TYPES OF INSULATION MATERIAL AND SIZES ETHYLENE UNIT-10 MAY 2013
Jan 11, 2016
TYPES OF INSULATION MATERIAL AND SIZES
ETHYLENE UNIT-10
MAY 2013
No. 2
TYPES OF INSULATION
Insulation Desired purpose Code & Thickness
Cold Insulation Cxx Anti Sweat (Dew point temperature) Axx Dual Temperature Dxx Full Heat Conservation Fxx Acoustic Nxx (NINxx) Personal Protection PPxx
XX stands for insulation thickness in mm.
COLD INSULATION CXX
INSULATION TYPE
No. 4
• Pipe painted Surface• Insulation Polyisocyanurate (PIR)
Measured 25mm.• Caulking between Segments• Mastic Vapor Barrier• Aluminum JacketNote: Insulation material could be either Foam Glass or Polyisocyanurate (PIR)
COLD INSULATION C25
No. 5
• Pipe painted Surface• Insulation Polyisocyanurate (PIR)• Caulking between Segments• Mastic Vapor Barrier• Aluminum Jacket
• Polyisocyanurate Measured 40mmNote: Insulation material could be either Foam Glass or Polyisocyanurate (PIR)
COLD INSULATION C40
No. 6
• Pipe painted Surface• Insulation Polyisocyanurate (PIR)• Caulking between Segments• Mastic Vapor Barrier• Aluminum Jacket
• Polyisocyanurate Measured 50mmNote: Insulation material could be either Foam Glass or Polyisocyanurate (PIR)
COLD INSULATION C50
No. 7
COLD INSULATION C65
• Pipe painted Surface• Insulation Polyisocyanurate
(PIR)• Caulking between Segments• Mastic Vapor Barrier• Aluminum Jacket• Polyisocyanurate Measured
50mmNote: Insulation material could
be either Foam Glass or Polyisocyanurate (PIR)
No. 8
COLD INSULATION C75
• Pipe painted Surface• Insulation Polyisocyanurate
(PIR)• Caulking between Segments• Mastic Vapor Barrier• Aluminum Jacket• Polyisocyanurate Measured
75mmNote: Insulation material could
be either Foam Glass or Polyisocyanurate (PIR)
ANTI SWEAT INSULATION AXX
INSULATION TYPES
No. 10
• Pipe painted Surface• Insulation Polyisocyanurate (PIR)
Measured 25mm.• Caulking between Segments• Mastic Vapor Barrier• Aluminum JacketNote: Insulation material Foam Glass should not be used for Anti Sweat Service
ANTI SWEAT INSULATION A25
DUAL TEMPERATURE INSULATION CXX
INSULATION TYPES
No. 12
• Pipe painted Surface• Fiber Glass Blanket• Foam Glass / Cellular Glass• Caulking between Foam Glass Segments• Mastic Vapor Barrier• Aluminum Jacket
• Measured Total 60mm Thickness• Fiber Glass 20mm• Foam Glass 40mm• As per YANPET Spec Fiber Glass shall
be Minimum 40mm Thick• Note: No PIR should use
DUAL TEMPERATURE INSULATION D65
FULL HEAT CONSERVATION INSULATION FXX
INSULATION TYPES
No. 14
FULL HEAT CONSERVATION F25
• Pipe painted Surface• Insulation Mineral Wool
Block Type 40mm Thickness
• Aluminum Jacket
No. 15
FULL HEAT CONSERVATION F40
• Pipe painted Surface• Insulation Mineral Wool Block Type
40mm Thickness• Aluminum Jacket
• Measured single layer 40mm Thickness
No. 16
• Pipe painted Surface• Insulation Mineral Wool Block Type
50mm Thickness• Aluminum Jacket
• Measured single layer 60mm Thickness
FULL HEAT CONSERVATION F50
ACOUSTIC NOISE INSULATION NXX (NINXX)
INSULATION TYPES
No. 18
ACOUSTIC NOISE INSULATION COLD 25C & 50N (NIN30)
No. 19
• Pipe painted Surface• Insulation Mineral Wool Block Type
100mm Thickness• Polyisocyanurate (PIR)• Mastic Vapor Barrier• Aluminum Jacket with Lead loaded
• Lead loaded Aluminum Jacket
• Note: I believe Insulation order (mineral wool & PIR) should be vise versa
ACOUSTIC NOISE INSULATION COLD C40 & N100 (NIN35)
No. 20
• Mineral Wool Measured 100mm • Polyisocyanurate Measured 40mm
ACOUSTIC NOISE INSULATION COLD C40 & N100 (NIN35)
No. 21
• Pipe painted Surface• Insulation Mineral Wool Block Type
50mm Thickness• Vinyl Loaded Barrier• Aluminum Jacket
• Measured single layer 50mm Thickness
ACOUSTIC NOISE INSULATION HOT N50 (NIN30)
No. 22
• Pipe painted Surface• Insulation Mineral Wool Block Type
125mm (40+85) Thickness• Vinyl Loaded Barrier• Aluminum Jacket
Measured Thickness 45mm each layer
ACOUSTIC NOISE INSULATION HOT N100 (NIN40)
No. 23
• Pipe painted Surface• Insulation Mineral Wool Block Type
125mm (40+85) Thickness• Vinyl Loaded Barrier• Aluminum Jacket
• NIN 40mm thickness Measured
ACOUSTIC NOISE INSULATION HOT N125 (NIN40)
PERSONAL PROTECTION INSULATION PXX
INSULATION TYPE
No. 25
PERSONAL PROTECTION PP25
• Pipe painted Surface
• Insulation Mineral Wool Blanket 25mm Thickness
• Aluminum Jacket
DIVIDER TEXTPRESENTATION RUNNING HEAD
No. 27
CREATE ONE LINE HEADLINES 20PT ARIAL, CAPITALS
Use 16pt Arial Regular for all paragraph text and bullet points. You can increase text size to 18pt or 20pt, but you must keep to one text size throughout your presentation to make it more consistent and seamless. All text should have a line spacing of 1.0, and paragraphs are separated with a Return. Bullets have an additional 0.36 lines of space before each line.• Press the Increase list level icon on the ‘Paragraph’ group to generate a bullet• Press Return to get another bullet• Do not use additional levels of sub-bullets, even though the slide master supports
five levels