Top Banner
JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type 702044 Type 702041 Type 702043 Type 702040
41

Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

Mar 02, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

JUMO iTRONCompact

microprocessorcontrollers

B 702040Operating Instructions

2008-11-1100357918

Type 702042 Type 702044 Type 702041

Type 702043

Type 702040

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

Please read these Operating Instructions carefully before starting up the instrument Keepthese operating instructions in a place which is at all times accessible to all users Pleaseassist us to improve these operating instructions where necessary Your suggestions will bemost welcome

Phone in Germany (0661) 6003-727from abroad (+49) 661 6003-0

Fax in Germany (0661) 6003-508abroad (+49) 661 6003-607

All necessary settings are described in these operating instructions However if any difficul-ties should still arise during start-up you are asked not to carry out any unauthorized ma-nipulations on the unit You could endanger you rights under the instrument warrantyPlease contact the nearest subsidiary or the main factory in such a case

EWhen returning chassis assemblies or components the regulations of EN 100 015 ldquoProtec-tion of electrostatically sensitive componentsrdquo must be observed Use only the appropriateESD packaging for transport

Please note that we cannot accept any liability for damage caused by ESD (electrostatic dis-charge)

b702040enbk Seite 2 Mittwoch 19 November 2008 1015 10

Co

ntentsContents

1 Identifying the instrument version 42 Installation 63 Electrical connection 74 Operation 12

41 Displays and keys 1242 Principle of operation 1343 Operation of the timer function 15

5 Functions 1651 Process value input 1752 Logic input 1853 Controller 1954 Limit comparator (alarm contact) 2155 Ramp function 2256 Self-optimization 2357 Level inhibit via code 2458 Timer function (extra code) 25

6 Configuration and parameter tables 317 Alarm messages 378 Technical data 39

b702040enbk Seite 3 Mittwoch 19 November 2008 1015 10

1 Identifying

the instrument versio

n

4

1 Identifying the instrument version

arameter level

96 x 48 (landscape) 44 = 96 x 96

2

Type 7020424344

relay (no make)

putlogic 05V

relay (no make)

Type 7020424344

putlogic 012V

ailable)not possible

b702040enbk Seite 4 Mittwoch 19 November 2008 1015 10

1 single-setpoint controller with limit comparator see factory settings under configuration and p2 see customerrsquos ordering text or settings under configuration and parameter level

(1) (2) (3) (4) (5) (6)

7020 ndash ndash ndash

(1) Basic type(bezel in mm)

40 = 48 x 24 41 = 48 x 48 42 = 48 x 96 (portrait) 43 =

(2) Basic typeextension

88 =99 =

controller type configurable1

controller type configured to customer specification

(3) Inputs 888 =999 =

inputs configurable1

inputs configured to customer specification2

(4) Outputs 000 = Standard Type 70204041

Output 1 relay (no make)

Output 2 logic 05V optionallyconfigurable als logic in

Output 3 (not available)

Options Type 70204041

113 = Output 2(outputs 1+3 as forStandard)

logic 012V optionallyconfigurable als logic in

101 = Output 2(output 1 as for Standard)

relay (no make)(logic input is always av

1 Identifying

the instrument versio

n

5

1

(5

(6

D Type 7020424344

2 mounting brackets

tions 702040

b702040enbk Seite 5 Mittwoch 19 November 2008 1015 10

The linearizations for KTY11-6 and thermocouple B have been deleted

) Supply 16 =22 =23 =

10mdash18V DC20mdash53V ACDC 48mdash63Hz

110mdash240V -15+10 AC 48mdash 63Hz

) Extra code 210 =220 =

Timer functionTimer function + limit switch1

elivery package Type 70204041

1 mounting frame

1 seal 1 Operating instruc

2 Installation

6

2 Installation

-edge-mountingings of panel cut-outs)

verticalgt 8mmgt 8mmgt 10mmgt 10mmgt 10mm

on mounting bracketsen screws

b702040enbk Seite 6 Mittwoch 19 November 2008 1015 10

Type (bezel) Panel cut-out (WxH) in mm

Edge-to(minimum spac

horizontal702040 (48mm x 24mm) 45+06 x 222+03 gt 8mm702041 (48mm x 48mm) 45+06 x 45+06 gt 8mm702042 (48mm x 96mm) 45+06 x 92+08 gt 10mm702043 (96mm x 48mm) 92+08 x 45+06 gt 10mm702044 (96mm x 96mm) 92+08 x 92+08 gt 10mm

1 Push on seal2 Insert instrument

3 Push4 Tight

Installation 702042as 702044

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 2: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

Please read these Operating Instructions carefully before starting up the instrument Keepthese operating instructions in a place which is at all times accessible to all users Pleaseassist us to improve these operating instructions where necessary Your suggestions will bemost welcome

Phone in Germany (0661) 6003-727from abroad (+49) 661 6003-0

Fax in Germany (0661) 6003-508abroad (+49) 661 6003-607

All necessary settings are described in these operating instructions However if any difficul-ties should still arise during start-up you are asked not to carry out any unauthorized ma-nipulations on the unit You could endanger you rights under the instrument warrantyPlease contact the nearest subsidiary or the main factory in such a case

EWhen returning chassis assemblies or components the regulations of EN 100 015 ldquoProtec-tion of electrostatically sensitive componentsrdquo must be observed Use only the appropriateESD packaging for transport

Please note that we cannot accept any liability for damage caused by ESD (electrostatic dis-charge)

b702040enbk Seite 2 Mittwoch 19 November 2008 1015 10

Co

ntentsContents

1 Identifying the instrument version 42 Installation 63 Electrical connection 74 Operation 12

41 Displays and keys 1242 Principle of operation 1343 Operation of the timer function 15

5 Functions 1651 Process value input 1752 Logic input 1853 Controller 1954 Limit comparator (alarm contact) 2155 Ramp function 2256 Self-optimization 2357 Level inhibit via code 2458 Timer function (extra code) 25

6 Configuration and parameter tables 317 Alarm messages 378 Technical data 39

b702040enbk Seite 3 Mittwoch 19 November 2008 1015 10

1 Identifying

the instrument versio

n

4

1 Identifying the instrument version

arameter level

96 x 48 (landscape) 44 = 96 x 96

2

Type 7020424344

relay (no make)

putlogic 05V

relay (no make)

Type 7020424344

putlogic 012V

ailable)not possible

b702040enbk Seite 4 Mittwoch 19 November 2008 1015 10

1 single-setpoint controller with limit comparator see factory settings under configuration and p2 see customerrsquos ordering text or settings under configuration and parameter level

(1) (2) (3) (4) (5) (6)

7020 ndash ndash ndash

(1) Basic type(bezel in mm)

40 = 48 x 24 41 = 48 x 48 42 = 48 x 96 (portrait) 43 =

(2) Basic typeextension

88 =99 =

controller type configurable1

controller type configured to customer specification

(3) Inputs 888 =999 =

inputs configurable1

inputs configured to customer specification2

(4) Outputs 000 = Standard Type 70204041

Output 1 relay (no make)

Output 2 logic 05V optionallyconfigurable als logic in

Output 3 (not available)

Options Type 70204041

113 = Output 2(outputs 1+3 as forStandard)

logic 012V optionallyconfigurable als logic in

101 = Output 2(output 1 as for Standard)

relay (no make)(logic input is always av

1 Identifying

the instrument versio

n

5

1

(5

(6

D Type 7020424344

2 mounting brackets

tions 702040

b702040enbk Seite 5 Mittwoch 19 November 2008 1015 10

The linearizations for KTY11-6 and thermocouple B have been deleted

) Supply 16 =22 =23 =

10mdash18V DC20mdash53V ACDC 48mdash63Hz

110mdash240V -15+10 AC 48mdash 63Hz

) Extra code 210 =220 =

Timer functionTimer function + limit switch1

elivery package Type 70204041

1 mounting frame

1 seal 1 Operating instruc

2 Installation

6

2 Installation

-edge-mountingings of panel cut-outs)

verticalgt 8mmgt 8mmgt 10mmgt 10mmgt 10mm

on mounting bracketsen screws

b702040enbk Seite 6 Mittwoch 19 November 2008 1015 10

Type (bezel) Panel cut-out (WxH) in mm

Edge-to(minimum spac

horizontal702040 (48mm x 24mm) 45+06 x 222+03 gt 8mm702041 (48mm x 48mm) 45+06 x 45+06 gt 8mm702042 (48mm x 96mm) 45+06 x 92+08 gt 10mm702043 (96mm x 48mm) 92+08 x 45+06 gt 10mm702044 (96mm x 96mm) 92+08 x 92+08 gt 10mm

1 Push on seal2 Insert instrument

3 Push4 Tight

Installation 702042as 702044

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 3: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

Co

ntentsContents

1 Identifying the instrument version 42 Installation 63 Electrical connection 74 Operation 12

41 Displays and keys 1242 Principle of operation 1343 Operation of the timer function 15

5 Functions 1651 Process value input 1752 Logic input 1853 Controller 1954 Limit comparator (alarm contact) 2155 Ramp function 2256 Self-optimization 2357 Level inhibit via code 2458 Timer function (extra code) 25

6 Configuration and parameter tables 317 Alarm messages 378 Technical data 39

b702040enbk Seite 3 Mittwoch 19 November 2008 1015 10

1 Identifying

the instrument versio

n

4

1 Identifying the instrument version

arameter level

96 x 48 (landscape) 44 = 96 x 96

2

Type 7020424344

relay (no make)

putlogic 05V

relay (no make)

Type 7020424344

putlogic 012V

ailable)not possible

b702040enbk Seite 4 Mittwoch 19 November 2008 1015 10

1 single-setpoint controller with limit comparator see factory settings under configuration and p2 see customerrsquos ordering text or settings under configuration and parameter level

(1) (2) (3) (4) (5) (6)

7020 ndash ndash ndash

(1) Basic type(bezel in mm)

40 = 48 x 24 41 = 48 x 48 42 = 48 x 96 (portrait) 43 =

(2) Basic typeextension

88 =99 =

controller type configurable1

controller type configured to customer specification

(3) Inputs 888 =999 =

inputs configurable1

inputs configured to customer specification2

(4) Outputs 000 = Standard Type 70204041

Output 1 relay (no make)

Output 2 logic 05V optionallyconfigurable als logic in

Output 3 (not available)

Options Type 70204041

113 = Output 2(outputs 1+3 as forStandard)

logic 012V optionallyconfigurable als logic in

101 = Output 2(output 1 as for Standard)

relay (no make)(logic input is always av

1 Identifying

the instrument versio

n

5

1

(5

(6

D Type 7020424344

2 mounting brackets

tions 702040

b702040enbk Seite 5 Mittwoch 19 November 2008 1015 10

The linearizations for KTY11-6 and thermocouple B have been deleted

) Supply 16 =22 =23 =

10mdash18V DC20mdash53V ACDC 48mdash63Hz

110mdash240V -15+10 AC 48mdash 63Hz

) Extra code 210 =220 =

Timer functionTimer function + limit switch1

elivery package Type 70204041

1 mounting frame

1 seal 1 Operating instruc

2 Installation

6

2 Installation

-edge-mountingings of panel cut-outs)

verticalgt 8mmgt 8mmgt 10mmgt 10mmgt 10mm

on mounting bracketsen screws

b702040enbk Seite 6 Mittwoch 19 November 2008 1015 10

Type (bezel) Panel cut-out (WxH) in mm

Edge-to(minimum spac

horizontal702040 (48mm x 24mm) 45+06 x 222+03 gt 8mm702041 (48mm x 48mm) 45+06 x 45+06 gt 8mm702042 (48mm x 96mm) 45+06 x 92+08 gt 10mm702043 (96mm x 48mm) 92+08 x 45+06 gt 10mm702044 (96mm x 96mm) 92+08 x 92+08 gt 10mm

1 Push on seal2 Insert instrument

3 Push4 Tight

Installation 702042as 702044

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 4: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

1 Identifying

the instrument versio

n

4

1 Identifying the instrument version

arameter level

96 x 48 (landscape) 44 = 96 x 96

2

Type 7020424344

relay (no make)

putlogic 05V

relay (no make)

Type 7020424344

putlogic 012V

ailable)not possible

b702040enbk Seite 4 Mittwoch 19 November 2008 1015 10

1 single-setpoint controller with limit comparator see factory settings under configuration and p2 see customerrsquos ordering text or settings under configuration and parameter level

(1) (2) (3) (4) (5) (6)

7020 ndash ndash ndash

(1) Basic type(bezel in mm)

40 = 48 x 24 41 = 48 x 48 42 = 48 x 96 (portrait) 43 =

(2) Basic typeextension

88 =99 =

controller type configurable1

controller type configured to customer specification

(3) Inputs 888 =999 =

inputs configurable1

inputs configured to customer specification2

(4) Outputs 000 = Standard Type 70204041

Output 1 relay (no make)

Output 2 logic 05V optionallyconfigurable als logic in

Output 3 (not available)

Options Type 70204041

113 = Output 2(outputs 1+3 as forStandard)

logic 012V optionallyconfigurable als logic in

101 = Output 2(output 1 as for Standard)

relay (no make)(logic input is always av

1 Identifying

the instrument versio

n

5

1

(5

(6

D Type 7020424344

2 mounting brackets

tions 702040

b702040enbk Seite 5 Mittwoch 19 November 2008 1015 10

The linearizations for KTY11-6 and thermocouple B have been deleted

) Supply 16 =22 =23 =

10mdash18V DC20mdash53V ACDC 48mdash63Hz

110mdash240V -15+10 AC 48mdash 63Hz

) Extra code 210 =220 =

Timer functionTimer function + limit switch1

elivery package Type 70204041

1 mounting frame

1 seal 1 Operating instruc

2 Installation

6

2 Installation

-edge-mountingings of panel cut-outs)

verticalgt 8mmgt 8mmgt 10mmgt 10mmgt 10mm

on mounting bracketsen screws

b702040enbk Seite 6 Mittwoch 19 November 2008 1015 10

Type (bezel) Panel cut-out (WxH) in mm

Edge-to(minimum spac

horizontal702040 (48mm x 24mm) 45+06 x 222+03 gt 8mm702041 (48mm x 48mm) 45+06 x 45+06 gt 8mm702042 (48mm x 96mm) 45+06 x 92+08 gt 10mm702043 (96mm x 48mm) 92+08 x 45+06 gt 10mm702044 (96mm x 96mm) 92+08 x 92+08 gt 10mm

1 Push on seal2 Insert instrument

3 Push4 Tight

Installation 702042as 702044

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 5: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

1 Identifying

the instrument versio

n

5

1

(5

(6

D Type 7020424344

2 mounting brackets

tions 702040

b702040enbk Seite 5 Mittwoch 19 November 2008 1015 10

The linearizations for KTY11-6 and thermocouple B have been deleted

) Supply 16 =22 =23 =

10mdash18V DC20mdash53V ACDC 48mdash63Hz

110mdash240V -15+10 AC 48mdash 63Hz

) Extra code 210 =220 =

Timer functionTimer function + limit switch1

elivery package Type 70204041

1 mounting frame

1 seal 1 Operating instruc

2 Installation

6

2 Installation

-edge-mountingings of panel cut-outs)

verticalgt 8mmgt 8mmgt 10mmgt 10mmgt 10mm

on mounting bracketsen screws

b702040enbk Seite 6 Mittwoch 19 November 2008 1015 10

Type (bezel) Panel cut-out (WxH) in mm

Edge-to(minimum spac

horizontal702040 (48mm x 24mm) 45+06 x 222+03 gt 8mm702041 (48mm x 48mm) 45+06 x 45+06 gt 8mm702042 (48mm x 96mm) 45+06 x 92+08 gt 10mm702043 (96mm x 48mm) 92+08 x 45+06 gt 10mm702044 (96mm x 96mm) 92+08 x 92+08 gt 10mm

1 Push on seal2 Insert instrument

3 Push4 Tight

Installation 702042as 702044

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 6: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

2 Installation

6

2 Installation

-edge-mountingings of panel cut-outs)

verticalgt 8mmgt 8mmgt 10mmgt 10mmgt 10mm

on mounting bracketsen screws

b702040enbk Seite 6 Mittwoch 19 November 2008 1015 10

Type (bezel) Panel cut-out (WxH) in mm

Edge-to(minimum spac

horizontal702040 (48mm x 24mm) 45+06 x 222+03 gt 8mm702041 (48mm x 48mm) 45+06 x 45+06 gt 8mm702042 (48mm x 96mm) 45+06 x 92+08 gt 10mm702043 (96mm x 48mm) 92+08 x 45+06 gt 10mm702044 (96mm x 96mm) 92+08 x 92+08 gt 10mm

1 Push on seal2 Insert instrument

3 Push4 Tight

Installation 702042as 702044

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 7: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

3 Electrical co

nnection

7

3

In

- nnection must conform to wer Circuits with nominal

- onnel

- t it must be isolated on

- f a short-circuit The load ent welding of the output

- ations listed under

- ch other

- instrument

-

- damage to controlled of parameter and

b702040enbk Seite 7 Mittwoch 19 November 2008 1015 10

Electrical connection

stallation notes

The choice of cable the installation the fusing and the electrical cothe requirements of VDE 0100 ldquoRegulations on the Installation of Povoltages below 1000Vrdquo or the appropriate local regulations

The electrical connection must only be carried out by qualified pers

If contact with live parts is possible when working on the instrumenboth poles from the supply

A current limiting resistor interrupts the supply circuit in the event ocircuit must be fused for the maximum relay current in order to prevrelay contacts in the event of an external short-circuit

Electromagnetic compatibility conforms to the standards and regulTechnical Data

Run input output and supply lines separately and not parallel to ea

Do not connect any additional loads to the supply terminals of the

The instrument is not suitable for installation in hazardous areas

Apart from faulty installation there is a possibility of interference orprocesses due to incorrect settings on the controller (setpoint data

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 8: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

3 Electrical co

nnection

8

configuration levels internal adjustments) Safety devices independent of the controller such as overpressure valves or temperature

pable of adjustment only by

tion Since auto-tuning (self-loops there is a theoretical value should therefore be

etwork must be laid out as ower cables or components) strument side

b702040enbk Seite 8 Mittwoch 19 November 2008 1015 10

limitersmonitors should always be provided and should be caspecialist personnel Please refer to the appropriate safety regulations in this connecoptimization) cannot be expected to handle all possible control possibility of unstable parameter settings The resulting processmonitored for its stability

- All input and output lines that are not connected to the supply nshielded and twisted cables (do not run them in the vicinity of pThe shielding must be grounded to the earth potential on the in

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 9: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

3 Electrical co

nnection

9

20mdash53V

10mdash18V

ACDC

DC

AC

110mdash240V

(configurable)

ut 1

3A

+

+

ndash

ndash

N L19

2

=

Supplysee label

al con-st only out by rsonnel

T

b702040enbk Seite 9 Mittwoch 19 November 2008 1015 10

5V(12V)20mA

1 Output or logic input 2 resistive load

Outp

250V

Logic input

Process value input

+

+ndash+ ndash

ndash

8654321

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

Output 21

Logic output Relay

+ ndash floating contact

1

VThe electricnection mube carried qualified pe

ype 70204041

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 10: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

3 Electrical co

nnection

10

20mdash53V

ACDC

AC

110mdash240V

1

+ndash

N L198

Outputs

50 V3 A Supplysee label

10mdash18V

DC

+ndash

=l connection

e carried out personnel

Type 70204041 with

b702040enbk Seite 10 Mittwoch 19 November 2008 1015 10

2

Logic input

Process value input

-+

+ ndash

54321

Current04mdash20 mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage002mdash1 V

Relay 2

+ ndash

7

VThe electricamust only bby qualified

2 relay outputs (option)

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 11: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

3 Electrical co

nnection

11

20mdash53V

AC

110mdash240V

ut 3

3A

+ndash

13 N L1

2

y

2 resistive load

ACDC

10mdash18V

DC

+ndash

=

Supplysee label

T

st ed

b702040enbk Seite 11 Mittwoch 19 November 2008 1015 10

Output 2

5V(12V)20mA

Current04mdash20mA

Pt1001000KTY11-6(2-wire)

Pt1001000(3-wire)

Thermocouple

Voltage02mdash10V

OutpOutput 1

250V3A 250V

Logic input

Process value input+

+ndash

+ ndash

ndash

121097654321

floating contact

2Logic output Relay Rela

+ ndash

ype 7020424344

VThe electrical connection muonly be carried out by qualifipersonnel

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 12: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

4 Op

eration

12

4 Operation

wheners and and

10mm20mm

it

e display)

utputs 1 and 2 yellow

rogramming the instrumention of settings and parameterswith i with dceptance after 2 seconds

b702040enbk Seite 12 Mittwoch 19 November 2008 1015 10

41 Displays and keys

(1) Display

7-segment display 4 places greenDisplay alternates setpoints parametcodes are entered indicated

Character height Type 7020404142Type 70204344

Display range -1999 to +9999 dig

Decimal places none one two

Unit degC degF (process valu

(2) Status indicators

LED two LEDs for the o

(3) Keys

q i d for operating and pDynamic modificath Increase value

h Decrease value

Automatic value ac

Example Type 702041

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 13: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

4 Op

eration

13

4NT

OT input SP 1 or SP 2 ap-p nt SPr is displayed Withac 0 is shownT ing will be accepted auto-m

PT meters and the ramp slo-p

CT

e configuration level ATT e timer start value are al-te in the display

TIf splay after approx 30 sec(e is displayed) If the timerva

b702040enbk Seite 13 Mittwoch 19 November 2008 1015 10

2 Principle of operationormal displayhe display shows the process value

perating levelhe setpoint SP is input here On active setpoint switching via the logicears in the display When the ramp function is active the ramp setpoitivated timer function the timer value t i or the timer start value t i

he setpoint is altered dynamically using the i and d keys The settatically after approx 2 sec

arameter levelhe setpoints the limit value of the limit comparator the controller parae are programmed here

onfiguration levelhe basic functions of the controller are set here

In order to make the settings it is necessary to change to thvia the parameter y0 (parameter level)

imer levelhe current timer value (only when the timer has been started) and thred here The parameters at this level are marked with an underscore

ime-out no operation occurs the controller returns automatically to normal dixception with timer functions starting via power ON the timer valuelue is displayed at the operating level time-out is not active

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 14: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

4 Op

eration

14

Parameter level

uration level

level (timer stopped)

C111

Pb1t 1+2lue for

omparatorller parameterslope

rentlueen timer hasrted)

rt value

ti

ti0

ration codesrd signal scalings value correctionng differentialcomparator

gt 2s

Normal display Operating level

after lastparameter via y0

Y0

A

re to differentiate operating level

b702040enbk Seite 14 Mittwoch 19 November 2008 1015 10

Process value

Config

Timer

259

- setpoin- limit va

limit c- contro- ramp s

Setpoint

(with setpointswitching

or )SP 1 SP 2

alter curtimer va(only whbeen sta

setaltertimer sta

only displayed if function is configured

Ramp setpoint(display only)

Timer value(operating onlydifferent displaydepending ontimer condition (see table))

SP

SPr

ti

- configu- standa- proces- switchi

of limit

q d+

gt 2s

gt 2s

Time-out(30s)

Time-out

or

after lastparameter

i i d +

Underscoand timer

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 15: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

4 Op

eration

15

4T dge) if the timer at opera-tin is configured accordinglyth n also be operated even ifth

P l

D ateActioner has stoppedContinue with iCancel with i + d

er has run downAcknowledge with any key(timer start value t i 0 is indicated)With time-delayed control (C120=3) acknowledge with i + d

W imer value will blink

b702040enbk Seite 15 Mittwoch 19 November 2008 1015 10

3 Operation of the timer functionhe timer can be operated with the keys (start stop cancel acknowleg level is indicated Time-out is not active here If the logic input en a key such as the i key can be used In this case the timer cae timer value does not appear in the display

ossible displayed parameters for timer function at operating leve

isplay StateAction Display StTimer not runningh Start with i

Timh

h

Timer has been started but the tolerance limit has not yet been reachedh Cancel with i + d

Timh

Timer running t i is displayedh Stop with ih Cancel with i + d

hen the timer has been started the decimal point in the display for the t

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 16: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

16

5 Functions

tables provided for this pur-mark selection with a cross in the order of theirt (see table below)

t

for ParameterPb2 Cy 2 db HyS2

111

C114 HySt ALC117

HySt AL

11 C117

SCL SCH

rASd SPrel SP 1 SP 2

ti C121 C122 C123

C118

b702040enbk Seite 16 Mittwoch 19 November 2008 1015 10

We recommend the following procedure

1 not for Type 70204041 with 2 relay outputs (option)

h Familiarize yourself with the controller functions

h Enter the configuration codes and the parameter values in the pose in Chapter 6 Write down the appropriate values ( ) or ( ) The parameters and the configuration codes are listed appearance Parameters which are not relevant are masked ou

h Enter the configuration code and parameters on the instrumen

Configuration Masking out the parametersSingle-setpoint controller Double-setpoint controller

Double-setpoint controller Limit comp for Type 7020404Logic input for Type 7020404

Limit comparator no function Limit comparator

Limit comparator activated Logic input for Type 7020404

Resistance thermometer thermocouple Standard signal scaling

Ramp function off Ramp function

Setpoint switching not activated Setpoints at the parameter lev

Timer function no function Timer function

Type 70204041 Output 3

X

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 17: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

17

5

S

C

C e 31

S

S

Oected by a programmable

cuit through process value

d c = filter off) vpage 36

nges in the process value

b702040enbk Seite 17 Mittwoch 19 November 2008 1015 10

1 Process value input

ymbol Notes

111 Transducerprobe (process value input) vpage 31

112 Unit of process value (degCdegF)decimal places of display vpag

CL Startend value of value range for standard signals vpage 35Example 0mdash20 mArarr20mdash200degC SCL = 20 SCH = 200

CH

FFS Process value correction vpage 35Using the process value correction a measured value can be corramount upwards or downwards (offset)Lead compensation can be implemented in software for 2-wire circorrection

ExamplesMeasured value Offset Displayed value 2947 + 03 2950 2953 - 03 2950

F Filter time constant (damping) to adapt the digital input filter (0seif dF high - high damping of interference signals

- slow reaction of the process value display to cha- low cut-off frequency (2nd order low-pass filter)

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 18: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

18

52 Logic input

tion from keys

ss to the parameter andtion levels

self-optimization is not possible

opped

SP 2 is active

are displayed at the operating

(edge-triggered)

ut 2 has been programmed as igured (C114) (double assign-

b702040enbk Seite 18 Mittwoch 19 November 2008 1015 10

Key inhibit Operation is possible from keys No opera

Level inhibit Access to the parameter andconfiguration levels is possibleStarting self-optimization is possible

No acceconfiguraStarting

Ramp stop Ramp running Ramp st

Setpoint switching Setpoint SP 1 is active Setpoint

The appropriate symbols SP 1 and SP 2level

Timer control Acknowledge startstopcontinuetimer run-down

Symbol Notes

C117 Function of the logic input vpage 33On Type 70204041 the parameter C117 is masked out if outpcontroller output (C113) or the limit comparator has been confment not on Type 70204041 with 2 relay outputs (option))

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 19: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

19

5CTE

S

C physical

Cf overunderrange probe

C(controller type as C113)

P

ucture is not effectiveP

d no D action

ro I action

C

process is virtuallyive wear C

b702040enbk Seite 19 Mittwoch 19 November 2008 1015 10

3 Controllerontroller structurehe controller structure is defined via the parameters Pb dt and rtxample Setting for PI controller rarr Pb 1=120 dt=0sec rt=350sec

ymbol Notes

113 Controller type and assignment of the controller outputs to theoutputs 1+2 vpage 32

116 Outputs in fault condition vpage 33The switching states of the outputs are defined here in the event obreakshort circuit or display overflowv Chapter 7

118 Assignment of the outputs vpage 33Only for Type 7020424344 overwrites the assignment of C113

b1 Proportional band 1 (controller output 1) vpage 36Proportional band 2 (controller output 2)Influences the P action of the controller If Pb=0 the controller strb2

t Derivative time vpage 36Influences the D action of the controller If dt=0 the controller has

t Reset time vpage 36Influences the I action of the controller If rt=0 the controller has n

y 1 Cycle time 1 (controller output 1) vpage 36Cycle time 2 (controller output 2)The cycle time has to be selected so that the energy supply to thecontinuous while not subjecting the switching elements to excessy 2

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 20: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

20

Contact spacing vpage 36

Symbol Notes

Pb2=0) it is necessary

b702040enbk Seite 20 Mittwoch 19 November 2008 1015 10

dbfor double-setpoint controller

HYS1 Differential 1 (controller output 1) vpage 36Differential 2 (controller output 2)for controllers with Pb1=0 or Pb2=0HYS2

Y0 Working point (basic load) vpage 36Output if process value=setpoint

Y1 Output limiting vpage 36y1 - maximum outputy2 - minimum outputY2

H For controllers without controller structure (Pb1=0 or that y1=100 and y2=-100

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 21: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

21

5

S

C

H

A

lk

lk

lk

6 Monitoring referredto the setpoint

8 Monitoring referredto a fixed value AL

tpoint x = process value

On

On

b702040enbk Seite 21 Mittwoch 19 November 2008 1015 10

4 Limit comparator (alarm contact)

ymbol Notes

114 Limit comparator function (lk1mdash lk8) vpage 32

yst Differential of limit comparator vpage 35

L Limit value of limit comparator vpage 36

lk2 lk3

4 lk5 lk6

7 lk8

1

lk1mdashlk

lk7 lk

w = se

On On

On On

On On

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 22: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

22

55 Ramp function

t

b702040enbk Seite 22 Mittwoch 19 November 2008 1015 10

Symbol Note

C115 Ramp function (onoff time unit) vpage 32

C117 Ramp stop via logic input (floating contact) vpage 33

rAsd Ramp slope in degCh or degCmin vpage 36

t1

SP1

SP2

t2 t3 t4 t5 t6

t1 power ON (SP 1 active)t2mdash t3 power failure or overrangeunderranget4mdasht5 ramp stopt6 setpoint switching to SP 2

ramp setpoint SPrprocess value

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 23: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

23

5S D or PI controllers

T 1 Cy 2 dF

T ontrol deviation

S

Sce

H

a tart

xw

260tunE

gt2s

d

b702040enbk Seite 23 Mittwoch 19 November 2008 1015 10

6 Self-optimizationelf-optimization determines the optimum controller parameters for PI

he following controller parameters are defined rt dt Pb1 Pb2 Cy

he controller selects procedure a or b depending on the size of the c

tarting self-optimization

elf-optimization is automatically terminated or can be can-lled

Starting self-optimization is not possible with activelevel inhibit and ramp function

) Self-optimizationin theapproach phase

b) Self-optimi-zationat set-point

Start S

= process value = setpoint

Switchinglevel

i +d

i+

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 24: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

24

57 Level inhibit via code

ration levels (corresponds to

l Timer level

enabled

enabled

enabled

inhibited2

b702040enbk Seite 24 Mittwoch 19 November 2008 1015 10

As an alternative to the logic input the level inhibit can beset via a code (logic input has priority)

h Set the code using q + d (at least 5sec) innormal display

Level inhibit via the logic input will lock the parameter and configucode 011)

1 The values at the operating level can only be indicated but not modified2 Timer operation (startstopcontinuecancel) will continue to be possible

Code Operating level Parameter level Configuration leve

000 enabled enabled enabled

001 enabled enabled inhibited

011 enabled inhibited inhibited

111 inhibited1 inhibited inhibited

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 25: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

25

5U ns of the adjustable timet key or via the logic inputth ter the process value hasg er has run down severalev int switching Furthermo-re

pointcess valuegrammed setpointer start valueer signallinge C122=1)ement key

E

b702040enbk Seite 25 Mittwoch 19 November 2008 1015 10

8 Timer function (extra code)sing the timer function the control action can be influenced by meai 0 After the timer has been started by power ON by pressing the e timer start value t i 0 is counted down to 0 either instantly or af

one above or below a programmable tolerance limit When the timents are triggered such as control switch-off (output 0) and setpo it is possible to implement timer signalling via an output

w - setx - proS P - prot i 0 - tim----- - tim

(heri - incr

xample

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 26: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

26

Notes on the timer function in conjunction with the ramp function

function

oint is approached with the ithout ramp

p end value) is monitored

xception here is the timer figured setpoint switching via

except for events that are r value will be shown in the

b702040enbk Seite 26 Mittwoch 19 November 2008 1015 10

- Generally the setpoints can also be approached using the ramp

- Stopping the timer does not influence the ramp function

- If control is active after the timer has run down the current setpramp Cancellation of the timer is followed by a setpoint step w

- For timer functions with a tolerance limit only the setpoint (=ram

Note on setpoint switching via the logic input

- Setpoint switching via the logic input is generally possible An efunction ldquoTime-dependent setpoint switchingrdquo In this case conthe logic input will not be active

Note on the display status in the event of a power failure

- The state of the display before the power failure will be restoredrelated to the timer (start cancel continue stop) Then the timedisplay

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 27: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

27

S

CC as run down (output 0)

C unction the process is con-automatically switches over

Diagrams with andwithout start abovetolerance limit

---- Tolerance limit

C121=3 4 7 or 8

b702040enbk Seite 27 Mittwoch 19 November 2008 1015 10

ymbol Notes

120120=1

Timer function vpage 34

Time-limited control The control is switched off after the timer h

120=2 Time-dependent setpoint switching After the start of the timer ftrolled to setpoint SP2 After the timer has run down the controller to SP1

C121=3 4 7 or 8C121=1 2 5 or 6

C121=2 or 6 C121=1 or 5

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 28: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

28

Time-delayed control The control action starts after the timer has run down

own to 0 The control action is e signalled via an output

Symbol Notes

er has run down (End) theys are used for acknowledge-

0s

C122=1

b702040enbk Seite 28 Mittwoch 19 November 2008 1015 10

C120C120=3

C120=4 Timer After the start of the timer function t i 0 is counted dindependent of the timer Here too the timer run-down can b

H After the timi + d kementSet ti0 gt

C121=1 2 5 or 6

C121=1 2 5 or 6

Timer signallingC122=3

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 29: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

29

Clowing events

keyslogic input)e

ow the tolerance limit the

restored or thehe power failure the timer 121=1 or 5 of a power failure

Ce run-down a signal can be

C

S

b702040enbk Seite 29 Mittwoch 19 November 2008 1015 10

121 Start condition of the timer vpage 34The timer start value t i 0 is counted down as selected in the fol1 Power ON or logic inputkeys2 Start via keyslogic input3 Process value has reached tolerance limit (1degC or 5degC) (start via The position of the tolerance limit depends on the controller typ - 1-setpoint controller (direct) tolerance limit above setpoint - 1-setpoint controller (reversed) tolerance limit below setpoint - 2-setpoint controller tolerance limit below setpoint If during the control process the process value goes abovebel timer will be stopped for the duration of the infringement

Response to a power failure vpage 34After a power failure the condition before the power failure can betimer function can be cancelled If the timer had run down before tstart value will be loaded The timer will start automatically when CThe timer value is saved at one minute intervals to cover the case

122 Timer signalling vpage 35From the start of the timer function until timer run-down or after thproduced via an output

123 Time unit for the timer vpage 35

ymbol Notes

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 30: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

5 Functions

30

Programming example

s to be controlled for 30 min-the event of a power failure

llation on power failure

b702040enbk Seite 30 Mittwoch 19 November 2008 1015 10

After the start via the logic input or from the keys the process hautes to a setpoint of 80degC The control action is to be cancelled in

Configuration

- C111mdash C116 Controller programming

- C117=5 Logic input = timer control

- C120=1 Timer function = time-limited control

- C121=6 Start condition for timer = via logic inputkeys - cance

- C122=0 Timer signalling = no function

- C123=1 Time unit (timer) = mmss

Operation

h Enter the setpoint SP (80degC)

h Press the q key until t i0 is indicated

h Change over to the timer level using q (at least 2sec)

h Enter the timer start value t i0_ (3000)

h Return to the operating level (timer value) with q

h Start the control action via the logic input or with i

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 31: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

6 Co

nfiguratio

n and p

arameter tab

les

31

6

lacesunit X

q

P

your selection with a

123

NO

b702040enbk Seite 31 Mittwoch 19 November 2008 1015 10

Configuration and parameter tables

C111 Transducer X

001 Pt 100 (3-wire)006 Pt 1000 (3-wire)601 KTY11-6 (2-wire)003 Pt 100 (2-wire)005 Pt 1000 (2-wire)039 Cu-Con T 040 Fe-Con J041 Cu-Con U042 Fe-Con L043 NiCr-Ni K044 Pt10Rh-Pt S045 Pt13Rh-Pt R046 Pt30Rh-Pt B048 NiCrSi-NiSi N052 Standard signal 0 ndash 20mA053 Standard signal 4 ndash 20mA063 Standard signal 0 ndash 10V2

071 Standard signal 2 ndash 10V3

C112 Decimal p

0 9999degC1 9999degC2 9999degC3 9999degF4 9999degF5 9999degF

q

q

b11

gt2s

q

y0

qgt2s

X Mark cross

SP 1 AL or Pb1 is shown here depending on the configuration

0 ndash 1V for Type 70204041 with 2 relay outputs (option)

02 ndash 1V for Type 70204041 with 2 relay outputs (option)

ormal displayperating level

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 32: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

6 Co

nfiguratio

n and p

arameter tab

les

32

limit comparator (LK) has priorityover the timer signalling

th Type 7020424344 see C118

C113 Controller type Output 1 (relay) Output 2+3 (logic+relay)

X

LKtimer signalling1

LKtimer signalling1

controller output 2

controller

controller

controller output 1

mp function Xp function offp function (degCmin)p function (degCh)

q

ow setpoint) = controller output 1 setpoint) = controller output 2

b702040enbk Seite 32 Mittwoch 19 November 2008 1015 10

1 A programmed

Further settings for the outputs wi

10 single setpoint (reversed) controller11 single setpoint (direct) controller30 double setpoint controller output 1

20 single setpoint (reversed) LKtimer signalling1

21 single setpoint (direct) LKtimer signalling1

33 double setpoint controller output 2

q

C114 Limit comparator (LK) X

0 no function1 lk 12 lk 23 lk 34 lk 45 lk 56 lk 67 lk 78 lk 8

C115 Ra0 ram1 ram2 ram

q

reversed = heating (output is active when process value is beldirect = cooling (output is active when process value is above

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 33: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

6 Co

nfiguratio

n and p

arameter tab

les

33

input X

ctionibithibittopt switchingontrol

qut 3 Relay X

r signalling comparatorr signallingroller output comparatorroller output

comparatortimerroller output 2 comparatortimerroller output 1roller output 2roller output 1

b702040enbk Seite 33 Mittwoch 19 November 2008 1015 10

C116 Outputs on fault X

0 01 LKtimer signalling OFF1 1002

2 -1001 3 01 LKtimer

signalling ON4 1002

C117 Logic

0 no fun1 key inh2 level in3 ramp s4 setpoin5 timer c

C118 Output 1 Relay (K1) Output 2 Logic (K2) Outp

0 Functions of outputs as defined under C1131

for 1

-set

pt c

ontr

l controller output limit comparator time2 controller output timer signalling limit3 limit comparator controller output time4 limit comparator timer signalling cont5 timer signalling controller output limit6 timer signalling limit comparator cont

7

for 2

-set

pt c

ontrl

controller output 1 controller output 2 limit8 controller output 1 limit comparatortimer cont9 controller output 2 controller output 1 limit10 controller output 2 limit comparatortimer cont11 limit comparatortimer controller output 1 cont12 limit comparatortimer controller output 2 cont

q

q

1 Minimum output limiting y2 is effective2 Maximum output limiting y1 is effective

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 34: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

6 Co

nfiguratio

n and p

arameter tab

les

34

C120 Timer function X

power failure Xs before there

n ofion ars in the

ot valid for C120=3 or 4

b702040enbk Seite 34 Mittwoch 19 November 2008 1015 10

0 no function1 time-limited control2 time-dependent setpoint switching3 time-delayed control4 timer (control independent of timer)

C121 Start condition for timer Action on 1 after power ON logic inputkeys Condition a

power failu2 via logic inputkeys3 via logic inputkeys timer counts 1degC

from tolerance limit4 via logic inputkeys timer counts 5degC

from tolerance limit5 after power ON logic inputkeys Cancellatio

timer funct(StOP appedisplay)

6 via logic inputkeys7 via logic inputkeys timer counts 1degC

from tolerance limit8 via logic inputkeys timer counts 5degC

from tolerance limit

q

q

The start conditions with tolerance limit (C121=3 4 7 8) are nIf C120 is altered the validity of C121 must be checked

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 35: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

6 Co

nfiguratio

n and p

arameter tab

les

35

tory-set Yoursetting

0

0

0

he factory setting

ime (timer) X

(max 9959)(max 9959)ax 9999)

= minutes

q

b702040enbk Seite 35 Mittwoch 19 November 2008 1015 10

Parameter Explanation Value range fac

SCL start value of thestandard signal

-1999 to +9999digit1 0

sCH end value of thestandard signal

-1999 to +9999digit1 10

SPL lowersetpoint limiting

-1999 to +9999digit1 -20

SPH uppersetpoint limiting

-1999 to +9999digit1 85

OFFS process value correction -1999 to 9999digit1 0

HySt switching differential of the limit comparator

0 mdash 9999digit1 1

1 For displays with one or two decimal places the value range and tchange accordinglyExample 1 decimal place rarr value range -1999 to +9999

q

C122 Timer signalling X

0 no function1 timer start until run-down2 after run-down for 10sec 3 after run-down for 1min4 after run-down until

acknowledgement

qC123 Unit of t

1 mmss 2 hhmm 3 hhhh (ms = seconds m h = hours

One output has to be configuredcorrespondingly(C113C118)

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 36: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

6 Co

nfiguratio

n and p

arameter tab

les

36and the factory setting

Parameter Explanation Value range factory-set

Yoursetting

0

0

0

0

0

80sec

350sec

200sec

200sec

0

1

1

0

100

-100

06sec

0

b702040enbk Seite 36 Mittwoch 19 November 2008 1015 10

1 For displays with one or two decimal places the value range change accordingly

sP 1 setpoint 1 SPL mdash SPH

sP 2 setpoint 2 SPL mdash SPH

AL limit value oflimit comparator

-1999 to +9999digit1

Pb1 proportional band 1 0 mdash 9999digit1

Pb2 proportional band 2 0 mdash 9999digit1

dt derivative time 0 mdash 9999sec

rt reset time 0 mdash 9999sec

Cy 1 cycle time 1 10 mdash 9999sec

Cy 2 cycle time 2 10 mdash 9999sec

db contact spacing 0 mdash 1000digit1

HYS1 differential 1 0 mdash 9999digit1

HYS2 differential 2 0 mdash 9999digit1

Y0 working point -100 to 100

Y1 maximum output 0 mdash 100

Y2 minimum output -100 to +100

dF filter time constant 00 mdash 1000sec

rAsd ramp slope 0 mdash 999 degCh (degCmin)1

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 37: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

7 Alarm

messag

es

37

7

D

of process valueit comparators referred to input behave in accord-figuration of the outputsed

n has been cancelled due to he timer value that wase of the supply failure will be

H ge

is connected

b702040enbk Seite 37 Mittwoch 19 November 2008 1015 10

Alarm messages

isplay Description Causeresponse

The displays for the process value or timer value flashes ldquo1999rdquoDisplay current timer value by repeatedly pressing the q key

OverunderrangeController and limthe process valueance with the conThe timer is stopp

The display for the timer value alternates between showing ldquoStOPrdquo and the timeh Acknowledge by using any

key (the timer start value t i 0 is loaded)

The timer functioa supply failure Tpresent at the timindicated

The following events come under the heading overunderran- Probe breakshort-circuit- Measurement is outside the control range of the probe that- Display overflow

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 38: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

7 Alarm

messag

es

38

Measurement circuit monitoring (bull = recognized)

-circuitProbelead break

bull

bull

bull-

bull-

b702040enbk Seite 38 Mittwoch 19 November 2008 1015 10

Transducer Overrangeunderrange

Probelead short

Thermocouple bullbull -

Resistance thermometer bullbull bull

Voltage 2 ndash 10V and02 ndash 1V0 ndash 10V and 0 ndash 1V

bullbullbull-

bull-

Current 4 ndash 20mA0 ndash 20mA

bullbullbull-

bull-

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 39: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

8 Technical data

39

8In

1

In

23

nce thermometer

3A at 250V AC resistive load at rated load

mA Rload ge250Ω

mA Rload ge600Ω

5+10 48 mdash 63Hz or 48 mdash 63Hz or

nnect to SELV or PELV)

Range

-200 to +850degC

-200 to +850degC

-50 to +150degC

uracy le01 50ppmdegCle10 50ppmdegC

20Ω max per lead250microA

b702040enbk Seite 39 Mittwoch 19 November 2008 1015 10

Technical dataput for thermocouple

These ranges refer to the ambiente temperature of 20degC

put for standard signals

0mdash1V REgt10MΩ for Type 70204041 with 2 relays02mdash1V REgt10MΩ for Type 70204041 with 2 relays

Designation Range 1

Fe-Con LFe-Con J EN 60584Cu-Con UCu-Con T EN 60584NiCr-Ni K EN 60584NiCrSi-NiSi N EN 60584Pt10Rh-Pt S EN 60584Pt13Rh-Pt R EN 60584Pt30Rh-Pt6Rh B EN 60584

-200 to + 900degC-200 to +1200degC-200 to + 600degC-200 to + 400degC-200 to +1372degC-200 to +1300degC

0 mdash 1768degC0 mdash 1768degC0 mdash 1820degC

Measurement accuracy le04 100ppmdegCCold junction Pt100 internal

Designation Range

Voltage 0 mdash 10V RE gt 100kΩ2

2 mdash 10V RE gt 100kΩ3

RE - input resistance

Current 4 mdash 20mA voltage drop le 15V0 mdash 20mA voltage drop le 15V

Measurement accuracy le01 100ppmdegC

Input for resista

OutputsRelayno(make) contact150000 operationsLogic 05VCurrent limiting 20Logic 012VCurrent limiting 20

Supply110 mdash 240V AC -120 mdash 53V ACDC10 mdash 18V DC (Co

Designation

Pt100 EN 60751

Pt1000 EN 60751

KTY11-6

Measurement accPt1001000KTY11-6Sensor leadresistance Meas current

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 40: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

8 Technical data

40

ControllerController type 1-setpt controller with

Data backup EEPROMHousing type

or panel mounting

nt panelater (add mildly acidic neutral

detergents if necessary) Do sive cleaning agents or high-s Limited resistance to organic irits benzol etc)

ng3 834

rage temperatureo +70degC

onsity no condensation

ion any

)160g (702043)200g (702044)

60529

n to EN 61010

b702040enbk Seite 40 Mittwoch 19 November 2008 1015 10

Accuracy of timer 07 10ppmdegC

Test voltages (type test)to EN 61 010 Part 1 March 1994overvoltage category II pollution degree 2 for Type 70204041overvoltage category III pollution degree 2 for Type 7020424344

Power consumption 7VA max

Electrical connectionat the rear via plug-in screw terminalsconductor cross-section le 25mm2 (13mm2 withType 70204041) solid wire or 15mm2 (10mm2 for Type 70204041) stranded wire with ferrules

Electromagnetic compatibility EN 61 326Immunity to interfer Class B Interfer emission industrial requirements

Approval UL and CSA (only devices with JUMO indication)

limit comparator 2-setpt controllerController structure PPDPIPIDAD converter resolution gt15 bitSampling time 210msec (250msec with timer

function)

plastic housing fto DIN 43700Cleaning the frouse warm or hot wor mildly alkalinenot use any abrapressure cleanersolvents (e g sp

Housing mountiin panel to DIN 4

Ambient and sto0 to 55degC -40 t

Climatic conditile 75 rel humid

Operating posit

Weight (approx75g (702040)95g (702041)

145g (702042)Protection IP66 (front) to ENIP20 (rear)Safety regulatio

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data
Page 41: Type 702042 Type 702044 Type 702041 JUMO iTRON · 2013. 9. 30. · JUMO iTRON Compact microprocessor controllers B 70.2040 Operating Instructions 2008-11-11/00357918 Type 702042 Type

JUMO GmbH amp Co KG

Street adressMoltkestraszlige 13 - 3136039 Fulda GermanyDelivery addressMackenrodtstraszlige 1436039 Fulda GermanyPostal address36035 Fulda GermanyPhone +49 661 6003-0Fax +49 661 6003-607e-mail mailjumonetInternet wwwjumonet

JUMO Instrument Co Ltd

JUMO HouseTemple Bank RiverwayHarlow Essex CM20 2TT UKPhone +44 1279 635533Fax +44 1279 635262e-mail salesjumocoukInternet wwwjumocouk

JUMO Process Control Inc

8 Technology BoulevardCanastota NY 13032 USAPhone 315-697-JUMO

1-800-554-JUMOFax 315-697-5867e-mail infojumousInternet wwwjumous

b702040enbk Seite 1 Mittwoch 19 November 2008 1015 10

  • 1 Identifying the instrument version
  • 2 Installation
  • 3 Electrical connection
  • 4 Operation
    • 41 Displays and keys
    • 42 Principle of operation
    • 43 Operation of the timer function
      • 5 Functions
        • 51 Process value input
        • 52 Logic input
        • 53 Controller
        • 54 Limit comparator (alarm contact)
        • 55 Ramp function
        • 56 Self-optimization
        • 57 Level inhibit via code
        • 58 Timer function (extra code)
          • 6 Configuration and parameter tables
          • 7 Alarm messages
          • 8 Technical data