UNIT OPTIONS Reverse Handing with Various Airfl ow Options• Economizer• Outside Air Damper• Low Ambient / High Static Outdoor Fans• Compressor Soft Starters• Phase Protection • Additional Full Coil Coat Protection• Fault Detection Board•
CONTROL OPTIONS & FEATURES0-10V DC / 24V AC - Third Party Controller Inputs
Night Mode / Economy Mode Inputs•
ActronAir C7-4 (BCA Compliant) 7-Day Programmable Controller with 2 Events/Day, • Temperature Set Back and After Hours Timer Operation• Auto, Heat & Cool Modes• Auto/Continuous Indoor Fan Operation• 3 Stage Cooling / 3 Stage Heating• Remote Temperature Sensors•
* Based on unit rating excluding indoor fan kW.** Measured and tested in accordance with AS/NZS 3823.1.2.
*** At 270C DB / 190C WB entering air temperatures and 350C ambient.^ At 200C DB entering air temperature and 70C DB / 60C WB ambient.
^^ input power includes indoor fan kW.^^^ Max. - Min. airfl ow application range.
^^^^ Full Load Amps are based on compressor and fan motors’ maximum expected current. See Specifi cations sheet for cable size and circuit breaker size details.
TH - Total Heating Capacity (kW). IH - Integrated Heating Capacity (kW) Includes defrost losses.
NOTES:1. No allowance has been made for the effect of indoor fan motor.2. Selection tables are based on nominal airfl ows. Correction factors must be applied for selection away from these conditions.
NOTES:W = Indoor Fan Power, WattsVolts = Fan Speed Control Setting, Volts DC (Adjustable through CVI Board located in electrical panel). Factory Speed Control Setting = 5.5 Volts for 100 Pa. - Data in the box indicates Factory Default Setting.
CVI123782-1
D4D3
DISP2 DISP1
PS1
U5
D2 MODEL
+VIN PWM GDN
P3
ABCDE
F
SP A
IR
P4ADJUSTU3P5
6-84
33
AU
X
C2C4
C3
+
+
+
P2
U2
TX2
P1R9 R10
C7U4
R11R12R13R14R15R16
U1
C6R18
R1
R3
R4 R
2
C1
R6
R7
R8
RV1
NOTES:LED will not show decimal point.•
Example: 5.5 Volts = 55 in LED.LED adjustments are in 0.1 increments.•
(CVI) INDOOR FAN VARIABLE SPEED BOARD
VOLTAGE ADJUSTMENT(POTENTIOMETER)
LED FANVOLTAGE DISPLAY
JUMPER PIN SET AS PER TABLE ON RIGHT
JUMPER PIN
POSITIONINDOOR FAN
A PKY470TB PKY540TC PKY620TD PKY700TE PKY820TF PKY960T
NOTES: 1. All dimensions are in mm unless specifi ed. 2. Do not scale drawing. 3. LH / RH refers to Left Hand or Right Hand location of supply air 4. Above drawings shows left side handing.
* For reverse handing, service clearance for plug fan and airfl ow clearance for hood will be reversed.** If the optional hood is not installed, 500mm clearance is required for service access.
NOTES: 1. All dimensions are in mm unless specifi ed. 2. Do not scale drawing. 3. LH / RH refers to Left Hand or Right Hand location of supply air. 4. Drawings shows left side handing. 5. Refer to corresponding unit dimensional drawing for mounting hole details.
IMPORTANT - The local electricity authority may require limits on starting current and voltage drop, please check prior to purchase.
* Full Load Amps are based on Compressor and Fan Motor’s maximum expected current.
** Rated Load Amps are measured and tested in accordance with AS/NZS3823.1.2.
CABLE SIZE & CIRCUIT BREAKER SIZESuggested minimum cable size should be used as a guide only, refer to AS/NZS 3000 “Australian/New Zealand Wiring Rules” for more details.
OUTDOOR COILTUBE TYPE Copper - Rifl e BoreFIN TYPE Aluminium - Wave
FACE AREA (m sqr) - Coil 1 & 2 1.87 & 3.75FIN SPACING (per m) - Coil 1 & 2 472 & 472COIL COATING Blue Hydrophilic Coil Fin ProtectionROWS ---
OUTDOOR FANNUMBER OF FANS x TYPE 3 x Axial Low NoiseNUMBER OF BLADES PER FAN 5DIAMETER (mm) 710OUTPUT kW (each) 0.63MOTOR TYPE / DRIVE TYPE 6 Pole External Rotor / DirectFAN SPEED CONTROL 2 Speed via Capacitor
The standard type outdoor fans fi tted to this unit will only accept 20Pa of external static resistance.
INDOOR COILTUBE TYPE Copper - Rifl e BoreFIN TYPE Aluminium - Louvre
FACE ARE (m sqr) 2.61FIN SPACING (per m) 472COIL COATING Blue Hydrophilic Coil Fin ProtectionROWS ---
INDOOR FANNUMBER OF FANS x TYPE 2 x Backward Curve Plug FanDIAMETER (mm) ---OUTPUT kW 2.97 MOTOR TYPE / DRIVE TYPE Variable Speed EC Motor / Direct Drive
COMPRESSORNUMBER PER UNIT x TYPE 3 x Scroll (Hermetic)FULL LOAD AMPS (each) 21.0
LOCKED ROTOR AMPS (each) 111.0
STARTING METHOD D.O.L. (optional soft starter)
REFRIGERATION SYSTEMREFRIGERANT TYPE R-410A
EXPANSION CONTROL- TYPE x NO. PER UNIT Bi-Flow TXV (Thermostatic Valve) x 3
FACTORY CHARGE (each comp.) 8,300 grams
FILTER DRIERCONNECTION SIZE & TYPE (each comp.) 15.9 mm (5/8”) ODF - SolderedFACTORY SUPPLIED / FITTED NoSee Installation Section for complete Filter Drier specifi cations.
PROTECTION DEVICESHIGH PRESSURE CUTOUT SWITCH Nonadjustable (Automatic Reset)LOW PRESSURE CUTOUT SWITCH Nonadjustable (Automatic Reset)COMPRESSOR MOTOR TEMP. Internal Thermal Cut-OutINDOOR FAN OVERLOAD Full Electronic MonitoringOUTDOOR FAN OVERLOAD Internal Thermal Cut-Out
SUMP HEATER WATTS (each comp.) 50
ELECTRIC CONTROLSDEFROST METHOD Reverse CycleDEFROST TYPE Adaptive Demand DefrostCONTROL CIRCUIT BREAKER 16.0 AmpsC7-4 FIELD CONTROL WIRING 2 Core 14 / 0.20 Screened Cable
OPTIONAL THIRD PARTY CONTROLLER INPUTS
Commercial Control Interface (CCI)0-10V DC / 24V AC
OPERATING RANGEIt is essential that the unit is correctly sized for the application and operates within its recommended range of operating conditions as shown below.
MODE RANGEINDOOR
AIR INTAKE TEMPERATURE
OUTDOOR AIR INTAKE
TEMPERATURE
CoolingMax. 29oC DB / 19oC WB 50oC DBMin. 20oC DB / 15oC WB 15oC DB
HeatingMax. 24oC DB 21oC DB / 16oC WBMin. 16oC DB -10oC DB
IMPORTANT - Lower ambient available on request. Contact your nearest ActronAir offi ce for more details.
AIR FILTER PROVISIONAll return air including fresh air must have adequate fi lters supplied and fi tted by the installing contractor. Filters are to be located in the return air fi lter retainer in the unit or in accessible location between the return air grille and the unit.-
FILTER RAILS FITTED (Filters not Supplied) FILTER SIZE - H x W x T 594 x 492 x 96QUANTITY 9