TRANSFORMER PROTECTION
Nov 21, 2014
TRANSFORMER PROTECTION
INTRODUCTION TYPES OF FAULTS TYPES OF PROTECTION RELAY APPLICATION CONCLUSION
CONTENTS
Transformers are static devices without any rotating part and are totally enclosed.
Chances of faults occurring on transformers are much rare as compared to generators
If fault occurs, they have to be cleared quickly If not they develop into major faults which may
be very serious for the transformerFor protection Small rating transformers use fuses But large rating transformers always need some
type of automatic protective relaying equipment
INTRODUCTON
The various possible transformer faults are, 1. Overheating 2. Winding faults 3. Open circuits 4. External faults 5. Over fluxing
TYPES OF FAULTS
They are due to Sustained overloads and short circuits Failure of cooling system
Protection The thermal overload relays and temperature relays,
sounding the alarm are used The thermocouples or resistance temperature
indicators are also provided near the winding. These are connected in a bridge circuits. When the bridge balance gets disturbed for more
than the permissible duration circuit breaker trips.
OVERHEATING
The winding faults are called internal faults. The overheating or mechanical shocks deteriorates the winding insulation. If the winding insulation-is weak, there is a possibility of
Phase to phase faults Earth faults Inter turn faultsPersistent fault would have a possibility of oil-fire.PROTECTION Differential protection Overcurrent protection is also used as a backup protection For earth fault protection, the restricted earth fault
protection system, neutral current relays or leakage to frame protection system is used.
WINDING FAULTS
The open circuit in one of the three phases is causes the undesirable heating of the transformer.
Open circuits are much harmless compared to other faults.
Transformers can be manually disconnected from the system during such faults.
OPEN CIRCUIT
Through faults are the external faults which occur outside the protected zone.
These are not detected by the differential protection. If faults persists the transformer gets subjected to
thermal and mechanical stresses which can damage the transformer.
PROTECTION The overcurrent relays with undervoltage blocking, zero
sequence protection and negative sequence protection are used to give protection
The setting of the overcurrent protection not only protects transformer but also covers the station busbar and portion of a transmission line.
THROUGH FAULTS
The flux density in the transformer core is proportional to the ratio of the voltage to frequency i.e. V/f
Transformers are designed to work with certain value of flux density in the core. In the generator transformer unit, if full excitation is applied before generator reaches its synchronous speed then due to high V/f the overfluxing of core may occur.
PROTECTION V/f relay called volts/hertz relay is provided to
give the protection against overfluxing operation.
OVERFLUXING
Other faults Tap changer faults High voltage surges due to lightning Switching surges Incipient faults
Also called as percentage differential protection
It is based on circulating current principle
It protects against phase to phase and phase to ground faults
Merz –Price protection
The primary of the power transformer is star connected while the secondary is delta connected.
To compensate for the phase difference, the C.T. secondaries on primary side must be connected in delta while the C.T. secondaries on delta side must be connected in star
The restraining coils are connected across the C.T. secondary windings while the operating coils are connected between the tapping points on the restraining coils and the star point of C.T. secondaries
It compares the currents at entering and leaving end
The vector difference(I1 –I2)/2 passes through the operating coil
The average current (I1+I2)/2passes through the restraining coil
The two currents at the two ends are equal so balance is maintained
No current flows through the operating coil and the relay is inoperative
Principle
During normal operating conditions the C.T. secondaries carry equal currents which are inphase.
With an internal fault in power transformer windings, the balance in the C.T.s get disturbed.
The operating coils of differential relay carry currents proportional to the difference of current between the two sides of a power transformer.
This causes the relay operation which trips the main circuit breakers on both the sides of the power transformer
Working
This method is to provide earth fault protection
The frame of the switch gear is grounded When there is a fault the fault leaks from
the frame and passes through the earth connection provided
The primary of the C.T senses due to which current passes through the sensitivity earth fault relay
This operates the relay
Frame leakage protection
It is a gas operated relay used for the protection of oil immersed transformers
When faults occur decomposition of oil occurs
Gas accumulates at the top hence decreasing the oil level
Buchholz relay
Oil reduction makes the hollow floats to tilt And close the contacts of the mercury
switch attached to it Hence completing the alarm circuit to sound
an alarm The transformer could hence be
disconnected to test the gas sample
Advantages
Buchholz relay gives the fault indication at a very early stage
It is the simplest transformer protection
Limitations
Only used for oil immersed transformers Only faults below oil level are detected The relay is slow having minimum operating
time of 0.1sec and average time of 0.2 sec.
Local overheating Bad and loose electrical contacts Winding earth faults Short circuited laminations Winding short circuited Loss of oil and reduction of oil level
Applications
Even though faults in the transformers are very rare different types of possible faults were seen
Different protection relays and devices were shown
Advantages and limitations were seen
Conclusion
H.C.Branes and R.H.Mcpherson “field experience-transformer protection”, AIEE Trans,72 part 3
M.H.Haque,2004”use of local information for protection", international power engineering conference
G.Verbic and F.Gubina ,”a new concept on protection based on distance relaying schemes” ,IEEE transaction on power delivery19.
www.howstuffworks.com
References
Thank you