Trixbox quickstart guide 1.0.0 Overview : Trixbox is an end to end digital control system design tool to perform simulations, generate control coefficients and control code that can be directly used with microprocessor. This tool is intended as a help to generate the code for discrete (digitally) controlled power supplies/motor drives. Trixbox is a web based app. Hence no downloads, no upgrades etc are required. It does not require knowledge of advanced control system design techniques and allows the user to get a workable solution quickly without trial and error and without dealing with complex equations. Trixbox also allows users to simulate their own code while configuring the system (PWM modulation) in almost every conceivable mode. Having said that trixbox is no substitute for experience and physical insight that may be required on a case to case basis. Trixbox is not traditional simulation software where circuits or systems are drawn and simulated to the last nanosecond. It’s an end to end design tool which handles many (most common) modes and systems. However every single case and quirk cannot be handled. It is meant as an auxiliary to our consulting services. Note: Trixbox works best in fire fox and google chrome. Internet Explorer is not supported and will crash.
44

Trixboxguide

Jun 15, 2015

Download

Technology

Nahar Anusheel

Quickstart guide for trixbox. New to trixbox, start here
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Trixboxguide

Trixbox quickstart guide

1.0.0 Overview :

Trixbox is an end to end digital control system design tool to perform simulations, generate control

coefficients and control code that can be directly used with microprocessor. This tool is intended as a help to

generate the code for discrete (digitally) controlled power supplies/motor drives.

Trixbox is a web based app. Hence no downloads, no upgrades etc are required. It does not require

knowledge of advanced control system design techniques and allows the user to get a workable solution

quickly without trial and error and without dealing with complex equations.

Trixbox also allows users to simulate their own code while configuring the system (PWM

modulation) in almost every conceivable mode.

Having said that trixbox is no substitute for experience and physical insight that may be required on a case to

case basis. Trixbox is not traditional simulation software where circuits or systems are drawn and simulated to

the last nanosecond. It’s an end to end design tool which handles many (most common) modes and systems.

However every single case and quirk cannot

be handled. It is meant as an auxiliary to our consulting services.

Note: Trixbox works best in fire fox and google chrome. Internet Explorer is not supported and will crash.

Page 2: Trixboxguide

2.0.0 Key Features:

1. Supports many topologies (presently all derived from the buck topology and boost topology)

2. Automatic generation of control coefficients

3. C Code generation for digital control system for fixed point DSC

4. Various control and system operation modes (VSI, CSI, DCM, CCM, VMC, CMC, PCMC)

5. Advanced control system design methods (description below)

6. User Programmable dynamic triggering strategy

7. System level simulation of user code interaction

2.0.1 Description of features

Trixbox works in 2 modes standard mode and user code mode

Is the standard mode end to end control system design takes place? Starting from physical system

level parameters the gains are calculated, plots are generated and C code I generated with

instructions to integrate the C files.

In the user code mode the user can write his/her own custom code, configure the system in a much

wider variety of ways such as variable period, valley current mode, dynamically change the on time, off

time etc.

In essence any generic switching pattern can be used to drive the system and the subsequent results

can be observed. In this mode only time domain simulation plots are generated.

The sample files are the same for both the modes. Some of the data contained in the sample files

which may be modified by the user may or may not be relevant. However it may be left as it is or

deleted.

Page 3: Trixboxguide

2.1.0 Standard mode:

The following features are relevant for the standard mode and are described below.

2.1.1 Topologies supported

Various common topologies derived from the buck topology are supported. These are

1. Buck

2. Sync Buck

3. Push Pull

4. Full Bridge for inverters

5. Full Bridge DC DC converter

6. Phase Shift full bridge

7. Half bridge for inverter

8. Half bridge for DC DC

9. Current fed push pull

10. Boost

11. Synchronous Boost

By doing slight modifications, dynamics of topologies such as series and parallel resonant circuits

can also be simulated.

However the code needs to be modified to accommodate some more effects. (Needs

little customization)

Other dynamic systems such as various kinds of motors can also be simulated and code generated

• Servo motor drives (speed and position control) (DC, BLDC, PMSM and ACIM)

• Linear actuators /solenoids (needs little customization)

Page 4: Trixboxguide

In addition in conjunction with the trixbox software customized solutions can be obtained for

following systems

(Simulation, control system design and fixed point or floating point microprocessor based code for

various operating mode for the following systems)

1. Buck topology (and derived topologies such as half bridge, full bridge, push pull, phase shift full

bridge, forward)

2. Boost topology (and derived systems)

3. Buck Boost topology (and derived systems such as Flyback)

4. LLC series and parallel resonant topologies

5. Servo motor drives (Speed and position control)

6. Power factor correction using various algorithms

7. BLDC, DC, AC induction, PMSM motor (censored and sensor less speed and position control)

8. Linear electromagnetic actuators

9. Electro capacitive motors and actuators

The complete list of projects and algorithms that we have experience is provided under services and

technology.

www.controltrix.com/service.html

www.controltrix.com/tech.html

2.1.2 Automatic generation of control coefficients

The control coefficients are generated algorithmically based on the user parameters. Various checks

are also performed to ensure that the coefficients will give desired performance.

Page 5: Trixboxguide

2.1.3 C code generation

The C code for digital implementation is automatically generated by trixbox software. The C code and some

other relevant pieces can be easily combined to get a working code fairly quickly and easily.

The C code snippets that are generated are as follows

Preprocessing of ADC signals

• C code performing calculations

• Converting Q15 to Duty or phase values (modulation) for various topologies

• Definitions of various constants (# define)

• A readme file that describes how to combine the various code snippets

2.1.4 Modes supported

Various modes are supported for the relevant topologies. These are listed below

Conduction modes

1. Simulation and design for discontinuous current conduction mode in asynchronous topologies

2. Simulation and design for continuous current conduction mode

Source

1. Voltage source (where the objective is to control the output voltage)

2. Current source (where the objective is to control the inductor current)

Control modes

1. Voltage mode control

2. Average Current mode control

3. Peak Current mode control

2.1.5 Advanced mathematical models and simulation techniques

Trixbox uses advanced algorithms to ensure better performance for your system. Some of key advantages are

Page 6: Trixboxguide

as follows

1. Models the physical reality better than the averaged models. Performs ideal switched simulation

2. Fast proprietary simulation compared to most traditional solvers such as RungeKutta based ones.

3. Code is executed and simulated in lock step (like actual system).

4. Handles many digital system related quirks like zero order hold, computational delays and deadtime.

5. Analytical averaged model frequency domain simulation. (No numerical instabilities and consequent

incomprehensible results) as compared to traditional simulation software.

2.1.6 User programmable triggering strategy

Triggering the ADC at the correct instant is an important aspect of all digitally controlled Power systems. Trixbox

allows the user to program the triggering strategy. The trigger point is thus calculated based on the user code.

In the standard mode the switching period is fixed. The program that the user needs to write to describe the

trigger point needs to be in PYTHON syntax.

Note: The syntax is mostly like C, except special care needs to be paid to indentation. Refer to following

section for the valid format. Also for security reasons, use of special symbols and string operations are

prohibited.

2.2.0 User code execution mode

The user code execution mode allows the user to try out any customized code, and how it will interact with

the entire system and look at the performance.

The user can configure the system in many ways.

Essentially limits on Ton, Toff and period and other limiting conditions may be put. Under these limiting

conditions, the user code is executed.

The user code should be written in python syntax. Many special symbols and keywords are not allowed in the

code for security reasons.

PYTHON is a strongly typed language. Special emphasis has to be made regarding indentation. It is

recommended that TAB is used for indenting the code.

Page 7: Trixboxguide

Only time domain plots are executed when the system is in User code execution mode as (any non linear code

can also be put down by the user and frequency response will be invalid as the condition for Linear time

invariant system may get violated).

In some of the topologies when the circuit is reduced to the basic topology, the effective switching

frequency may be different (Usually two times). This has to be kept in mind when setting limits etc.

Such topologies are center tapped secondary side, current doublers secondary side, Full Bridge for inverter.

Other topology also needs correction.

2.2.1 Limiting modes

The user can configure the system into various limiting modes. The code that gets executed is restricted by

these modes. This allows the user to simulate variable on time, off time and PWM time.

List of modes is presented .Some modes are not mutually exclusive. There is considerable overlap

Fixed or variable frequency

1. Fixed Period or Fixed frequency mode: This is the typical mode where the period is configured and

remains fixed. On time and off time may change

2. Variable period or frequency mode

Peak Current and valley current

1. Peak current based Ton reset mode

Active state of the pwm is started as usual. As soon as the current hits a preset value, the PWM output is turned

inactive. When the Current is below a certain limit the state is active. When the current hits a certain limit, the

PWM is made inactive for the rest of

the period (or some other condition that again starts the timer).The peak current limit can be

programmatically set in every interrupt.

This operation is similar to cycle by cycle current limiting and peak current mode control and is also useful in

hysteresis mode

2. Valley current based Period set mode

Page 8: Trixboxguide

The PWM runs as usual determined by perhaps other modes. As soon as the current goes below a specified

threshold, the period is terminated and a new switching cycle starts. This mode is useful for valley current

control mode and hysteresis based control.

In addition minimum and maximum limits may be placed on Ton, Toff and the period. These limits serve as

limiting conditions. These conditions may be enabled and disabled

These limiting conditions supersede any calculations that are made and take precedence. The enabling and

disabling of limits and specifying the limit values may be performed by setting the appropriate values in the

‘.xlsx’ file. (please refer to getting started section).

For e.g.

If the maximum Ton is set to a certain value and if the current does not hit the peak value, under normal

circumstances 100 % duty will be reached. However with a maximum Ton set, the on

time will be limited to that value.

3.0.0 Getting started

Trixbox is very easy to use. To start with, the user has to download a couple of files, modify them with their own

parameters and upload them.

3.1.0 Input:

The first file is a Excel (.xlsx) file with parameter values such as passive components, feedback network etc.

You may download a sample .xlsx file from under the help tab, modify the parameter values and save it as

.csv(comma delimited) file and upload in the designated space. The parameter description is provided in

Appendix 3.0

All parameters are not necessary and the order of the various parameters can also be changed. In fact

some of the parameters may be not applicable in some of the modes. It is advisable to start from a fresh

.xlsx file (found under the help tab) and modifies the relevant fields. You may even delete those which are

not required

Page 9: Trixboxguide

The second (.txt) file input has a number of sections. The user may edit them based on the formats

specified. Each section begins with xxxx<Sectionname>start and ends with xxxx<Sectionname>stop

Anything written outside of the respective sections is ignored. Please do not write the keywords which specify

start and stop of a section anywhere else.

The operating conditions in .xlsx file represent the time varying quantities like desired voltage (Vref), Load

current (Io) , input voltage (Vin) for voltage source (where the primary control objective is output voltage).

The files are essentially excel files where the data can be specified in various formats. The formats are specified

in Appendix 1.0 at the end of this document.

These are required to perform time domain simulations.

The sections in .txt file are code snippets for dynamic triggering strategy. In a digital power control system the

choice of triggering the ADC (the point in the switching cycle the waveforms are sampled is very critical). This

piece of code is directly executed for simulation. Example code snippets are specified in Appendix 2.0 that

can be used for dynamic triggering.

Also the same file can be modified to incorporate user defined code.

In the user code mode the code also needs to be written as part of the ‘.txt’ file.

The specified format is presented in Appendix 4.0

Many parameters or sections in either .xlsx file may not be required for some particular operation. These

values may be left as they are in the sample files.

3.2.0 Output:

Once all the data has been entered, submit should be pressed. The plots may need to be refreshed as

browser may cache old data.

The tool generates the following output:

1. Bode plots for loop gain (phase margin and gain margin) for both analog and digital equivalent circuits.

2. Bode plot for closed loop (closed loop performance)

Page 10: Trixboxguide

3. Disturbance rejection (inverse of output impedance for voltage source and output impedance for

current source) bode plot (the system performance when changes in load take place. It’s an absolute

metric. The higher the value the, more robust the system is. Details in later sections.

4. Time domain simulation plots include (Ripple content in voltage and current waveform,

average Output Voltage, Average inductor current, Average topside mosfet current in equivalent buck/boost

topology, Average bottomside mosfet current in equivalent buck/boost topology circuit), In the beta version,

these plots are limited in terms of number of points that can be simulated. The time domain simulations are

only performed

for the discrete (digital) power system.

5. All the results are available in the form of the download zip file which may be plotted using a

spreadsheet program such as Microsoft excel or goggle spreadsheets or open office. The data is all comma

separated values (x0, y0) (x1, y1) etc…

6. Automatically generated code files

i. .c code file, that needs to be integrated into your system by defining proper macros

ii. .h Parameter file with control coefficients

iii. Code for modulation (converting the output of the C code to duty etc) Needs to be copy pasted

iv. Readme with instructions

v. Log file to report any errors etc..

7. The download files include, the data for all the plots, c pseudo code files (which have to be modified based

on your processor by adding macros and specific libraries for multiply etc).

8. A generated readme file with description for which c file (pseudo code) needs to be used in the

microcontroller. The readme file also describes some code snippets that needs to be copy pasted

into the c file. These code snippets are basically related to modulation strategies.

More code snippets for preprocessing current will be added in due course

9. Readme file and log file :

Please look at the readme file and log file. The readme file is dynamically generated based on the

system. A brief overview is presented for what you should be looking for:

Page 11: Trixboxguide

The generated pseudo code is in controlcode.c

ii. The modulation pseudo code is in mod.c

iii. If secondary side modulation is required , the secondarydutygen.c has the code for

synchronous rectification

iv. The control coefficients are present in defs.h

v. Various output data are present in different files in the download.zip.

A description of the data in each of the filesoutputxx.txt is provided in the table below.

File num

Plot num

Xaxis data ( 1st column)

Yaxis data ( 2nd

column) Plot description

legend

Output xx.txt xx = 01,02,03…

output01.txt 1 log 10 (f) Frequency (Hz)

Gain in dB 20 log10 (gain)

Loop gain bode plot [gain] Vo(s)/Verr(s) for Voltage source (primary control objective output voltage)

Io(s)/Ierr(s) for Current source (primary control objective is output current)

Analog system loop gain magnitude

Page 12: Trixboxguide

output02.txt 2 log 10 (f) Frequency (Hz)

Angle (degrees) Loop gain bode plot [phase] Vo(s)/Verr(s) for Voltage source (primary control objective output voltage) Io(s)/Ierr(s) for Current source (primary control objective is output current)

Analog system loop gain phase

output03.txt 1 log 10 (f)

Frequency

(Hz)

Gain in dB

20 log10 (gain)

Loop gain bode plot [gain]

Vo(s)/Verr(s) for Voltage

source

(primary control objective

output voltage)

Io(s)/Ierr(s) for Current

source

(primary control objective is

output current)

Digital system loop

gain magnitude

output04.txt 2 log 10 (f)

Frequency

(Hz)

Angle (degrees) Loop gain bode plot [phase]

Vo(s)/Verr(s) for Voltage

source

(primary control objective

output voltage)

Io(s)/Ierr(s) for Current

source

(primary control objective is

output current)

Digital system loop

gain phase

output05.txt 3 log 10 (f)

Frequency

(Hz)

Gain in dB

20 log10 (gain)

Closed Loop gain bode plot

[gain]

Vo(s)/Vref(s) for Voltage

source

(primary control objective

output voltage) Io(s)/Iref(s)

for Current

Closed loop Analog

gain

magnitude

Page 13: Trixboxguide

source

(primary control objective is

output current)

output06.txt 4 log 10 (f)

Frequency

(Hz)

Angle (degrees) Closed Loop gain bode plot

[phase]

Vo(s)/Vref(s) for Voltage

source

(primary control objective

output voltage)

Io(s)/Iref(s) for Current

source

(primary control objective is

output current)

Closed loop Analog

gain phase

output07.txt 3 log 10 (f)

Frequency

(Hz)

Gain in dB

20 log10 (gain)

Closed Loop gain bode plot

[gain]

Vo(s)/Vref(s) for Voltage

source

(primary control objective

output voltage) Io(s)/Iref(s)

for Current source

(primary control objective is

output current)

Closed loop digital

gain magnitude

output08.txt 4 log 10 (f)

Frequency

(Hz)

Angle (degrees) Closed Loop gain bode plot

[phase]

Vo(s)/Vref(s) for Voltage

source

Closed loop Digital

gain phase

Page 14: Trixboxguide

(primary control objective

output voltage)

Io(s)/Iref(s) for Current

source

(primary control objective is

output current)

output09.txt 5 log 10 (f)

Frequency

(Hz)

log(|Io(s)/Vo(s)|) for

voltage source

(primary control

objective output

voltage)

log(|Vo(s)/Io(s)|) for

voltage source

(primary control

objective output

current)

Disturbance rejection[gain]

Higher this value the stiffer

the stiffer and better the

system

log(|Io(s)/Vo(s)|) for voltage

source

(primary control objective

output voltage)

Also the inverse of output

impedance

log(|Vo(s)/Io(s)|) for voltage

source

(primary control objective

output current)

Output impedance

Analog system

disturbance

rejection magnitude

output10.txt 5 log 10 (f)

Frequency

(Hz)

log(|Io(s)/Vo(s)|) for

voltage source

(primary control

objective output

voltage)

log(|Vo(s)/Io(s)|) for

voltage source

(primary control

objective output

Disturbance rejection[gain]

Higher this value the stiffer

the stiffer and better the

system

log(|Io(s)/Vo(s)|) for voltage

source

(primary control objective

output voltage)

Also the inverse of output

impedance

Digital system

disturbance

rejection

magnitude

Page 15: Trixboxguide

current) log(|Vo(s)/Io(s)|) for voltage

source

(primary control objective

output current)

Output impedance

output11.txt 6 Time (s) Inductor Current ripple

(delta IL) pk to pk (A)

Current ripple vs time

output12.txt 7 Time (s) Output Voltage ripple

(delta Vo) pk to pk (V)

Voltage ripple vs time

output13.txt 8 Time (s) Average output voltage

(V)

Average voltage vs time

output14.txt 9 Time (s) Average inductor

current (A)

Average current vs time

output15.txt 10 Time (s) Average Topside

Mosfet current (A).

(equivalent Buck/boost

ckt)

Average Topside Mosfet

current vs time

output16.txt 11 Time (s) Average Bottom Mosfet

current (A)

(equivalent Buck/boost

ckt)

Average Bottomside Mosfet

current vs time

output17.txt 12 Time (s) Rising current slope A/s Rising current slope vs time

output18.txt 13 Time (s) Falling current slope A/s Falling current slope vs time

output19.txt 14 Time (s) Peak current (A) Peak current vs time

output20.txt 15 Time (s) Valley current (A) Valley current vs time

4.0.0 Future additions

Other converter topologies of the buck boost family

Better UI

Detailed Documentation

5.0.0 Appendix 1: Input file formats

Formats for simulation time domain series.

Page 16: Trixboxguide

There are multiple formats in which the Signals like reference voltage Vref, output current Io etc can be

uploaded.

For some special waveforms like sine wave, square wave etc there is a templatized version where writing

only a few lines and uploading it will generate the correct waveform internally.

5.1.0 General rules

1. The first line specifies what type of wave is being generated. Sinewave, rectified sinewave, square

wave, triangle wave (also almost a sawtooth wave), an interpolated wave,

2. constant or a simple time vs voltage sequence can be generated in a periodic or non

3. periodic manner.

4. Instead of letting the user just upload time value pairs, some common functions like sine,

square etc have been provided which can be used in a parametric form.

5. Some assume a periodic wave needs to be generated. If a non periodic wave is required, enter a

non zero very small value for frequency such as 0.1 or 0.01 Hz.

6. The .xlsx file must be opened and entries must be entered in successive lines in the space

provided.

7. Save the file in .csv (comma delimited) format and upload it in the designated space.

8. The points generated will always be at the system sampling frequency used in simulation.

9. It assumes that changes in these variables time sequences always occur aligned to PWM edges.

The period is always the PWM period.

10. So if PWM period is 10us and 500 points need to be generated then the system will only

simulate for a duration of 5ms.

11. The number of points takes precedence over simulation time.

Page 17: Trixboxguide

So even if the simulation time is larger than the time represented by number of points, the system

will truncate before that.

5.2.0 Formats:

5.2.1 Sine wave/rectified sinewave To generate a sine wave, enter the values in the space provided under operating conditions in .xlsx file.

e.g. to generate a sine wave of 100 Hz, 10 amplitude, pi/2 rad phase lag , DC offset 0 and 500 points

enter the values in the space provided in a .xlsx file under operating conditions as below.

WAVEFORM (type / shape): sine FREQUENCY (in Hz): 100 AMPLITUDE (in SI units): 10 PHASE (in radians): -1.159 DCOFFSET (in SI units): 0 NUMPOINTS (Number of points): 500 Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

e.g. to generate a rectified sine wave of 100 Hz, 10 amplitude, pi/2 rad phase lag , DC offset 0 and 500

points enter the values in the space provided in a .xlsx file under operating conditions as below.

WAVEFORM (type / shape): rectsine FREQUENCY (in Hz): 100 AMPLITUDE (in SI units): 10 PHASE (in radians): -1.159 DCOFFSET (in SI units): 0 NUMPOINTS (Number of points): 500 Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

Page 18: Trixboxguide

5.2.2 Square Wave

To generate a square wave, enter the values in the space provided under operating conditions in .xlsx

file.

e.g. to generate a square wave of 100 Hz, 10 amplitude, phase advance by 0.001 s, DC offset 0, 500

points and 30% duty, enter the values in the space provided in a .xlsx file under operating conditions

as below.

WAVEFORM (type / shape): square FREQUENCY (in Hz): 100 AMPLITUDE (in SI units): 10 PHASE (in seconds): -1.159 DCOFFSET (in SI units): 0 NUMPOINTS (Number of points): 500 DUTY (between 0 and 1): 0.3 Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

5.2.3 Triangle Wave

To generate a triangular wave, enter the values in the space provided under operating conditions in

.xlsx file.

e.g. to generate a triangle wave of 100 Hz, 10 amplitude, phase advance by 0.001 s, DC offset 0, 500

points and 30% duty, enter the values in the space provided in a .xlsx file under operating conditions

as shown below. In this case the upward slope will be for 30% of the period and downward slope will

be for 70%.

WAVEFORM (type / shape): square FREQUENCY (in Hz): 100 AMPLITUDE (in SI units): 10 PHASE (in seconds): -1.159 DCOFFSET (in SI units): 0 NUMPOINTS (Number of points): 500 DUTY (between 0 and 1): 0.3 Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

Page 19: Trixboxguide

5.2.4 Subsampled sequence

Subsample sequence allows you to generate interpolated waveforms while specifying only a few

points.

It basically performs parabolic interpolation between points, where the interpolation needs to be

disabled to generate discontinuous waveforms like steps and jagged ones.

e.g. To generate a non periodic ramp passing though (0, 1) and (1, 2) and (2, 3) enter the values in the

space provided under operating conditions in .xlsx file.

So instead of specifying many points, it will fit a curve through these 3 points and generate 500 points

based on the system sampling frequency.

WAVEFORM (type / shape): subsampled FREQUENCY (in Hz): 0.01 NUMPOINTS (Number of points): 500 Time:value:continuity: 0, 1, 1 Time:value:continuity: 1, 2, 1 Time:value:continuity: 2, 3, 1 Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

5.2.5 Arbitrary wave periodically sampled as a time, value pair

To enter brute force time versus amplitude in the rawest form use this. With this any arbitrary

waveform can be entered but it is also the most cumbersome. You may use some spreadsheet

software and then copy the data to the .xlsx. To enter 100 Hz wave with arbitrary shape enter as

follows: The sampling period is still determined by the PWM period in data set 1 as given in general

instructions given above.

In this format no interpolation (curve fitting or smoothening) is performed. The user may still enter

time and value pair where time values may still be arbitrary.

So if sampling period is 100us and user enter the values in the space provided under operating

conditions in .xlsx file.

Page 20: Trixboxguide

WAVEFORM (type / shape): simpleseq FREQUENCY (in Hz): 100 Time:value:continuity: 0, 0 Time:value:continuity: 0.001, 1 Time:value:continuity: 0.004, 2 Time:value:continuity: 0.005, 3 So for the first 10 samples (time interval of 100us between successive samples) the value will be 0.

Next 30 samples the value will be 1.

Next 10 samples value will be 0.

This allows the user to not have to enter values for all possible data point. Without having to worry

about entering time as a multiple of PWM period. This considerably condenses the data that needs

to be entered especially for waveforms with significant flat areas such as 6 step.

e.g.

WAVEFORM (type / shape): simpleseq FREQUENCY (in Hz): 100 NUMPOINTS (Number of points): 500 Time:value:continuity: 0.0001, 1 Time:value:continuity: 0.0004, 4 Time:value:continuity: 0.0005, 3

Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

5.2.6 Constant To enter a constant, enter the values in the space provided under operating conditions in .xlsx

file.

E.g. To enter a constant of 10 amplitude and 500 points enter as follows. WAVEFORM (type / shape): Constant AMPLITUDE (in SI units): 10 NUMPOINTS (Number of points): 500

Note: Save the given .xlsx file in .csv (comma delimited) format before uploading.

Page 21: Trixboxguide

6.0.0 Appendix 2.0: Dynamic triggering strategy

Use itrig variable when referring to current loop. Use

vtrig variable when referring to voltage loop.

The syntax of the code should be like python language.

Indentation is especially important in python. Always use tab for indentation.

Any complex code may be written to accommodate triggering strategy.

However string operations and many special characters are not allowed to be used.

In the sample file a dummy code is already present. This may be modified as required

<tab>itrig = 0

Some rudimentary error reporting has been implemented. The errors get written in the log file.

All units here are based on Q15 or fraction scale.

32767 is 100 % or full effective period. (For topologies

Default value is 0.

Sample code for dynamic triggering e.g. 1: This will trigger at the start of the PWM period

<Tab>itrig = 0

Sample code for dynamic triggering e.g. 2: The below code will trigger @ 25 % of the period.

<Tab>itrig = 8191

Sample code for dynamic triggering e.g. 3: The below code will trigger at 50% of the duty

<Tab>itrig = Duty/2

Sample code for dynamic triggering e.g. 4: The following code will trigger at 10% of period before

the duty. If duty is 50 % then the below code will trigger at 40%.

itrig = Duty – 3276

Similarly for changing voltage loop triggering use vtrig

instead of itrig.

Page 22: Trixboxguide

7.0.0 Appendix 3.0: Parameter description

The following section describes all the parameters that are used to describe the system and are

present in the ..xlsx file

All values should be input in standard metric/SI units such as Henries, farads, seconds, ohms, volts,

amperes and watts

Not all parameters may be required in all situations. The original values which are the default may

be left as they are if they are not required.

7.1.0 TOPOLOGY AND SYSTEM DESCRIPTION

The following section describes the various topology specific parameters that are used

to specify the system

7.1.1 Primary topology PRMRY_TPLGY

Select the topology on the primary side. Enter the respective number in the .xlsx file in respective place

Reserved 0

Buck 1

Synchronous 2

Push pull 3

Full bridge (for inverter) 4

Full bridge (for DC DC) 5

Half Bridge for inverter 6

Phase Shift Full Bridge 7

Forward 8

Series resonant xx(not supported in beta version)* 9xx

Half Bridge (for DCDC) 10

Current fed push pull 11

Boost 0 (in boost family mode)

Synchronous Boost 1 (in boost family mode)

Page 23: Trixboxguide

7.1.2 Secondary topology SCNDRY_TPLGY Select the topology on the secondary side.

For non isolated converters select not applicable.

Enter the respective number in the .xlsx file in respective place

Center tap rectifier 0

Current Doubler rectifier 1

Centre tap Synchronous rectifier 2

Current Doubler Synchronous rectifier 3

Voltage Doubler half bridge rectifier 4

Full bridge rectifier 5

Not applicable (N/A) -1

7.1.3 Primary control objective PRMY_CNTRL_OBJ

Select primary control objective. If the goal is to control output voltage (irrespective of load

current) select output voltage. If the goal is to control the output current (where the output voltage

is determined by external factors).

Enter the respective number in the .xlsx file in respective place

output voltage

0

output current

1

7.1.4 Secondary control objective SCNDRY_CNTRL_OBJ

Select Secondary control objective.

E.g. usage Power factor correction output voltage. Not applicable in beta version.

Enter the respective number in the .xlsx file in respective place

Page 24: Trixboxguide

Output voltage 0

Output current 1

Not applicable -1

7.1.5 Control mode CONTROL_MODE

Select Control strategy. Voltage mode control if only voltage feedback is taken. Peak current mode if

comparator action is used to limit Duty. Refer standard texts on the above. For Current source

converters (where primary control objective is current) only average current mode is valid.

Enter the respective number in the .xlsx file in respective place

Voltage mode control 0

Average current mode control 1

Peak current mode control 2

7.1.6 Transformer turn ratio TURNS_RATIO

A transformer is used in topologies like push pull, forward etc. Enter the turn ratio primary to

secondary.

E.g. If primary number of turns is 10 and secondary is 4 then enter 10/4 = 2.5 * Note: For center tap

configuration on the secondary side, the turn ratio to be entered is ratio of primary side to turns in

one of the legs of the secondary side.

7.1.7 Parallel modules or interleaved phases NUM_PAR_PHASES

In many topologies there are multiple phases running in parallel. Enter the number of parallel

modules or phases.

These phases must have a common input as well as common output point.

Page 25: Trixboxguide

7.2.0 PASSIVE COMPONENTS

The following section describes various passive components in the system

7.2.1 Nominal value of inductance INDUCTANCE

If there are multiple paralleled modules / inductors enter the per phase inductance. If the secondary

side is current doubler circuit in some converters like Full Bridge, push pull etc, then only put the

value of inductance of one of the phases. Does not support inductor saturation in beta release. For

current fed push pull topology, enter the primary side inductance

7.2.2 Output capacitance CAPACITANCE

The total output capacitance in the L-C plant. If multiple phases are present then enter the total

capacitance at the point of load.

7.2.3 Lumped series resistance LSR

The Lumped series resistance needs to be measured for the system using the following steps

1. Provide constant duty such that output voltage is near operating point voltage for DC –DC

application.

2. Slowly increase load while measuring output voltage.

3. The output voltage will droop with increasing load.

4. The V vs I slope provide the lumped resistance.

Refer documentation for more details

7.2.4 Equivalent series resistance ESR

If multiple equivalent capacitors are present in the output. Enter value ESR/n where n is the

number of capacitors.

Page 26: Trixboxguide

7.3.0 INPUT VOLTAGE

The following sections describes the min and max input voltages

7.3.1 Maximum input voltage VIN_MAX

Max input voltage allowed by the converter before it enters over voltage protection

7.3.2 Nominal input voltage VIN

The generated code can handle wide range of input voltages but specify nominal input voltage. E.g. If

allowed input voltage is 36-75 V then enter 55 which is somewhere in between.

7.3.3 Minimum input voltage VIN_MIN

Minimum input voltage where the system is expected to operate reliably without entering under

voltage protection

7.4.0 DSP CONFIG PARAMETERS

DSP configuration specific parameters

7.4.1 PWM switching frequency in Hz PWM_FREQ 7.4.2 PWM clock frequency PWM_CLK_FREQ

PWM clock frequency determines the resolution of the PWM and plays a very important role in

quantization

7.4.3 Voltage loop execution rate in Hz VLOOP_INTFREQ

The rate at which the voltage loops code is executed.

Page 27: Trixboxguide

7.4.4 Current loop execution rate in Hz ILOOP_INTFREQ

The rate at which the current loop code is executed.

7.4.5 Deadtime as a fraction of PWM Period DEADTIME_FRACTION

Dead time for synchronous converters.

E.g. if deadtime is 1 us and period is 10 us then enter 1/10 =0.1. Enter a small value like 0.001 if not

using deadtime.

7.5.0 COMPUTATION DELAY

Computational delays to be modeled in the analysis is provided here

7.5.1 Computational delay of the innermost loop in s INNR_LOOP_DLY

The inner most loop, in current mode control is current loop, in voltage mode control or peak current

mode control it is the voltage loop. The time between signals is sampled and duty ratio to change is

captured in this parameter. Should be less than the relevant interrupt period / or relevant execution

loop

For e.g. PWM switching period is 10 us , The sampling for feedback takes place @ 1us and the duty is

updated at the end of the period then enter 9us.(Time between sampling and actual updating of

duty). This parameter is used only for generation of bode plots.

Typical values could be about half of the interrupt period or execution period when the

triggering or ADC sampling is performed properly.

Worst case scenario could be 1 interrupt period.

The delay is determined in real time for simulation purposes.

Page 28: Trixboxguide

7.5.2 Computational delay of the outer loop in s OUTR_LOOP_DLY

The outer most loop, in average current mode control it is voltage loop. The time between signals is

sampled and duty ratio to change is captured in this parameter. Should be less than the relevant

interrupt period / or relevant execution loop

For e.g. PWM switching period is 10 us, The sampling for feedback takes place @ 1us and the duty is

updated at the end of the period then enter 9us.

(Time between sampling and actual updating of duty). For other cases it is not relevant. This entry

should be less than the relevant interrupt period.

This parameter is used only for generation of bode plots.

Typical values could be about half of the interrupt period or execution period when the

triggering or ADC sampling is performed properly.

Worst case scenario could be 1 interrupt period.

The delay is determined in real time for simulation purposes.

7.6.0 ADC AND PWM INTERFACE PARAMETERS 7.6.1 Voltage feedback cutoff frequency VFBK_BW

The voltage feedback circuit will have a finite bandwidth. Voltage can only be measured reliably

without attenuation up to certain frequencies this effects the simulation and calculation of gains.

Disabled in beta version.

7.6.2 Manipulator bandwidth of the system MANIP_BW

Limited implementation in beta version. Should be less than or equal to PWM frequency.

This factor decides how fast the manipulated input (e.g. steering wheel in a car) can be made to move.

For most buck converter using switch based drives, it is about the PWM frequency used.

Page 29: Trixboxguide

However for some topologies like LLC resonant, where the transformer output is connected to

a bulk capacitor, the rate of change of applied voltage to the equivalent L-C plant is determine by the transformer + capacitor circuit. Hence it becomes very critical when designing control system.

It needs to be measured experimentally:

1. Give a step change in the manipulated input. Manipulated signal = (Drive signal such as duty ratio,

reference in peak current mode and period in LLC resonant circuit)

2. The output voltage is then measured.

3. By using manipulator BW = 1/2/π/τ where τ is the time taken to reach 60 % of the change in the

voltage applied to the LC plant

For e.g. consider an LLC circuit

The system is controlled by changing the frequency or period of the PWM. Suppose the period is

changed from 5 to 4.5 micro seconds as a step change suddenly. The resulting voltage on the

capacitor bank on the secondary side also changes.

The voltage applied to the LC plant at the output (Not the LLC impedance on the primary side) is the

voltage across the capacitor bank after the rectifier on the secondary side. If the voltage changes

from 4.5 V to a final value of 5 V in 1ms then, on the scope measure the time taken by the system to

reach 0.63* (5 - 4.5) = 0.325 V change from the initial level.

Suppose this time is found to be 700 us Then the manipulator bandwidth is given by

1/2/π/700e-6 ~ 250Hz.

This is like your steering wheel. The system cannot respond any faster than the steering wheel can be

turned. If the steering wheel turns too slowly, it doesn’t matter how good the driver is.

In performing the control system design, low manipulator bandwidth is required to be handled.

Page 30: Trixboxguide

7.6.3 Triggered or Average TRIG_OR_AVG

Indicates that the ADC feedback is triggered at a certain instant or the averaged quantity (Significant R-C time constant feedback network is present) is used for current measurement.

Triggered 0

Average

1

7.7.0 DESIRED SPEC

7.7.1 Maximum allowable steady state voltage error

VERROR_STEADYSTATE_MAX

Suppose the voltage needs to be 5 V with +/- 1% regulation. Then, enter 5 *0.01 = 0.05 V. This is the

maximum steady state error that can be tolerated.

It cannot be less than 0.1% because the ADC resolution is fixed at 10 bits (~0.1 %).

Suppose the voltage needs to be 5 V with +/- 1% regulation. Then, enter 5 *0.01 = 0.05 V. This is the

maximum steady state error that can be tolerated.

It cannot be less than 0.1% because the ADC resolution is fixed at 10 bits (~0.1 %)

7.8.0 ADC

7.8.1 Base voltage for output voltage VOUT_BASE

Enter the base voltage for the output voltage when using 10 bit ADC, the amount of actual voltage

that will generate full range ADC readout (1023) in the microprocessor.

When there are offsets involved in the feedback path, then it can be defined as delta V / (1 unit

change in 10 bit ADC reading) * 1024

e.g. 12V reads 700 counts in ADC and no offsets are present in the feedback circuit then Enter

Vbase as 12/700*1024 = 17.55 V

If there is a 512 count offset. ( 0 V will still read as 512) and 12 V reads as 700

Delta V is 12 V

Page 31: Trixboxguide

Delta ADC counts is (700 -512) = 188

Enter Vbase as 12/188*1023 = 60. 5 V

Do not enter 0

7.8.2 Base Current used to calculate all current quantities IBASE

Base current which is used to normalize all current quantities. Used in average current mode control

When using 10 bit ADC, the amount if actual voltage that will generate a full range ADC readout in the

microprocessor.

When there are offsets involved in the feedback path, then it can be defined as delta I /(1 unit change

in 10 bit ADC reading) * 1024

Suppose e.g. 12 A reads 700 counts in ADC and no offsets in the feedback ckt then, Enter base as

12/700*1024 = 17.55 V

If there is a 512 count offset. (0 A will still read as 512) and 12 A read 700 Delta I is 12A Delta

ADC counts is (700 -512) 188 Enter I base as 12/188*1023 = 60.5 A

I base may not be relevant for voltage mode control, yet enter some positive value. I base is also

used for peak current mode control.

For this mode, In the above calculations replace ADC with DAC counts. Presently works for 10 bit

DAC!! Do not enter zero even if it is N/A.

7.8.3 Base voltage for Input voltage VIN_BASE

Enter the base voltage for input voltage. The base voltage is defined as below. When using 10 bit ADC,

the amount of actual voltage that will generate a full range ADC readout (1023) in the microprocessor.

When there are offsets involved in the feedback path, then it can be defined as delta V /(1 unit change

in 10 bit ADC reading) * 1024

Page 32: Trixboxguide

e.g. 12V reads 700 counts in ADC and no offsets are present in the feedback circuit then Enter

Vbase as 12/700*1024 = 17.55 V

If there is a 512 count offset. ( 0 V will still read as 512) and 12 V reads as 700 Delta V is 12 V

Delta ADC counts is (700 -512) = 188

Enter Vbase as 12/188*1023 = 60.5 V Do not

enter 0

7.8.4 Operating point output voltage in Discontinuous Conduction Mode

OP_VOUT

The control system when the system is in discontinuous conduction mode of operation (in

asynchronous converters) will be designed around this operating point.

The control system will behave as designed only around this point.

The farther the system state moves from this point, more and more the system will behave in a

different manner.

7.8.5 Operating point Duty ratio for Discontinuous Conduction Mode

OP_DUTY

Estimated operating point duty ratio in Discontinuous conduction mode (DCM) operation of

asynchronous converters.

Disabled in beta version. Enter some value between 0 and 1.

7.8.6 Operating point Current for discontinuous conduction mode

OP_CURRENT

The control system when the system is in Discontinuous conduction mode of operation (in

asynchronous converters) is designed around this operating point current.

Page 33: Trixboxguide

The control system will behave as designed only around this point. The farther the system state

moves from this point, more and more the system will behave in a different manner.

7.9.0 DRIVE LIMITS

Parameters to limit the drive between maximum and minimum values

7.9.1 Maximum duty ratio DUTY_MAX

The drive to the equivalent buck/boost converter will be limited to this number. Used to generate

code and time domain simulation. Enter a number between (0 and 1) to limit the drive.

DMax should be > DMin

7.9.2 Minimum duty ratio DUTY_MIN The drive to the equivalent buck/boost converter will be limited to this number. Used to

generate code and time domain simulation.

Enter a number between (0 and 1) to limit the drive. DMax

should be > DMin

7.9.3 Maximum currentref I_MAX

The drive in peak current mode control to the equivalent buck/boost converter will be limited to this

number. Used to generate code and time domain simulation

Enter a number between (0 and 1) to limit the drive. DMax

should be > DMin

7.9.4 Minimum currentref I_MIN

The drive in peak current mode control to the equivalent buck/boost converter will be limited to this

number. Used to generate code and time domain simulation. Enter a number between (0 and 1) to

limit the drive. DMax should be > DMin

Page 34: Trixboxguide

7.10.0 INITIAL VALUES

Initial values of state variables

7.10.1 Vo initial value VOUT_INIT

Initial value of output voltage for time domain simulation

7.10.2 IL initial value IL_INIT

Initial value of inductor current for time domain simulation

7.11.0 CONFIDENCE LEVELS OR ACCURACY

7.11.1 Confidence factor in voltage measurement VOUT_ACC

This parameter is called decoupling. The decoupling is performed for all converters operating in

continuous conduction mode of operation. For peak current mode control this is N/A. This factor is

used to judge the tolerance of the system in the simulation.

Practical values are 0.9 to 1.1. 1 is ideal case (in real systems it’s never so)

0.9 means that the estimated or measured value of voltage is only 90% of the actual voltage

1.1 means that the estimated or measured value of voltage is 110% of the actual voltage

7.11.2 Confidence factor in Equivalent series resistance and

capacitance TAU_CZ_ACC

The ESR and capacitance have a time constant that effects (complicates) the dynamics and limits the

system performance. It can be compensated if it is somewhat known. Enter 0.01 if it is almost

unknown, Enter 1 if it is perfectly known. Enter 0.8 if the estimated value is 20% less than actual value

Enter 1.2 if the estimated value is 20% more than actual value Practical values 0.7 to 0.9 or 1.1 to 1.3.

7.11.3 Confidence factor in Lumped resistance RP_ACC

The value of lumped resistance (which was experimentally measured) may be underestimating or

overestimate. This uncertainty is captured here Enter 1 if it is perfectly known. Enter 0.8 if the

Page 35: Trixboxguide

estimate is 20 % less than the actual one Enter 1.2 if the estimate is 20 % more than the actual one.

Practical value may fall in the following ranges (0.7-0.9) and (1.1 to 1.3)

7.12.0 PLOTTING AND DATA VISUALIZATION 7.12.1 Number of points in the range (Fmin and F max) spaced logarithmically BODE_NUM_POINTS

For the bode plot generation the data for the bode plots will be generated for approximately these

many instances. A typical number could be in the range of 100 to 300

7.12.2 Minimum frequency for bode plot generation BODE_FMIN

Minimum frequency or lower limit of bode plots

7.12.3 Maximum frequency for bode plot generation BODE_FMAX

Maximum frequency or upper limit of bode plots

7.13.0 SIMULATION

7.13.1 Simulation time in s SIM_TIME

Time for which the simulation will run. Enter less than 10000 PWM cycles for response in reasonable

time frame. e.g. for a converter operating @ 100 KHz frequency, we can enter 0.1 s Enter less than

400*switching frequency for beta version.

7.14.0 ROOTS EIGEN VALUES OR POLES

7.14.1 F1 Desired pole, eigenvalue or root of characteristic equation. F1 >F2 >F3

ROOT1

7.14.2 F2 Desired pole, eigenvalue or root of characteristic equation. F1 >F2 >F3

ROOT2

7.14.3 F1 Desired pole, eigenvalue or root of characteristic equation. F1 >F2 >F3

ROOT3

Page 36: Trixboxguide

Guidelines in choosing the value of F1, F2 and F3

Keep F1 < 1/7th the sampling and the code execution frequency. F1 < 1/10th the sampling

frequency is even better

1. Keep separation between F1, F2 and F3 to account for parameter tolerances. A factor

of 2 to 3 or more between them would suffice e.g. 900,300, and 100

2. All frequencies F1, F2 and F3 should be different from one another

3. In some cases only 1 or 2 roots may be required. Even then enter some value different.

4. For voltage mode control for voltage source converter F1 becomes the cutoff

5. For current mode control for voltage source converter F2 becomes the voltage loop

bandwidth, crossover freq etc.

6. For peak current mode control F1 is voltage loop bandwidth, crossover frequency etc.

7. For current mode control for current source F1 is the current loop bandwidth,

crossover freq etc.

8. In some modes not all F1, F2 and F3 are required. The user may still enter them.

7.15.0 MODE PARAMETERS 1 = ENABLED and 0 =DISABLED

In the user code mode the following parameters are used

7.15.1 Enable/Disable fixed period modeFIXED_PERIOD

When this mode is enabled the period or switching frequency is always fixed. The user code may set the duty as a fraction of this value. In this mode Ton + Toff (the time of PWM active and inactive states) is always constant specified.

ENABLED 1

DISABLED 0

7.15.2 Enable/Disable Cycle by cycle peak current limit mode IPEAK_TON_RESET

When this mode is enabled the system enters cycle by cycle peak current limit mode. At the onset

of the period, the PWM is driven to active state as usual. When the current crosses a limit, (which

may be set dynamically and programmatically) the PWM is driven inactive where it remains till the

end of the PWM period. This mode may be operated with or without FIXED_PERIOD and

Page 37: Trixboxguide

IVALLEY_TOFF_RESET.

ENABLED 1

DISABLED 0

7.15.3 Cycle by cycle valley current limit mode IVALLEY_TOFF_RESET

When this mode is enabled, the PWM period is reset whenever the valley current falls below a limit.

The limit may be changed programmatically and dynamically by the user code. When the event

occurs the PWM is driven to an active state. This mode works with and without enabling

FIXED_PERIOD.

ENABLED 1

DISABLED 0

7.16.0 LIMIT PARAMETERS 1= LIMIT and 0 =DISABLED

These parameters enable and disable the min and max values. If these parameters are enabled

then the respective time quantity is bounded. For e.g. if TONMAX is enabled, then TON will always be

less than Tonmax limit set next. Though user code may also do some software protection to limit

these values, Sometimes a hardware limit is desirable. The following parameters are mainly used for

protection purposes in real systems.

7.16.1 Enable PWM active state (Ton) minimum limit TONMIN

If enabled, will limit the minimum Ton (time of PWM active state) to TONMIN_VAL.

ENABLED 1

DISABLED 0

7.16.2 Enable PWM active state (Ton) maximum limit TONMAX

If enabled, will limit the minimum Ton (PWM active state) to TONMAX_VAL

Page 38: Trixboxguide

ENABLED 1

DISABLED 0

7.16.3 Enable PWM inactive state (Toff) minimum limit TOFFMIN

If enabled, will limit the minimum Toff (PWM inactive state) to TOFFMIN_VAL

ENABLED 1

DISABLED 0

7.16.4 Enable PWM inactive state (Toff) maximum limit TOFFMAX

If enabled, will limit the maximum Toff (PWM inactive state) to TOFFMAX_VAL

ENABLED 1

DISABLED 0

7.16.5 Enable PWM period (Tpwm) minimum limit TPWMMIN

If enabled, will limit the minimum Tpwm (PWM period) to TPWMMIN_VAL. Only valid when

FIXED_PERIOD is DISABLED.

ENABLED 1

DISABLED 0

7.16.6 Enable PWM period (Tpwm) maximum limit TPWMMAX

If enabled, will limit the maximum Tpwm (PWM period) to TPWMMAX_VAL. Only valid when

FIXED_PERIOD is DISABLED.

ENABLED 1

DISABLED 0

Page 39: Trixboxguide

7.17.0 LIMITING VALUES

The following parameters allows the user to specify the limits on Ton, Toff and Tpwm. These values

become relevant when the respective LIMIT parameters are enabled. All values are in seconds.

These limits are typically relevant for safety and protection of the system. They only come into

effect when the corresponding LIMIT parameter is ENABLED.

7.17.1 Lower limit of Ton TONMIN_VAL

7.17.2 Upper limit of Ton TONMAX_VAL

7.17.3 Lower limit of Toff TOFFMIN_VAL

7.17.4 Upper limit of Toff TOFFMAX_VAL

7.17.5 Lower limit of Tpwm TPWMMIN_VAL

7.17.6 Upper limit of Tpwm TPWMMAX_VAL

7.18.0 ADC AND INTERFACE PARAMETERS

These are required to simulate the effect of quantization due to ADC bit resolution

7.18.1 Digital to analog converter/comparator input DAC_FULLRANGE

Full range counts of the DAC used for comparing in peak and valley current mode. For 10 bit it is 1024

and so and so forth. Essentially in peak current and valley current mode, the reference has to be said

programmatically. The reference number (in software) needs to be converted to a analog signal by a

digital to analog convertor for cycle by cycle limit. This parameter captures the resolution of the DAC.

Page 40: Trixboxguide

7.18.2 Analog digital convertor full range ADC_FULLRANGE

Full range counts of the ADC used for sampling feedback signals. For 10 bit ADC it is 1024 and so and

so forth. In any digital control system, the analog feedback has to be sampled and converted into

digital value. The resolution of the sampling process is governed by this parameter.

8.0.0 Appendix 4.0 8.1.0 User code format (Only relevant for user code simulation mode)

In the user code mode, the user can simulate his own code. The following section describes the code

format.

The code has to follow PYTHON syntax

Some key features are as follows

Python is a strongly typed language which means that indentation (space at the start of each line is

very critical)

The code has to be properly indented.

The code should not contain special characters such as ; ‘ ,” .characters such as ‘[‘ and ‘]’

square brackets are allowed

The code should be a mathematical code. No string or shell utility based operations are allowed

The only variables allowed are Vrbl[0],Vrbl[1] and so on till Vrbl[200]. Vrbl is

an array of size 200.

Page 41: Trixboxguide

The user code is essentially a function that gets called every interrupt.

In conjunction with the physical system model, the entire system is thus simulated.

In the PYTHON programming language, variables have local scope by default. So any variable stored will be

wiped off every time the function is called. Hence it is impossible to implement anything with memory within

these rules. Therefore an array Vrbl is passed to the function. Any values stored in the Vrbl array remains as it

is next time the function is called.

The code structure is typically as follows

The various real world signal feedback are copied into local variables. User code

where various calculations etc may be performed.

Finally the outputs are dumped into another set of variables which are returned by the function to

perform simulation.

An example code is provided here

<tab> Vrbl[1] = 3000

<tab> Toncounts = Vrbl[1]

<tab> Toffcounts = 6700

<tab> Tpwmcounts= 10000

<tab> DutyQ15 = 10000

<tab> Ipkrefcounts = 0

<tab> Ivlrefcounts = 0

<tab> ilooptrigQ15 = 0

<tab> vlooptrigQ15 = 0

Page 42: Trixboxguide

The variables which are returned such as ‘Toncounts’ , ’Toffcounts’ automatically get declared when

they are called unlike a typical C implementation. Hence these assignment statements before return

such as

Toncounts = 1000 etc are critical.

The right hand side of the assignment statement may change based on user desire, but the left hand

side of the = sign should remain as they are.

Essentially all the user has to write the code, and get the numbers into a set of variables such as

Vrbl[0] ,Vrbl[1]…

Then these values may be assigned to the return group of variables like

Toncounts etc.

The system should be handling any valid user code under the framework defined for usercode.

8.2.0 Description of return group of variables

The following is the list of return variables and their description.

8.2.1 Toncounts :The on time Ton in counts. E.g. if Ton is 1us and PWM resolution is 1ns then

Toncounts will be 1000.

Toncounts is at the same scale as duty registers such PDCx in microchip processors

dspic33fjxxgsxxx

Page 43: Trixboxguide

8.2.2 Toffcounts :The off time Toff in counts.

E.g. if Toff is 1us and PWM resolution is onces then Toffcounts will be 1000.

Toffcounts is at the same scale as duty register.

Toffcounts is at the same scale as duty registers such PDCx in microchip processors

dspic33fjxxgsxxx

8.2.3 Tpwmcounts :The time period in counts

E.g. if Toff is 1us and PWM resolution is 1ns then Toffcounts will be 1000.

Toffcounts is at the same scale as period register.

8.2.4 DutyQ15 : Duty value as a fraction expressed in Q15 format.

E.g. If duty ratio needs to be 0.5 then DutyQ15 will be 16383

8.2.5 Ipkrefcounts : Peak current value as counts in the system

When using mode that requires DAC based peak current, then the value used in DAC register

E.g. If 1A corresponds to 1024 counts in user hardware system, then to enter 0.5 A as the peak limit

the value should be 512

8.2.6 Ivlrefcounts : Valley current value as counts in the system

When using mode that requires DAC based valley current, then the value used in DAC register. E.g. If 1A

corresponds to 1024 counts in user hardware system, then to enter 0.5 A as the valley

Limit the value should be 512.

Page 44: Trixboxguide

8.2.7 ilooptrigQ15 : Trigger value as a fraction of period for current sampling

The ADC for current related quantities are triggered and measured at this instant. It is

expressed as a fraction of the period Q15 format.

E.g. suppose the current needs to be triggered at 10 % of the period (Tpwm value). Then this variable

should be round (32768 * 0.1) = 3277

8.2.8 vlooptrigQ15 : Trigger value as a fraction of period for voltage sampling

The ADC for voltage related quantities are triggered and measured at this instant. It is

expressed as a fraction of the period Q15 format.

E.g. suppose the voltage needs to be triggered at 10 % of the period (Tpwm value). Then this variable

should be round (32768 * 0.1) = 3277