Top Banner
TT 0710/03 TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1 TT0710.03 A3 Tavukçuyolu Türker Cad. No:8 Kat:3 34775 Y.Dudullu - Ümraniye - İSTANBUL - TÜRKİYE T: +90 216 364 69 40 F : +90 216 364 69 31 www.emelec.com.tr Tested by: IPH, Berlin RPT No : 2977.2100555.0379 Date: 09 June to 24 June, 2010 Pages: 30 Appendix: ---
31

TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

Mar 16, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TT 0710/03

TYPE TEST

OF

3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1

TT0710.03 A3

Tavukçuyolu Türker Cad. No:8 Kat:3 34775 Y.Dudullu - Ümraniye - İSTANBUL - TÜRKİYE T: +90 216 364 69 40 F : +90 216 364 69 31

www.emelec.com.tr

Tested by: IPH, Berlin RPT No : 2977.2100555.0379 Date: 09 June to 24 June, 2010 Pages: 30 Appendix: ---

Page 2: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

Independent test laboratory, accredited by Deutsche Akkreditierungsstelle Technik (DATech) e.V. in the fields of h.v. apparatus and switchgear, power cables and power cable accessories, l.v. apparatus and switchgear, installation equipment and switching and control equipment. Institut „Prüffeld für elektrische Hochleistungstechnik“ GmbH (IPH Berlin) is a subsidiary of CESI S.p.A, Milan.

Independent, accredited testing station · Member laboratory of STL and LOVAG

T E S T R E P O R T

NO. 2977.2100555.0379

EM Electrical Materials Contracting Co. Tavukcuyolu, Türker Cad. No. 08 Y. Dudullu-Umraniye 34776 Istanbul TURKEY

CLIENT

EM Electrical Materials Contracting Co. MANUFACTURER

Earthing bonding link box TEST OBJECT

LB.W.3SA.3.1 TYPE

Test sample SERIAL NO.

Rated DC withstand voltage Rated lightning impulse withstand voltage

Up

25 40 (60)

kV kV

RATED CHARACTERISTICS GIVEN BY THE CLIENT

Client's instructions NORMATIVE

DOCUMENT

Dielectric tests Leakage current test Measurement of contact resistance Measurement of residual voltage

RANGE OF TESTS PERFORMED

09 and 24 June 2010 DATE OF TEST

See Clause 8 TEST RESULT

RONALD BORCHERT Senior engineer

RAINER BORCHERT For Test engineer in charge

Berlin, 21 July 2010

Page 3: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 2

Contents Sheet

1. Present at the test............................................................................................................................................................. 3

2. Test performed.................................................................................................................................................................... 3

3. Identity of the test object ............................................................................................................................................ 4 3.1 Technical data and characteristics.......................................................................................................................................................................................... 4 3.2 Identity documents ......................................................................................................................................................................................................................................... 4

4. Dielectric tests...................................................................................................................................................................... 5 4.1 Test laboratory ........................................................................................................................................................................................................................................................ 5 4.2 Normative document................................................................................................................................................................................................................................... 5 4.3 Required test parameters...................................................................................................................................................................................................................... 5 4.4 Test arrangement............................................................................................................................................................................................................................................... 5 4.5 Test and measuring circuits............................................................................................................................................................................................................... 6 4.6 Test results..................................................................................................................................................................................................................................................................... 8

5. Leakage current test .................................................................................................................................................... 11 5.1 Test laboratory ....................................................................................................................................................................................................................................................11 5.2 Normative document...............................................................................................................................................................................................................................11 5.3 Required test parameters..................................................................................................................................................................................................................11 5.4 Test arrangement...........................................................................................................................................................................................................................................11 5.5 Test and measuring circuits...........................................................................................................................................................................................................12 5.6 Test results.................................................................................................................................................................................................................................................................13

6. Measurement of contact resistance................................................................................................................. 14 6.1 Test laboratory ....................................................................................................................................................................................................................................................14 6.2 Normative document...............................................................................................................................................................................................................................14 6.3 Test and measuring circuits...........................................................................................................................................................................................................14 6.4 Test results.................................................................................................................................................................................................................................................................15

7. Measurement of residual voltage...................................................................................................................... 16 7.1 Test laboratory ....................................................................................................................................................................................................................................................16 7.2 Normative document...............................................................................................................................................................................................................................16 7.3 Test results.................................................................................................................................................................................................................................................................16

8. Summary of results ....................................................................................................................................................... 17

9. Photos..................................................................................................................................................................................... 18

10. Oscillograms ...................................................................................................................................................................... 21

11. Drawing................................................................................................................................................................................. 30 This test document consists of 30 sheets. Distribution Copy No. 1 Copy No. 1 in English: EM Electrical Materials Contracting Co.

The test results relate only to the object tested.

This document is confidential. Its transfer to third parties as well as its reproduction in extracts require the consent of the client.

Page 4: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 3

1. Present at the test

Mr. Wittwer IPH test engineer in charge

Mr. Heske IPH test engineer

Mr. Borchert, Rainer IPH test engineer

Mr. Erdeniz EM Electrical Materials Contracting Co.

2. Test performed

Dielectric tests Leakage current test Measurement of contact resistance Measurement of residual voltage

Page 5: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 4

3. Identity of the test object

3.1 Technical data and characteristics

The technical data and characteristics of the test object are defined by the following parameters and specified by the client. Test object: Earthing bonding link box Type: LB.W.3SA.3.1 Manufacturer: EM Electrical Materials Contracting Co. Serial No.: Test sample Year of manufacture:

2010

Data: Rated voltage Not specified Rated DC withstand voltage 25 kV Rated lightning impulse withstand voltage Up 40 (60) kV Characteristics: Thickness of housing 3 mm

3.2 Identity documents

The manufacturer confirms that the test object has been manufactured in compliance with the drawings given in this document. IPH did not verify this compliance in detail. The identity of the test object is fixed by the following drawings and data submitted by the client:

Name of drawing Drawing No. Date of drawing Author Notes

SOLID EARTHING BONDING LINK BOX with SVL TYPE: LB.W.3SA.3.1

10.04.06 Rev. 0

30.04.2010 EMELEC Sheet 30

Entry of test object at IPH: 31 May 2010

Page 6: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 5

4. Dielectric tests

4.1 Test laboratory

High-voltage test laboratory, high-voltage hall 2

4.2 Normative document

Client's instructions

4.3 Required test parameters

Active parts (L1, L2, L3, MP) against each other and against earth (F): DC 25 kV, 5 min LI 1.2/50 s, 40 kV Active parts (L1, L2, L3) against each other only LI 1.2/50 s, 60 kV

4.4 Test arrangement

See Sub-clause 4.6 For the dielectric tests the surge arrestors were replaced by insulating dummy parts.

Page 7: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 6

4.5 Test and measuring circuits

DC voltage test Technical data of test circuit DC voltage source Test transformer: Rated voltage 100 kV Rated power 8 kVA Rated frequency 50 Hz Rectifier: Rated voltage 135 kV Rated current 15 mA Smoothing capacitor: Capacitance 10 nF

PO

1

C G

Gl

Tr E

E Supply Tr Test transformer with variable transformer connected in series Gl Rectifier CG Smoothing capacitor 1 Measuring point PO Test object Figure 1: Test and measuring circuit for the DC voltage test Technical data of measuring circuit

Measuring point Measured quantity Measuring sensor/device Technical parameters

1 Test voltage Ohmic divider with DC peak voltmeter type MU11 (made by TuRD)

Ratio 561

Page 8: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 7

Test and measuring circuits (continued) Lightning impulse voltage test Technical data of test circuit Impulse circuit: Number of stages n = 2 Impulse capacitance CS = 70 nF Loading capacitance CB = 1.5 nF Damping resistance RD = 122 Discharge resistance RE = 1200

1C R

R

S C

BE

D

PO

+/-

ZFS Gl

~

Gl Rectifier RD Damping resistance CS Impulse capacitance CB Loading capacitance ZFS Spark gap PO Test object RE Discharge resistance 1 Voltage measurement

Figure 2: Test and measuring circuit for the lightning impulse voltage test Technical data of measuring circuit

Measuring point Measured quantity Measuring sensor/device Technical parameters

1 Test voltage R divider of SMR 10/770 type (made by TuRD) with digital measuring instrument of DMI 551 type (made by Haefely) and TDS220 digital oscilloscope (made by Tektronix)

Ratio 472.3

Page 9: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 8

4.6 Test results

DC voltage test Date of test: 09 June 2010 Testing time after having reached full amplitude: 5 min Air temperature: 21.4 C Air pressure: 100.21 kPa Air humidity (relative): 58 % Atmospheric correction of test voltage: Without atmospheric correction

Every voltage is related to an air pressure of 101.3 kPa, an air temperature of 20 C and an air humidity of 11 g/m3. Test set-up

MP

A

B

C

L1

L2

Frame

L3

DC withstand voltage

Test voltage 1)

Disruptive discharge 2)

Configuration Voltage applied to

Earthed kV kV

-

L1

L2, L3, MP, F

25

25

0

-

L2

L1, L3, MP, F

25

25

0

-

L3

L1, L2, MP, F

25

25

0

-

MP

L1, L2, L3, F

25

25

0

Notes:

1) Related to normal atmospheric conditions 2) Within the testing period no disruptive discharge shall occurred

Page 10: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 9

Test results (continued) Lightning impulse voltage test Date of test: 09 June 2010 Front time of lightning impulse wave: 0.94 μs Tail time of lightning impulse wave: 51.7 μs Air temperature: 21.4 C Air pressure: 100.21 kPa Air humidity (relative): 58 % Atmospheric correction of test voltage: Without atmospheric correction

Every voltage is related to an air pressure of 101.3 kPa, an air temperature of 20 C and an air humidity of 11 g/m3.

Test set-up

MP

A

B

C

L1

L2

Frame

L3

Impulse withstand voltage

Test voltage 1)

Number of impulses/ disruptive discharges

Configuration Voltage applied to

Earthed kV kV

-

L1

L2, L3, MP, F

40

+40 -40

10/0 10/0

-

L2

L1, L3, MP, F

40

+40 -40

10/0 10/0

-

L3

L1, L2, MP, F

40

+40 -40

10/0 10/0

-

MP

L1, L2, L3, F

40

+40 -40

10/0 10/0

Notes:

1) Related to normal atmospheric conditions

Page 11: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 10

Test results (continued) Lightning impulse voltage test 60 kV Date of test: 09 June 2010 Front time of lightning impulse wave: 0.94 μs Tail time of lightning impulse wave: 52.0 μs Air temperature: 21.4 C Air pressure: 100.21 kPa Air humidity (relative): 58 % Atmospheric correction of test voltage: Without atmospheric correction

Every voltage is related to an air pressure of 101.3 kPa, an air temperature of 20C and an air humidity of 11 g/m3.

Test set-up

MP

A

B

C

L1

L2

Frame

L3

Impulse withstand voltage

Test voltage 1)

Number of impulses/ disruptive discharges

Configuration Voltage applied to

Earthed kV kV

-

L1

L2, L3

60

+60 -60

10/0 10/0

-

L2

L1, L3

60

+60 -60

10/0 10/0

-

L3

L1, L2

60

+60 -60

10/0 10/0

Notes:

1) Related to normal atmospheric conditions

Page 12: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 11

5. Leakage current test

5.1 Test laboratory

High-voltage test laboratory, high-voltage hall 2

5.2 Normative document

Client's instructions

5.3 Required test parameters

DC 5 kV, 1 min Leakage current

5.4 Test arrangement

See Sub-clause 5.6

Page 13: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 12

5.5 Test and measuring circuits

DC voltage test Technical data of test circuit DC voltage source Test transformer: Rated voltage 100 kV Rated power 8 kVA Rated frequency 50 Hz Rectifier: Rated voltage 135 kV Rated current 15 mA Smoothing capacitor: Capacitance 10 nF

PO

1

C G

Gl

Tr E

2

E Supply Tr Test transformer with variable transformer connected in series Gl Rectifier CG Smoothing capacitor 1 – 2 Measuring point PO Test object Figure 3: Test and measuring circuit for the DC voltage test Technical data of measuring circuit

Measuring point Measured quantity Measuring sensor/device Technical parameters

1 Test voltage Ohmic divider with DC peak voltmeter type MU11 (made by TuRD)

Ratio 561

2 Leakage current Digital multimeter Keithley 137

Page 14: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 13

5.6 Test results

Leakage current test Date of test: 09 June 2010 Testing time after having reached full amplitude: 1 min Air temperature: 21.4 C Air pressure: 100.21 kPa Air humidity (relative): 58 % Atmospheric correction of test voltage: Without atmospheric correction

Every voltage is related to an air pressure of 101.3 kPa, an air temperature of 20 C and an air humidity of 11 g/m3. Test set-up 2)

MP

L1

L2

Frame

L3

DC withstand voltage

Test voltage 1)

Leakage current

Configuration Voltage applied to

Earthed kV kV μA

-

L1

MP, F

5

5

<1

-

L2

MP, F

5

5

<1

-

L3

MP, F

5

5

<1

Notes:

1) Related to normal atmospheric conditions 2) Serial no. of surge arrestors: L1: 594 L2: 596 L3: 595

Page 15: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 14

6. Measurement of contact resistance

6.1 Test laboratory

Low-voltage test laboratory, test room 1

6.2 Normative document

Client’s instructions

6.3 Test and measuring circuits

Page 16: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 15

6.4 Test results

Date of test: 24 June 2010 Test object: Earthing bonding link box Ambient temperature: 18.4 ˚C

Contact Resistance (μΩ)

C.01 C.02 C.03 C.04 C.05 C.06 C.07

1.38 1.16 1.53 2.08 1.60 1.76 1.52

Page 17: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 16

7. Measurement of residual voltage

7.1 Test laboratory

Low-voltage test laboratory, test room 1

7.2 Normative document

Client’s instructions

7.3 Test results

Date of test: 24 June 2010 Test object: Earthing bonding link box Test no. 210 2877 210 2878 210 2879

Impulse current 8/20 s, peak value kA 10.3 10.3 10.2

Residual voltage kV 18.1 18.1 18.2

Pole red yellow blue

Test no. 210 2880 210 2881 210 2882

Impulse current 8/20 s, peak value kA 20.0 20.8 20.5

Residual voltage kV 18.1 20.0 19.9

Pole blue yellow red

Test no. 210 2889 210 2890 210 2891

Impulse current 8/20 s, peak value kA 44.7 43.1 44.1

Residual voltage kV 23.3 23.1 23.3

Pole red yellow blue

Page 18: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 17

8. Summary of results

Dielectric tests

As agreed with the client, the test object was subjected to a DC voltage withstand voltage of 25 kV Phase-to-earth insulation Lightning impulse withstand voltage of 40 kV Phase-to-earth insulation Lightning impulse withstand voltage of 60 kV Phase-to-phase insulation In the DC test no disruptive discharge occurred. In the lightning impulse voltage test the number of disruptive discharges was 0 for every 10 impulses. The requirements for the dielectric tests as specified by the client have been fulfilled. Leakage current test

As agreed with the client, the test object was subjected to a DC voltage withstand voltage of 5 kV Phase-to-earth insulation The requirements for the leakage current test as specified by the client have been fulfilled. Measurement of residual voltage

The maximum residual voltage measured during the tests was 23.3 kV.

Page 19: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 18

9. Photos

Photo 1: View of the test object with closed outer cover plate

Photo 2: View of the test object with opened outer cover plate

Page 20: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 19

Photo 3: View of the test object with removed inner isolating cover plate

Photo 4: View of the test object with removed inner isolating cover plate and dummies in place

of surge arrestors

Page 21: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 20

Photo 5: View of the cable entry in the box

Photo 6: Test object after measurement of residual voltage test

Page 22: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 21

10. Oscillograms

Page 23: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 22

Page 24: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 23

Page 25: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 24

Page 26: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 25

Page 27: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 26

Page 28: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 27

Page 29: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 28

Page 30: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 29

Page 31: TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: …emelec.com.tr/images/uploads/b8ae86be27494ffeb5049aa... · 2018. 1. 17. · Test object: Earthing bonding link box Type:

TEST REPORT NO. 2977.2100555.0379 SHEET 30

11. Drawing