N/A N/A

MI-3-1 Concrete Blocks CMU Exterior Concrete: No Asbestos Detected

N/Q N/A N/A

TG-4-1 Ceramic Tile, Grout and Mastic Bathrooms

Grout: No Asbestos Detected Mastic: 5% Chrysotile Asbestos

400 SF Cat II Class 2

CT-5-1, 2 White Ceiling Tile Throughout Building Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

FA-6-1, 2 12” X 12” Brown Floor Tile and Black Adhesive

Throughout Building Tile: No Asbestos Detected Mastic: No Asbestos Detected See Mastic Samples Below

N/Q N/A N/A

AD-7-1, 2, 3

Black Adhesive for 12” Brown Floor Tiles

Throughout Building Mastic: 5% Chrysotile Asbestos

700 SF Cat I Class 2

Page 8: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 8 of 18

Sample No. Material Description Location Description Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

CA-8-1 Black and Yellow Carpet Adhesive

Throughout Building Mastic: 2% Chrysotile Asbestos

200 SF Cat I Class 2

CK-9-1 Grey Caulking Exterior on CMU Caulking: No Asbestos Detected

N/Q N/A N/A

BA-10-1, 2, 3

Brown Base Adhesive Throughout Building Adhesive: No Asbestos Detected N/Q N/A N/A

JC-11-1, 2, 3, 4, 5, 6, 7, 8, 9

Drywall & Joint Compound Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

3,200 SF Unclassifi

ed Class 2

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions. Summary of Asbestos Materials

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Central Plant Tar and Gravel Roofing

Southwest Roof

Felt: 10% Chrysotile Asbestos Off White Canvas: No Asbestos Detected Tar: 10% Chrysotile Asbestos

9,200 SF $46,000

Central Plant Perimeter Roofing Southwest Roof Tar: 10% Chrysotile Asbestos

2,100 SF $2,100

Central Plant Drywall & Joint Compound

Throughout Building B

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

3,200 SF $6,400

Central Plant Hardpack Pipe Insulation

Throughout Plant Complex

Insulation: 10% Amosite Asbestos

1,410 LF $14,100

Central Plant Ceramic Tile on Drywall

Throughout Building B

Grout: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Drywall: No Asbestos Detected

240 SF $900

Central Plant Roof Patch Parapet Walls and Penetrations Bldg A

Tar: 15% Chrysotile Asbestos

420 SF $2,100

Central Plant White Painted Rolled Roofing Bldg A

Felt: 35% Chrysotile Asbestos Tar: No Asbestos Detected

420 SF $2,100

Central Plant Debris Insulation Throughout Plant Complex

Debris: <1% Amosite Asbestos

2,250 SF $6,750

Med Sci 1B 12” X 12” Beige Floor Tile and Black Adhesive

Throughout Building Tile: 2% Chrysotile Asbestos Mastic: No Asbestos Detected 700 SF $1,400

Med Sci 1B Tar and Gravel Roofing

Mechanical Wells Tar: 10% Chrysotile Asbestos Felt: 40% Chrysotile Asbestos

980 SF $500

Olson Hall Wall Texture on Concrete

Throughout Building Wall Texture: 2% Chrysotile Asbestos

52,000 SF

$16,000

Olson Hall Hardpack Pipe Insulation

Throughout Building Insulation: 10% Amosite Asbestos

1,700 LF $5,100

Page 9: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 9 of 18

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Olson Hall Pipe Elbows on Fiberglass Lines

Throughout Building Insulation: 2% Chrysotile Asbestos

900 EA $5,000

Olson Hall Acoustic Plaster with Metal Lath

Stairwells and Center Lobbies

Plaster: 2% Chrysotile Asbestos

4,000 SF $4,000

Olson Hall 12” X 12” Beige Floor Tile over 9” X 9” and Black Adhesive

Throughout Building Bottom Tile: 5% Chrysotile Asbestos Bottom Mastic: 5% Chrysotile Asbestos 2,400 SF $2,400

Olson Hall 12” X 12” Green and Purple Floor Tile Black and Yellow Adhesive

Throughout Building, Hallways

Tile: No Asbestos Detected Mastic: 2% Chrysotile Asbestos

15,400 SF

$30,800

Olson Hall Black Adhesive on Ductwork

Basement Mechanical Room

Mastic: 2% Chrysotile Asbestos 1,200 SF $500

Olson Hall Insulation Debris

Mechanical Rooms and Mechanical Closets Throughout Building

Debris: 2% Amosite Asbestos 20,400 SF

$5,000

Olson Hall 9” X 9” Tan Floor Tile and Black Adhesive

Throughout Building, Partially Concealed by various Floor Coverings and Elevated Floors

Bottom Tile: 5% Chrysotile Asbestos Bottom Mastic: 5% Chrysotile Asbestos

48,000 SF $96,000

Olson Hall Drywall & Joint Compound Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

16,200 SF $32,400

Olson Hall 12” X 12” Tan Floor Tile and Yellow Adhesive

Elevator Tile: 2% Chrysotile Asbestos Mastic: No Asbestos Detected 30 SF

Olson Hall Tan/Brown Adhesive on Perimeter of Ceiling Grids

Throughout Building Mastic: 2% Chrysotile Asbestos 9,400 LF $18,800

Olson Hall Fire Doors Throughout Building Assumed Asbestos 16 Each $800

Wright Hall Acoustic Plaster with Metal Lath

Throughout Theatre and Theatre Lobby

Plaster: 10% Chrysotile Asbestos

900 SF $500

Wright Hall Hardpack Pipe Insulation

Throughout Building Insulation: 15% Amosite Asbestos

2,200 LF $8,500

Wright Hall Brown Base Adhesive Throughout Building Adhesive: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos

900 LF $900

Wright Hall Drywall & Joint Compound Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

2,600 SF $5,200

Wright Hall 9” X 9” Tan Floor Tile and Black Adhesive

Throughout Building Tile: <1% Chrysotile Asbestos Mastic: 5% Chrysotile Asbestos

800 SF $2,400

Wright Hall Transite Panels Above Showers in Basement Bathroom

Assumed Asbestos 100 SF $500

Fire/Police Ceramic Tile, Grout and Mastic Bathrooms

Grout: No Asbestos Detected Mastic: 5% Chrysotile Asbestos

400 SF $800

Page 10: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 10 of 18

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Fire/Police Black Adhesive for 12” Brown Floor Tiles

Throughout Building Mastic: 5% Chrysotile Asbestos

700 SF $500

Fire/Police Black and Yellow Carpet Adhesive

Throughout Building Mastic: 2% Chrysotile Asbestos

200 SF $200

Fire/Police Drywall & Joint Compound Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Composite Point Count: <1% Chrysotile Asbestos

6,400 SF $19,200

Total $348,350

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions.

1EPA’s NESHAPS regulations define categories of asbestos-containing materials (ACM) based on their potential of asbestos fiber release when disturbed:

• Friable - Any material containing more than 1 percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

• Category I Non-friable ACM (Cat 1 NF) - Asbestos-containing packings, gaskets, resilient floor covering and asphalt roofing products containing more than 1 percent asbestos.

• Category II Non-friable ACM (Cat II NF) - Any material, excluding Category I non-friable ACM containing more than 1 percent asbestos as determined using the methods specified under AHERA, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

2OSHA’s Asbestos in Construction Standard (Federal - 29 CFR 1926.1101 and California – 8 CCR 1529) define specific “Classes” of work based on the risk of exposure to employees with the potential for disturbance of asbestos-containing materials. The classes of work are defined as

• Class 1 - Asbestos-related activities involving the removal of thermal systems insulation (TSI) and surfacing ACM or presumed ACM.

• Class 2 - Asbestos-related activities involving the removal of ACM, which are not TSI, or surfacing ACM. Based on the sample results, the planned investigation project will impact asbestos-containing materials. The final scope of work should be reviewed against the asbestos survey information. If asbestos-containing materials will be disturbed during the projects, licensed asbestos abatement contractors working under standard University of California asbestos program requirements should perform all work. A review of all other asbestos survey information available for the property in conjunction with these results should be conducted prior to proceeding with project activities and when a change in the project scope is developed. If suspect asbestos-containing materials will be impacted that are not addressed in this survey or in the historical survey records, additional sampling should be conducted prior to disturbance. Historical records (typically predating 1995) have limited value for project planning and should be verified with confirmatory inspection and additional sampling.

Lead Sample Results Mr. Chris Yama, a California Department of Public Health Lead Inspector/Assessor/Monitor (I/A/M-3814) with ACC, collected fifty-five (55) bulk samples to establish lead-paint concentration for clean up and disposal requirements. Samples with detectable amounts of lead must be properly removed and disposed of according to local, state and federal regulations. Lead sampling was conducted to identify suspect lead-containing coatings that

Page 11: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 11 of 18 may be disturbed by project activities for the purpose of compliance with Cal-OSHA’s Lead in Construction Standard and is not intended to be a “Lead Inspection” or “Lead Risk Assessment” as defined by the California Department of Public Health. The bulk samples were obtained from suspect lead-containing building materials identified at the building. Paint colors and/or descriptions are identified based on the surface color observed by ACC at the time of the survey and does not necessarily identify paint descriptions underlying the surface coat. The sample was delivered to Forensic Analytical Laboratories, of Hayward, California; an independent American Industrial Hygiene Association (AIHA) accredited laboratories, for analysis and was analyzed by Atomic Absorption (AA) Spectroscopy in accordance with the EPA 3050B/7420 Method. The colors, locations, and lead contents of these paints are listed below.

Summary of Lead Bulk Sample Results Med Sci 1B Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-2 Beige on Exterior Stucco

Throughout Building 0.0024 Intact $0-100

PT-3 White, Beige, Tan and Green on Drywall

Throughout Building 0.013 800 SF $800

PT-4 Red and Brown on Metal Studs

Throughout Building 0.20 500 SF $1,000

PT-5 Orange and Red on Structural Steel

Throughout Building 0.13 Intact $0

PT-6 Tan Ceramic Tile Bathrooms 0.014 1,200 SF $4,800

PT-7 Blue/Grey on Exterior Trim and Roof

Throughout Exterior 0.23 50 SF $0-200

PT-8 Blue/Grey on Exterior Stucco

Throughout Exterior .035 1,500 SF $7,500

PT-9 Tan and Yellow on Exterior Trim

Throughout Exterior 0.11 50 SF $0-200

PT-10 Blue Ceramic Tile Bathrooms .053 800 SF $3,200

Total $17500-17,800

*Quantity for “paint” reflects approximate area of loose & peeling only, not all painted surfaces

Central Plant Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-1 Black and White Ceramic Tile

Bathroom 15 ppm 240 SF $500

PT-2 Beige on Exterior Trim Throughout Building 0.04 50 SF $100

PT-3 Grey, Tan Red and Green on Doors and Frames

Throughout Building 0.16 Intact $0

Page 12: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 12 of 18 Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-4 Green and Yellow on Pipes

Throughout Building 0.15 500 SF $1,000

PT-5 Lt. Blue on Drywall Bathroom <0.006 Intact $0

PT-6 White/Beige on Drywall Throughout Building <0.006 Intact $0

PT-7 Green and White on Interior Concrete

Throughout Building 0.072 50 SF $200

PT-8 Green and Red on Ducts

Throughout Building .035 500 SF $500

PT-9 Grey, Green, Blue and Red on Structural Steel

Throughout Building 7.7 50 SF $200

PT-10 Red and Yellow on Guard Rails

Throughout Building 1.1 50 SF $200

PT-11 Grey Epoxy Floor Throughout Building 0.071 260 SF $1,000

PT-12 Lt Blue, Grey and Green on Interior Concrete

Throughout Building 0.11 200 SF $1,000

PT-13 Grey on Floor Throughout Building <0.006 2,500 SF $0

PT-14 Brown on Louvers Throughout Building 0.080 Intact $0

PT-15 Beige on Exterior Concrete

Throughout Exterior 0.040 1,000 SF $10,000

Total $14,700

*Quantity for “paint” reflects approximate area of loose & peeling only, not all painted surfaces

Fire/Police Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-1 1” Blue Ceramic Tile Bathrooms <0.0007 Intact $0

PT-2 White/Beige, on Drywall Throughout Building <0.006 800 SF $0

PT-3 Red on Exterior Trim Throughout Building 0.058 150 SF $1,000

PT-4 Black and Red on Windows and Doors

Throughout Building <0.02 Intact $0

Total $1,000

*Quantity for “paint” reflects approximate area of loose & peeling only, not all painted surfaces

Wright Hall Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-1 Beige/White on Drywall Throughout Building <0.006 Intact $0

PT-2 Orange/Black on Structural Steel

Throughout Building 26 Intact $0-100

PT-3 White/Beige on Plaster Throughout Building 0.18 14,400 SF $57,600

Page 13: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 13 of 18 Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-4 Beige and Tan on Exterior Concrete

Throughout Building 0.12 500 SF $1,000

PT-5 Grey, Orange and Brown on Doors and Frames

Throughout Building 7.0 Intact $0

PT-6 Black on Stage Floor Stage <0.007 Intact $0

PT-7 Beige on Drywall Throughout Building <0.006 Intact $0

PT-8 Epoxy Floor Bathrooms 0.002 500 SF $1,500

PT-9 Brown Ceramic Tile Bathrooms 0.002 1,000 SF $3,000

PT-10 Tan Ceramic Tile Bathrooms 0.0025 8,400 SF $25,200

Total $88,400

*Quantity for “paint” reflects approximate area of loose & peeling only, not all painted surfaces

Olson Hall Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-1 Ceramic Wall Tiles Bathrooms 0.001 3,200 SF $12,800

PT-2 Ceramic Wall Tiles Janitor Closets/Mech Rooms 0.053 700 SF $0

PT-3 Brown, Green and Grey on Doors and Frames

Throughout Building 0.46 200 SF $400

PT-4 Beige and White on Concrete

Throughout Building 0.39 1,000 SF $2,000

PT-5 Tan Epoxy Flooring South End of Second Floor 0.013 1,200 SF $6,000

PT-6-1 Lead Paint Debris Throughout Building 0.035 11,400 SF $6,000

PT-6-2 Lead Paint Debris Throughout Building 0.004 11,400 SF Included Above

PT-7-1 Grey, White, Beige and Green on Plaster

Throughout Building 0.63 12,600 SF $6,300

PT-7-2 Grey, White, Beige and Green on Plaster

Throughout Building 0.63 12,600 SF Included Above

PT-8-1 Grey, White, Beige and Green on Concrete

Throughout Building 0.83 10,200 SF $5,000

PT-8-2 Grey, White, Beige and Green on Concrete

Throughout Building 0.47 10,200 SF Included Above

PT-9 Ceramic Floor Tiles Bathrooms <0.0006 N/A $0

PT-10 Green and Beige on Exterior Trim

Throughout Building 0.63 50 SF $500

PT-11 Varnish on Handrails Throughout Building <40 N/A $0

PT-12 Blue/Beige on Drywall Throughout Building <0.007 N/A $0

Page 14: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 14 of 18 Sample

No. Material Description Material Location

Lead Content (wt% unless otherwise

noted)

Approximate Quantity*

Estimated Removal Costs

PT-13 Green and White on Ducts and Pipes

Throughout Building 0.50 950 SF $1,000

PT-14 Silver and Orange on Handrails

Throughout Building 0.72 950 SF $5,000

PT-15 Varnish on Doors Throughout Building 0.005 50 SF $100

PT-16 White on Drywall Throughout Building <0.006 N/A $0

Total $45,100

*Quantity for “paint” reflects approximate area of loose & peeling only, not all painted surfaces Of the fifty-five (55) samples collected, ten were reported to contain lead above 0.5%, 5,000 parts per million (weight by weight), or 1.0 mg/cm2 which is the definition for lead based paint by the Environmental Protection Agency (EPA) and the California Department of Public Health (DPH). Of the fifty-five samples taken forty-three samples were found to have detectable amounts of lead. The OSHA Lead in Construction Standard requires the use of special work practices during the disturbance of paint with any detectable amounts of lead. See attached OSHA Lead Regulation Summary. Lead containing waste materials with a concentration greater than 0.1%, for total lead, is considered hazardous waste in the State of California. Lead containing waste materials with a total lead concentration between 0.005% (50 ppm) and 0.10% (1000 ppm) must be re-analyzed using the waste extraction test (WET) method to determine the soluble lead content for waste disposal requirements. The EPA – Renovation, Repair and Painting Final Rule (40 CFR 745) requires that renovations conducted for compensation (where lead-based paint will be disturbed), must be performed by Certified Firms using Certified Renovators following the requirements set forth in the regulation. Contractors are also required to notify the Division of Occupational Safety and Health (DOSH) prior to disturbing greater than 100 square feet or l00 linear feet of material containing lead greater than 0.5% by weight, 5000 parts per million (ppm) or 1.0 milligram per square centimeter (mg/cm2).

OSHA Lead Regulation Summary

The Federal Occupational Safety and Health Administration (OSHA), has enacted a lead standard, which was adopted by the Cal/OSHA as 8 CCR 1532.1. The purpose of both standards is to protect construction workers from exposure to lead. OSHA is primarily concerned with activities that disturb paints with any detectable amounts of lead. Lead was used in most paints until the mid 1950’s and was banned in amounts in excess of 0.06% by weight in 1978 for most non-industrial paints by the Consumer Product Safety Commission (CPSC). The Cal/OSHA standard requires contractors and employers to notify the State of California Division of Occupational Safety and Health (DOSH) prior to disturbing greater than 100 square feet or 100 linear feet of material containing lead greater than 0.5%, 5,000 parts per million (weight by weight), or 1.0 mg/cm2. The Cal/OSHA standard also requires contractors and employers who perform paint removal activities to monitor their employees to determine whether they are being exposed in excess of the action level of 30 micrograms per cubic meter of air (µg/m3) over an eight-hour time weighted average (TWA) or the “Permissible Exposure Limit” (PEL) of 50 µg/m3 TWA. Monitoring is performed by personal air sampling.

Page 15: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 15 of 18 Even when concentrations are below the action level, an employer must provide employees with High Efficiency Particulate Air (HEPA) filtered vacuums, wetting agents and hand-washing facilities. If the exposure exceeds the action level or the PEL, other procedures such as containing the area, local exhaust ventilation, respiratory and worker protection, worker training, decontamination facilities and medical monitoring are required. OSHA has identified several work practices that pose varying levels of lead exposure to laborers disturbing lead-containing paint. Estimated exposure levels of lead are founded on the activity itself, rather than the concentrations of lead present in paint. Therefore, as an example, paint that contains 0.5% versus 15% of lead by weight or 0.8 mg/cm2 versus 3.5 mg/cm2 of lead in paint could pose the same exposure levels to workers depending on the activities that cause the disturbance and the administrative and engineering controls that are followed. The following is a summary of work activities that disturb paint, the expected exposure and the respiratory protection requirements that result as outlined in the OSHA standards:

Activities Potential Exposure Minimum Respiratory Protection Class I activities include: Manual demolition, manual scraping, manual sanding, heat gun applications, general cleanup, power tool cleaning with dust collection systems and spray painting activities

50 µg/m3 to 500 µg/m3 Half mask air purifying respirator equipped with HEPA filters having a protection factor of 10

Class II activities include: Using lead-containing mortars, lead burning, lead riveting, rivet busting, power tool cleaning without dust collection systems, cleanup of dry expendable abrasives and abrasive blasting

500 µg/m3 to 2,500 µg/m3 Full face powered air purifying respirators equipped with HEPA filters having a protection factor of 100

Class III activities include: Abrasive blasting, welding, cutting and torch burning on steel structures

Greater than 2,500 µg/m3 Full face supplied air respirator operated in pressure demand mode or other positive pressure mode (type “C”)

Polychlorinated Biphenyls (PCB) Sampling ACC conducted sampling of caulking typically suspected to contain Polychlorinated Biphenyls (PCBs). The samples were delivered to EMSL, an independent accredited laboratory for analysis by the EPA 8082 Method. Copies of the laboratory results are attached for reference. PCBs are mixtures of synthetic organic chemicals with the same basic chemical structure and similar physical properties ranging from oily liquids to waxy solids. Due to their non-flammability, chemical stability, high boiling point and electrical insulating properties, PCBs were used in hundreds of industrial and commercial applications including electrical, heat transfer, and hydraulic equipment; as plasticizers in paints, plastics and rubber products; in pigments, dyes and carbonless copy paper and many other applications. More than 1.5 billion pounds of PCBs were manufactured in the United States prior to cessation of production in 1977. PCBs have been demonstrated to cause a variety of adverse health effects, including cancer in animals. PCBs have also been shown to cause a number of serious non-cancer health effects in animals, including effects on the immune system, reproductive system, nervous system, endocrine system and other health effects. Studies in humans provide supportive evidence for potential carcinogenic and non-carcinogenic effects of PCBs. The different health effects of PCBs may be interrelated, as alterations in one system may have significant implications for the other systems of the body. The proper identification and handling of PCB-contaminated equipment and wastes is critical to the prevention of

Page 16: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 16 of 18 future waste management problems. All equipment or waste containing PCBs should be properly labeled, alerting people to the requirement for special handling procedures. While procedures may vary depending on the industry or specific operation, as a general rule, any time there is a risk of contact with PCBs, appropriate protective equipment should be worn to limit contact with the skin and eyes and to protect against inhalation of PCB fumes. Such equipment may include plastic or rubber gloves, boots, overalls, aprons, face shields or self-contained breathing apparatus. For workers cleaning up a major spill containing high concentrations of PCBs, a full suit of non-porous material should be worn. Clothing that has become contaminated should be disposed of along with other PCB wastes. PCB manufacture, use, storage and disposal are regulated by U.S. EPA under TSCA and Part 761, Title 40 of the Code of Federal Regulations (40 CFR Part 761). TSCA regulates any materials or wastes that contain PCBs at concentrations of 50 ppm (parts per million) or greater. PCB wastes are also regulated as hazardous waste by DTSC under the Health and Safety Code (HSC) and Title 22 of the California Code of Regulations (22 CCR). Criteria for determining PCB wastes are:

• total threshold limit concentration (TTLC) of 50 ppm of PCBs, and/or • soluble threshold limit concentration (STLC) of 5 ppm of PCBs as oily liquid.

Summary of PCB Sampling Results

Building Sample

No. Material Description Material Location

PCB Concentration

(ppm unless otherwise noted)

Approximate Quantity*

Removal Cost Estimate

Olson PCB-1 Grey Caulking Around Windows and on Expansion Joints

Throughout Building 22,000 ppm 2,800 LF $9,000

Olson PCB-2 Tan Caulk on Top of Roof Seams

Roof Area 860 ppm 800 LF $2,400

Med Sci 1B

PCB-3 Roof Wells on Stucco Roof Wells 17 ppm N/A $0

Olson PCB-4 Grey Window Putty Rooftop Windows 9.8 ppm N/A $0

Central Plant

PCB-5 Beige/Tan Caulk Around Windows and Louvers

None Detected N/A $0

Fire/Police

PCB-6 Grey Caulk On CMU Wall 39,000 ppm 20 LF $500

Total $11,900

Other Hazardous Materials ACC quantified the number of mercury containing light tubes; suspect PCB-containing ballasts and Mercury thermostat switches as part of the scope of work. These materials and the quantities indicated below should be Included in the hazardous materials removal scope of work or handled by properly trained workers of the demolition contractor and segregated into specific waste streams prior to disturbance by general demolition activities.

Page 17: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 17 of 18

Universal Waste/Other Hazardous Wastes Estimated Quantity Estimated Removal Costs

Florescent/Mercury Vapor Light Tubes 4,000 Each $4,000

Suspect PCB-containing Light Ballasts in Building 2,000 Each $8,000

Smoke Detectors 275 Each $1,000

Limitations ACC conducted the limited survey with the standard of care ordinarily exercised by qualified and reputable members of the environmental/industrial hygiene profession based on conditions and practices observed at the property and information provided to ACC related to the project and/or purpose of the survey at the time of the investigation. The survey was limited to specific project areas and was not intended to identify all suspect asbestos-containing materials within the building. Areas and materials not included in the survey should be inspected and sampled prior to any renovation, maintenance, demolition or other activity that may cause disturbance to the materials. This report does not intend to identify all hazards or unsafe practices, nor to indicate that other hazards or unsafe conditions do not exist at the property. ACC encountered the following inaccessible areas in addition to general concealed conditions (i.e. within wall cavities, above/below solid ceilings or flooring/sub-flooring materials, etc.) and are excluded from the scope of the survey. These areas should be inspected and any suspect materials and sampled accordingly prior to any renovation, maintenance, demolition or other activity that may cause disturbance to the materials. Inaccessible Areas

• No inaccessible areas/equipment were identified within the provided project areas Materials that would require intrusive or destructive sampling were generally not sampled as part of the project unless written direction was provided to ACC to perform intrusive and/or destructive sampling on specific building systems, the area was unoccupied at the time of the survey and by performing intrusive/destructive sampling would not create an unsafe condition. Furthermore, ACC shall not be responsible for identifying and/or sampling suspect materials concealed within walls, columns, beneath flooring, above solid ceilings, underground or in any other concealed areas. ACC shall not be responsible for identification, sampling and/or characterization of lead-containing materials, PCB and lighting/mercury wastes, and water or mold impacted materials. General observations may be noted if ACC observed suspect conditions to the client either separately or within this report. ACC excludes sampling concrete and asphalt paving as suspect asbestos-containing materials. Aggregate found in these materials may contain asbestos if supplied from quarries located in known ultra-mafic areas. It is possible that prior to recycling and/or disposal, recycling agents or landfills may require sampling of these materials to determine the presence of asbestos prior to acceptance.

ACC excludes characterization of soils in areas on known ultramafic rock (where naturally occurring asbestos may be found in soils) as part of the scope of work. If the project area is located within a known ultramafic rock area, provisions should be made to address regulatory requirements for any planned excavation and grading as part of the project. ACC can provide further detail on regulatory requirements related to naturally occurring asbestos in soils.

Page 18: UC Davis Asbestos Analysis

UC Davis Seismic V; Asbestos & Lead Paint Surveys UC Davis DCM November 2013 Page 18 of 18 Quantities identified may not represent entire quantities of each material in the building based on the scope of the survey. The analyzing laboratory quantifies asbestos concentrations by calibrated visual estimation using standard PLM methodology, with detection of asbestos is material/matrix dependent. Detection of trace asbestos (<1%) may not be reliable or reproducible by PLM and percentage of asbestos weight cannot be determined with standard PLM methodology. Confirmation of asbestos concentrations within complex matrices (i.e. plaster, gypsum wallboard/taping/joint compounds, stucco, resilient flooring, roofing) or when asbestos concentrations are 1% or less may warrant additional analysis by PLM point counting, gravimetric reduction or Transmission Electron Microscopy for proper characterization of asbestos-containing materials and/or waste-stream analysis. This report is prepared for the express use of University of California at Davis, its agents and employees. The information in this report or portions thereof may be required to be included in notifications to employees, occupants, contractors, vendors or other visitors to the building. This report is not intended to be used as a specification or work plan for removal of asbestos-containing or other hazardous materials identified in the report or for any work suggested by the report. Please contact me at (510) 638-8400 ext. 111, should you have any questions on the findings. Sincerely, ACC ENVIRONMENTAL CONSULTANTS, INC.

Chris Yama, CAC, CHMM, LEED AP Senior Project Manager Cal-OSHA Certified Asbestos Consultant (CAC #98-2356) CDPH I-3814 CY/jpt Attachments: Laboratory Reports

Page 19: UC Davis Asbestos Analysis

Final Report

Bulk Asbestos Analysis(EPA Method 600/R-93-116, Visual Area Estimation)

Forensic Analytical Laboratories

1117Client ID:ACC Environmental ConsultantsB183049Report Number:Project Manager

Date Received:7977 Capwell Dr., Suite 10010/14/13Date Analyzed:10/15/13Date Printed:Oakland, CA 94621

First Reported:

11173028-066 - UC Davis Olson Hall, One Shields FALI Job ID:Job ID/Site:

Date(s) Collected:5Total Samples Submitted:

Total Samples Analyzed: 5

10/14/13

10/15/13

Sample ID Lab NumberAsbestos

TypePercent in

LayerAsbestos AsbestosPercent in Percent in

Type TypeLayer Layer

PC-1-1 11437681Layer: White/Black Plaster NDLayer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:Cellulose (Trace)

PC-1-2 11437682Layer: White/Black Plaster NDLayer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:Cellulose (Trace)

PC-1-3 11437683Layer: White/Black Plaster NDLayer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:Cellulose (Trace)

RM-2-1 11437684Layer: Black Felt NDLayer: Black Tar NDLayer: White Foam ND

Asbestos (ND)Total Composite Values of Fibrous Components:Cellulose (40 %) Fibrous Glass (10 %)

RM-2-2 11437685Layer: Black Felt NDLayer: Black Tar NDLayer: White Foam ND

Asbestos (ND)Total Composite Values of Fibrous Components:Cellulose (40 %) Fibrous Glass (10 %)

1 of 23777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

Page 20: UC Davis Asbestos Analysis

Report Number: B183049Date Printed: 10/15/13Client Name: ACC Environmental Consultants

Sample ID Lab NumberAsbestos

TypePercent in

LayerAsbestos AsbestosPercent in Percent in

Type TypeLayer Layer

Analytical results and reports are generated by Forensic Analytical Laboratories Inc. (FALI) at the request of and for the exclusive use of the person or entity (client) named on suchreport. Results, reports or copies of same will not be released by FALI to any third party without prior written request from client. This report applies only to the sample(s) tested.Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by FALI. The client is solely responsible for theuse and interpretation of test results and reports requested from FALI. Forensic Analytical Laboratories Inc. is not able to assess the degree of hazard resulting from materialsanalyzed. FALI reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. All samples werereceived in acceptable condition unless otherwise noted.

Note: Limit of Quantification ('LOQ') = 1%. 'Trace' denotes the presence of asbestos below the LOQ. 'ND' = 'None Detected'.Tad Thrower, Laboratory Supervisor, Hayward Laboratory

2 of 23777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

Page 21: UC Davis Asbestos Analysis
Page 22: UC Davis Asbestos Analysis

Report Number: B183048Date Printed: 10/15/13Client Name: ACC Environmental Consultants

Sample ID Lab NumberAsbestos

TypePercent in

LayerAsbestos AsbestosPercent in Percent in

Type TypeLayer Layer

JC-4-1 11437680Layer: White Drywall NDLayer: Off-White Joint Compound NDLayer: Off-White Tape NDLayer: Off-White Joint Compound NDLayer: Paint ND

Asbestos (ND)Total Composite Values of Fibrous Components:Cellulose (20 %) Fibrous Glass (10 %)

Analytical results and reports are generated by Forensic Analytical Laboratories Inc. (FALI) at the request of and for the exclusive use of the person or entity (client) named on suchreport. Results, reports or copies of same will not be released by FALI to any third party without prior written request from client. This report applies only to the sample(s) tested.Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by FALI. The client is solely responsible for theuse and interpretation of test results and reports requested from FALI. Forensic Analytical Laboratories Inc. is not able to assess the degree of hazard resulting from materialsanalyzed. FALI reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. All samples werereceived in acceptable condition unless otherwise noted.

Note: Limit of Quantification ('LOQ') = 1%. 'Trace' denotes the presence of asbestos below the LOQ. 'ND' = 'None Detected'.Tad Thrower, Laboratory Supervisor, Hayward Laboratory

2 of 23777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

Page 23: UC Davis Asbestos Analysis

Client ID:Report Number:Date Received:

M143755

Job ID / Site: 3028-066.00, UC Davis, Olson Hall + Med Sci 1B

ACC Environmental Consultants 1117

FALI Job ID:

Date Analyzed:

1117

Project Manager

Oakland, CA 94621

7977 Capwell Dr., Suite 100

Date Printed: 10/15/1310/15/13

First Reported: 10/15/13

Metals Analysis of Bulks

10/14/13

Forensic Analytical Laboratories

Final Report

Date(s) Collected: Total Samples Submitted:Total Samples Analyzed:

1

1

Sample Number Lab Number ResultResult Reporting Method

Analyte Units Limit* Reference

EPA 3050B/742024PbPT-2 30661847 mg/kg 6

Analytical results and reports are generated by Forensic Analytical at the request of and for the exclusive use of the person or entity (client) named on such report. Results,reports or copies of same will not be released by Forensic Analytical to any third party without prior written request from client. This report applies only to the sample(s)tested. Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by Forensic Analytical. The clientis solely responsible for the use and interpretation of test results and reports requested from Forensic Analytical. Forensic Analytical is not able to assess the degree of hazardresulting from materials analyzed. Forensic Analytical reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federalguidelines, unless otherwise specified. Any modifications that have been made to referenced test methods are documented in Forensic Analytical's Standard OperatingProcedures Manual. Sample results have not been blank corrected. Quality control and sample receipt condition were acceptable unless otherwise noted.

* The Reporting Limit represents the lowest amount of analyte that the laboratory can confidently detect in the sample, and is not aregulatory level. The Units for the Reporting Limit are the same as the Units for the Final Results.

Daniele Siu, Laboratory Supervisor, Hayward Laboratory

3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

1 of 1

Page 24: UC Davis Asbestos Analysis

Client ID:Report Number:Date Received:

M143754

Job ID / Site: 3028-066.00, UC Davis, Olson Hall + Med Sci 1B

ACC Environmental Consultants 1117

FALI Job ID:

Date Analyzed:

1117

Project Manager

Oakland, CA 94621

7977 Capwell Dr., Suite 100

Date Printed: 10/15/1310/15/13

First Reported: 10/15/13

Metals Analysis of Paints

10/14/13

Forensic Analytical Laboratories

Final Report

Date(s) Collected: Total Samples Submitted:Total Samples Analyzed:

1

1

Sample Number Lab Number ResultResult Reporting Method

Analyte Units Limit* Reference

EPA 3050B/74200.079PbPT-1 30661846 wt% 0.006

Analytical results and reports are generated by Forensic Analytical at the request of and for the exclusive use of the person or entity (client) named on such report. Results,reports or copies of same will not be released by Forensic Analytical to any third party without prior written request from client. This report applies only to the sample(s)tested. Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by Forensic Analytical. The clientis solely responsible for the use and interpretation of test results and reports requested from Forensic Analytical. Forensic Analytical is not able to assess the degree of hazardresulting from materials analyzed. Forensic Analytical reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federalguidelines, unless otherwise specified. Any modifications that have been made to referenced test methods are documented in Forensic Analytical's Standard OperatingProcedures Manual. Sample results have not been blank corrected. Quality control and sample receipt condition were acceptable unless otherwise noted.

* The Reporting Limit represents the lowest amount of analyte that the laboratory can confidently detect in the sample, and is not aregulatory level. The Units for the Reporting Limit are the same as the Units for the Final Results.

Daniele Siu, Laboratory Supervisor, Hayward Laboratory

3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

1 of 1

Page 25: UC Davis Asbestos Analysis
Page 26: UC Davis Asbestos Analysis

Final Report

ACC Environmental Consultants

7977 Capwell Dr., Suite 100Project Manager

Oakland, CA 94621

Client ID:Report Number:Date Received:

Date Printed:Date Analyzed:

N0058771117

11/22/1311/22/13

Job ID/Site: FALI Job ID:3028-067 - UC Davis, Olson Hall, One Shields 1117

(NESHAP Final Rule, 40 CFR, Part 61)

Bulk Asbestos Point Count Analysis

Sample Preparation and Analysis:

11/19/13

Forensic Analytical Laboratories

Total Samples Submitted:Total Samples Analyzed:

11PLM Report Number: B184568

The NESHAP Final Rule does not define the preparation method for multi-layered samples. In order to determine the composite quantity ofasbestos, the volume percent of each layer is determined, the asbestos containing layers are analyzed by point counting and the composite quantity ofasbestos is calculated. The NESHAP Final Rule can not be applied to matrices that dissolve in refractive index liquid. This includes tar, mastic oradhesive typically found on the back of floor tiles. According to the NESHAP Final Rule, point count data is only necessary when the visual estimateof asbestos is below 10%.

Lab NumberSample ID Layer Description

JC-34-1 11452696 Composite of ALL LayersWhite DrywallBeige Joint CompoundPaint

Asbestos type(s) detected: Chrysotile

< 1100

Number of asbestos points counted:Number of non-empty points: 400

0

Point Count Results:

Percent asbestos in layer:Layer percentage of entire sample:

Composite percentage of asbestos in entire sample: <1.0Comment: Asbestos was detected but no points were counted due to counting criteria. Therefore quantitation deemed to

be < 1%.

Note: Point count results are reported to the nearest percent per EPA method.

Analytical results and reports are generated by Forensic Analytical Laboratories Inc. (FALI) at the request of and for the exclusive use of the person or entity (client) named on suchreport. Results, reports or copies of same will not be released by FALI to any third party without prior written request from client. This report applies only to the sample(s) tested.Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by FALI. The client is solely responsible for theuse and interpretation of test results and reports requested from FALI. Forensic Analytical Laboratories Inc. is not able to assess the degree of hazard resulting from materialsanalyzed. FALI reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified. All samples werereceived in acceptable condition unless otherwise noted.

Note: Limit of Quantification (LOQ) = 1%. Trace denotes the presence of asbestos below the LOQ. ND = None Detected.Tad Thrower, Laboratory Supervisor, Hayward Laboratory

1 of 13777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-421

Page 27: UC Davis Asbestos Analysis

Client ID:Report Number:Date Received:

M144805

Job ID / Site: 3028-067, UC Davis, Olson Hall, One Shields

ACC Environmental Consultants 1117

FALI Job ID:

Date Analyzed:

1117

Project Manager

Oakland, CA 94621

7977 Capwell Dr., Suite 100

Date Printed: 11/20/1311/20/13

First Reported: 11/20/13

Metals Analysis of Bulks

11/19/13

Forensic Analytical Laboratories

Final Report

Date(s) Collected: Total Samples Submitted:Total Samples Analyzed:

6

6

Sample Number Lab Number ResultResult Reporting Method

Analyte Units Limit* Reference

EPA 3050B/742010PbPT-1 30665380 mg/kg 6

EPA 3050B/7420530PbPT-2 30665381 mg/kg 30

EPA 3050B/742039PbPT-6-2 30665382 mg/kg 8

EPA 3050B/7420< 6PbPT-9 30665383 mg/kg 6

EPA 3050B/7420< 40PbPT-11 30665384 mg/kg 40

Comment: Insufficient sample size for repeatable analysis.

EPA 3050B/742055PbPT-15 30665385 mg/kg 8

Analytical results and reports are generated by Forensic Analytical at the request of and for the exclusive use of the person or entity (client) named on such report. Results,reports or copies of same will not be released by Forensic Analytical to any third party without prior written request from client. This report applies only to the sample(s)tested. Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by Forensic Analytical. The clientis solely responsible for the use and interpretation of test results and reports requested from Forensic Analytical. Forensic Analytical is not able to assess the degree of hazardresulting from materials analyzed. Forensic Analytical reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federalguidelines, unless otherwise specified. Any modifications that have been made to referenced test methods are documented in Forensic Analytical's Standard OperatingProcedures Manual. Sample results have not been blank corrected. Quality control and sample receipt condition were acceptable unless otherwise noted.

* The Reporting Limit represents the lowest amount of analyte that the laboratory can confidently detect in the sample, and is not aregulatory level. The Units for the Reporting Limit are the same as the Units for the Final Results.

Daniele Siu, Laboratory Supervisor, Hayward Laboratory

3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

1 of 1

Page 28: UC Davis Asbestos Analysis
Page 29: UC Davis Asbestos Analysis

Client ID:Report Number:Date Received:

M144804

Job ID / Site: 3028-067, UC Davis, Olson Hall, One Shields

ACC Environmental Consultants 1117

FALI Job ID:

Date Analyzed:

1117

Project Manager

Oakland, CA 94621

7977 Capwell Dr., Suite 100

Date Printed: 11/22/1311/22/13

First Reported: 11/22/13

Metals Analysis of Paints

11/19/13

Forensic Analytical Laboratories

Final Report

Date(s) Collected: Total Samples Submitted:Total Samples Analyzed:

13

13

Sample Number Lab Number ResultResult Reporting Method

Analyte Units Limit* Reference

EPA 3050B/74200.46PbPT-3 30665367 wt% 0.03

EPA 3050B/74200.39PbPT-4 30665368 wt% 0.02

EPA 3050B/74200.013PbPT-5 30665369 wt% 0.007

EPA 3050B/74200.035PbPT-6-1 30665370 wt% 0.006

EPA 3050B/7420< 0.007PbPT-4-1 30665371 wt% 0.007

EPA 3050B/74200.63PbPT-7-2 30665372 wt% 0.03

EPA 3050B/74200.83PbPT-8-1 30665373 wt% 0.07

EPA 3050B/74200.47PbPT-8-2 30665374 wt% 0.04

EPA 3050B/74200.63PbPT-10 30665375 wt% 0.03

EPA 3050B/7420< 0.007PbPT-12 30665376 wt% 0.007

EPA 3050B/74200.50PbPT-13 30665377 wt% 0.03

EPA 3050B/74200.72PbPT-14 30665378 wt% 0.04

EPA 3050B/7420< 0.006PbPT-16 30665379 wt% 0.006

Analytical results and reports are generated by Forensic Analytical at the request of and for the exclusive use of the person or entity (client) named on such report. Results,reports or copies of same will not be released by Forensic Analytical to any third party without prior written request from client. This report applies only to the sample(s)tested. Supporting laboratory documentation is available upon request. This report must not be reproduced except in full, unless approved by Forensic Analytical. The clientis solely responsible for the use and interpretation of test results and reports requested from Forensic Analytical. Forensic Analytical is not able to assess the degree of hazardresulting from materials analyzed. Forensic Analytical reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federalguidelines, unless otherwise specified. Any modifications that have been made to referenced test methods are documented in Forensic Analytical's Standard OperatingProcedures Manual. Sample results have not been blank corrected. Quality control and sample receipt condition were acceptable unless otherwise noted.

* The Reporting Limit represents the lowest amount of analyte that the laboratory can confidently detect in the sample, and is not aregulatory level. The Units for the Reporting Limit are the same as the Units for the Final Results.

Daniele Siu, Laboratory Supervisor, Hayward Laboratory

3777 Depot Road, Suite 409, Hayward, CA 94545 / Telephone: (510) 887-8828 (800) 827-FASI / Fax: (510) 887-4218

1 of 1

Page 30: UC Davis Asbestos Analysis
Page 31: UC Davis Asbestos Analysis
Page 32: UC Davis Asbestos Analysis
Page 33: UC Davis Asbestos Analysis
Page 34: UC Davis Asbestos Analysis
Page 35: UC Davis Asbestos Analysis
Page 36: UC Davis Asbestos Analysis
Page 37: UC Davis Asbestos Analysis

Northern California: 7977 Capwell Drive, Suite 100 • Oakland, CA 94621 • (510) 638-8400 • Fax (510) 638-8404 Southern California: 1055 Wilshire Blvd., Suite 1450, Los Angeles, CA 90017 • (213) 353-1240 • Fax (213) 353-1244

February 26, 2014 Ms. Debra Smith Transmitted electronically: [email protected] University of California at Davis Design & Construction Management 255 Cousteau Place Davis, CA 95618 Re: Comprehensive Hazardous Materials Survey for the Planned Renovation/Demolition Project University of California at Davis. Haring Hall One Shields Avenue, Davis, California

ACC Project No. 3028-068.00 Dear Ms. Smith: Per your request, ACC Environmental Consultants, Inc. (ACC) performed a comprehensive asbestos and lead paint survey of the above referenced site from January 13th 2014 through February 7th 2014. The survey of the site was performed to identify suspect asbestos-containing building materials, loose & peeling lead-containing paint, mercury light tubes, mercury thermostat switches, PCB-light ballasts, and PCB caulkings that may be impacted during the planned Renovation/Demolition project. Common suspect asbestos-containing building materials that may be impacted by typical renovation/demolition projects may include but are not limited to, the following materials:

• Roofing Materials • Reflective Paint • Boiler Insulation • Pipe Insulation, Elbows & Fittings • Duct Insulation • Mudded Duct Joints • Vibration/Expansion Joints • Asbestos-cement Piping/Flues • Flooring Materials and Associated Adhesive • Baseboard and Baseboard Adhesive • Carpet Adhesive • Leveling Compound • Wall Materials • Drywall and Joint Compound • Texturing Compound • Ceiling Tile • Plaster Walls/Ceilings • Above Ceiling Materials • Exterior Stucco

ACC conducted the survey of the building according to the scope of work as outlined in the proposal dated December 8, 2013. Building components not associated with the planned Renovation/Demolition project were not

Page 38: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 2 of 19 sampled. Furthermore, lead sampling was conducted to identify suspect lead-containing coatings that may be disturbed by project activities for the purpose of compliance with Cal-OSHA’s Lead in Construction Standard and is not intended to be a “Lead Inspection” or “Lead Risk Assessment” as defined by the California Department of Public Health (CDPH). ACC did not conduct destructive sampling (i.e. opening wall cavities, removal of sub-floor assemblies, etc.) and as such, if any planned renovation, maintenance or demolition activities will impact concealed materials, additional investigation and sampling should be conducted prior to disturbance of these systems.

Asbestos Bulk Sample Results

Mr. Chris Yama, a Certified Asbestos Consultant (#98-2356) with ACC, performed bulk sampling of suspect asbestos-containing materials from January 13th 2014 through February 7th 2014. One hundred ninety two samples of suspect materials were submitted for analysis. Copies of the laboratory results are attached. The samples were delivered to Forensic Analytical Laboratories, of Hayward, California, an independent laboratory that participates in the bulk sample proficiency analysis program conducted by the United States Environmental Protection Agency (EPA) and is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP). The samples were analyzed using Polarized Light Microscopy (PLM) with dispersion staining to estimate percent composition by volume. Samples with less than 1% (<1%) asbestos are designated as “Trace asbestos.” Samples with no observable asbestiform minerals are designated as “no asbestos detected.”

Summary of Asbestos Bulk Sample Results Sample

No. Material Description Material Location Results Approx.

Quantity* NESHAPS Category1

OSHA Class2

RM-1-1 Membrane Roofing and Remnant Tar

East Wing North and South

Non-Fibrous: No Asbestos Detected Tar: No Asbestos Detected Felt: No Asbestos Detected Foam: No Asbestos Detected

N/Q N/A N/A

RM-2-1 Membrane Roofing and Remnant Tar

Southwest Corner Roof

Non-Fibrous: No Asbestos Detected Tar: No Asbestos Detected Foam: No Asbestos Detected

N/Q N/A N/A

RM-3-1 Membrane Roofing and Remnant Tar

Southwest Middle Roof

Non-Fibrous: No Asbestos Detected Tar: No Asbestos Detected Foam: No Asbestos Detected

N/Q N/A N/A

RM-4-1 Membrane Roofing and Remnant Tar

Southwest Upper Roof

Non-Fibrous: No Asbestos Detected Tar: No Asbestos Detected Felt: No Asbestos Detected Foam: No Asbestos Detected

N/Q N/A N/A

Page 39: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 3 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

RM-5-1 Membrane Roofing and Remnant Tar

Northwest Middle Roof

Non-Fibrous: No Asbestos Detected Tar: No Asbestos Detected Foam: No Asbestos Detected Cementitious: No Asbestos Detected

N/Q N/A N/A

RM-6-1 Membrane Roofing and Remnant Tar

Northwest Lower Roof

Non-Fibrous: No Asbestos Detected Tar: No Asbestos Detected Felt: No Asbestos Detected Foam: No Asbestos Detected Cementitious: No Asbestos Detected

N/Q N/A N/A

RM-7-1 & 2

Membrane Roof over Built-up Roof

Northwest Upper Roof

Semi-Fibrous: No Asbestos Detected Silver Paint: No Asbestos Detected Tar: No Asbestos Detected Felt: No Asbestos Detected

N/Q N/A N/A

JC-8-1, 2, 3, 4, 5, 6, & 7

Gypsum Wallboard and Taping Compound

Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Paint: No Asbestos Detected By PLM 400 Point Count Analysis: <1.0% Chrysotile Asbestos

125,000 SF Friable Class 2

PL-9-1, 2, 3, 4, 5, 6, 7

Plaster Throughout Building

Gray Plaster: No Asbestos Detected White Plaster: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

ES-10-1, 2, 3, 4, & 5

Exterior Stucco West Wing North

Gray Cementitious: No Asbestos Detected Brown Cementitious: No Asbestos Detected Beige Cementitious: No Asbestos Detected Non-Fibrous: Trace (<1%) Chrysotile Asbestos Paint: No Asbestos Detected By PLM 400 Point Count Analysis: <1.0% Chrysotile Asbestos

2,200 SF Category II Class 2

Page 40: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 4 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

MI-11-1, 2, 3, 4, 5, 6, & 7

Exterior Concrete and Paint/Texture

Throughout Exterior

Cementitious: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

ES-12-1, 2, 3, 4, & 5

Exterior Stucco Throughout Exterior

Cementitious: No Asbestos Detected Non-Fibrous: Trace (<1%) Chrysotile Asbestos Paint: No Asbestos Detected By PLM 400 Point Count Analysis: <1.0% Chrysotile Asbestos

4,500 SF Category II Class 2

FA-13-1 9”x9” Black Floor Tile and Black Adhesive

Throughout Building

Tile: 2% Chrysotile Asbestos Mastic: 5% Chrysotile Asbestos

79,400 SF Category I Class 2

FA-14-1, 2, & 3

9”x9” Tan Floor Tile and Black Adhesive

Throughout Building

Tan Tile: 2% Chrysotile Asbestos Black Mastic: No Asbestos Detected

4,300 SF Category I Class 2

CT-15-1, & 2

1’x1’ Large Preformation Ceiling Tile with Brown Adhesive

Halls and Various Rooms

Adhesive: No Asbestos Detected Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-16-1 2’x2’ Ceiling Tile Room 1006

Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-17-1, & 2

1’x1’ Ceiling Tile with Small Fissures and Brown Adhesive

West Wing North

Adhesive: No Asbestos Detected Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-18-1 1’x1’ Ceiling Tile with Pinholes and Beige & Brown Adhesive

Large Classroom

Adhesive: No Asbestos Detected Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CM-19-1 Brown Ceiling Tile Adhesive

Room 1310A

Adhesive: No Asbestos Detected Cementitious: No Asbestos Detected

N/Q N/A N/A

CM-20-1 Beige Ceiling Tile Adhesive Room 1310A

Cementitious: No Asbestos Detected Adhesive: No Asbestos Detected Paint: No Asbestos Detected Fibrous: No Asbestos Detected

N/Q N/A N/A

Page 41: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 5 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

CT-21-1 1’x1’ Ceiling Tile with Fissures and Brown Adhesive

Rooms 1016, 1014

Adhesive: No Asbestos Detected Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-22-1 1’x1’ Ceiling Tile with Small Fissures

Throughout Building

Adhesive: No Asbestos Detected Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-23-1 & 2

2’x4’ Ceiling Tile Large Fissures

Throughout Building

Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-24-1 2’x4’ Ceiling Tile Small Fissures

Throughout Building

Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-25-1 2’x4’ Solid Ceiling Tile on Drywall

Room 1241 Lockers

Drywall: No Asbestos Detected Fibrous: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-27-1 & 2

1’x1’ Large Fissure Ceiling Tile and Brown Adhesive

East Lobby

Adhesive: No Asbestos Detected Fibrous Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CT-28-1 & 2

1’x1’ Fissured Ceiling Tile and Brown Adhesive

West Wing South

Adhesive: No Asbestos Detected Fibrous Tile: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

MI-29-1, 2, & 3

Concrete Slab Throughout Building

Cementitious: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

TI-30-1 & 2

Tank Insulation (new) 1st Floor Center Mechanical Room Semi-Fibrous: No Asbestos Detected

N/Q N/A N/A

TI-31-1, 2, & 3 Tank Insulation 1st Floor Center Mechanical Room

Semi-Fibrous: 10% Chrysotile Asbestos; 10% Amosite Asbestos

350 SF Friable Class 1

DI-32-1 & 2

HVAC Duct Insulation, Fiberglass with Black Paper

Throughout Building

Tan Fibrous: No Asbestos Detected Yellow Fibrous: No Asbestos Detected Black Fibrous: No Asbestos Detected

N/Q N/A N/A

DI-33-1 & 2

HVAC Duct Insulation, Silver Tar and Felt and Cork

Throughout Building, Concealed in some Locations.

Semi-Fibrous Tar: 15% Chrysotile Asbestos Silver Non-Fibrous: No Asbestos Detected

7,500 SF Friable Class 1

DI-34-1, 2, & 3

HVAC Duct Insulation Air Cell

Throughout Building, Concealed in some Locations.

Fibrous: 80% Chrysotile Asbestos

17,400 SF Friable Class 1

Page 42: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 6 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

PI-35-1, 2, & 3 Pipe Insulation Hardpack

Throughout Building, Concealed in some Locations.

Semi-Fibrous: 10% Chrysotile Asbestos; 10% Amosite Asbestos

35,400 LF Friable Class 1

PI-36-1, 2, & 3

Pipe Insulation, Black Tar and Cork

Throughout Building, Concealed in some Locations.

Black Tar: No Asbestos Detected Fibrous: 80% Chrysotile Asbestos Paint: No Asbestos Detected

9,400 LF Friable Class 1

PE-37-1, 2, & 3

Pipe Elbows Throughout Building, Concealed in some Locations.

Beige Semi-Fibrous: No Asbestos Detected White Semi-Fibrous: 7% Chrysotile Asbestos; 15% Amosite Asbestos

2,500 Each Friable Class 1

DB-38-1, & 2

Above Ceiling Debris Throughout Building

Semi-Fibrous: 10% Amosite Asbestos; 5% Chrysotile Asbestos

33,700 SF Friable Class 1

DB-39-1 & 2 Debris, Crawl Space Throughout Crawl Space

Semi-Fibrous: 5% Chrysotile Asbestos; 10% Amosite Asbestos Paint: No Asbestos Detected

74,700 SF Friable Class 1

DB-40-1 & 2

Debris, Mechanical Rooms Throughout Building

Semi-Fibrous: 7% Chrysotile Asbestos; 10% Amosite Asbestos Non-Fibrous: No Asbestos Detected

12,900 SF Friable Class 1

WT-41-1, 2, 3

Wall Texture on Gypsum Wallboard

Room 1227 B

Drywall: No Asbestos Detected Texture: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

TG-42-1 & 2

Tile Grout for Tan Ceramic Tile

Bathrooms and Labs

Ceramic Tile: No Asbestos Detected Gray Grout: No Asbestos Detected Off-White Grout: No Asbestos Detected

N/Q N/A N/A

MI-43-1 & 2

Spaghetti Board and Felt Central Wing East

Black Tar: No Asbestos Detected Black Felt: No Asbestos Detected

N/Q N/A N/A

CK-44-1 & 2

Beige/Gray Caulking Exterior Windows

Semi-Fibrous: 3% Chrysotile Asbestos Paint: No Asbestos Detected

22,500 LF Category II Class 2

SK-45-1 Brown Sink Undercoating Room 2149 Non-Fibrous: 2% Chrysotile Asbestos

50 Each Category II Class 2

SK-46-1 White Sink Undercoating Room 2152 Non-Fibrous: 5% Chrysotile Asbestos

44 Each Category II Class 2

SK-47-1 Black Sink Undercoating Room 2170 Non-Fibrous: Trace (<1%) Chrysotile Asbestos

370 Each Category II Class 2

Page 43: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 7 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

SK-48-1 Black Tar Paper Under Sink

Room 1227C

Fibrous: No Asbestos Detected Semi-Fibrous: 10% Chrysotile Asbestos

3 Each Category II Class 2

MI-49-1 Gray Epoxy Flooring Room 1131 Cementitious: No Asbestos Detected

N/Q N/A N/A

MI-50-1 Freezer Insulation – Cork and Tar

Throughout Building

Silver Paint: No Asbestos Detected Cementitious Tar: 2% Chrysotile Asbestos Non-Fibrous: No Asbestos Detected

18,350 SF Category II Class 2

MI-51-1 Tan Epoxy Floor Room 1322

Cementitious: No Asbestos detected Non-Fibrous: No Asbestos

N/Q N/A N/A

MI-52-1 & 2

Brown Epoxy Floor Room 1227C Cementitious: No Asbestos Detected

N/Q N/A N/A

MI-53-1, 2, & 3

Transite Sinks and Air/Gas Boxes

Throughout Building

Semi-Fibrous: 15% Chrysotile Asbestos Non-Fibrous: No Asbestos Detected

1,230 Each Category II Class 2

MI-54-1 Duct Mastic on Fume Vents Room 1070 Non-Fibrous: Paint: No Asbestos Detected

N/Q N/A N/A

MI-55-1 Chalkboards Throughout Building Semi-Fibrous: 7% Chrysotile Asbestos; 3% Amosite Asbestos

3,250 SF Category II Class 2

TF-56-1 2’ Diameter Asbestos Cement (Transite) Flues

From First Floor through Roof, Throughout Building

Semi-Fibrous: 15% Chrysotile Asbestos; 10% Crocidolite Asbestos

4,400 LF Category II Class 2

DI-57-1 Air Handler Duct Insulation Fibrous. Fiberglass Appearance

Roof

Semi-Fibrous: 50% Chrysotile Asbestos; Fibrous: No Asbestos Detected

1,200 SF Friable Class 1

MI-58-1 & 2

Grout on Exterior Stone East Entry

Cementitious: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

CK-59-1 Gray Caulking West Wing – New Non-Fibrous: No Asbestos Detected

N/Q N/A N/A

MI-60-1 Gray Vinyl Lab Tabletop Room 1047

Light Gray Non-Fibrous: No Asbestos Detected Gray Non-Fibrous: No Asbestos Detected

N/Q N/A N/A

MI-61-1 & 2

Gray Solid Lab Tabletop Rooms 1097, 2116 Non-Fibrous: No Asbestos Detected

N/Q N/A N/A

MI-62-1 & 2

Black Laminate Thin Lab Table

Throughout Building

Black Coating: No Asbestos Detected Fibrous: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

MI-63-1, 2, 3, 4, 5, & 6

Black Solid Lab Tabletop Throughout Building

Non-Fibrous: No Asbestos Detected Semi-Fibrous: 15% Chrysotile Asbestos

25,500 SF Category II Class 2

Page 44: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 8 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

MI-64-1 & 2

Black Lab Table Top, Thick Laminate

Throughout Building Semi-Fibrous: 20% Chrysotile Asbestos

12,400 SF Category II Class 2

CK-65-1 & 2

Gray Caulking at Interior Windows

Rooms 2126, 2166 Non-Fibrous: No Asbestos Detected

N/Q N/A N/A

BA-66-1 & 2

Brown/Beige Baseboard Adhesive

Rooms 1310A, 2149

Non-Fibrous: No Asbestos Detected Off-White Mastic: No Asbestos Detected Brown Mastic: No Asbestos Detected Yellow Mastic: No Asbestos Detected

N/Q N/A N/A

BA-67-1 & 2

Brown Baseboard Adhesive

Throughout Building

Non-Fibrous: No Asbestos Detected Mastic: Trace (<1%) Chrysotile Asbestos

11,900 LF Category II Class 2

BA-68-1 & 2

Beige Baseboard Adhesive Hall 1st and 2nd Floors Mastic: No Asbestos Detected

N/Q N/A N/A

BA-69-1 Yellow Baseboard Adhesive

Room 1330F Mastic: No Asbestos Detected

N/Q N/A N/A

LN-70-1 & 2

Tan Marble Linoleum and Yellow Adhesive

2nd Floor Store Lab Rooms 2125 and 2137

Sheet Flooring: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

SV-71-1 & 2

Green Pebble Pattern Sheet Vinyl Flooring

Rooms 1139, 1342

Sheet Flooring: No Asbestos Detected Fibrous Backing: 70% Chrysotile Asbestos

700 SF Friable Class 2

FA-72-1 & 2

12”x12” Gray Floor Tile and Black Adhesive

Room 2216

Tile: No Asbestos Detected Black Mastic: 3% Chrysotile Asbestos

480 SF Category I Class 2

TG-73-1 & 2

Tile Grout for Ceramic Floor Tile

Room 2067, Bathroom – Cen Wing

Ceramic Tile: No Asbestos Detected Grout: No Asbestos Detected

N/Q N/A N/A

FA-74-1 & 2

9”x9” Brown Floor Tile and Black Adhesive

Room 1024

Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

FA-75-1 & 2

12”x12” Beige Floor Tile and Black Adhesive, on Wood

Large Classroom (Room 1310A) and Hallway

Yellow Mastic: No Asbestos Detected Tile: No Asbestos Detected Black Mastic: 2% Chrysotile Asbestos

2,400 SF Category I Class 2

LN-76-1 & 2

Tan Marble Sheet Vinyl Flooring with Black Adhesive

Throughout Building

Sheet Flooring: No Asbestos Detected Mastic: 3% Chrysotile Asbestos

2,400 SF Category I Class 2

LN-77-1 & 2

Tan Marble Linoleum over Black Tar Large Classroom Central Wing

Sheet Flooring: No Asbestos Detected Mastic: 3% Chrysotile Asbestos Cementitious Tar: Trace (<1%) Chrysotile Asbestos

3,200 SF Category I Class 2

Page 45: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 9 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

FA-78-1 & 2

12”x12” Green Floor Tile and Yellow Adhesive

Room 1204

Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

SV-79-1 Tan Pebble Sheet Vinyl Flooring

Elevator

Sheet Flooring: No Asbestos Detected Fibrous Backing: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

LN-80-1 & 2

Tan Marble Linoleum over Brown Epoxy

See MI-52 West Wing

Sheet Flooring: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

SV-81-1 & 2

Tan Pebble Sheet Vinyl Flooring over 9”x 9” Tile

Throughout Building

Sheet Flooring: No Asbestos Detected Fibrous Backing: No Asbestos Detected Tile: 5% Chrysotile Asbestos Mastic: 10% Chrysotile Asbestos

3,200 SF Friable Class 2

AD-82-1 & 2

Black Mastic for 9”x 9” Tiles

Throughout Building

Tile Debris: 5% Chrysotile Asbestos Black Mastic: 10% Chrysotile Asbestos

30,200 SF Category II Class 2

FA-83-1 & 2

12”x12” Beige Floor Tile and Yellow Adhesive

Rooms 1131, 1227

Tile: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

CA-84-1 & 2

Yellow Carpet Adhesive Rooms 1211, 1310A Mastic: No Asbestos Detected

N/Q N/A N/A

FA-85-1, 2, & 3

12”x12” Beige Floor Tile and Black Adhesive

Throughout Building

Tile: No Asbestos Detected Black Mastic: 5% Chrysotile Asbestos

34,100 SF Category I Class 2

LN-86-1 & 2

Green Linoleum Throughout Building

Sheet Flooring: No Asbestos Detected Woven: No Asbestos Detected Mastic: No Asbestos Detected

N/Q N/A N/A

SV-87-1 Tan Pebble Sheet Vinyl Flooring over Green Linoleum

Room 1078

Off-White Sheet Flooring: No Asbestos Detected Fibrous Backing: No Asbestos Detected Mastic: No Asbestos Detected Green Sheet Flooring: No Asbestos Detected Woven: No Asbestos Detected

N/Q N/A N/A

Page 46: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 10 of 19

Sample No. Material Description Material Location Results

Approx. Quantity*

NESHAPS Category1

OSHA Class2

FA-88-1, 2, & 3

12”x12” Beige Floor Tile over 9”x 9” Black Floor Tile

Throughout Building

Off-White Tile: No Asbestos Detected Yellow Mastic: No Asbestos Detected Black Tile: 5% Chrysotile Asbestos Black Mastic: 10% Chrysotile Asbestos Tan Tile: 7% Chrysotile Asbestos

22,600 SF Category I Class 2

DT-89-1 Canvas Duct Tape Throughout Building White Tape: No Asbestos Detected

N/Q N/A N/A

MI-90-1, 2, 3, 4, 5, 6, & 7

Concrete and Paint/Texture on Interior Stairwells

Throughout Building

Cementitious: No Asbestos Detected Paint: No Asbestos Detected

N/Q N/A N/A

FD-91 Fire Doors Throughout Building Assumed Asbestos 325 Each Friable Class 2

MI-92 Fume Hoods with Transite

Throughout Building Assumed Asbestos 225 Each Category II Class 2

MI-93 Mastic and Felt around Freezer/Refrigeration Units

Throughout Building Assumed Asbestos 8,000 SF Category II Class 2

*Approximate quantities should be verified during any project planning as the building was occupied during the survey and ACC was unable to perform a fully destructive investigation to identify all concealed conditions. 1EPA’s NESHAPS regulations define categories of asbestos-containing materials (ACM) based on their potential of asbestos fiber release when disturbed:

• Friable - Any material containing more than 1 percent asbestos that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

• Category I Non-friable ACM (Cat 1 NF) - Asbestos-containing packings, gaskets, resilient floor covering and asphalt roofing products containing more than 1 percent asbestos.

• Category II Non-friable ACM (Cat II NF) - Any material, excluding Category I non-friable ACM containing more than 1 percent asbestos as determined using the methods specified under AHERA, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

2OSHA’s Asbestos in Construction Standard (Federal - 29 CFR 1910.126 and California – 8 CCR 1529) define specific “Classes” of work based on the risk of exposure to employees with the potential for disturbance of asbestos-containing materials. The classes of work are defined as

• Class 1 - Asbestos-related activities involving the removal of thermal systems insulation (TSI) and surfacing ACM or presumed ACM.

• Class 2 - Asbestos-related activities involving the removal of ACM which are not TSI or surfacing ACM. Summary of Asbestos Materials

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Haring Hall Gypsum Wallboard and Taping Compound

Throughout Building

Drywall: No Asbestos Detected Joint Compound: 2% Chrysotile Asbestos Paint: No Asbestos Detected By PLM 400 Point Count Analysis: <1.0% Chrysotile Asbestos

125,000 SF $375,000

Haring Hall Exterior Stucco West Wing North

Gray Cementitious: No Asbestos Detected Brown Cementitious: No Asbestos

2,200 SF $11,000

Page 47: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 11 of 19

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Detected Beige Cementitious: No Asbestos Detected Non-Fibrous: Trace (<1%) Chrysotile Asbestos Paint: No Asbestos Detected By PLM 400 Point Count Analysis: <1.0% Chrysotile Asbestos

Haring Hall

Exterior Stucco Throughout Exterior

Cementitious: No Asbestos Detected Non-Fibrous: Trace (<1%) Chrysotile Asbestos Paint: No Asbestos Detected By PLM 400 Point Count Analysis: <1.0% Chrysotile Asbestos

4,500 SF $22,500

Haring Hall 9”x9” Black Floor Tile and Black Adhesive

Throughout Building Tile: 2% Chrysotile Asbestos Mastic: 5% Chrysotile Asbestos

79,400 SF

$160,000

Haring Hall 9”x9” Tan Floor Tile and Black Adhesive

Throughout Building Tan Tile: 2% Chrysotile Asbestos Black Mastic: No Asbestos Detected

4,300 SF $8,600

Haring Hall Tank Insulation

1st Floor Center Mechanical Room

Semi-Fibrous: 10% Chrysotile Asbestos; 10% Amosite Asbestos

350 SF $1,000

Haring Hall HVAC Duct Insulation, Silver Tar and Felt and Cork

Throughout Building, Concealed in some Locations.

Semi-Fibrous Tar: 15% Chrysotile Asbestos Silver Non-Fibrous: No Asbestos Detected

7,500 SF $37,500

Haring Hall HVAC Duct Insulation Air Cell

Throughout Building, Concealed in some Locations.

Fibrous: 80% Chrysotile Asbestos 17,400

SF $87,500

Haring Hall Pipe Insulation Hardpack

Throughout Building, Concealed in some Locations.

Semi-Fibrous: 10% Chrysotile Asbestos; 10% Amosite Asbestos

35,400 LF $354,000

Haring Hall Pipe Insulation, Black Tar and Cork

Throughout Building, Concealed in some Locations.

Black Tar: No Asbestos Detected Fibrous: 80% Chrysotile Asbestos Paint: No Asbestos Detected

9,400 LF $50,000

Haring Hall

Pipe Elbows Throughout Building, Concealed in some Locations.

Beige Semi-Fibrous: No Asbestos Detected White Semi-Fibrous: 7% Chrysotile Asbestos; 15% Amosite Asbestos

2,500 Each $25,000

Haring Hall Above Ceiling Debris Throughout Building Semi-Fibrous: 10% Amosite Asbestos;

5% Chrysotile Asbestos 33,700

SF $33,700

Haring Hall Debris, Crawl Space

Throughout Crawl Space

Semi-Fibrous: 5% Chrysotile Asbestos; 10% Amosite Asbestos Paint: No Asbestos Detected

74,700 SF $150,000

Haring Hall Debris, Mechanical Rooms Throughout Building

Semi-Fibrous: 7% Chrysotile Asbestos; 10% Amosite Asbestos Non-Fibrous: No Asbestos Detected

12,900 SF $13,000

Haring Hall Beige/Gray Caulking Exterior Windows Semi-Fibrous: 3% Chrysotile Asbestos

Paint: No Asbestos Detected 22,500 LF $45,000

Haring Hall Brown Sink Undercoating

Room 2149 Non-Fibrous: 2% Chrysotile Asbestos 50 Each $500

Haring Hall White Sink Undercoating

Room 2152 Non-Fibrous: 5% Chrysotile Asbestos 44 Each $500

Haring Hall Black Sink Undercoating

Room 2170 Non-Fibrous: Trace (<1%) Chrysotile Asbestos

370 Each $1,000

Page 48: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 12 of 19

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Haring Hall Black Tar Paper Under Sink

Room 1227C Fibrous: No Asbestos Detected Semi-Fibrous: 10% Chrysotile Asbestos

3 Each $100

Haring Hall Freezer Insulation – Cork and Tar

Throughout Building

Silver Paint: No Asbestos Detected Cementitious Tar: 2% Chrysotile Asbestos Non-Fibrous: No Asbestos Detected

18,350 SF

$100,000

Haring Hall Transite Sinks and Air/Gas Boxes

Throughout Building Semi-Fibrous: 15% Chrysotile Asbestos Non-Fibrous: No Asbestos Detected

1,230 Each

$4,000

Haring Hall Chalkboards Throughout Building Semi-Fibrous: 7% Chrysotile Asbestos;

3% Amosite Asbestos 3,250 SF $4,000

Haring Hall 2’ Diameter Asbestos Cement (Transite) Flues

From First Floor through Roof, Throughout Building

Semi-Fibrous: 15% Chrysotile Asbestos; 10% Crocidolite Asbestos

4,400 LF $20,000

Haring Hall Air Handler Duct Insulation Fibrous. Fiberglass Appearance

Roof Semi-Fibrous: 50% Chrysotile Asbestos; Fibrous: No Asbestos Detected

1,200 SF $5,000

Haring Hall Black Solid Lab Tabletop

Throughout Building Non-Fibrous: No Asbestos Detected Semi-Fibrous: 15% Chrysotile Asbestos

25,500 SF

$12,000

Haring Hall Black Lab Table Top, Thick Laminate

Throughout Building Semi-Fibrous: 20% Chrysotile Asbestos 12,400 SF

$6,000

Haring Hall Brown Baseboard Adhesive Throughout Building

Non-Fibrous: No Asbestos Detected Mastic: Trace (<1%) Chrysotile Asbestos

11,900 LF $12,000

Haring Hall Green Pebble Pattern Sheet Vinyl Flooring Rooms 1139, 1342

Sheet Flooring: No Asbestos Detected Fibrous Backing: 70% Chrysotile Asbestos

700 SF $2,100

Haring Hall 12”x12” Gray Floor Tile and Black Adhesive

Room 2216 Tile: No Asbestos Detected Black Mastic: 3% Chrysotile Asbestos 480 SF $1,000

Haring Hall 12”x12” Beige Floor Tile and Black Adhesive, on Wood

Large Classroom (Room 1310A) and Hallway

Yellow Mastic: No Asbestos Detected Tile: No Asbestos Detected Black Mastic: 2% Chrysotile Asbestos

2,400 SF $5,000

Haring Hall Tan Marble Sheet Vinyl Flooring with Black Adhesive

Throughout Building Sheet Flooring: No Asbestos Detected Mastic: 3% Chrysotile Asbestos 2,400 SF $7,500

Haring Hall Tan Marble Linoleum over Black Tar

Large Classroom Central Wing

Sheet Flooring: No Asbestos Detected Mastic: 3% Chrysotile Asbestos Cementitious Tar: Trace (<1%) Chrysotile Asbestos

3,200 SF $10,000

Haring Hall Tan Pebble Sheet Vinyl Flooring over 9”x 9” Tile

Throughout Building

Sheet Flooring: No Asbestos Detected Fibrous Backing: No Asbestos Detected Tile: 5% Chrysotile Asbestos Mastic: 10% Chrysotile Asbestos

3,200 SF $10,000

Haring Hall Black Mastic for 9”x 9” Tiles

Throughout Building Tile Debris: 5% Chrysotile Asbestos Black Mastic: 10% Chrysotile Asbestos

30,200 SF

$30,000

Haring Hall 12”x12” Beige Floor Tile and Black Adhesive

Throughout Building Tile: No Asbestos Detected Black Mastic: 5% Chrysotile Asbestos

34,100 SF $70,000

Haring Hall 12”x12” Beige Floor Tile over 9”x 9” Black Floor Tile

Throughout Building

Off-White Tile: No Asbestos Detected Yellow Mastic: No Asbestos Detected Black Tile: 5% Chrysotile Asbestos Black Mastic: 10% Chrysotile Asbestos Tan Tile: 7% Chrysotile Asbestos

22,600 SF $75,000

Haring Hall Fire Doors Throughout Building Assumed Asbestos 325 Each $2,000

Haring Hall Fume Hoods with Transite

Throughout Building Assumed Asbestos 225 Each $4,000

Page 49: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 13 of 19

Building Material Description Location Description Results

Approx. Quantity*

Cost Estimate

Haring Hall Mastic and Felt around Freezer/Refrigeration Units

Throughout Building Assumed Asbestos 8,000 SF $24,000

Haring Hall Underground Transite Piping

Below Grade Around Building

Assumed Asbestos 5,000 LF $10,000

Haring Hall Underground ACM Friable Piping

Below Grade Around Building

Assumed Asbestos 1,000 LF $7,000

Total $1,796,500

Asbestos Sampling Conclusions & Recommendations Based on the sample results, the planned Renovation/Demolition project will impact asbestos-containing materials. The final scope of work should be reviewed against the asbestos survey information. If asbestos-containing materials will be disturbed during the projects, all work should be performed by licensed asbestos abatement contractors working under standard asbestos program requirements. A review of all other asbestos survey information available for the property in conjunction with these results should be conducted prior to proceeding with project activities and when a change in the project scope is developed. If suspect asbestos-containing materials will be impacted that are not addressed in this survey or in the historical survey records, additional sampling should be conducted prior to disturbance. Historical records (typically predating 1995) have limited value for project planning and should be verified with confirmatory inspection and additional sampling as necessary prior to project planning.

Lead Sample Results Mr. Chris Yama, a California Department of Public Health Lead Inspector/Assessor/Monitor (I/A/M-3814) with ACC, collected twenty-six (26) bulk samples to establish lead-paint concentration for clean up and disposal requirements. Samples with detectable amounts of lead must be properly removed and disposed of according to local, state and federal regulations. Lead sampling was conducted to identify suspect lead-containing coatings that may be disturbed by project activities for the purpose of compliance with Cal-OSHA’s Lead in Construction Standard and is not intended to be a “Lead Inspection” or “Lead Risk Assessment” as defined by the California Department of Public Health. The bulk samples were obtained from suspect lead-containing building materials identified at the building. Paint sampling was limited to major paint colors on interior and exterior walls, including the predominant trim color throughout the building and may not represent all accent or trim colors found at the property. Paint colors and/or descriptions are identified based on the surface color observed by ACC at the time of the survey and does not necessarily identify paint descriptions underlying the surface coat. The samples were delivered to Forensic Analytical Laboratories, of Hayward, California; an independent American Industrial Hygiene Association (AIHA) accredited laboratory, for analysis. Samples were analyzed by Atomic Absorption (AA) Spectroscopy in accordance with the EPA 3050B/7420 Method. The colors, locations, and lead contents of these paints are listed below.

Summary of Lead Bulk Sample Results

Page 50: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 14 of 19

Sample No.

Material Description Material Location Lead Content

(ppm unless otherwise noted)

Approximate Quantity*

Cost Estimate

PT-1 Tan Epoxy Floor Room 1322 <7 4,900 SF

PT-2-1 & 2 Tan/Brown Ceramic Wall Tile Rooms 2067, 2116 <7 12,400 SF

PT-3 Ceramic Floor Tile Room 2067 <7 3,750 SF

PT-4 Brown and Beige Paint on Base of Walls

Throughout 0.97 wt% 700 SF $1,400

PT-5-1 Tan and Brown Paint on Exterior Concrete Walls

0.031 wt% 900 SF $20,000

PT-6 Tan Paint on Exterior Stucco Southwest Exterior 140 Intact

PT-7 Tan Ceramic Wall Tile 2nd Floor West Wing 1,300 600 SF (area) $1,200

PT-8 Brown Epoxy Floor (Partially Concealed)

West Wing 21 16,300 SF (area) $1,000

PT-9 Varnish on Wood Panels Room 1108 <7 Intact

PT-10-1 & 2

Green, White, & Beige Paint Interior Concrete 0.44 wt% 1,500 SF $18,000

PT-11 Gray Epoxy Floor Room 1131 <7 1,700 SF

PT-12 Beige/Brown Paint on Exterior Stucco

West Wing – North 0.11 wt% Intact

PT-13 Beige/Tan Paint on Doors Throughout 0.39 wt% 50 SF $1,000

PT-14 Green, Blue, Beige, White Paint on Drywall

Throughout <0.007 wt% Intact

PT-15 Tan Paint on HVAC Equipment Roof 0.052 wt% 100 SF $500

PT-16 Varnish on Wood Doors Throughout 63 Intact $4,000

PT-17 Varnish on Wood Cabinets Throughout <7 Intact

PT-18 Gray Paint on Floor Loading Dock, Room 1268 <0.006 wt% 50 SF

PT-20-1 & 2

Green, Brown, Tan, White, Beige, Blue Paint on Plaster

Throughout 0.98 wt% 1,900 SF

$1,350,000 if manually

demolished for renovation. $20,000 if demolished with

building

PT-21 Beige Paint Inside Freezer Room 1261 0.052 wt% 900 SF $1,000

PT-22 Tan and Yellow Paint on Roof Equipment

Roof <0.007 wt% 500 SF

PT-23 Silver and Other Color Paints on Structural Steel

Rails/Beams 0.24 wt% Intact $5,000

PT-24 White/Beige Paint Cabinets 0.23 wt% Intact $1,000

Total $74,100-$1,404,100

*Quantity for “paint” reflects approximate area of loose & peeling only, not all painted surfaces Of the twenty-six (26) samples collected, four (4) were reported to contain lead above 0.5%, 5,000 parts per million (weight by weight), or 1.0 mg/cm2 which is the definition for lead based paint by the Environmental

Page 51: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 15 of 19 Protection Agency (EPA) and the California Department of Public Health (CDPH). Of the twenty-six samples collected, fourteen (14) were found to have detectable amounts of lead. The OSHA Lead in Construction Standard requires the use of special work practices during the disturbance of paint with any detectable amounts of lead. See OSHA Lead Regulation Summary below. Lead containing waste materials with a concentration greater than 0.1%, for total lead, is considered hazardous waste in the State of California. Lead containing waste materials with a total lead concentration between 0.005% (50 ppm) and 0.10% (1000 ppm) must be re-analyzed using the waste extraction test (WET) method to determine the soluble lead content for waste disposal requirements. The EPA – Renovation, Repair and Painting Final Rule (40 CFR 745) requires that renovations conducted for compensation (where lead-based paint will be disturbed) in Target Housing or Child-Occupied facilities, must be performed by Certified Firms using Certified Renovators following the requirements set forth in the regulation. Contractors are also required to notify the Division of Occupational Safety and Health (DOSH) prior to disturbing greater than 100 square feet or l00 linear feet of material containing lead greater than 0.5% by weight, 5000 parts per million (ppm) or 1.0 milligram per square centimeter (mg/cm2).

OSHA Lead Regulation Summary

The Federal Occupational Safety and Health Administration (OSHA), has enacted a lead standard, which was adopted by the Cal/OSHA as 8 CCR 1532.1. The purpose of both standards is to protect construction workers from exposure to lead. OSHA is primarily concerned with activities that disturb paints with any detectable amounts of lead. Lead was used in most paints until the mid 1950’s and was banned in amounts in excess of 0.06% by weight in 1978 for most non-industrial paints by the Consumer Product Safety Commission (CPSC). The Cal/OSHA standard requires contractors and employers to notify the State of California Division of Occupational Safety and Health (DOSH) prior to disturbing greater than 100 square feet or 100 linear feet of material containing lead greater than 0.5%, 5,000 parts per million (weight by weight), or 1.0 mg/cm2. The Cal/OSHA standard also requires contractors and employers who perform paint removal activities to monitor their employees to determine whether they are being exposed in excess of the action level of 30 micrograms per cubic meter of air (µg/m3) over an eight-hour time weighted average (TWA) or the “Permissible Exposure Limit” (PEL) of 50 µg/m3 TWA. Monitoring is performed by personal air sampling. Even when concentrations are below the action level, an employer must provide employees with High Efficiency Particulate Air (HEPA) filtered vacuums, wetting agents and hand-washing facilities. If the exposure exceeds the action level or the PEL, other procedures such as containing the area, local exhaust ventilation, respiratory and worker protection, worker training, decontamination facilities and medical monitoring are required. OSHA has identified several work practices that pose varying levels of lead exposure to laborers disturbing lead-containing paint. Estimated exposure levels of lead are founded on the activity itself, rather than the concentrations of lead present in paint. Therefore, as an example, paint that contains 0.5% versus 15% of lead by weight or 0.8 mg/cm2 versus 3.5 mg/cm2 of lead in paint could pose the same exposure levels to workers depending on the activities that cause the disturbance and the administrative and engineering controls that are followed. The following is a summary of work activities that disturb paint, the expected exposure and the respiratory protection requirements that result as outlined in the OSHA standards:

Activities Potential Exposure Minimum Respiratory Protection Class I activities include: Manual demolition, manual scraping, manual sanding, heat gun applications, general cleanup, power tool cleaning with dust collection systems

50 µg/m3 to 500 µg/m3 Half mask air purifying respirator equipped with HEPA filters having a protection factor of 10

Page 52: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 16 of 19

Activities Potential Exposure Minimum Respiratory Protection and spray painting activities Class II activities include: Using lead-containing mortars, lead burning, lead riveting, rivet busting, power tool cleaning without dust collection systems, cleanup of dry expendable abrasives and abrasive blasting

500 µg/m3 to 2,500 µg/m3 Full face powered air purifying respirators equipped with HEPA filters having a protection factor of 100

Class III activities include: Abrasive blasting, welding, cutting and torch burning on steel structures

Greater than 2,500 µg/m3 Full face supplied air respirator operated in pressure demand mode or other positive pressure mode (type “C”)

Polychlorinated Biphenyls (PCB) Sampling

Mr. Chris Yama with ACC conducted sampling of caulkings typically suspected to contain Polychlorinated Biphenyls (PCBs) on February 12, 2014. Three (3) samples were collected and delivered to EMSL Analytical, Inc., of San Leandro, California, an independent accredited laboratory for analysis by the EPA 8082 Method. Copies of the laboratory results are attached for reference. PCBs are mixtures of synthetic organic chemicals with the same basic chemical structure and similar physical properties ranging from oily liquids to waxy solids. Due to their non-flammability, chemical stability, high boiling point and electrical insulating properties, PCBs were used in hundreds of industrial and commercial applications including electrical, heat transfer, and hydraulic equipment; as plasticizers in paints, plastics and rubber products; in pigments, dyes and carbonless copy paper and many other applications. More than 1.5 billion pounds of PCBs were manufactured in the United States prior to cessation of production in 1977. PCBs have been demonstrated to cause a variety of adverse health effects, including cancer in animals. PCBs have also been shown to cause a number of serious non-cancer health effects in animals, including effects on the immune system, reproductive system, nervous system, endocrine system and other health effects. Studies in humans provide supportive evidence for potential carcinogenic and non-carcinogenic effects of PCBs. The different health effects of PCBs may be interrelated, as alterations in one system may have significant implications for the other systems of the body. Any single, unique, well-defined chemical compound in the PCB category is called a "Congener". The name of a congener specifies the total number of chlorine substituents and the position of each chlorine. PCBs were manufactured as a complex mixture of congeners, through progressive chlorination of batches of Biphenyl until a certain target percentage of Chlorine by weight was achieved. Commercial mixtures with higher percentages of Chlorine contained higher proportions of the more heavily chlorinated congeners, but all congeners could be expected to be present at some level in all mixtures. Once released into the environment and subjected to "weathering", or taken in by plants or animals and partially stored/metabolized/excreted, substantial changes in the congener ratios occurred, and continue to occur. Thus, determination of the parent mixture(s) ultimately resulting in a given environmental sample may be difficult or impossible. While PCB was manufactured and sold under many names, the most common were the "Aroclor" series, in many of which a numerical identifier included the percentage of Chlorine (e.g., "Aroclor 1254", with 54 percent Chlorine). Laboratory reports typically reflect equivalent Aroclor series for each sample. The proper identification and handling of PCB-contaminated equipment and wastes is critical to the prevention of future waste management problems. All equipment or waste containing PCBs should be properly labeled, alerting people to the requirement for special handling procedures. While procedures may vary depending on the industry or specific operation, as a general rule, any time there is a risk of contact with PCBs, appropriate protective equipment should be worn to limit contact with the skin and eyes and to protect against inhalation of PCB fumes.

Page 53: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 17 of 19 Such equipment may include plastic or rubber gloves, boots, overalls, aprons, face shields or self-contained breathing apparatus. For workers cleaning up a major spill containing high concentrations of PCBs, a full suit of non-porous material should be worn. Clothing that has become contaminated should be disposed of along with other PCB wastes. PCB manufacture, use, storage and disposal are regulated by U.S. EPA under TSCA and Part 761, Title 40 of the Code of Federal Regulations (40 CFR Part 761). TSCA regulates any materials or wastes that contain PCBs at concentrations of 50 ppm (parts per million) or greater. PCB wastes are also regulated as hazardous waste by DTSC under the Health and Safety Code (HSC) and Title 22 of the California Code of Regulations (22 CCR). Criteria for determining PCB wastes are: • total threshold limit concentration (TTLC) of 50 ppm of PCBs, and/or • soluble threshold limit concentration (STLC) of 5 ppm of PCBs as oily liquid.

Summary of PCB Sampling Results

Sample Number

Material Description Sample Location PCB Concentration

PCB-1 Beige/Gray/Olive Green Caulking Perimeter of Exterior Windows 0.68 mg/kg (None Detected)

PCB-2 Gray Caulking West Wing - New Windows 0.65 mg/kg (None Detected)

PCB-3 Gray Caulking Interior Windows 0.76 mg/kg (None Detected)

Other Hazardous Materials

ACC quantified the number of mercury containing light tubes; suspect PCB-containing ballasts and Mercury thermostat switches as part of the scope of work. These materials and the quantities indicated below should be included in the hazardous materials removal scope of work or handled by properly trained workers of the demolition contractor and segregated into specific waste streams prior to disturbance by general demolition activities.

Universal Waste/Other Hazardous Wastes Estimated Quantity Cost estimate

Florescent/Mercury Vapor Light Tubes (4’equivalent) 7,900 Each $8,000

Suspect PCB-containing Light Ballasts 3,950 Each $20,000

Mercury-containing Thermostat Switches 300 Each $900

Lead Soundproofing Sheets None Identified

Water/Mold Impacted Materials 2,500 SF Included above in wall and ceiling

demo

A/C Units 520 Each $3,000

Freezers/ Refrigerators and CFCS 90 Each Assumed $3,000

Oil in Pumps and Elevators 50 Each $2,000

Mercury in P-Traps 840 Each $2,000

Transformers with Assumed PCBs 7 Each $10,000-14,000

Total $48,900-52,900

Limitations

Page 54: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 18 of 19 ACC conducted the limited survey with the standard of care ordinarily exercised by qualified and reputable members of the environmental/industrial hygiene profession based on conditions and practices observed at the property and information provided to ACC related to the project and/or purpose of the survey at the time of the investigation. The survey was limited to specific project areas and was not intended to identify all suspect asbestos-containing materials within the building. Areas and materials not included in the survey should be inspected and sampled prior to any renovation, maintenance, demolition or other activity that may cause disturbance to the materials. This report does not intend to identify all hazards or unsafe practices, nor to indicate that other hazards or unsafe conditions do not exist at the property. ACC encountered the following inaccessible areas in addition to general concealed conditions (i.e. within wall cavities, above/below solid ceilings or flooring/sub-flooring materials, etc.) and are excluded from the scope of the survey. These areas should be inspected and any suspect asbestos-containing materials sampled for the presence of asbestos prior to any renovation, maintenance, demolition or other activity that may cause disturbance to the materials. Inaccessible Areas

• No inaccessible areas/equipment were identified within the provided project areas Materials that would require intrusive or destructive sampling were generally not sampled as part of the project unless written direction was provided to ACC to perform intrusive and/or destructive sampling on specific building systems, the area was unoccupied at the time of the survey and by performing intrusive/destructive sampling would not create an unsafe condition. Furthermore, ACC shall not be responsible for identifying and/or sampling suspect materials concealed within walls, columns, beneath flooring, above solid ceilings, underground or in any other concealed areas. ACC shall not be responsible for identification, sampling and/or characterization of water or mold impacted materials. General observations may be noted if ACC observed suspect conditions to the client either separately or within this report. ACC excludes sampling concrete and asphalt paving as suspect asbestos-containing materials. Aggregate found in these materials may contain asbestos if supplied from quarries located in known ultra-mafic areas. It is possible that prior to recycling and/or disposal, recycling agents or landfills may require sampling of these materials to determine the presence of asbestos prior to acceptance.

ACC excludes characterization of soils in areas on known ultramafic rock (where naturally occurring asbestos may be found in soils) as part of the scope of work. If the project area is located within a known ultramafic rock area, provisions should be made to address regulatory requirements for any planned excavation and grading as part of the project. ACC can provide further detail on regulatory requirements related to naturally occurring asbestos in soils. Quantities identified may not represent entire quantities of each material in the building based on the scope of the survey. The analyzing laboratory quantifies asbestos concentrations by calibrated visual estimation using standard PLM methodology, with detection of asbestos is material/matrix dependent. Detection of trace asbestos (<1%) may not be reliable or reproducible by PLM and percentage of asbestos weight cannot be determined with standard PLM methodology. Confirmation of asbestos concentrations within complex matrices (i.e. plaster, gypsum wallboard/taping/joint compounds, stucco, resilient flooring, roofing) or when asbestos concentrations are 1% or less may warrant additional analysis by PLM point counting, gravimetric reduction or Transmission Electron Microscopy for proper characterization of asbestos-containing materials and/or waste-stream analysis.

Page 55: UC Davis Asbestos Analysis

UC Davis – Haring Hall; Comprehensive Hazardous Materials Survey Ms. Debra Smith – UCD Design & Construction Management February 26, 2014 Page 19 of 19 This report is prepared for the express use of University of California at Davis, its agents and employees. The information in this report or portions thereof may be required to be included in notifications to employees, occupants, contractors, vendors or other visitors to the building. This report is not intended to be used as a specification or work plan for removal of asbestos-containing or other hazardous materials identified in the report or for any work suggested by the report. Please contact me at (510) 638-8400 extension 111 if you have any questions. Sincerely, ACC ENVIRONMENTAL CONSULTANTS, INC. Chris Yama, CAC, CHMM, LEED AP Senior Project Manager Cal-OSHA Certified Asbestos Consultant #98-2356 California Department of Public Health Lead I/A/M #3814 /jpt Attachments: Laboratory Reports

Page 56: UC Davis Asbestos Analysis

∆ DELTA DEVELOPMENT Environmental Consulting

Mailing Address: P.O. Box 3203 • Rancho Cordova, CA 95741-3203

11275 Sunrise Gold Circle, Suite Q • Rancho Cordova, CA 95742 Phone (916) 631-1400 • Fax (916) 631-0200

August 22, 2014 Mr. Fred Torres, Project Manager Facilities, Mechanical / HVAC University of California One Shields Avenue Davis, California 95616 Dear Mr. Torres: Per your request, I have reviewed additional hazardous material (asbestos/lead) pre-job start and post project close-out information you provided August 20, 2014. The aforementioned documents are associated with Olson Hall HVAC System Upgrades, Phase II, in Room 0040, Basement Mechanical Room (University Project Number 2503800). Two Rivers Demolition commenced site work associated with the aforementioned project on June 16, 2014 and the University accepted said site work as complete on June 20, 2014. Olson Hall is located on the UC Davis Campus, in Davis, California. Deviations from University Asbestos and Lead Remediation specifications (Sections 028200 & 028300), and the Contractor’s approved Work and Disposal Plans have complicated Project Close Out. This is due in part to the University’s pre-demolition activities which resulted in a lead dust release, and ultimately changed the Contractor’s lead work classification from non-trigger task work to lead trigger task work. The aforementioned deviations include but are not limited to the following: Pre-Job Start Submittals; Contractor’s approved Work Plan (means & methods); Contractor’s approved waste disposal plans; and University clearance criteria. This letter identifies pre-job start and post-job completion submittal deficiencies and/or omissions related to the University’s Asbestos Remediation Specification (Section 028200) and Lead Remediation Specification (Section 028300). Said deficiencies and/or omissions listed below must be corrected and accepted by the University’s prior to issuing the Contractor final payment. Also, please let me know if additional documentation is needed to address mid-project modifications to requirements found in the University’s Asbestos and Lead Remediation Specifications, including lead clearance criteria and asbestos / lead disposal. Asbestos Pre-Job Start & Post Job Completion Submittal Deficiencies and/or Omissions:

1. One electronic copy of supplemental pre-job start submittals was provided. Contractor shall provide required number of hard copies of project submittals per Section 028200, 1.5 Submittals, D.

2. Laboratory Qualifications: EMSL Analytical, Inc. of San Leandro, California is identified as the Contractor’s asbestos laboratory, however, asbestos analysis reports have not been provided. Contractor shall submit asbestos analysis reports.

Page 57: UC Davis Asbestos Analysis

∆ DELTA DEVELOPMENT Environmental Consulting

Mailing Address: P.O. Box 3203 • Rancho Cordova, CA 95741-3203

11275 Sunrise Gold Circle, Suite Q • Rancho Cordova, CA 95742 Phone (916) 631-1400 • Fax (916) 631-0200

Mr. Fred Torres, Project Manager UCD, Olson Hall HVAC System Upgrades Room 0040, Basement Mechanical Room University Project Number 2503800 Asbestos/Lead Removal Close-Out Documentation Review # 2 August 22, 2014 Page Two

3. A statement titled “3.15 Project Close-Out” was provided on Two Rivers Demolition’s letterhead, and appears to contain information pertaining to both asbestos and lead Project Close-Out documentation. Although Asbestos and Lead Project Close Out documentation may contain some duplicate information, said information must be provided as two independent documents. Contractor shall provide Asbestos Project Close Out information identified in Project Close-Out Requirements, Section 028200 Asbestos Remediation Specification, 3.15. Close Out documentation shall pertain to actual work performed, not proposed work, and clarify deviations from project specifications and approved Work and Disposal Plans, including means and methods, and waste packaging / transportation / disposal.

4. Contractor’s statement titled “3.15 Project Close-Out”, which was provided on Two Rivers Demolition’s letterhead, states “All asbestos was turned over to the University for disposal per John Nichols of Delta Development.” The aforementioned statement is false and must be removed from the Contractor’s Close Out documentation. Neither John Nichols or Delta Development directed the Contractor to deviate from the approved waste disposal plan. Furthermore, Asbestos Project Close Out documentation should accurately reflect waste disposal and any deviations from approved Exhibit 21 Asbestos Waste Disposal Plan.

5. Exhibit 22 – Asbestos As-Built Summary is incomplete with regard to waste disposal and transportation, and states “See attached document “Asbestos Waste””. However, the aforementioned “Asbestos Waste” document was not provided. Contractor shall provide waste disposal and transportation information requested in Exhibit 22 Asbestos As-Built Summary, Section 028200 Asbestos Remediation Specification.

Lead Pre-Job Start & Post Job Completion Submittal Deficiencies and/or Omissions:

1. One electronic copy of supplemental pre-job start submittals was provided. Contractor shall provide required number of hard copies of project submittals per Section 028300, 1.5 Submittals, D.

2. Recycler weight tickets include slips from Sims Metal, however, Sims Metal is not the recycler identified in the Contractor’s approved disposal plan. Additionally, recycler weight tickets appear to include materials not associated with the Olson Hall project. Contractor shall clarify.

3. A statement titled “3.15 Project Close-Out” was provided on Two Rivers Demolition’s letterhead, and appears to contain information pertaining to both asbestos and lead Project Close-Out documentation. Although Asbestos and Lead Project Close Out documentation may contain some duplicate information, said information must be provided as two independent documents.

Page 58: UC Davis Asbestos Analysis

∆ DELTA DEVELOPMENT Environmental Consulting

Mailing Address: P.O. Box 3203 • Rancho Cordova, CA 95741-3203

11275 Sunrise Gold Circle, Suite Q • Rancho Cordova, CA 95742 Phone (916) 631-1400 • Fax (916) 631-0200

Mr. Fred Torres, Project Manager UCD, Olson Hall HVAC System Upgrades Room 0040, Basement Mechanical Room University Project Number 2503800 Asbestos/Lead Removal Close-Out Documentation Review # 2 August 22, 2014 Page Three

Contractor shall provide Lead Project Close Out information identified in Project Close-Out Requirements, Section 028300 Lead Remediation Specification, 3.15. Close Out documentation shall pertain to actual work performed, not proposed work, and clarify deviations from project specifications and approved Work and Disposal Plans, including means and methods and waste handling. Identify all waste streams, and account for waste hazard classification / packaging / transportation / disposal.

4. Contractor’s statement titled “3.15 Project Close-Out” was provided on Two Rivers Demolition’s letterhead, and states “Materials were hauled off by Two Rivers Demolition Inc. and transported to Schnitzer Steel Products. Identify the materials hauled to Schnitzer Steel Products. Additionally, transport vehicles observed on site were marked as Primoris Demolition, not Two Rivers as stated in Project Close Out documentation. Contractor shall clarify.

5. Exhibit 25 – Lead As-Built Summary is incomplete with regard to waste disposal and transportation, and states “See attached document “Lead Waste””. However, the aforementioned “Lead Waste” document was not provided. Contractor shall provide waste disposal and transportation information requested in Exhibit 25 Lead As-Built Summary, Section 028300 Lead Remediation Specification. Be sure to account for all waste streams, including, but not limited to dust, vacuum debris, decontamination materials and supplies, and personal protective equipment.

If you have questions regarding information included in this letter please contact me at (916) 631-1400. Thank you for the opportunity to serve you. Sincerely, John M. Nichols Certified Lead Consultant, 2839 Certified Asbestos Consultant, 92-0039 Cc: Tom Emme, UCD Cynthia Hongola, UCD

Page 59: UC Davis Asbestos Analysis

35585

July 30, 2015 Project No.: 2505030.01.00 Scott Slayton, Project Manager Design and Construction Management University of California, Davis 255 Cousteau Place Davis, CA 95618 RE: Asbestos Air and Visual Clearance - Pass

Olson Hall Classroom Renovations – Classroom 0101 198 Peter J Shields Avenue Davis, CA 95616

Dear Mr. Slayton, The following report is in regards to the completed air monitoring clearance sampling that was conducted at the above listed address, in Olson Hall Classroom 0101 (CAAN #3803; Zone #C005). Prior to the visual inspection and air clearance sampling being conducted by N.A.L., Allied Environmental, Inc., removed the asbestos containing Floor Tile, Mastic, and Transite Chalkboard materials from the work area. Denis Edwards, Certified Asbestos Consultant, for National Analytical Laboratories, Inc., completed the air clearance sampling on July 29, 2015. Because the visual inspection showed no asbestos containing construction materials (ACCM), asbestos debris, or any other impairment, Mr. Edwards proceeded with the Phase Contrast Microscopy (PCM) air clearance sampling using 25mm cassettes. The cassettes used had a Mixed Cellulose Ester membrane 0.8 µm, micron pore size that is used specifically for PCM sampling. The air monitoring cassette was calibrated with a Dwyer series VFB Visi-Float Flowmeter at 8.33 liters per minute (lpm). The air monitor operated for total of 150 minutes, for a total cassette volume of 1249.50 liters. The total volume fell within the projected range of 400 to 1800 liters for PCM sampling. A total of two (2) samples were collected from the Center of Classroom 0101 and transported to MicroTest Laboratories, Inc., for analysis. The average concentration for airborne fibers found in the two (2) samples was <0.002 f/cc. The clearance result is below the Environmental Protection Agency’s (EPA’s) PCM clearance level of 0.01 f/cc. Laboratory analytical report and chain of custody form attached. Classroom 0101 work area has been cleared for re-occupancy. Individuals may enter the Classroom without any health or safety concerns in regards to the exposure of airborne asbestos fibers. If you have any questions regarding this report or if we can be of further assistance, please contact our office.

Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant, DOSH #92-0261

MULMSLNS

Page 60: UC Davis Asbestos Analysis

MicroTest Laboratories Inc.AIHA IHPAT # 160934

5150 Sunrise Blvd, Suite B-1Fair Oaks, CA 95628

. Tel. (916) 567-980g-Fax: (916) 4-36-3603

E-mail: mlcrotestlabsincepvahoo.com

PROJECT:

NAL2201 Francisco Drive, Ste 140-261EI Dorado Hills, CA 95762

Olson Hall

..CLIENT:

SAMPLESCOLLECTEDBY: Edwards

TYPEOF SAMPLE: PCM Cassette x2

COLLECTION DATE:

SUBMISSION DATE:

7/29/2015

7/29/2015

ACCESSIONNUMBER: 41120-41121

TYPEOF ANALYSIS: Phase Contrast Microscopy, NIOSH 7400 Method "A" Rules

REPORTDATE: 7/30/2015

REPORTEDAND REVIEWED BY: Rebecca Hutty, MicroTest Laboratories Inc., Analyzed by: M. Nguyen

PHASECONTRAST MICROSCOPY-NIOSH 7400The "Samples" collected demonstrated the following:

Sample # Sample Description Sample Type Total Volume Fibers Fields Fibers/mm2 U.c.L. LOD fb/cc

3853-03ACClearance Rm 101 Clearance 1250 <5.5 100 <7 <0.007 0.002 <0.002

411203853-04AC

Field Blank Blank N/A <5.5 100 <7 N/A N/A N/A41121

,

*AII samples tested as submitted to Microtest Labs, Inc. We do not assume responsibility for the accuracy of the

information submitted. I*Any numerical value which calculates to be less than 0.01 fb/cc should be view as <0_01 fb/cc due to the inaccuracy ofthe NIOSH 7400 Method (LOD 7fb/mm2).

*Comments such as "Overloaded", "Dirty", "Wet Filter", "Uneven disbursement of Fibers" or "Torn Filter", ill~s.trate thatthe analyst found discrepancies or problems with the sample and the results are not considered accurate. ..•..

Page 61: UC Davis Asbestos Analysis

Page

Login #

1 of 1 35585 NAL LOG-IN RECORD

Ph: 916.361.0555 Fx: 916.361.0540

National Analytical Laboratories, Inc. Job Site/Job #:

Client#-Lot# 4373 / 741 Olson Hall (CAAN #3803; Zone #C005): Date 7/30/2015

UC Davis Design & Construction Management Classrooms 0101, 0105, 0118, 0125, 0141, 0163 & 0227 Sampling Date: 7/29/2015

Phone Number Davis, CA 95616 Sampling Time 9:55:00 AM

FAX Number Type of Work: PCM Clearance

Contact Scott Slayton 2505030 No. of Samples 2 E-Mail Address Turnaround: Rush

Chain of Custody Information

Released By Signature Date/ Time Received By Signature Date/

Time Due: 7/29/2015 Denis Edwards 072915

1640

Released By Signature Date/ Time Received By Signature Date/

Time At: 13:55

Num. Sample ID# Min. LPM Volume Location/Description

1 3803-03AC 150 8.33 1249.5 Classroom 0101, Center of Room / Clearance

2 3803-04ACFB 0 0 0 Field Blank / 30 Second Cap Off

Page 62: UC Davis Asbestos Analysis

',!..

Y)I'r=

-'-i

1\L\

IPa

geOf

:,N

·A·L

'1NATIO

NAL

ANAl\'TICAl

I.AIlO

RATOIUES,

INC.

,'•....

..

Login

#:

....:

Com

pany:

.rco

Contact:

~c;""'

-Add

ress:

Phone:

E-Mail:

-Sa

mpler:

t:;7:Jc

J.,4.R

..'OS

Job

Site:

2201

Francisco

Dr.

Ste.

140-2611

ElDorado

Hills,

CA.9

5762

Phone

(916)361-0555

Fax(916)361-0540

www.nall.com

Job

Num

ber:

#of

Samples:

SAMPL

EDATE

:---

------

------

------

----

Contact:

,TY

PEOF

WORK

TURNAROUND

OTH

ERPL

MC.I~

EMLE

AD

BULK

LEAD

WIPES

LEAD

AIR

Laboratory

Rush

Water

PLM

r--

~:::~

~na~

Chip

Clearance

Area

Consulting

,/6Hour

-Soil

r--TT

FP*So

ilBaseline

-Personal

.~OnSite

24Hour

-Mold

I---

400

Pt.C

t.I---

Area

-TTL

C-

AmbientAir

72Hour

,..---

I---

1000

Pt.C

t.tK=C

learance

-STL

C-

I---

I---TC

LlP

.Sample

Time

Total

Liters

PerMinute

Total

Measurement

Locatio

nlDescriptio

nNum

ber

On

Off

Minutes

On

Off

Aver

Volum

eSF

/LF/CF

3K:1-61{tG

d~~;-

/~1{:

J:j0".,

t.3~

Ci:37

,~tilS(j

Ct&UTi£/Z6~~

L(I(LO

.."

S--

0,;;-:>

CL6

~c:6.

.PH

/O(

'. ..,

-3gS0,d<!;4<

r/£C,t)

1J.L~t.

y(ILl

,

\

'.

r !

Special

Instructions:

DatelTime

Received

B:

DatelTime

Page 63: UC Davis Asbestos Analysis

35596

July 31, 2015 Project No.: 2505030.01.00 Scott Slayton, Project Manager Design and Construction Management University of California, Davis 255 Cousteau Place Davis, CA 95618 RE: Asbestos Air and Visual Clearance - Pass

Olson Hall Classroom Renovations – Classrooms 0105 & 0227 198 Peter J Shields Avenue Davis, CA 95616

Dear Mr. Slayton, The following report is in regards to the completed air monitoring clearance sampling that was conducted at the above listed address, in Olson Hall Classrooms 0105 & 0227 (CAAN #3803; Zone #C005). Prior to the visual inspection and air clearance sampling being conducted by N.A.L., Allied Environmental, Inc., removed the asbestos containing materials from the work area. Denis Edwards, Certified Asbestos Consultant, for National Analytical Laboratories, Inc., completed the air clearance sampling on July 30, 2015. Because the visual inspection showed no asbestos containing construction materials (ACCM), asbestos debris, or any other impairment, Mr. Edwards proceeded with the Phase Contrast Microscopy (PCM) air clearance sampling using 25mm cassettes. The cassettes used had a Mixed Cellulose Ester membrane 0.8 µm, micron pore size that is used specifically for PCM sampling. The air monitoring cassette was calibrated with a Dwyer series VFB Visi-Float Flowmeter at 6.48 liters per minute (lpm) in Classroom 0105, and 8.33 lpm in Classroom 0227. The air monitor operated for total of 200 minutes in Classroom 0105, and 148 minutes in Classroom 0227 for a total cassette volume of 1296 in Classroom 0105, and 1232.84 in Classroom 0227. The total volume of both samples fell within the projected range of 400 to 1800 liters for PCM sampling. A total of two (2) samples were collected from the Center of Classrooms 0105 and 0227 and were transported to MicroTest Laboratories, Inc., for analysis. The average concentration for airborne fibers found in the three (3) samples was <0.002 f/cc. The clearance result is below the Environmental Protection Agency’s (EPA’s) PCM clearance level of 0.01 f/cc. Laboratory analytical report and chain of custody form attached. Classroom 0105 and 0227 work areas have been cleared for re-occupancy. Individuals may enter the Classrooms without any health or safety concerns in regards to the exposure of airborne asbestos fibers. If you have any questions regarding this report or if we can be of further assistance, please contact our office.

Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant, DOSH #92-0261

MULMSLNS

Page 64: UC Davis Asbestos Analysis

MicroTest Laboratories Inc.AIHA IHPAT # 160934

5150 Sunrise Blvd, Suite B-1Fair Oaks, CA 95628

. Tel. (916) 567-980S·Fax: (916) 436-3603

E-mail: mfcrotestlabsinctavahoo.com

PROJECT:

NAL2201 Francisco Drive, Ste 140-261EI Dorado Hills, CA 95762

Olson HallCAAN 3853

•CLIENT:

SAMPLES COLLECTEDBY: Edwards

TYPEOF SAMPLE: PCM Cassette x3

ACCESSIONNUMBER:

7/30/2015

7/30/2015

41167-41169

COLLECTION DATE:

SUBMISSION DATE:

TYPEOF ANALYSIS: Phase Contrast Microscopy, NIOSH 7400 Method (fA" Rules

REPORTDATE: 7/31/2015

REPORTEDAND REVIEWED BY: Rebecca Hutty, MicroTest Laboratories Inc., Analyzed by: M. Nguyen

PHASECONTRAST MICROSCOPY-NIOSH 7400The "Samples" collected demonstrated the following:

Sample # Sample Description Sample Type Total Volume Fibers Fields Fibers/mm2 U.c.L. LOD fb/cc3853-05AC Rm 0105 Center of

Clearance 1296 <5.5 100 <7 <0.007 0.01)2 <0.00241167 Room

3853-06AC Rm 0227 Center ofClearance

Reom1233 <5.5 100 <7 <0.007 0.002 <0.002

. 41168I

3853-07ACField Blank Blank N/A <5.5 100 <7 N/A N/A N/A

41169

*AII samples tested as submitted to Microtest Labs, Inc. We do not assume responsibility for the accuracy of the'information submitted. /'*Any numerical value which calculates to be less than 0.01 fb/cc should be view as <0.01 fb/cc due to the in~ccuracy of~the NIOSH 7400 Method (LOD 7fb/mm2).

*Comments such as "Overloaded", "Dirty", "Wet Filter", "Uneven disbursement of Fibers" or "Torn Filter", illustrate thatthe analyst found discrepancies or problems with the sample and the results are not considered accurate.

Page 65: UC Davis Asbestos Analysis

Page

Login #

1 of 1 35596 NAL LOG-IN RECORD

Ph: 916.361.0555 Fx: 916.361.0540

National Analytical Laboratories, Inc. Job Site/Job #:

Client#-Lot# 4373 / 743 Olson Hall (CAAN #3803; Zone #C005): Date 7/31/2015

UC Davis Design & Construction Management Classrooms 0101, 0105, 0118, 0125, 0141, 0163 & 0227 Sampling Date: 7/30/2015

Phone Number Davis, CA 95616 Sampling Time 6:15:00 AM

FAX Number Type of Work: PCM Clearance

Contact Scott Slayton 2505030 No. of Samples 3 E-Mail Address Turnaround: Rush

Chain of Custody Information

Released By Signature Date/ Time Received By Signature Date/

Time Due: 7/30/2015 Denis Edwards 07/30/15

1615

Released By Signature Date/ Time Received By Signature Date/

Time At: 10:15

Num. Sample ID# Min. LPM Volume Location/Description

1 3803-05AC 200 6.48 1296 Classroom 0105, Center of Room / Clearance

2 3803-06AC 148 8.33 1232.84 Classroom 0227, Center of Room / Clearance

3 3803-07ACFB 0 0 0 Field Blank / 30 Second Cap Off

Page 66: UC Davis Asbestos Analysis

·....

y'\l..o~-~I\V

'\(

Of

Login#:

(**ortkialusc

only***

Page

...."

,.'

~,

,""

',!>.•

N·A

·LJob

Site:

Com

pany:

Sampler:

"','

~..".:

Contact:

- "":

,,

',•......

NArll)N

At.

AN'\lYTI(",\1

1'\1

I0RATORlfo

;.IN{

".-

Address:

220IF

rancisc

oDr

.Ste.

140-26

11EI

Dorado

Hills,CA

.95762

Phon

e(916)

361-0555

Fax(916

)36

1-05

40www.nal

l.corn

~/t'

Job

Num

ber:

CA/tA

i8~

~#of

Samples:

Phone:

E-Mail:

SAMPL

EDATE

:17

3<:)

/SContact:

~Gf

,•

I~,

TYPE

OFW

ORK

TURN

AROUND

OTH

ERPL

MCYQj)T

EMLE

AD

BULK

LEAD

WIPES

LEAD

AIR

Laboratory

t::zRU

Shf-------

Water

PLM

Baseline

Chip

_Clearance

Area

Consulting

6Hour

f-------

TTFP

'_P

ersonal

_Soil

-So

il_B

aseline

_Personal

/OnSite

f-------

24Hour

Mold

f-------

400

PI.C

t.Area

TTLC

AmbientAir

f-------

72Hour

~IOOOPt.Ct.

t:z=C

learance

STLC

TCLlP

.Sample

Time

Total

Liters

PerMinute

Total

Mea

suremen

t;

Num

ber

On.

Off

Minutes

On

Off

Aver

Volum

eSF

/LF/CF

Locatio

n/Descriptio

n

3~3"'-6

SI1<0&

,5'&'f-t.i'

.:t.(X

lcP

.<~G,

«tJ(..98

~%eLt£~a

f2H

t:)/61:('

C~C

£~L(

H197 U'Q,.

..'

o5<;;~cG

k1/3

013

f{1;

&.~~8,~~

~.~

~i3~

-G~

I?,M

6~7

~~60

~~

\,,

.5~"3

~6.)~

HEt]J

!3Lf4;AIK-

WCD

"\

v,

Special

lnstructio

ns:

Date/Time

Date/Time

Received

B:

I .1

Page 67: UC Davis Asbestos Analysis

35608

August 04, 2015 Project No.: 2505030.01.00 Scott Slayton, Project Manager Design and Construction Management University of California, Davis 255 Cousteau Place Davis, CA 95618 RE: Asbestos Air and Visual Clearance - Pass

Olson Hall Classroom Renovations – Classroom 0118 198 Peter J Shields Avenue Davis, CA 95616

Dear Mr. Slayton, The following report is in regards to the completed air monitoring clearance sampling that was conducted at the above listed address, in Olson Hall Classroom 0118 (CAAN #3803; Zone #C005). Prior to the visual inspection and air clearance sampling being conducted by National Analytical Laboratories, Inc. (N.A.L.), Allied Environmental, Inc., removed the asbestos containing materials from the work area. Denis Edwards, Certified Asbestos Consultant for N.A.L., completed the air clearance sampling on August 03, 2015. Because the visual inspection showed no asbestos containing construction materials (ACCM), asbestos debris, or any other impairment, Mr. Edwards proceeded with the Phase Contrast Microscopy (PCM) air clearance sampling using 25mm cassettes. The cassettes used had a Mixed Cellulose Ester membrane 0.8 µm, micron pore size that is used specifically for PCM sampling. The air monitoring cassette was calibrated with a Dwyer series VFB Visi-Float Flowmeter at 8.33 liters per minute (lpm). The air monitor operated for total of 150 minutes, for a total cassette volume of 1250 liters. The total volume fell within the projected range of 400 to 1800 liters for PCM sampling. A total of two (2) samples were collected from the Center of Classroom 0118 and transported to MicroTest Laboratories, Inc., for analysis. The average concentration for airborne fibers found in the two (2) samples was <0.002 f/cc. The clearance result is below the Environmental Protection Agency’s (EPA’s) PCM clearance level of 0.01 f/cc. Laboratory analytical report and chain of custody form attached. Classroom 0118 work area has been cleared for re-occupancy. Individuals may enter the Classroom without any health or safety concerns in regards to the exposure of airborne asbestos fibers. If you have any questions regarding this report or if we can be of further assistance, please contact our office.

Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant, DOSH #92-0261

MULMSLNS

Page 68: UC Davis Asbestos Analysis

MicroTest Laboratories Inc.AIHA IHPAT # 160934

5150 Sunrise Blvd, Suite B-1Fair Oaks, CA 95628Tel. (916) 567-9808

..Fax: (916) 436-3603

E-mail: [email protected]

PROJECT:

NAL2201 Francisco Drive, Ste 140-261EI Dorado Hills, CA 95762

Olson HallCAAN 3853

CLIENT:

SAMPLES COLLECTEDBY: Edwards

TYPEOF SAMPLE: PCM Cassette x2

COLLECTION DATE:

SUBMISSION DATE:

8/3/2015

8/4/2015

ACCESSIONNUMBER: 41387-41388

TYPEOF ANALYSIS: Phase Contrast Microscopy, NIOSH 7400 Method "A" Rules

REPORTDATE: 8/4/2015

REPORTEDAND REVIEWED BY: Rebecca Hutty, MicroTest Laboratories Inc., Analyzed by: M. Nguyen

PHASECONTRAST MICROSCOPY-NIOSH 7400The "Samples" collected demonstrated the following:

Sample # Sample Description Sample Type Total Volume Fibers Fields Fibers/mm2 U.c.L. LOD fb/cc3853-10AC Room 0118 Center

Clearance 1250 <5.5 100 <7 <0.007 0.002 <0.00241387 of Room

3853-11AC

Field Blank Blank N/A <5.5 100 <7 N/A N/A N/A41388

*AII samples tested as submitted to Microtest Labs, Inc. We do not assume responsibility for the accuracy of theinformation submitted.*Any numerical value which calculates to be less than 0.01 fb/cc should be view as <0.01 fb/cc due to the inaccuracy ofthe NIOSH 7400 Method (LOD 7fb/mm2).

*Comments such as "Overloaded", "Dirty", "Wet Filter", "Uneven disbursement of Fibers" or "Torn Filter", illustrate thatthe analyst found discrepancies or problems with the sample and the results are not considered accurate.

Page 69: UC Davis Asbestos Analysis

..-.:

".

LfIJ6(-

L\\>

C(j~

Login

#:(

Page

__(

If

..............

N·A

·L•••,

••••:.

N\II()N

,\I

AN,\IYII(

\1I

\!lllR,\TORIf:'i.

IN(

1,•....·

·Com

pany:

'uc1)

Contact:

1:.c60

Address:

Phone:

E-Mail:

,Sam

pler:

Job

Site:

,.220

IFran

cisco

Dr.

Sic,

140-26

11III

Dorad

oHills,

'11.,9

5762

Pho

ne(916)

361-05

55Fax(916

)361-0540

www.nul

l.com

SAMPL

EDATE

:r?3f

3;1s"

------

--~~.~

------

-----

Job

Num

ber:

C~

~S3

#of

Samples:

Contact:

TYPE

OF

WORK

TURN

AROIIND

O'I'I-II£R

PLM

<rCM

)/T1

i:MLE

Al}

BULl(

LEAl}

WIPI<:S

LEAl}

AIR

l.abo

ratory

Rus

hWater

PLM

Bas

eline

Chip

Clearan

cef-----Area

Con

sulting

~61

-lour

-Soil

I----

Perso

nal

I----Soil

r-----

'I'TI'P

'Bas

eline

Perso

nal

/OnS

it~-M

old

---

400PI.Ct.

I----

Area

f-----'IT

LCr-----

f-----

Ambien

t.Air

24Hou

r-nl-Iou

r-

1000PI.('I.

t=z:

Clearance

I----S'I'LC

f-----

'

----

---

I----'I'CLIP

Sam

ple

Tim

eTotal

I.irc

rsPerMinute

Total

Measurement

I.ocat

iun/Descriptio

n"

Num

ber

On

orr

Minutes

On

orr

Ave

rVolum

eSF

/LI'/(,

I',

.ggf'l-lO

A<13

~/~

ItJCJ

~,33

&.,,'$

8.33

1J.51J

Lit]:?

>?GL~

Qf..

KHcJ/rB

C~Q

t:=~

~8S'~-IIAc

413S

'BE'IC

LO'i3£./

c7UK

.,

---

'.

I I

Spe

cial

Instructions

:

Chain

ofCustod

Date/Time

Date/Time

Received

By:

Page 70: UC Davis Asbestos Analysis

35582

July 29, 2015 Project No.: 2505030.01.00 Scott Slayton, Project Manager Design and Construction Management University of California, Davis 255 Cousteau Place Davis, CA 95618 RE: Asbestos Air and Visual Clearance - Pass

Olson Hall Classroom Renovations – Classroom 0125 198 Peter J Shields Avenue Davis, CA 95616

Dear Mr. Slayton, The following report is in regards to the completed air monitoring clearance sampling that was conducted at the above listed address, in Olson Hall Classroom 0125 (CAAN #3803; Zone #C005). Prior to the visual inspection and air clearance sampling being conducted by N.A.L., Allied Environmental, Inc., removed the asbestos containing Floor Tile, Mastic, and Transite Chalkboard materials from the work area. Denis Edwards, Certified Asbestos Consultant, for National Analytical Laboratories, Inc., completed the air clearance sampling on July 28, 2015. Because the visual inspection showed no asbestos containing construction materials (ACCM), asbestos debris, or any other impairment, Mr. Edwards proceeded with the Phase Contrast Microscopy (PCM) air clearance sampling using 25mm cassettes. The cassettes used had a Mixed Cellulose Ester membrane 0.8 µm, micron pore size that is used specifically for PCM sampling. The air monitoring cassette was calibrated with a Dwyer series VFB Visi-Float Flowmeter at 8.33 liters per minute (lpm). The air monitor operated for total of 151 minutes, for a total cassette volume of 1257.83 liters. The total volume fell within the projected range of 400 to 1800 liters for PCM sampling. A total of two (2) samples were collected from the Center of Classroom 0163 and transported to MicroTest Laboratories, Inc., for analysis. The average concentration for airborne fibers found in the two (2) samples was <0.002 f/cc. The clearance result is below the Environmental Protection Agency’s (EPA’s) PCM clearance level of 0.01 f/cc. Laboratory analytical report and chain of custody form attached. Classroom 0125 work area has been cleared for re-occupancy. Individuals may enter the Classroom without any health or safety concerns in regards to the exposure of airborne asbestos fibers. If you have any questions regarding this report or if we can be of further assistance, please contact our office.

Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant, DOSH #92-0261

MULMSLNS

Page 71: UC Davis Asbestos Analysis

-~~~~~ -----~---

MicroTest Laboratories Inc.AIHA IHPAT # 160934

5150 Sunrise Blvd, Suite B-1Fair Oaks, CA 95628

. Tel. (916) 567-98mrFax: (916) 436-3603

E-mail: mlcrotestlabstncravahoo.com

PROJECT:

NAL2201 Francisco Drive, Ste 140-261EI Dorado Hills, CA 95762

Olson HallCAAN 3853

CLIENT:

SAMPLES COLLECTEDBY: Edwards

TYPEOF SAMPLE: PCM Cassette x2

COLLECTIONDATE:

SUBMISSION DATE:

7/28/2015

7/28/2015

40955-40956ACCESSIONNUMBER:

TYPEOF ANALYSIS: Phase Contrast Microscopy, NIOSH 7400 Method "A" Rules

REPORTDATE: 7/29/2015

REPORTEDAND REVIEWED BY: Rebecca Hutty, MicroTest Laboratories Inc., Analyzed by: M. Nguyen

PHASECONTRASTMICROSCOPY-NIOSH 7400

The "Samples" collected demonstrated the following:

Sample # Sample Description Sample Type Total Volume Fibers Fields Fibers/mm2 U.c.L. LOD fb/cc3853-01AC

Room 0125 Clearance 1258 <5.5 100 <7 <0.008 0.002 <0.00240955

3853-02ACField Blank Blank N/A <5.5 100 <7 N/A N/A N/A

40956

*AII samples tested as submitted to Microtest Labs, Inc. We do not assume responsibility for the accuracy of theinformation submitted.

*Any numerical value which calculates to be less than 0.01 fb/cc should be view as <0.01 fb/cc due to the inaccuracy ofthe NIOSH 7400 Method (LOD 7fb/mm2).

*Comments such as "Overloaded", "Dirty", "Wet Filter", "Uneven disbursement of Fibers" or "Torn Filter", illustrate thatthe analyst found discrepancies or problems with the sample and the results are not considered accurate.

Page 72: UC Davis Asbestos Analysis

Page

Login #

1 of 1 35582 NAL LOG-IN RECORD

Ph: 916.361.0555 Fx: 916.361.0540

National Analytical Laboratories, Inc. Job Site/Job #:

Client#-Lot# 4373 / 739 Olson Hall (CAAN #3803; Zone #C005): Date 7/29/2015

UC Davis Design & Construction Management Classrooms 0101, 0105, 0118, 0125, 0141, 0163 & 0227 Sampling Date: 7/28/2015

Phone Number Davis, CA 95616 Sampling Time 8:30:00 AM

FAX Number Type of Work: PCM Clearance

Contact Scott Slayton 2505030 No. of Samples 2 E-Mail Address Turnaround: Rush

Chain of Custody Information

Released By Signature Date/ Time Received By Signature Date/

Time Due: 7/28/2015 Denis Edwards 07/28/15

15:20

Released By Signature Date/ Time Received By Signature Date/

Time At: 12:30

Num. Sample ID# Min. LPM Volume Location/Description

1 3803-01AC 151 8.33 1257.83 Classroom 0125, Center / Clearance

2 3803-02ACFB 0 0 0 Field Blank / 30 Second Cap Off

Page 73: UC Davis Asbestos Analysis

((

Of

Login

#:--

~---

----

----

----

----

----

Page

Com

pany:

/)GO

Con

tact:

-SCOTt

Address:

Phone:

E-Mail:'

:,N

·A·L

,••.•

NATIONAL

ANALY

TICAL

LAIlO

RATO

IUES.

INC.

1',•.......

Job

Site:

2201

Francisco

Dr.

Ste.

140-2611

ElDorado

Hills,

CA.95

762

Phone

(916)36

1-05

55Fa

x(916

)361-0540

www.nal

l.com

SAMPL

EDATE

:7!2

-¥«

Job

Num

ber:

c.,4ArJ

'S~-~

#of

Samples:

Con

tact:

-TY

PEOF

WORK

TURNAROUND

OTH

ERPL

M~E

MLE

AD

BULK

LEAD

WIPES

LEAD

AIR

Labo

ratory

Rush

Water

PLM

Baseline

Chip

Clearance

f----A

rea

.Consulting

-6Hou

rSo

ilr---TT

FP*r---

r---So

ilr---

I'./

OnSite

24Hour

-MId

f----

400Pt.C

t.f----

Personal

TTLC

f----

Baseme

f----

Personal

_0

Area

f----

AmbientAir

72Hou

r~IOOOPt.Ct.

~Clearance

STLC

,---

f---- TCLIP

"

Sample

Time

Total

Liters

PerMinute

Total

Measurement

Locatio

nlDescriptio

nNum

ber

On

Off

Minutes

On

Off

Aver

Volum

eSF

fLFfCF

.g§S3

..olA:C

O1frD

/~I/

Is!~£

8·33

8,i.!3

V~j""~

10(\00

Ct:..~C~

e6/Y1

6/.2-5/

~rtZle

ef&Pt.~o9

S~'

~~3

-o:lA

cI\)/{O

OEi

~Vt5L/VU

IttV/'

5{q

I

Special

Instructions:

Chain

ofCustod

OatefTime

DatefTime

\

Page 74: UC Davis Asbestos Analysis

35578

July 27, 2015 Project No.: 2505030.01.00 Scott Slayton, Project Manager Design and Construction Management University of California, Davis 255 Cousteau Place Davis, CA 95618 RE: Asbestos Air and Visual Clearance - Pass

Olson Hall Classroom Renovations – Classroom 0163 198 Peter J Shields Avenue Davis, CA 95616

Dear Mr. Slayton, The following report is in regards to the completed air monitoring clearance sampling that was conducted at the above listed address, in Olson Hall Classroom 0163 (CAAN #3803; Zone #C005). Prior to the visual inspection and air clearance sampling being conducted by N.A.L., Allied Environmental, Inc., removed the asbestos containing materials from the work area. Denis Edwards, Certified Asbestos Consultant, for National Analytical Laboratories, Inc., completed the air clearance sampling on July 27, 2015. Because the visual inspection showed no asbestos containing construction materials (ACCM), asbestos debris, or any other impairment, Mr. Edwards proceeded with the Phase Contrast Microscopy (PCM) air clearance sampling using 25mm cassettes. The cassettes used had a Mixed Cellulose Ester membrane 0.8 µm, micron pore size that is used specifically for PCM sampling. The air monitoring cassette was calibrated with a Dwyer series VFB Visi-Float Flowmeter at 10 liters per minute (lpm). The air monitor operated for total of 135 minutes, for a total cassette volume of 1413 liters. The total volume fell within the projected range of 400 to 1800 liters for PCM sampling. A total of two (2) samples were collected from the Center of Classroom 0163 and transported to MicroTest Laboratories, Inc., for analysis. The average concentration for airborne fibers found in the two (2) samples was <0.002 f/cc. The clearance result is below the Environmental Protection Agency’s (EPA’s) PCM clearance level of 0.01 f/cc. Laboratory analytical report and chain of custody form attached. Classroom 0163 work area has been cleared for re-occupancy. Individuals may enter the Classroom without any health or safety concerns in regards to the exposure of airborne asbestos fibers. If you have any questions regarding this report or if we can be of further assistance, please contact our office.

Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant, DOSH #92-0261

MULMSLNS

Page 75: UC Davis Asbestos Analysis

Page: 1 of 1

Login #: 35578 Scott Slayton

UC Davis Design & Construction Management Job Site: Date Samples Taken: 7/27/2015 225 Cousteau Place Olson Hall (CAAN #3803; Zone #C005)

Davis, CA 95618 Classrooms 0101, 0105, 0118, 0125, 0141, 0163& 0227 Date Report Submitted: 7/28/2015

Phone # Davis, CA 95616 NAL ID # / Lot #: 4373 / 738 Fax #:

Lab Tracking #: 40809-40812 Attention: Scott Slayton Job Number

Total Samples: 2 Email: 2505030

PHASE CONTRAST MICROSCOPY ANALYTICAL CLEARANCE REPORT (PCM)

KEY: **TWA: Time Weighted Average per sample. Eight hour TWA summary is provided at the end of each month. ***INF: Sample not suitable for analysis. See sample description.

Analyst: M. Nguyen Reviewed By: Rebecca Hutty, MicroTest Laboratories, Inc. Sample analyzed by Phase Contrast Microscopy in accordance with the N.I.O.S.H. 7400 Method utilizing the “A” Counting Rules. *U.C.L. – Refers to the 95% Upper Confidence Limit, that insures that the differences in measured concentrations between laboratories within laboratories will be no higher than the U.C.L. This information is based in part on the volume of the air sampled and fibers counted.

National Analytical Laboratories, Inc. 2201 Francisco Dr. Ste.140-261, El Dorado Hills, CA 95762 Phone (916) 361-0555 Fax (916) 361-0540 Website www.NAL1.com

Samples ID # Liters/Min Volume

Fibers per

Fields

Fibers Per

MM2

Fibers per CC UCL*

Sample ID #: 3803-02A NAL ID: 4373-738-1 Location: Center of Classroom 0163 Description: Clearance

10.47 1413 <5.5/100 <7.0 <0.002 <0.007

Sample ID #: 3803-FB NAL ID: 4373-738-2 Location: Description: 30 Second Cap Off Field Blank

--- --- 0/100 < 7.0 --- ---

Page 76: UC Davis Asbestos Analysis

Page

Login #

1 of 1 35578 NAL LOG-IN RECORD

Ph: 916.361.0555 Fx: 916.361.0540

National Analytical Laboratories, Inc. Job Site/Job #:

Client#-Lot# 4373 / 738 Olson Hall (CAAN #3803; Zone #C005): Date 7/27/2015

UC Davis Design & Construction Management Classrooms 0101, 0105, 0118, 0125, 0141, 0163 & 0227 Sampling Date: 7/27/2015

Phone Number Davis, CA 95616 Sampling Time

FAX Number Type of Work: PCM Clearance

Contact Scott Slayton 2505030 No. of Samples 2 E-Mail Address Turnaround: Rush

Chain of Custody Information

Released By Signature Date/ Time Received By Signature Date/

Time Due: 7/27/2015 Denis Edwards 07/27/15

1500

Released By Signature Date/ Time Received By Signature Date/

Time At:

Num. Sample ID# Min. LPM Volume Location/Description

1 3803-02A 135 10.47 1413 Center of Classroom 0163 / Clearance

2 3803-FB 0 10 0 Field Blank / 30 Second Cap Off

Page 77: UC Davis Asbestos Analysis

MicroTest Laboratories Inc.AIHA IHPAT # 160934

5150 Sunrise Blvd, Suite B-1Fair Oaks, CA 95628Tel. (916) 567-9808Fax: (916) 436-3603

E-mail: mlcrotestlabsincrevahoc.com

PROJECT:

NAL2201 Francisco Drive, Ste 140-261EI Dorado Hills, CA 95762

Olson HallCAAN#3803

CLIENT:

SAMPLES COLLECTEDBY:

TYPEOF SAMPLE:

Edwards

PCM Cassette x4

COLLECTION DATE:

SUBMISSION DATE:

ACCESSIONNUMBER:

7/27/2015

7/27/2015

40809-40812

TYPEOF ANALYSIS: Phase Contrast Microscopy, NIOSH 7400 Method itA" Rules

REPORTDATE: 7/27/2015

REPORTEDAND REVIEWED BY: Rebecca Hutty, MicroTest Laboratories Inc., Analyzed by: M. Nguyen

PHASECONTRASTMICROSCOPY-NIOSH 7400The "Samples" collected demonstrated the following:

Sample # Sample Description Sample Type Total Volume Fibers Fields Fibers/mm2 u.c.i, LOD fb/cc

3803-01A Outside Decon Unit25 100 32 0.026 0.003 0.017Area 714

40809 Rm 0163

3803-02A Center of Room RmClearance 1413 <5.5 100 <7 <0.007 0.001 <0.002

40810 01633803-03A Outside Decon Unit

Area 284 32 100 41 0.078 0.007 0.05540811 Rm 0125 Hallway

FBField Blank Blank N/A <5.5 100 <7 N/A N/A N/A

40812

* All samples tested as submitted to Microtest Labs, Inc. We do not assume responsibility for the accuracy of the-c

information submitted. .•..

*Any numerical value which calculates to be less than 0.01 fb/cc should be view as <0.01 fb/cc due to the inaccuracy ofthe NIOSH 7400 Method (LOD 7fb/mm2).

*Comments such as "Overloaded", "Dirty", "Wet Filter", "Uneven disbursement of Fibers" or "Torn Filter", illustrate thatthe analyst found discrepancies or problems with the sample and the results are not considered accurate.

Page 78: UC Davis Asbestos Analysis

',::,..

"','

Com

pany:

'."

.:

Contact:

".

Address:

(LfcB

o'1-t

-)08

I'L(

Login#:

Page

...."

.:'I,

.'...

Sampler:

£Z)~S

Of

N·A

·LJob

Site:

-,.-

,.

',•......

NATIONAL

ANALY

TICAL

LAIlO

RATO

RIE$.

INC.

d.~/k(,

2201

FranciscoDr.Ste.

140-2611

ElDoradoHills,

CA.9

5762

Phone(916)361-0555

Fax(916)361-0540

www.na~~com

7/c

/

SAMPL

EDATE

:I!...-

'//~

------

----~~

~,~~--

-----Jo

bNum

ber:

CAM.!

"'-B

~~Ph

one:

E-Mail:

#of

Samples:

Contact:

-TY

PEOF

WORK

TURNAROUND

OTH

ERPL

MC.~TE

MLE

AD

BULK

LEAD

WIPES

LEAD

AIR

Laboratory

Rush

Water

PLM

Baseline

Chip

Clearance

Area

Consulting

~6Hour

Soil

-TTFP

*I----

Personal

I----Soil

I----

Baseline

I----

Person

al./

OnSite

Mold

,---

400Pt.C

t.r--:::;

:;--Area

I---- TTLC

I----

AmbientA

ir24

Hour

I----

72Hour

I----

1000

Pt.C

t.r--:::;;:;--C

learance

~STLC

,I----

I----

I----

TCLIP

;

Sample

Tim

eTotal

Liters

PerMinute

Total

Measurement

ILo

catio

n/Descriptio

nNum

ber

On

Off

Minutes

On

Off

Aver

Vo.wme

SFILF/CF

(:t{

'I;()

-:If)

~./

-;'.1

(;.1

~IW

/24

"

3Z>6

3<J#

4%

~/Z>

tEtJ£C

a;-<JUAt'r

(JI(!;.'3

;t;uW

f;e.'Y

..'

I-

386B

~I~

~WIgc

,£)10

.I0Jt7

~o/J

11.{1

3C/~~AA.JC6

CMr~e/~

h-I

~/03

I

C/7

--

3&ff·~

I~s'

&6,

131{~l

';J..{

~,1

~r~/D

t{~

b:?Allr

ma6

<6'"

~ttJ'Ac(

,I

"

-;J

EfE..

.ri~

/3(/b

t/K

,

to u

SpecialInstructions:

Date/Time

DatelTime

Received

B:

Page 79: UC Davis Asbestos Analysis

35600

August 03, 2015 Project No.: 2505030.01.00 Scott Slayton, Project Manager Design and Construction Management University of California, Davis 255 Cousteau Place Davis, CA 95618 RE: Asbestos Air and Visual Clearance - Pass

Olson Hall Classroom Renovations – Classroom 0228 198 Peter J Shields Avenue Davis, CA 95616

Dear Mr. Slayton, The following report is in regards to the completed air monitoring clearance sampling that was conducted at the above listed address, in Olson Hall Classroom 0228 (CAAN #3803; Zone #C005). Prior to the visual inspection and air clearance sampling being conducted by N.A.L., Allied Environmental, Inc., removed the asbestos containing materials from the work area. Denis Edwards, Certified Asbestos Consultant, for National Analytical Laboratories, Inc., completed the air clearance sampling on July 31, 2015. Because the visual inspection showed no asbestos containing construction materials (ACCM), asbestos debris, or any other impairment, Mr. Edwards proceeded with the Phase Contrast Microscopy (PCM) air clearance sampling using 25mm cassettes. The cassettes used had a Mixed Cellulose Ester membrane 0.8 µm, micron pore size that is used specifically for PCM sampling. The air monitoring cassette was calibrated with a Dwyer series VFB Visi-Float Flowmeter at 10.47 liters per minute (lpm). The air monitor operated for total of 120 minutes, for a total cassette volume of 1256.4 liters. The total volume fell within the projected range of 400 to 1800 liters for PCM sampling. A total of two (2) samples were collected from the Northeast Corner of Classroom 0228 and shipped via FedEx to EMSL Analytical, Inc., for analysis. The average concentration for airborne fibers found in the two (2) samples was <0.002 f/cc. The clearance result is below the Environmental Protection Agency’s (EPA’s) PCM clearance level of 0.01 f/cc. Laboratory analytical report and chain of custody form attached. Classroom 0228 work area has been cleared for re-occupancy. Individuals may enter the Classroom without any health or safety concerns in regards to the exposure of airborne asbestos fibers. If you have any questions regarding this report or if we can be of further assistance, please contact our office.

Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant, DOSH #92-0261

MULMSLNS

Page 80: UC Davis Asbestos Analysis

SampleVolume(liters)

Fibers/mm²Fibers

LOD(fib/cc) NotesLocation FieldsSample Date

Fibers/cc

Test Report: Fiber Count by Phase Contrast Microscopy (PCM), NIOSH 7400 Method, Revision 3, Issue 2, 8/15/94

EMSL Analytical, Inc.200 Route 130 North, Cinnaminson, NJ 08077Phone/Fax: (800) 220-3675 / (856) 786-5974http://www.EMSL.com [email protected]

Attn: National Analytical Laboratories (NAL)2201 Francisco Dr.Ste. 140-261El Dorado Hills, CA 95762

Received: 08/01/15 12:00 PM

Edwards / Olson Hall / CAAN 3853

Fax: (916) 361-0540Phone: (916) 361-0555

Project:

8/1/2015Analysis Date:Collected:

041522952CustomerID: NAL51CustomerPO:ProjectID:

EMSL Order:

3853-8AC

041522952-0001

1256.00 <7.01Clearance Rm 0228 NE Corner

<5.5 100 <0.0020.002

3853-9AC

041522952-0002

<7.01 Field BlankField Blank <5.5 100

The results reported have been blank corrected as applicable.

Benjamin Ellis, Laboratory Manageror other approved signatory

Test Report PCM-7.22.0 Printed: 8/1/2015 3:30:15 PM 1

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

Limit of detection is 7 fibers/mm². Intra-laboratory Sr values: 5-20 fibers = 0.31, 21-50 fibers = 0.30, 51-100 fibers = 0.25. Inter-laboratory Sr values (Average of EMSL round robin data) = 0.29. EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. EMSL is not responsible for data reported in fibers/cc, which is dependent on volume collected by non-laboratory personnel. Results have been blank corrected as applicable. The results in this report meet all requirements of the NELAC standards unless otherwise noted. Samples received in good condition unless otherwise noted.Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NYS ELAP 10872, AIHA-LAP, LLC--IHLAP Accredited #100194, NJ DEP 03036, PA ID# 68-00367

Dave Poitras (2)

Initial report from 08/01/2015 15:30:13

Page 81: UC Davis Asbestos Analysis

Page

Login #

1 of 1 35600 NAL LOG-IN RECORD

Ph: 916.361.0555 Fx: 916.361.0540

National Analytical Laboratories, Inc. Job Site/Job #:

Client#-Lot# 4373 / 745 Olson Hall (CAAN #3803; Zone #C005): Date 8/3/2015

UC Davis Design & Construction Management Classrooms 0101, 0105, 0118, 0125, 0141, 0163 & 0227 Sampling Date: 7/31/2015

Phone Number Davis, CA 95616 Sampling Time

FAX Number Type of Work: PCM Clearance

Contact Scott Slayton 2505030 No. of Samples 2 E-Mail Address Turnaround: Rush

Chain of Custody Information

Released By Signature Date/ Time Received By Signature Date/

Time Due: 7/31/2015 Denis Edwards 07/31/15

1645

Released By Signature Date/ Time Received By Signature Date/

Time At:

Num. Sample ID# Min. LPM Volume Location/Description

1 3803-8AC 120 10.47 1256.4 Classroom 0228, Northeast Corner / Clearance

2 3803-9AC 0 0 0 Field Blank / 30 Second Cap Off

Page 82: UC Davis Asbestos Analysis

OrderID: 041522952

Page 1 Of 1

Page 83: UC Davis Asbestos Analysis

Asbestos & Lead Building Inspection Report For:

Wellman Hall Room 0027

CAAN #4050 ZONE #B042

Davis, CA

Presented To:

Astrid Senger-Gibbons

UC Davis - Design & Construction Management 225 Cousteau Place

Davis, CA 95618

By:

Anthony M. De Arcos Certified Asbestos Consultant

National Analytical Laboratories, Inc. (916) 361-0555 Fax: (916) 361-0540

E-Mail: [email protected] Web Page: www.NAL1.com

Page 84: UC Davis Asbestos Analysis

33047

July 11, 2013 Astrid Senger-Gibbons UC Davis - Design & Construction Management 225 Cousteau Place Davis, CA 95618 RE: Asbestos & Lead Inspection – Wellman Hall-Room 0027 Dear Ms. Senger-Gibbons, The following report is in regards to the building inspection completed at the Wellman Hall located at CAAN #4050 ZONE #B042, in Davis, California. Of the three (3) suspected asbestos containing samples collected two (2) were found to contain asbestos containing construction materials (ACCM). Of the three (3) suspected lead containing samples collected one (1) was found to contain Lead Containing Material (LCM). Anthony M. De Arcos, Certified Asbestos Consultant and Registered Environmental Property Assessor (REPA), conducted the inspection. The inspection was completed on July 9, 2013. The inspection was completed according to the EPA’s Asbestos Containing Building Materials (ACBM) In-Schools Rule; 40 CFR 763.85 (Inspection and Re-Inspection). Currently, EPA regulations classify ACBM as materials containing more that 1-percent (1%) of asbestos. Cal-OSHA currently regulates asbestos to 1/10th of 1% (0.1%) and requires that a certified asbestos worker conduct this work. Based on the sample results the Texture (Sheetrock-Joint Compound is to be considered homogeneous) were found to contain ACCM. All square footage should be verified by contractor. No destructive sampling was conducted during the site visit, in the event that future renovation and/or demolition work reveals any unforeseen suspect materials; the contractor shall contact the project manager for further testing. The lead suspect samples were collected according to the Housing Urban Development (HUD) Guidelines, the Environmental Protection Agency (EPA) and California Public Health Department (formally DHS), who regulate and require the abatement or in-place management of LCM hazards equal to or greater than 1.0 milligram per square centimeter (1.0 mg/cm2) of lead or more than 0.5% lead by weight. The following regulation shall be adhered to because OSHA considers all surfaces to contain lead: OSHA’s 29 CFR 1926.62, California Occupational Safety and Health Standard, Title 8 (Cal/OSHA 8 CCR 1532.1). The samples from the Multi-Colored Paint surfaces were found to contain LCM levels above the OSHA Limit of Detection. Thus, a certified CPHD (formerly DHS) lead worker and individuals certified by EPA, with Renovator, Repair and Painting (RRP) designation, must complete any work that will disturb the painted surfaces at the site including prep, in-place management, and/or abatement.

Page 85: UC Davis Asbestos Analysis

Wellman Hall CAAN #4050 ZONE #B042, Davis, CA July 11, 2013 Page 3 of 5

33047/33048

EMSL Analytical, Inc. (EMSL) in Carle Place, New York, analyzed the bulk suspect asbestos containing samples utilizing Polarized Light Microscopy (PLM) Method and utilizing the SW-846-3050B*/7000B method analyzed the suspect LCM samples. National Voluntary Laboratory Accreditation Program (NVLAP) Certification #10148-10 and California Environmental Laboratory Accreditation Program (CAELAP) Certification #2339, certifies EMSL. SECTION I: ASBESTOS BUILDING INSPECTION- Federal and state regulations require that anyone disturbing asbestos containing materials are properly trained certified and have the required respiratory protection and medical surveillance. Although not all the rooms or materials throughout the site were sampled, the like materials that were not tested will be treated as homogeneous to the materials that were tested and will be considered as containing ACCM. The location and results of suspect samples found to contain ACCM are as follows: Sample ID# Material Location Condition Results 4050-2 Texture Rm 0027, N. Wall PT CT <0.25% *Trace,<1% Chrysotile 4050-3 Sheetrock-Joint Compound Rm 0027, NW Corner Homogeneous

Material Homogeneous Material

Based on the regulatory requirements by the National Emission Standards for Hazardous Air Pollutants (NESHAP), Regulation 40 CFR, Part 61, Subpart M the following must occur “If the asbestos content is less than 10 percent, verification shall be made using the point counting method specified in Appendix A, Subpart F, 40 CFR Part 763, Section 1.7.2.4, Polarized Light Microscopy, Qualification of Asbestos Content.” Samples found to contain a Trace, <1% amount of Chrysotile asbestos were re-analyzed utilizing the EPA 600/M4-82-020, Point Count Method to determine if the amount of ACCM is less than or greater than 1%. The results for the Material sample were found to contain <0.25% asbestos. Based on the results the surface materials will be treated to contain a Trace <1% Chrysotile asbestos containing construction material (ACCM). Although neither EPA nor Local County Air Quality regulates materials at <1% level, it does fall under the jurisdiction of OSHA in regards to worker protection. OSHA regulates the material at 1/10th of 1% [8 CCR-1529 (r) (1) Asbestos Containing Construction Material (ACCM)]. Based on this, the work must be completed by a certified asbestos contractor. The CONTRACTOR shall be required to call the landfill to verify that they will accept the waste as general construction debris. If the landfill does not accept the material as general construction debris, the material shall be REQUIRED to be disposed of as non-friable/non-hazardous material. The Sheetrock-Joint Compound is to be considered homogeneous and treated as containing Trace <1% Chrysotile. A certified asbestos abatement contractor must be retained to remove the above materials containing the Trace (<1%) amount prior to any renovation or demolition work being completed at the site. During the removal of the materials, the debris will be placed into an open top waste bin. The bin will have ''Asbestos Hazard'' signs posted around the perimeter of the waste bin. Upon completion of the removal process, the bin will be covered, the signs will be removed and the debris will be disposed of as general construction debris at a non-regulated waste facility. NAL recommends that a certified asbestos abatement contractor be retained to remove trace materials prior to any scheduled renovation/demolition work being completed at the site. Prior to the work process starting a work plan or specifications in regards to the abatement process should be completed and distributed to the abatement contractors during the job walk at the site.

Page 86: UC Davis Asbestos Analysis

Wellman Hall CAAN #4050 ZONE #B042, Davis, CA July 11, 2013 Page 4 of 5

33047/33048

On-Site Observation should be conducted by N.A.L’s Certified Asbestos Consultant or Certified Site Surveillance Technician to verify that the work plan/specification is being followed. This will verify that during the abatement work the outside air was clean. Once a certified asbestos contractor has removed the ACCM, following EPA and OSHA requirements; a visual inspection and air clearance sampling should be completed. Clearances will confirm that the general contractor can reoccupy the work area(s), without concern for exposure to asbestos airborne fibers to their employees thus allowing the renovation or demolition work to be completed by the general contractor. The following samples were non-asbestos containing materials: Sample ID# Material Location Results 4050-1 2x4 White Acoustical Ceiling Tile Rm 0027, W. Side Ceiling, None Detected SECTION II: LEAD BUILDING INSPECTION- Since the laboratory results are reported by weight percent, during the collection of the suspect LCM samples the paint must be removed down to, but not including, the bare substrate (wood, metal, etc.). Inclusion of the any amount of the substrate material in the paint sample will dilute the sample result(s). Once the determination is made on where the LCM is located, the In-place Management or the Abatement of the LCM can commence. If the In-Place Management method is to be used, prior to the repainting of the effected surface areas, the loose flaky paint must be removed until the remaining paint adheres smoothly to the substrate. Once this task is completed, the surface area can be repainted without the possibility of paint being dislodged and falling to the floor or ground areas. If the Abatement method of all surfaces is to be completed, then the debris and any loose flaky paint must be bagged or burrito wrapped prior to the removal of the debris from the work area(s) and subsequently the site. Because the paint samples listed below were found to contain LCM, all areas where the LCM will be disturbed will require abatement, encapsulation, and/or prep work by a certified lead worker. Although not all the rooms or materials were sampled, the like materials that were tested and their results will be treated as homogeneous and the materials will be treated as containing LCM throughout the site. The locations and results of the suspect samples found to be LCM are as follows:

Sample ID# Material Location Condition Concentration % By Weight

4050-3L Multi-Colored Paint Various Sheetrock Walls Good 0.3%-LCM

Page 87: UC Davis Asbestos Analysis

Wellman Hall CAAN #4050 ZONE #B042, Davis, CA July 11, 2013 Page 5 of 5

33047/33048

Prior to the demolition work being completed and/or the transporting of the debris from the site, Health and Safety Code 25157.8 (AB 2784 National Resources) requires that all lead debris be sampled for Waste Characterization. This will assist the Contractor in making a determination of whether or not the material is to be considered Hazardous or Non-Hazardous Lead waste or general construction debris. The sequence of testing to be completed by the Contractor is as follows:

i Total Threshold Limit concentration (TTLC) with a result of 50 mg/kg or more but less than 1,000 mg/kg of lead must be retested using the Soluble Threshold Limit concentration (STLC) method;

i A STLC result of 5.0 mg/L or greater is considered California Hazardous Waste; i Total Characteristic Leaching Procedure (TCLP) testing shall only be accomplished when approved by the

Owners Representative; This procedure shall be generally reserved for out-of-state shipments; and A TCLP result of 5.0 mg/L or more deems the waste Federal RCRA materials; and

i The California hazardous waste threshold for total lead using STLC is 5 mg/L and i Lead paint that is intact on a surface does not permit the material to be classed as non-hazardous. Waste

profiling shall be accomplished if the paint contains more than 350 ppm by Flame AAS. Exception: Metals that are coated with paint are to be recycled.

The following painted surfaces were found to be less than (<) the OSHA’s Limit of Detection for LCM:

Sample ID# Material Location Condition Concentration % By Weight

4050-1L Brown/Tan/White Paint Rm 0027, Metal Door Components Fair <0.01% 4050-2L Brown/Tan Paint Entry Wood Door Fair <0.01% In order to stabilize the current lead conditions, NAL recommends Lead Certified Workers certified by EPA, with Renovator, Repair and Painting (RRP) designation, conduct in-place management work of the LCM surfaces scheduled for renovation/demolition. Once the abatement, in-place management, and/or prep work is completed and the areas are stabilized, the existing surfaces will be in good condition and not create a health or safety concern to the workers conducting the general construction work at the site. A Scope of Work and/or specifications should be utilized to conduct the lead work at the site. If you have any questions regarding this report or if we can be of further assistance, please contact our office. Reviewed and submitted by: Anthony M. De Arcos Certified Asbestos Consultant DOSH #92-0261 Certified Lead Inspector/Assessor CDPH #2406

Page 88: UC Davis Asbestos Analysis

EMSL Analytical, Inc.528 Mineola Avenue, Carle Place, NY 11514Phone/Fax: (516) 997-7251 / (516) 997-7528http://www.emsl.com [email protected]

061307730CustomerID: NAL51CustomerPO:ProjectID:

EMSL Order:

Attn: Paula LeeNational Analytical Laboratories (NAL)2201 Francisco Dr.Ste. 140-261El Dorado Hills, CA 95762

Received: 07/11/13 9:28 AM

Wellman Hall: CAAN #4050 ZONE #B042 Davis, CA 95616

Fax: (916) 361-0540Phone: (916) 361-0555

Project:

7/11/2013Analysis Date:7/9/2013Collected:

Sample Description Appearance % Type

AsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 and/or EPA 600/M4-82-020 Method(s) using Polarized Light Microscopy

4050-1

061307730-0001

Rm 0027, W. Side Ceiling/2x4 White Acoustical Ceil

Tan/White None DetectedFibrousHeterogeneous

Cellulose30%Min. Wool20%

Non-fibrous (other)50%

4050-3

061307730-0003

Rm 0027, NW Corner/Sheetrock-Joint Compound

Various None DetectedFibrousHeterogeneous

Cellulose10% Ca Carbonate15%Non-fibrous (other)75%

1THIS IS THE LAST PAGE OF THE REPORT.Test Report PLM-7.28.7 Printed: 7/11/2013 2:44:05 PM

Michelle McGowan, Laboratory Manageror other approved signatory

Analyst(s)

EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non-friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis. Samples received in good condition unless otherwise noted. Estimated accuracy, precision and uncertainty data available upon request. Reporting limit is 1%Samples analyzed by EMSL Analytical, Inc. Carle Place, NY NVLAP Lab Code 101048-10, CA ELAP 2339, NYS ELAP 11469

Initial report from 07/11/2013 14:44:05

Pedro Calderon (2)

Page 89: UC Davis Asbestos Analysis

EMSL Analytical, Inc.528 Mineola Avenue, Carle Place, NY 11514Phone/Fax: (516) 997-7251 / (516) 997-7528http://www.emsl.com [email protected]

061307730CustomerID: NAL51CustomerPO:ProjectID:

EMSL Order:

Attn: Paula LeeNational Analytical Laboratories (NAL)2201 Francisco Dr.Ste. 140-261El Dorado Hills, CA 95762

Received: 07/11/13 9:28 AM

Wellman Hall: CAAN #4050 ZONE #B042 Davis, CA 95616

Fax: (916) 361-0540Phone: (916) 361-0555

Project:

7/11/2013Analysis Date:7/9/2013Collected:

Sample Description Appearance % TypeAsbestosNon-Asbestos

% Fibrous % Non-Fibrous

Test Report: Test Report: Asbestos Analysis of Bulk Material via EPA 600/R-93/116 and/or EPA 600/M4-82-020. Quantitation using 400 Point Count Procedure

4050-2061307730-0002

Rm 0027, N. Wall/Texture

Tan/CreamNon-FibrousHeterogeneous

Chrysotile<0.25%Ca Carbonate10.00%Non-fibrous (other)90.00%

Michelle McGowan, Laboratory Manageror other approved signatory

Test Report PLMPTC-7.25.0 Printed: 7/11/2013 2:44:05 PM 1

Analyst(s)

THIS IS THE LAST PAGE OF THE REPORT.

Disclaimer:Some samples may contain asbestos fibers present in dimensions below PLM resolution limits. The limit of detection as stated in the method is 0.25%. EMSL Analytical Inc suggests that samples reported as <0.25% or none detected undergo additional analysis via TEM. The above test report relates only to the items tested. This report may not be reproduced, except in full, without written approval of EMSL Analytical Inc. This test report must not be used by the client to claim product endorsement by NVLAP or any agency of the United States Government. EMSL Analytical Inc., bears no responsibility for sample collection activities, analytical method limitations, or the accuracy of results when requested to separate layered samples. EMSL Analytical Inc., liability is limited to the cost of sample analysis.The test results contained within this report meet the requirements of NELAC unless otherwise noted. Samples received in good condition unless otherwise noted. Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample.Samples analyzed by EMSL Analytical, Inc. Carle Place, NY NVLAP Lab Code 101048-10, CA ELAP 2339, NYS ELAP 11469

Pedro Calderon (1)

Initial report from 07/11/2013 14:44:05

Page 90: UC Davis Asbestos Analysis
Page 91: UC Davis Asbestos Analysis

Client Sample Description ConcentrationLab ID AnalyzedLead

Collected

EMSL Analytical, Inc.528 Mineola Avenue, Carle Place, NY 11514Phone/Fax: (516) 997-7251 / (516) 997-7528http://www.emsl.com [email protected]

Attn: Paula LeeNational Analytical Laboratories (NAL)2201 Francisco Dr.Ste. 140-261El Dorado Hills, CA 95762

Received: 07/11/13 9:28 AM

Wellman Hall: CAAN #4050, Zone #B042, Davis, CA 95616

Fax: (916) 361-0540Phone: (916) 361-0555

Project:

7/9/2013Collected:

Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B*/7000B)

061307726CustomerID: NAL51CustomerPO:ProjectID:

EMSL Order:

Site: Rm 0027, Metal door components/brown/tan white pai00014050-1L <0.010 % wt7/11/20137/9/2013

Site: Rm 0027, Entry Wood Door/Brown/Tan Paint00024050-2L <0.010 % wt7/11/20137/9/2013

Site: Rm 0027, Various Sheetrock Walls/Multi Colored Pai00034050-3L 0.30 % wt7/11/20137/9/2013

Page 1 of 1

Michelle McGowan, Laboratory Manageror other approved signatory

Test Report ChmSnglePrm/nQC-7.21.0 Printed: 7/11/2013 2:31:25 PM

Reporting limit is 0.010 % wt based on the minimum sample weight per our SOP. The QC data associated with these results included in this report meet the method QC requirements, unless specifically indicated otherwise. Unless noted, results in this report are not blank corrected. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. * slight modifications to methods applied. "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request.Samples analyzed by EMSL Analytical, Inc. Carle Place, NY AIHA-LAP, LLC--ELLAP Lab 102344, CT PH-0249, NYS ELAP 11469

Initial report from 07/11/2013 14:31:25

Page 92: UC Davis Asbestos Analysis
Page 93: UC Davis Asbestos Analysis

∆ DELTA DEVELOPMENT Environmental Consulting

Mailing Address: P.O. Box 3203 • Rancho Cordova, CA 95741-3203

11275 Sunrise Gold Circle, Suite Q • Rancho Cordova, CA 95742 Phone (916) 631-1400 • Fax (916) 631-0200

August 22, 2014 Mr. Fred Torres, Project Manager Facilities, Mechanical / HVAC University of California One Shields Avenue Davis, California 95616 Dear Mr. Torres: Per your request, I have reviewed additional hazardous material (asbestos/lead) pre-job start and post project close-out information you provided August 20, 2014. The aforementioned documents are associated with Olson Hall HVAC System Upgrades, Phase II, in Room 0040, Basement Mechanical Room (University Project Number 2503800). Two Rivers Demolition commenced site work associated with the aforementioned project on June 16, 2014 and the University accepted said site work as complete on June 20, 2014. Olson Hall is located on the UC Davis Campus, in Davis, California. Deviations from University Asbestos and Lead Remediation specifications (Sections 028200 & 028300), and the Contractor’s approved Work and Disposal Plans have complicated Project Close Out. This is due in part to the University’s pre-demolition activities which resulted in a lead dust release, and ultimately changed the Contractor’s lead work classification from non-trigger task work to lead trigger task work. The aforementioned deviations include but are not limited to the following: Pre-Job Start Submittals; Contractor’s approved Work Plan (means & methods); Contractor’s approved waste disposal plans; and University clearance criteria. This letter identifies pre-job start and post-job completion submittal deficiencies and/or omissions related to the University’s Asbestos Remediation Specification (Section 028200) and Lead Remediation Specification (Section 028300). Said deficiencies and/or omissions listed below must be corrected and accepted by the University’s prior to issuing the Contractor final payment. Also, please let me know if additional documentation is needed to address mid-project modifications to requirements found in the University’s Asbestos and Lead Remediation Specifications, including lead clearance criteria and asbestos / lead disposal. Asbestos Pre-Job Start & Post Job Completion Submittal Deficiencies and/or Omissions:

1. One electronic copy of supplemental pre-job start submittals was provided. Contractor shall provide required number of hard copies of project submittals per Section 028200, 1.5 Submittals, D.

2. Laboratory Qualifications: EMSL Analytical, Inc. of San Leandro, California is identified as the Contractor’s asbestos laboratory, however, asbestos analysis reports have not been provided. Contractor shall submit asbestos analysis reports.

Page 94: UC Davis Asbestos Analysis

∆ DELTA DEVELOPMENT Environmental Consulting

Mailing Address: P.O. Box 3203 • Rancho Cordova, CA 95741-3203

11275 Sunrise Gold Circle, Suite Q • Rancho Cordova, CA 95742 Phone (916) 631-1400 • Fax (916) 631-0200

Mr. Fred Torres, Project Manager UCD, Olson Hall HVAC System Upgrades Room 0040, Basement Mechanical Room University Project Number 2503800 Asbestos/Lead Removal Close-Out Documentation Review # 2 August 22, 2014 Page Two

3. A statement titled “3.15 Project Close-Out” was provided on Two Rivers Demolition’s letterhead, and appears to contain information pertaining to both asbestos and lead Project Close-Out documentation. Although Asbestos and Lead Project Close Out documentation may contain some duplicate information, said information must be provided as two independent documents. Contractor shall provide Asbestos Project Close Out information identified in Project Close-Out Requirements, Section 028200 Asbestos Remediation Specification, 3.15. Close Out documentation shall pertain to actual work performed, not proposed work, and clarify deviations from project specifications and approved Work and Disposal Plans, including means and methods, and waste packaging / transportation / disposal.

4. Contractor’s statement titled “3.15 Project Close-Out”, which was provided on Two Rivers Demolition’s letterhead, states “All asbestos was turned over to the University for disposal per John Nichols of Delta Development.” The aforementioned statement is false and must be removed from the Contractor’s Close Out documentation. Neither John Nichols or Delta Development directed the Contractor to deviate from the approved waste disposal plan. Furthermore, Asbestos Project Close Out documentation should accurately reflect waste disposal and any deviations from approved Exhibit 21 Asbestos Waste Disposal Plan.

5. Exhibit 22 – Asbestos As-Built Summary is incomplete with regard to waste disposal and transportation, and states “See attached document “Asbestos Waste””. However, the aforementioned “Asbestos Waste” document was not provided. Contractor shall provide waste disposal and transportation information requested in Exhibit 22 Asbestos As-Built Summary, Section 028200 Asbestos Remediation Specification.

Lead Pre-Job Start & Post Job Completion Submittal Deficiencies and/or Omissions:

1. One electronic copy of supplemental pre-job start submittals was provided. Contractor shall provide required number of hard copies of project submittals per Section 028300, 1.5 Submittals, D.

2. Recycler weight tickets include slips from Sims Metal, however, Sims Metal is not the recycler identified in the Contractor’s approved disposal plan. Additionally, recycler weight tickets appear to include materials not associated with the Olson Hall project. Contractor shall clarify.

3. A statement titled “3.15 Project Close-Out” was provided on Two Rivers Demolition’s letterhead, and appears to contain information pertaining to both asbestos and lead Project Close-Out documentation. Although Asbestos and Lead Project Close Out documentation may contain some duplicate information, said information must be provided as two independent documents.

Page 95: UC Davis Asbestos Analysis

∆ DELTA DEVELOPMENT Environmental Consulting

Mailing Address: P.O. Box 3203 • Rancho Cordova, CA 95741-3203

11275 Sunrise Gold Circle, Suite Q • Rancho Cordova, CA 95742 Phone (916) 631-1400 • Fax (916) 631-0200

Mr. Fred Torres, Project Manager UCD, Olson Hall HVAC System Upgrades Room 0040, Basement Mechanical Room University Project Number 2503800 Asbestos/Lead Removal Close-Out Documentation Review # 2 August 22, 2014 Page Three

Contractor shall provide Lead Project Close Out information identified in Project Close-Out Requirements, Section 028300 Lead Remediation Specification, 3.15. Close Out documentation shall pertain to actual work performed, not proposed work, and clarify deviations from project specifications and approved Work and Disposal Plans, including means and methods and waste handling. Identify all waste streams, and account for waste hazard classification / packaging / transportation / disposal.

4. Contractor’s statement titled “3.15 Project Close-Out” was provided on Two Rivers Demolition’s letterhead, and states “Materials were hauled off by Two Rivers Demolition Inc. and transported to Schnitzer Steel Products. Identify the materials hauled to Schnitzer Steel Products. Additionally, transport vehicles observed on site were marked as Primoris Demolition, not Two Rivers as stated in Project Close Out documentation. Contractor shall clarify.

5. Exhibit 25 – Lead As-Built Summary is incomplete with regard to waste disposal and transportation, and states “See attached document “Lead Waste””. However, the aforementioned “Lead Waste” document was not provided. Contractor shall provide waste disposal and transportation information requested in Exhibit 25 Lead As-Built Summary, Section 028300 Lead Remediation Specification. Be sure to account for all waste streams, including, but not limited to dust, vacuum debris, decontamination materials and supplies, and personal protective equipment.

If you have questions regarding information included in this letter please contact me at (916) 631-1400. Thank you for the opportunity to serve you. Sincerely, John M. Nichols Certified Lead Consultant, 2839 Certified Asbestos Consultant, 92-0039 Cc: Tom Emme, UCD Cynthia Hongola, UCD

Page 96: UC Davis Asbestos Analysis
Page 97: UC Davis Asbestos Analysis

2620 Mercantile Drive, Rancho Cordova, CA 95742 T: (916) 638-6775 / F: (916) 638-0511

CSLB # 726647

ASBESTOS WASTE

All of the Asbestos waste was taken by UC Davis EH&S Department to their containers on site where it was properly labeled and manifested with other asbestos waste.