Malachy Walsh and Partners Engineering & Environmental Consultants Cork | Tralee | Limerick | London Tullabeg 110kV Substation Ground Investigation Report Client: H&MV Engineering Ltd, Unit B10, Kingswood Business Park, Clondalkin, Dublin 22 D22 C7XO Project No: Revision: Prepared By: Approved By: Date: 20609-6003 E P. Curran J. O’Leary October 2019
33
Embed
Tullabeg 110kV Substation Ground Investigation Report€¦ · document “Specification for Road Works Series 600 – Earthworks (CC-SPW-00600 March 2013)”. The Glacial Till excavated
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Malachy Walsh and Partners Engineering & Environmental Consultants
Cork | Tralee | Limerick | London
Tullabeg 110kV Substation
Ground Investigation Report
Client: H&MV Engineering Ltd, Unit B10, Kingswood Business Park, Clondalkin, Dublin 22 D22 C7XO
Project No: Revision: Prepared
By:
Approved
By:
Date:
20609-6003 E P. Curran J. O’Leary October
2019
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
3
1 INTRODUCTION
The purpose of this report is to present the ground investigation information obtained at the site of the proposed Tullabeg Substation, Co Wexford. The trial pits were completed on 09.07.2019.
Figure 1-1 Site Location
2 GEOLOGY OF SITE The Geological Survey of Ireland online mapping system shows the bedrock at the site to be part of the Campile Formation which consists of Rhyolitic volcanics, grey & brown slates (See Figure 2-1). The Quaternary Sediments at the site are mapped as Irish Sea Till (“Till derived from Limestone”). Alluvium and “Bedrock at Surface” is also mapped to the north of the site (See Figure 2-2).
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
4
Figure 2-1 Bedrock Geology
Figure 2-2 Quaternary Geology
Site Location
Irish Sea Till
Site Location
Campile Formation
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
5
3 GROUND INVESTIGATION SUMMARY The below table summarises the findings of the ground investigation. Photographs of the trial pits are appended to this report.
Figure 3-1 Site Layout and Trial Hole Locations
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
6
Trial Pit Number
Stratigraphy Ground water Stability
TP01
0.00-0.4 Topsoil & Subsoil
None encountered
Good
0.40-3.00 Stiff Grey/Brown Sandy Gravelly CLAY with occasional cobble and boulder. Gravel is angular from Limestone origin
TP02
0.00-0.30/0.5 Topsoil & Subsoil (depth varied slightly throughout trial pit)
None encountered
Good
0.30/0.50 - 3.30 Firm to Stiff Grey/Brown Sandy Gravelly CLAY with occasional boulder. High boulder and cobble content from approx 2m depth
TP03
0.00-0.30/0.4 Topsoil & Subsoil
None encountered Good
0.30/0.40 - 3.30 Stiff to Very Stiff, Grey/Brown Sandy Gravelly CLAY with occasional cobble and boulder. Clay land drain noted at 0.3m depth.
TP04
0.00-0.30/0.4 Topsoil & Subsoil
None encountered Good
0.30/0.40 - 3.00 Stiff Grey/Brown Very Sandy, Very Gravelly CLAY with occasional cobble and boulder. Crumbles on rolling on hand. Pockets of very stiff black clay noted with soil mass.
TP05
0.00-0.30 Topsoil and Subsoil
None encountered Good
0.30-1.10 Firm to Stiff Grey/Brown Sandy Gravelly CLAY
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
7
4 INITIAL ENGINEERING ASSESSMENT The Glacial Till (Stiff Sandy Gravelly CLAY) encountered at approximately 0.3 to 0.5m ground level is likely to provide a suitable formation layer for the structures on this site. Plate load testing will be required at construction stage to prove the design bearing capacity is achieved. Permanent cuttings in Glacial Till at this site should be at an angle of 1V:2H or shallower. The reusability of material excavated from the substation site has been assessed based on TII document “Specification for Road Works Series 600 – Earthworks (CC-SPW-00600 March 2013)”. The Glacial Till excavated at this site is likely to classify as a Class 2 A/B/C (General Fill) or Class 4 (Fill to Landscape Areas). The Glacial Till is not likely to meet the requirements for Class 6F or 6N. Class 6F and 6N typically require the use of crushed rock to meet the specification. Import of quarried material from an external quarry will be required for construction of the substation compound. The material should be sourced from a quarry that is certified to provide Class 6F and 6N material that meets the requirements of SR21. A localised dip was noted on the western boundary of the substation compound which is likely to required additional fill to bring it to the same level as the rest of the site. A surface land drain was noted at the southern boundary of the site. The fall in the drain appeared to be from west to east. Clay pipe land drains were encountered at approximately 300 to 500mm below ground level in two of the trail holes. Further clay drains are likely to be encountered onsite.
Appendix A
Trial Pit Photographs
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
9
TP01 – Photo 1
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
10
TP01 – Photo 2
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
11
TP01 – Photo 3
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
12
TP01 – Photo 4
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
13
TP01 – Photo 5
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
14
TP02 – Photo 1
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
15
TP02 – Photo 2
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
16
TP02 – Photo 3
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
17
TP02 – Photo 4
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
18
TP02 – Photo 5
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
19
TP03 – Photo 1
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
20
TP03 – Photo 2
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
21
TP03 – Photo 3
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
22
TP03 – Photo 4
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
23
TP03 – Photo 4
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
24
TP04 – Photo 1
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
25
TP04 – Photo 2
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
26
TP04 – Photo 3
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
27
TP04 – Photo 4
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
28
TP04 – Photo 5
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
29
TP04 – Photo 6
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
30
TP05 – Photo 1
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
31
TP05 – Photo 2
Tullabeg Substation 20609-6003-E Ground Investigation Report October 2019
32
TP05 – Photo 3