CONTENTS General Notes…….……………………. 2 Joist Size and Span.…………...……….. 3 Beam size, Post Size, Bracing Detail….. 4 Post to Beam ............................................5 Siding Details…………………….....….. 6 Brick Veneer Details………………...…. 7 Stringers................................………..…. 8 Handrail/Guardrail, Bay and Chimney.... 9 guard joists post joist-to-beam connection rim joist footing post-to-beam connection guard post attachment beam ledger board attachement to existing house existing house floor construction ledger board fasteners decking Typical Deck Details Based on the 2006 International Residential Building Code and the DeKalb County Local Ordinance
9
Embed
TYPICAL DECK DETAILS - .xyzlibvolume3.xyz/civil/btech/semester6/designdrawingofrcstructures/... · Beams are to be minimum double 2x, or one 4x, as per design specifications. Properly
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
CONTENTS General Notes…….……………………. 2 Joist Size and Span.…………...……….. 3 Beam size, Post Size, Bracing Detail….. 4Post to Beam ............................................5Siding Details…………………….....….. 6 Brick Veneer Details………………...…. 7 Stringers................................………..…. 8Handrail/Guardrail, Bay and Chimney.... 9
guard
joists
postjoist-to-beamconnection
rim joist
footing
post-to-beam connection
guard post attachment
beam
ledger board attachement toexisting house
existing house floor construction
ledger boardfasteners
decking
Typical Deck Details
Based on the 2006 International Residential Building Code and the DeKalb County Local Ordinance
DEKALB COUNTY – PLANNING AND DEVELOPMENT GENERAL NOTES
1. All lumber shall be pressure treated in accordance with the American Wood-Preservers Association standards, southern pine or decay resistant species, grade #2 or better.
2. All screws, nails and bolts shall be hot-dipped galvanized or stainless steel. 3. All hardware (joist hangers, cast-in-place post anchors, etc.) shall be galvanized
with 1.85-oz/ sf of zinc (G-185 coating) or shall be stainless steel, type 304 or better. Look for products such as “Zmax” from Simpson Strong-Tie or “Triple Zinc” from USP.
4. Decks constructed according to this handout are not approved for future hot
tub installations. 5. Decks shall not be attached to house overhangs, bay windows, or chimneys. 6. Deviations from this handout and conditions, which do not meet the details
shown herein, may require a plan submission. 7. Inspections:
A footing, framing and final inspection is required on all decks Footing inspections are required PRIOR to the placement of concrete. Framing and final inspections may be combined if all portions of the deck
framing and mechanical attachments are at least 24 inches above grade. Inspections are required by law. Failure to receive any and all
inspections can result in the issuance of violations which may lead to legal proceedings.
8. It is the responsibility of the permit holder or their representative to notify
Dekalb County when the stages of construction are reached that require an inspection. Inspections are scheduled using the Automated Inspection Request System number that appears on your permit. Please have your permit number available. Follow the instructions and your inspections will be scheduled for the following day between the hours of 8:00am and 3:00pm.
9. All decking material shall be composed of 2 x 6 or larger material or 5/4 (‘five-
quarter”) boards. Decking may be placed from an angle perpendicular to the joist at an angle of 45 degrees to the joist. Decking must have a span length such that each board bears on a minimum of 4 joists.
10. Plastic or manufactured decking products may be substituted with an approved
evaluation report from the International Code Council. The evaluation must be on the job site and available to the inspector during the inspection process. Installation and span lengths of the substituted material must be in compliance with the evaluation report and the manufacturer’s instructions.
11. Decks shall not be used or occupied until a final inspection approval.
-2-
JOIST SIZE The span of a joist is measured from the centerline of bearing at one end of the joist to the centerline of bearing at the other end and does not include overhangs. Maximum joist span lengths are noted in Table 1. See Figures 1 and 2 for joist span types.
beam
post
joist hanger
(minimum span = 6'-0" with overhang)
optional overhang
overhang3' maximum Joist Span
existing house wall
ledger board
rim joist
joist
FIGURE 1: JOIST SPAN - DECK ATTACHED AT HOUSE
p o s t
b e a m
o ve rh a ng (m in im u m sp an = 6 '-0 " w ith o ve rh an g )3 ' m a x im u m Jo is t S pa n
o p tio n a l o ve rha ng o p tio n a l o ve rh an g
be a m
p o st
3 ' m a x im u mo ve rh a ng
rim jo is t r im jo is t
jo is t
FIGURE 2: JOIST SPAN - FREE-STANDING DECK
Table 1 Maximum Joist Spans Joist Size
Joist Spacing
On Center Joist Span1
(does not include overhang)
2 X 6 12″ 10′ 9″ 2 X 6 16″ 9′ 9″ 2 X 6 24″ 8′ 6″ 2 X 8 12″ 14′ 2″ 2 X 8 16″ 12′ 10″ 2 X 8 24″ 11′
2 X 10 12″ 18′ 2 X 10 16″ 16′ 1″ 2 X 10 24″ 13′ 1″ 2 X 12 12″ 21′ 9″ 2 X 12 16″ 18′ 10″ 2 X 12 24″ 15′ 5″
Spans based on 40 PSF live load, 10PSF dead load, southern yellow pine #2, normal loading duration
-3-
BEAM SIZE Beam size is based upon the joist span and the tributary load it supports. Use Table 2 to determine the beam size and the spacing of the post that support the beam. Beam splices shall be placed above post locations. Beam span is the actual clear distance between posts. Larger beams than those required may be used.
(Number below joist span represent maximum girder span) POST SIZE Post used for residential deck construction may be 4 X 4, 4X 6, 6 X 6 or 3 inch or greater metal post. Use Table 4 for height limitations of wood post. All post must be secured at the top and bottom of their position placement. Dimensions of the post shall match the beam width.
TABLE 4 Post Size Post Height
4 X 4 ≤ 8′ 4 X 6 ≤12′ 6 X 6 > 12′ & < 17′
POST TO BEAM BRACING
14'-0
" max
imum
w ith posts
2'
locationsjoist at post
2'beam2'
BRACING PERPENDICULAR TO BEAM
joists do not alignprovide blocking when
2'
2x4, typical
beam
BRACING PARALLEL TO BEAM
1-3/8" diameter thru-bolt with washers, typical
-4-
DeKalb County – Post to Beam Connection Detail
Post to Beam Connection Beams are to be minimum double 2x, or one 4x, as per design specifications. Properly attach beam to post (see illustrations). Brackets and hardware must be hot-dipped galvanized or stainless steel. The joists can be connected to the beams in a number of different ways. The best configuration allows the joist to bear directly on the beam, eliminating the dependency on fastener performance. Blocking should be used to stabilize the joist.
-5-
wlbarnet
Rectangle
ed by: DeKalb County Development Department
-No Scale-ision Date: January 2008
RAIL HEIGHT & PICKETT SPACING- NO SCALE -
- NO SCALE -
- NO SCALE -ATTACHMENT TO STRUCTURE
PICKETTS SPACED LESS
THAN4” OC
GUARD RAIL HEIGHT36”
MINIMUM
SEE DETAIL “B”GUARD & HAND RAIL DETAILS, PICKETT SPACING.*DECK JOISTS SHALL MEET SPAN TABLES FOR 40PSF LIVE LOAD.
DECKING:“CUP” DOWN
MINIMUM LANDING, TO BE NO LESS THAN 36” SQUARE
“MINIMUM” HAND RAIL HEIGHT SHALL BE 30”-38”
NOTE:“MINIMUM” SIZE FOOTINGS REQUIRED ON ALL POST & COLUMNS OF THE DECK TO BE NO LESS THAN 16” X 16” X 12” DEEP . (BELOW GRADE)POST MAY BE EMBEDDED IN CONCRETE UP TO 6" ORPLACED BELOW GRADE WITH USE OF .40 MATERIAL.
STAIR STRINGERPLACED “ON” LANDING
NOTES:•ALL WOOD USED IN CONSTRUCTION OF DECK SHALL BE PRESSURE TREATED OR DECAY RESISTANT SPECIES, .•ANY ADDITIONAL STRUCTURES SUPPORTED BY THE DECK MUST HAVE ENGINEER DESIGN TO INSURE LOADS ARE PROPERLY SUPPORTED. •DECKS LOCATED MORE THAN 30” ABOVE FINISHED GRADE SHALL HAVE GUARDRAILS NOT LESS THAN 36” IN HEIGHT.•ATTACHMENT BOLTS TO STRUCTURE; TO BE ½” DIAMETER, GALVANIZED HEX HEAD, OR ROUND BOX HEAD, DESIGN, WITH TWO FLAT WASHERS PER BOLT. BOLTS TO BE PLACED 16” O.C. OF BAND, WITH ONE WASHER PLACED ON EACH SIDE AND SECURED WITH NUT.•IF CHIPPENDALE, STARBURST, ETC. STYLED PICKETS ARE USED, PROPER SPACING MUST BE MAINTAINED BETWEEN PICKETS.•AS PER INTERNATIONAL RESIDENTIAL CODE.
NOTE:
PICKETT SPACING OF “ANY DESIGN” SHALL BE SUCH THAT NO SPHERICAL OBJECT 4” OR GREATER IN DIAMETER SHOULD BE ALLOWED TO PASS BETWEEN OR 4 3/8" ON STAIRS.
HAND RAILS&
STEPS
FINISHED GRADE
DECKING
DIAGONAL CROSS BRACES ON SUPPORT COLUMNS AT 45DEGREE ANGLE WHEN USING WOOD POSTS OVER 8’ IN HEIGHT
FLASHINGDECKING
JOIST HANGER
SIDINGSHEATHING
BOLT & WASHER
NUT & WASHER
HEAD JOIST
BAND JOIST
STRUCTURE
(FROST DEPTH)
MINIMUM CLEAR WIDTH OF HAND RAILS AND STEPS SHALL NOT BE LESS THAN 36”
-6-
Approv Planning &
Rev
DECK JOIST
GALVANIZED PLATED JOIST HANGERS REQUIRED ON HOUSE SIDE. USE OF BOND TIMBER (OR LEDGER STRIP) ALLOWED .ALL SUPPORT POSTS SHALL BE ANCHORED TO FOOTINGS WITH GALVANIZED PLATED SUPPORTS.CONCRETE FOOTINGS, TO BE A MINIMUM OF 12” BELOW GRADE ON UNDISTURBED SOIL OR COMPACTED FILL.
wlbarnet
Stamp
Approved by: DeKalb County Planning & Development Department
-No Scale- Revision Date: January 2008
RAIL HEIGHT & PICKETT SPACING- NO SCALE -
- NO SCALE -
PICKETTS SPACED LESS
THAN4” O.C.
GUARD RAIL HEIGHT36”
MINIMUM
*DECK JOISTS SHALL MEET SPAN TABLES FOR 40 PSF LIVE LOAD.
FLASHING IS OPTIONALWHERE DECK MEETS THE HOUSE IF CORRECTLYINSTALLED.
DECKING:“CUP” DOWN
MINIMUM LANDING, TO BE NO LESS THAN 36” SQUARE
“MINIMUM” HAND RAIL HEIGHT SHALL BE 30”-38”
GALVANIZED PLATED JOIST HANGERS REQUIRED ON HOUSE SIDE. USE OF BOND TIMBER (OR LEDGER STRIP) ALLOWED ON OUTER BAND.ALL SUPPORT POSTS SHALL BE ANCHORED TO PIERS WITH GALVANIZED PLATED SUPPORTS.CONCRETE FOOTINGS, TO BE A MINIMUM OF 12” BELOW GRADE ON UNDISTURBED SOIL OR COMPACTED FILL.(FROST DEPTH)
DECK JOISTNOTES:•ALL WOOD USED IN CONSTRUCTION OF DECK SHALL BE PRESSURE TREATED OR DECAY RESISTANT SPECIES..•ANY ADDITIONAL STRUCTURES SUPPORTED BY THE DECK MUST HAVE ENGINEER DESIGN TO INSURE LOADS ARE PROPERLY SUPPORTED.•DECKS LOCATED MORE THAN 30” ABOVE FINISHED GRADE SHALL HAVE GUARDRAILS NOT LESS THAN 36” IN HEIGHT.•IF CHIPPENDALE, STARBURST, ETC. STYLED PICKETS ARE USED, PROPER SPACING MUST BE MAINTAINED BETWEEN THE PICKETS. •DECK MUST BE BOLTED TO HOUSE WHEN USING BRICK VENEER CONSTRUCTION. 4’ O.C WITH HOLE SLOPED UPWARD AND FILLED WITH CAULK. BOLTS MUST BE 1/2" GALVANIZED WITH WASHERS AS SHOWN IN DETAIL "A". •ONE & TWO FAMILY BRICK VENEER DWELLING & MOBILE HOMES ONLY.•AS PER INTERNATIONAL RESIDENTIAL CODE.
NOTE:
PICKETT SPACING OF ANY DESIGN SHALL BE SUCH THAT NO SPHERICAL OBJECT GREATER THAN 4” IN DIAMETER SHOULD BE ALLOWED TO PASS BETWEEN OR 4 3/8" ON STAIRS.
MINIMUM CLEAR WIDTH OF HAND RAILS AND STEPS SHALL NOT BE LESS THAN 36”
HAND RAILS&
STEPS
FINISHED GRADE
STAIR STRINGERPLACED “ON” LANDING
DIAGONAL CROSS BRACES ON SUPPORT COLUMNS AT 45DEGREE ANGLE WHEN USING WOOD POSTS OVER 8’ IN HEIGHT.
SEE DETAIL “B”
DECKING
DECK MUST BESTRUCTURALLY INDEPENDENT
&FREE-STANDING
DECKING
BRICK
BOLT& WASHER
HEAD JOIST
NUT & WASHER
BAND JOISTJOIST HANGER
NOTE:“MINIMUM” SIZE FOOTINGS REQUIRED ON ALL POST & COLUMNS OF THE DECK TO BE NO LESS THAN 16” X 16” X 12” DEEP (BELOW GRADE).POST MAY BE EMBEDDED IN CONCRETE OR PLACED BELOW GRADE WITH USE OF .40 MATERIAL.
FLASHING
-7-
wlbarnet
Stamp
CUT STRINGER
max. span = 8'-0" with 2 stringersmax. span = 11'-3" with 3 stringers
maximum span = 16'-6"
SOLID STRINGER
5" min.
maximum spacing between stringers = 36"
STAIR STRINGER REQUIREMENTS
stringer
SOLID STRINGERCUT STRINGER
stringers2x4 ledger, each side, fulldepth of tread; attach with4-10d nails or #8 wood screws
attach 2x tread material with 2-#8 screws or 2-8d nails per board at each stringer or ledger
tread material: 2x or 5/4 board
TREAD CONNECTION REQUIREMENTS
4x4 guard post
sloped joist hanger;see JOIST HANGERSfor more requirements
ATTACHMENT WITH HANGERS
outside joistrim joist or
2 - 1/2" diameter thru-bolts with washers
outside joistrim joist or
ATTACHMENT TO POST
STAIR STRINGER ATTACHMENT DETAIL
-8-
between posts8'-0" maximum
diameter spherepermit the passage of a 6"triangular opening shall not
34" minimum from stair guard height:
nosing of step
stair guard is required for stairs with a total rise more than 30" or more. Graspable handrailrequired on one side.
STAIR GUARD REQUIREMENTS
double joist
extend 6" maximumdecking may
2-1/2" diameter thru-boltor lag screws at ledger
bay windowchimney or
6'-0" maximum
double headerdouble joist,each side
PLAN VIEW
or baychimney
ledgerboard
hanger, typical
window
SECTION
REQUIREMENTS FOR FRAMING AT CHIMNEY OR BAY WINDOW
-9-
handrail hardwarecorrosion-resistant
handrail
guard post
STAIRS HANDRAIL REQUIREMENTS
All stairs over 30" in height shall have a handrail on one side. Handrails shall be graspable and shall becomposed of decay-resistant and/or corrosion resistant material. The hand grip portion, if circular, shall be between 1-1/4 " and 2" in diameter. Shapes other than circular shall have a perimeter dimension between 4" and 6-1/4" with a maximum cross sectional dimension of 2-3/4". All shapes shall have a smooth surfacewith no sharp corners. Handrails shall run continuously from a point directly over the lowest riser to a point directly over the highest riser and shall return to the guard at each end.