T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015. 1 Installation Instructions T/PI/160 PRT Immersion Temperature Sensor Important: Retain these instructions These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com 2 Requirements 1 Dimensions 2 INSTALLATION 1 BOX CONTENTS T/PI/160 Installation Instructions (TG100310A) MANUFACTURED IN EU TREND CONTROL SYSTEMS LTD UK T/PI/160 6 mm (0.24”) 155 mm (6.1”) 97 mm (3.82”) 65 mm (2.56”) 8 mm (0.31”) 1 m (3’3”) stainless steel cable 75 mm (2.95”) 55 mm (2.17”) 70 mm (2.76”) Stainless steel pocket (WS150) 57 mm (2.24”) Universal Fitting Kit for use in existing pocket (ACC/UF) clip spring brass bush hexagonal socket grub screw 117 mm (4.61”) T/PI/160 HO 2 -10 °C +14 °F +160 °C +320 °F 0 %RH 95 %RH measurement ranges Protection :IP67, NEMA6 1 m max -10 °C to +160 °C +14 °F to +320 °F -40 °C to +50 °C -40 °F to +122 °F Ensure no stratification (e.g. downstream of mixing valves, junctions) (minimum distance from junctions =10xd). d Cl 2 Note: WS150 is NOT suitable for use in chlorine rich environments. 135 mm (5.31”) 14 mm (0.53”) 24 mm (0.95”) Ø8 mm (0.31”) Ø6.5 mm (0.25”) R½” (BSPT) 143 mm (5.63”)
4

T/PI/160 Installation Instructions - Honeywell

May 04, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: T/PI/160 Installation Instructions - Honeywell

T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015. 1

Installation Instructions

T/PI/160PRT Immersion Temperature Sensor

Important: Retain these instructions

These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specified by these instructions, the protection provided by the equipment may be impaired. https://partners.trendcontrols.com

2 Requirements

1 Dimensions

2 InSTallaTIon

1 Box ConTenTS

T/PI/160 Installation Instructions (TG100310A)

MANUFACTURED IN EUTREND CONTROL SYSTEMS

LTD UK

T/PI/160

6 mm (0.24”)

155 mm (6.1”) 97 m

m (3

.82”

)

65 mm (2.56”)

8 mm (0.31”)

1 m (3’3”) stainless

steel cable

75 m

m (2

.95”

)

55 mm (2.17”)70 mm (2.76”)

Stainless steel pocket (WS150)

57 mm (2.24”)

Universal Fitting Kit for use in existing pocket (ACC/UF) clip

spring

brass bush

hexagonal socket grub screw

117 mm (4.61”)

MANUFACTURED IN EUTREND CONTROL SYSTEMS

LTD UK

T/PI/160

H O2

-10 °C+14 °F

+160 °C+320 °F

0 %RH 95 %RH

measurement ranges

Protection :IP67, NEMA6

1 m max

-10 °C to +160 °C+14 °F to +320 °F

-40 °C to +50 °C-40 °F to +122 °F

Ensure no stratification (e.g. downstream of mixing valves, junctions)

(minimum distance from junctions =10xd).

d

Cl2Note: WS150 is NOT suitable for use in chlorine rich environments.

135 mm (5.31”)

14 mm (0.53”)

24 mm (0.95”)Ø8 mm

(0.31”)

Ø6.5 mm (0.25”)

R½” (BSPT)143 mm (5.63”)

Page 2: T/PI/160 Installation Instructions - Honeywell

2 T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015.

T/PI/160 Installation Instructions

3 Mount on Wall

4 Install Pocket

5 Install Sensor into Pocket

6 Remove lid

85 m

m (3

.35”

)

Drill 2 pilot holes

Tighten 2 screws

2 off No 6 screws

(if installing new pocket)

Drill hole for boss

Fix threaded boss

Screw pocket into boss

½” BSPT threaded bossapply sealent to boss thread

use M24 spanner

If using compatible pocket

If using universal adaptor

use 2 mm hexagonal socket key

Push adaptor onto probe

(if using new pocket)

(if using old pocket with grub screws)

Adjust probe length

if pocket has clip retaining groove, push clip over pocket

if pocket has grub screw, discard spring and clip

clip

spring

brass brush

tighten

use 2 mm hexagonal socket key

pocket length

clip engages in groove

tighten screws

probe is forced against end of pocket

tighten screw over bush

spring compession fi tting

Fix to pocket

2 InSTallaTIon (continued)

Page 3: T/PI/160 Installation Instructions - Honeywell

T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015. 3

Installation Instructions T/PI/160

7 Remove Connector

8 Insert Cable

9 Wire to Controller

10 Replace Connector

Caution: This unit contains static sensitive devices. Suitable anti-static precautions should be taken throughtout the operation to prevent damage to the units.

BS EN100015/1 Basic Specifi cation: protection of electrostatic sensitive devices.

either use M20 fl exible conduit or use M16 cable gland

polarity independent

IQ controllerSensor

24 Vdc

IN

Terminate screen at IQ end only

Analogue input channel confi gured for current (I)

IQ system TP/I/22/HF/200-600V(Belden 8761) cable recommended. Terminal size 0.5 to 2.5 mm2 (20 to 14 AWG)

Note: If connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to C (+24V), instead connect to AUX+ (+24V).

2 InSTallaTIon (continued)

Page 4: T/PI/160 Installation Instructions - Honeywell

4 T/PI/160 Installation Instructions TG100310A Issue 5, 23-Dec-2015.

T/PI/160 Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2015 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems limitedAlbery House, Springfi eld Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

TR CU Certifi cation

11 Replace lid

12 Confi gure Controller

13 Set up IQ Sensor Type

14 Test System 3 DISPoSal

Weee Directive :At the end of their useful life the packaging and product, should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste. Do not burn.

2 InSTallaTIon (continued)

Note: The IP67 (NEMA6) rating is only achieved if the sensor is correctly installed with cable or conduit connection fully tightened.

IQ

IQ

or IQ Confi guration Manual (90-1533)IQ3 Confi guration Manual (TE200768)IQ4 Confi guration Manual (TE201263)IQeco Confi guration Manual (TE201089)

It is recommended to use SET (Software Tool) for the setting of the sensor type module. For all IQ2 series controllers with fi rmware version 2.1 or greater, or IQ3/4 series controllers, the following SET Unique Sensor Reference should be used:

PRT Sensor -10+160 (°C) PRT Sensor +14+320 (°F)

Alternatively set scaling mode to 5 (characterise) and enter scaling manually as defi ned in adjacent table. Note that for IQ3/4 the scaling mode and exponent do not need to be set up.

For all other IQ controllers see Sensor Scaling Reference Card (TB100521A).

Y input type 2 (current)

E Exponent 3

Units °C °F

U Upper 160 320

L Lower -10 14

P Points 2 2

x Ix Ox Ox

1 4 -10 14

2 20 160 320

PRT Sensor (-10 °C +160 °C, +14 °F +320 °F)

IQMANUFACTURED IN EUTREND CONTROL SYSTEMS

LTD UK

T/PI/160

∆ T